You are on page 1of 5

DRPT2008 6-9 April 2008 Nanjing China

Selection of HVDC Models for Stability Studies


Xiao-ming Mao, Yao Zhang, Feng Ye and Xiao-long Chen

In this paper, simplified and detailed HVDC simulation


Abstract--Representation of High Voltage Direct Current models are described and compared. The system modeled is
(HVDC) transmission links in power system stability studies the ±500-kV, 3000-MW 12-pulse bipolar link which connects
requires special attention. A detailed model, while very precise, the Gaopo rectifier station in Guizhou province to the
requires considerable time for modeling and calculation.
Zhaoqing inverter station in Guangdong province, China.
Simplified models, on the other hand, do not always provide
sufficiently accurate results. In this paper, simplified and detailed Model suitability is discussed.
HVDC simulation models are described and compared. The dc The rest of the paper is organized as follows. Section II
system modeled is the ±500-kV, 3000-MW 12-pulse bipolar link describes the classifications of HVDC models. Section III
between Gaopo rectifier station in Guizhou province and depicts the development of the detailed model and a response
Zhaoqing inverter station in Guangdong province, China. model for the Gaopo-Zhaoqing (GZ) HVDC link. Simulations
NETOMAC, a powerful and flexible software package, is comparing different dc system models are presented in Section
employed for modeling and calculations. Simulation cases based
on the China Southern Power Grid data are presented and IV. Proper model selection is discussed in Section V. Section
analyzed. Appropriate model selection is discussed. VI contains concluding remarks.

Index Terms--HVDC Transmission, Simulation Models, II. CLASSIFICATIONS OF HVDC MODELS


Stability Analysis.
The dc converter in stability studies is represented by
equations relating average values of dc quantities and RMS
I. INTRODUCTION
values of ac fundamental components. The ac/dc interface is

I N order to investigate the behavior of HVDC


transmission in a power system, suitable simulation models
are required. The representation of the dc systems requires
modeled so that the ac system provides equivalent dc voltage
source for the dc network while the dc system is represented
as the load (negative for inverter) of the ac network.
consideration of converter model, dc transmission line model, According to the level of modeling of dc lines and dc controls,
interface between ac and dc systems and dc system controls HVDC models are usually categorized as follows.
model [1].
In a stability program, the ac network equations are A. Simple Models
represented in terms of positive-sequence fundamental For remote dc links, which do not have a significant impact
frequency quantities. This imposes a basic limitation on the on the results of the stability analysis, very simple models are
modeling of the dc systems. In particular, commutation usually adequate. The dc link may be represented as constant
failures and response of dc system to unsymmetrical ac faults active and reactive power injections at the converter buses or
cannot be accurately predicted [2]. represented by the static converter equations and the interface
In spite of the limitation, models of various degrees of between ac and dc systems is treated in a manner similar to
detail have been effectively used to represent dc systems in power-flow analysis [1].
stability studies [3]. Each model tends to have unique B. Response Models
characteristics tailored to meet the specific needs of its
application. And standard models of fixed structures for Response models tend to well reflect the performance of a
representation of dc systems in stability studies are not dc system under various system operating conditions with less
available [4]. Instead, three categories of models have evolved: detail. It provides a compromise between simulation accuracy
(1) simple model, (2) response model, and (3) detailed model and modeling efficiency. Usually the dynamics of the dc line
with flexible modeling capability. and pole controls may be neglected. The lines are represented
A detailed model, while very precise, requires considerable in their resistance and the pole control action is assumed to be
time for modeling and calculation. Simplified models, on the instantaneous. Many of the control functions are represented
other hand, are not accurate enough under specific conditions. in terms of their net effects, rather than actual characteristics
of the hardware [5, 6].
During ac faults, it is necessary to have adequate
This work was supported by key projects of National Science Foundation of
China under project 50337010. representation of the actions of controls to reflect the dc
X. M. Mao is with the Faculty of Automation, Guangdong University of system response. Special mode shift algorithm is required to
Technology, Guangdong, China (e-mail: mxmsunny@163.com). assume the proper control shift depending on the temporal
Y. Zhang is with College of Electrical Engineering, South China
University of Technology, Guangdong, China.
state of ac/dc systems. Constraints are imposed on the current-
F. Ye and X. L. Chen are both with the Faculty of Automation, order level to keep the current within minimum and maximum
Guangdong University of Technology, Guangdong, China.

