How to Calculate the Required Capacity kVA

Rating or Amperage Capacity for Single and


Three Phase Transformers
Published date: 29 July 2019

Issue:
Calculation of kVA capacity for a Single or Three Phase Transformer, based on Winding
Voltage and Amperage information.

Product Line:
Low Voltage (LV) Transformers
Learn more about DOE 2016 Energy Efficient Transformers by Schneider Electric

Environment:
Applies to all Single and Three Phase Transformers.

Cause:
kVA sizing must often be calculated from Primary or Secondary Winding Voltage
and Amperage information.

Resolution:

To determine kVA you must have at least two pieces of information:

1. the load line-to-line voltage (V)


2. the maximum load phase current (I)

Single Phase Transformers: kVA = (V * I) /1000


Three Phase Transformers: kVA = (V * I * 1.732) / 1000
where 1.732 is the simple numerical value for the square root of 3 (1.7320508...)
Then round up to the next standard 3ph kVA rating as found in Section 14 of SquareD/Schneider
Electric Catalog, Digest 177.

Single Phase Transformer Example: V = 240, I = 175; Therefore: kVA = (240 x 175) / 1000 =
42 kVA
This calculates to 42 kVA, thus we round up to a standard Single Phase size 50kVA. From the
Digest, an EE50S3H will satisfactorily serve this load.

Three Phase Transformer Example: V = 208, I = 175; Therefore: kVA = (208 x 175 x 1.732)
/ 1000 = 63.05kVA
This calculates to 63+ kVA, thus we round up to a standard Three Phase size 75kVA. From the
Digest, an EX75T3H will satisfactorily serve this load.
Note: This is a sample kVA calculation and does not take into account possible special load
requirements, such as found with motors or some medical equipment, or other specialty
applications.

Amperage provided for a given KVA can be determined by similar techniques:

Single Phase Example: Using a 50 KVA Single Phase Transformer as a starting point. 50KVA
is equal to 50,000 VA. (K= 1,000) The full value in VA, 50,000 is then divided by the Voltage
240V = 208 Amperes. This is a "Two Step Division", technique: VA / Voltage = Amperage.

Three Phase Example: Using a 75 KVA Three Phase Transformer as a starting point. 75 KVA
is equal to 75,000 VA. (K= 1,000) The full value in VA, 75,000 divided by 1.732 = 43,302,
which is then divided by the Voltage 208V = 208.2 Amperes. This is a "Three Step Division",
technique: VA / 1.732 / Voltage = Amperage.

As an alternative to these calculations, you may prefer to use the charts below. Standard
KVA sizes are shown on the left margin, Standard Line-to-Line Voltages are shown along the
top margin.

Chart Example: Using the numbers from the earlier Three Phase Transformer Example
V=208, I=175. Use the chart titled "Three Phase Low Voltage Dry Type
Transformers". Following the 208V top margin entry, and reading down vertically, it is seen that
the first entry in that 208V vertical column that will