978-7-900714-13-8/08/ ©2008DRPT 1933


DRPT2008 6-9 April 2008 Nanjing China

limits where the voltage-dependent current-order limit direct voltage with a voltage feedback loop to provide a
(VDCOL) is taken into account. transition between the current control and the voltage control
of the inverter to facilitate control stabilization.
C. Detailed Models
Denote control error as the difference between the reference
Detailed model uses more complicated descriptions of the value and the measured value of a dc quantity, in the GZ
dc line and especially the HVDC controls hence it can reflect HVDC system the control modes are properly shifted
HVDC dynamics and response to the ac disturbances precisely according to control error and appropriate angle limits. Fig.1
[7-10]. The resistance, inductive and capacitive effects of the illustrates the diagram of the rectifier pole control where K
dc line is represented. Pole controls capable of representing and T represent the gain and integration time constants of PI
different control options such as constant current control, control respectively.
constant extinction angle control, constant direct voltage
VDCOL
control, etc are provided. The converter angle limits are Ud
PI control Arc cos
embedded in the controls so that no special mode shift Min
Iref ∆ Id Firing
angle a
I d reference
algorithm is required. Mux
a limit
Id measured

U margin
III. MODEL ESTABLISHMENT ∆ Ud KId
KUd
Uref
The HVDC system modeled in this paper is a 3000-MW, Ud measured
Mux

±500-kV 12-pulse bipolar link between the Gaopo converter TId


station in GZ province and the Zhaoqing converter station in T Ud
Mux
Guangdong province, China. The two terminals are connected
through 880 kM dc lines. The rectifier normally controls the
direct current while the inverter maintains a constant voltage. Fig. 1. Diagram for rectifier pole control of GZ HVDC link
All HVDC schemes used to date have controls of three
layers, the master control, the pole control, and the valve Auxiliary controls for ac system and tap changer control are
control. The master control and pole control layers work as also represented in detail in the model developed. For ac/dc
decision levels. The valve control is the executive level and interface, the correct representation of the commutating
neglected in control modeling in stability studies. voltage and the converter transformer together with the
Usually, an HVDC link is required to transmit a scheduled tertiary bus to which compensation capacitance and filters are
power. In such an application, the master control layer connected is provided.
receives the power schedule, modifies it by auxiliary power B. Development of a Response Model
control and then converts the power signal into the
As for the response model, the dc line is modeled by its
coordinated bi-pole current order commensurate with the dc
resistance. The rectifier is assumed to have CC control and
voltage. Pole control is the core of HVDC control and
CIA control. The inverter is assumed to posses CEA, CC and
activates the appropriate controller of the rectifier and inverter
β (constant ignition advance angle) control where β control
station according to the state of ac/dc systems and produces
provides a voltage-current characteristic of positive slope for
the firing angle for both rectifier and inverter stations.
stable transition between CEA and CC control. The three
Detailed and response model provide the identical
modes of control are
representation for the master control whereas different levels
z Mode 1- Rectifier on CC and inverter on CEA control
of modeling for the pole control.
z Mode 2- Rectifier on CIA and inverter on CC control
A. Development of the Detailed Model z Mode 3- Rectifier on CIA and inverter on β control
In our simulation, the dc line is separated into nineteen The mode shift logic is implemented by
segments each with representation of resistance as well V Cosα min − Vdoi Cosγ min
I t = dor (1)
inductive and capacitive effects to model dynamics. Rcr + Rd − Rci
Pole control at the rectifier side of the GZ HVDC link has a
current controller and a voltage controller. The voltage where Rcr and Rci are the equivalent commutating resistance
controller limits dc voltage to below1.05 p.u. while the current of the rectifier and inverter, Vdor and Vdoi are the ideal no-load
controller takes the maximum and minimum current direct voltage at the rectifier and inverter terminal. Rd is the
constraints and the VDCOL into consideration. Besides, the
minimum firing angle control (i.e. constant ignition angle-CIA resistance of the dc line. And α min and γ min correspond to
control) is embedded implicitly in the current controller by the minimum rectifier ignition angle and inverter extinction
angle limits. angle.
Pole control of the inverter station includes a voltage The mode shift logic is that
controller (Vd control), a constant extinction angle (CEA) z If I t > I dN , the dc system operates in mode 1
controller, a constant current (CC) controller and a current
z If I t < ( I dN − I m ) , the dc system operates in mode 2
error controller (CEC). The first three controllers maintain a
constant direct voltage, extinction angle, and direct current z If ( I dN − I m ) ≤ I t ≤ I dN , the dc system operates in mode 3
respectively while the current error controller controls the

1934
DRPT2008 6-9 April 2008 Nanjing China

where I m is the current margin. do not consistently agree with each other and more dynamics
Among the controllers modeled, the CC control is of the are provided by the detailed model, the response model on the
most importance whose block diagram is shown in Fig.2. In whole reflects the response of the dc system. In special, it is
seen from this simulation case and other similar simulation
the control, S is switched to I set = 0 if Eacr < Emin r or
cases that with the response model the floating current mode is
Eaci < Emin i for a period ∆T > TD1 to reflect the shut down not available under the rectifier side ac fault. Such a mode
logic. S is switched back to I ord if line has been shut off may last for some time if the maximum rectifier voltage is not
high enough to keep the current from dropping and, at the
and Eacr and Eaci are greater than Ere cov ery for ∆T > TD 2 to same time, is not low enough to cause current reduction in
simulate the recovery logic. T3 is the response time of the excess of current margin to activate the inverter current
current control loop. controller. In such a situation the rectifier operates at its
minimum firing angle, the inverter controls its voltage, and the
variation of the current is mainly governed by the total
1 + sT1 1 1 inductance between the rectifier and inverter. In the response
1 + sT2 T3 s model developed, the inductance modeling is neglected, thus
the transition from inverter CEA control to CC control is too
Fig. 2. Block diagram for current control fast to be reflected by the model.
System performance comparison is also shown in Fig.5 and
Besides, the CEA control of the inverter is implemented Fig.6 under a three-phase short-circuit fault near the inverter
according to equation (2). And the inverter β control is terminal. The curves in Fig.5 and Fig.6 have the same
achieved by formula (3). meaning as in Fig.3 and Fig.4.
2R I For a close-in inverter side ac system three-phase fault, the
cos γ = cos β + ci d (2) inverter commutation voltage drops significantly. Repeated
Vd 0i
commutation failures cannot be avoided. The dc system shuts
α =π −β (3) down under VDCOL control until the fault is cleared. A sharp
During the tuning of the response model, the detailed increase and subsequent decrease in direct current occurs
model is used to provide a basis. during the transitions as a result of the current control at the
rectifier. Along with the recovery of ac voltage after the
IV. MODEL PERFORMANCE COMPARISON clearance of ac fault, the dc system resumes its operation.
Performance of the models developed is tested in the During the restoration, the detailed HVDC model reflects the
simulation environments of the China Southern power grid. actual controller startup and ingoing process while the
Fig.3 and Fig.4 show system performance under a three-phase response model assumes the dc system to ramp up at the
short-circuit on the rectifier side ac system using the detailed predetermined rate depending on the magnitude of the ac
HVDC model and the response HVDC model respectively. voltage. Therefore, dc recovery performance observed from
There are nine diagrams in each figure. The solid and dashed the response model does not agree with that reflected by the
curve in diagram 1 gives the ac voltage at the rectifier and detailed model. In Fig.6, a much faster recovery is given by
inverter terminal apart. The solid and dashed curve in diagram the response model compared with that provided by the
2 shows the temporal activated controller in the rectifier and detailed model in Fig.5. On the other hand, rotor angles
the inverter respectively where “0” denotes CIA control, “1” plotted by the two models are similar. The simulations
represents CC control, “2” corresponds to rectifier Vd control, indicate that the response model is not accurate enough for
“3” inverter Vd control, “4” CEA control and “5” β control. HVDC recovery studies while suitable for dc modulation
Diagram 3 gives the ignition delay angle. Diagram 4 shows research.
the inverter extinction angle. Diagram 5 and 6 represents the
direct voltage and direct current respectively. Diagram 7 gives V. APPROPRIATE MODEL SELECTION
the active and reactive power flow drawn from the rectifier The description in Section II points out that the simple
side ac system. And the last two diagrams show the rotor model uses only static equations to model converter operation
angles of key generating units in the system. without considerations of dc control actions. Therefore, it is
For the tested rectifier ac fault, voltage reduction at the appropriate only for simulations of HVDC dynamics under
rectifier ac bus is not significant. This will result in a reduction remote ac fault which has slightly effect on the dc system.
of rectifier direct voltage and hence the current. The current The response model represents the control performance of a
regulator decreases α to restore current by increasing voltage. dc system in terms of their net effects and satisfactorily the
If α hits the α min limit, the rectifier switches to CIA mode of response of a dc system under various system operating
control and the current control is transferred to the inverter
whose current order is less than that of the rectifier by the
current margin. The simulations show that the response model
provides very similar plots versus the detailed model.
Although the controllers in work reflected by the two models

1935
DRPT2008 6-9 April 2008 Nanjing China

Fig.3. System response to a three-phase fault on the rectifier side ac system Fig.4. System response to a three-phase fault on the rectifier side ac system
using the detailed model using the response model

Fig.5. System response to a three-phase fault near the inverter terminal using Fig.6. System response to a three-phase fault near the inverter terminal using
the detailed model the response model

1936
DRPT2008 6-9 April 2008 Nanjing China

conditions thus is adequate for a wide range of studies systems,” IEEE Trans. Power Delivery, vol.10, No.4, pp. 2048-2053,
Oct. 1995.
associated with system planning and modulation design. As [9] J. Rittiger, “Digital simulation of HVDC transmission and its correlation
the post-fault recovery logic is supposed a priori in this kind of to simulator studies,” IEEE Conference 1991, Publication Number 345,
modeling, it is not appropriate for studies associated with dc pp. 414-416.
[10] Yang Weidong, Xu Zheng, Han Zhenxiang, “Application of NETOMAC
recovery performance. on HVDC system simulation,” Electric Power Automation Equipment,
The detailed model provides the highest level of detail for vol.21, No.4, pp. 10-14, Apr. 2001.
modeling of a dc system in stability studies. It is more
appropriate for shorter-term and more specialized studies. VIII. BIOGRAPHIES
Examples of these studies are: investigation of existing and Xiao-ming Mao received the B.S. degree from Huazhong University of
new equipment on the dc side and on the ac side close to the Science and Technology, Hubei, China, in 1996 and the Ph.D. degree from
dc system, analysis of precise post-fault recovery of a HVDC South China University of Technology, Guangdong, China, in 2006. She is
now an Associate Professor with Guangdong University of Technology. Her
link, studies involving dc links connected to weak ac systems major field of interest is HVDC, analysis and control of ac/dc power systems.
and studies involving multi-terminal HVDC systems. In Yao Zhang received the B.S. and Ph.D. degrees from Tianjin University,
addition, detailed models may serve as the basis for tuning the Tianjin, China, in 1981 and 1993, respectively. He is now a Professor with
South China University of Technology, Guangdong, China.
response model. Feng Ye is now a M.S. candidate with Guangdong University of
Notwithstanding the above advantages, the detailed model, Technology. His field of interest is HVDC, analysis and control of ac/dc
which uses quasi steady-state equations to describe converter power systems.
Xiao-long Chen is now a M.S. candidate with Guangdong University of
performance commensurate with the positive-sequence phasor Technology. His field of interest is HVDC, analysis and control of ac/dc
representation of ac quantities, is not accurate for analysis of power systems.
unbalanced faults and for prediction of commutation failure.
Accurate simulation of such conditions may require an EMTP-
transient stability combination model.

VI. CONCLUSIONS
Representation of High Voltage Direct Current (HVDC)
transmission links in power system stability studies requires
special attention. Employment of detailed model may slow
down the simulations while such details are required in some
cases. Simplified models, on the other hand, is not accurate
enough under specific conditions. In this paper, simulations
are performed on the stability models developed for the ±500-
kV, 3000-MW 12-pulse bipolar HVDC link between Gaopo
rectifier station in Guizhou province and Zhaoqing inverter
station in Guangdong province, China, using NETOMAC.
Performance of simplified and detailed HVDC simulation
models are compared and analyzed. Appropriate model
selection is discussed.

VII. REFERENCES
[1] Prabha Kunder, Power System Stability and Control, Beijing:
Authorized English language reprint edition jointly published by
McGraw-Hill Education (Asia) Co. and China Electric Power Press,
2002, pp. 566-577.
[2] Xu Zheng, Cai Ye, Liu Guoping, “Some Problems in the simulation of
large-scale AC/DC power systems,” Automation of Electric Power
System, vol.26, No.15, pp. 4-8, Aug. 2002.
[3] B. K. Johnson, "HVDC models used in stability studies," IEEE Trans.
Power Delivery, vol.4, No.2, pp. 1153-1163, Apr. 1989.
[4] S. Arabi, P. Kunder, and J. H. Sawada, "Appropriate HVDC
transmission simulation models for various power system stability
studies," IEEE Trans. Power Delivery, vol.13, No.4, pp. 1292-1297,
Nov. 1998.
[5] “Functional model of two-terminal HVDC systems for transient and
steady-state stability,” IEEE committee report, IEEE PAS, vol. PAS-103,
No.6, pp. 1249-1255, June 1984.
[6] Huang Ying, Xu zheng, He Hui, “HVDC Models of PSS/E and their
Applicability in Simulations,” Power System Technology, vol.28, No.5,
pp. 25-29, May. 2004.
[7] “Modeling of an HVDC system for digital simulation of AC/DC
transmission interaction,” CIGRE symposium 09-87, pp.100-102.
[8] P. Lehn, J. Rittiger and B.Kulicke, “Comparison of the ATP version of
the EMTP and the NETOMAC program for simulation of HVDC

1937

You might also like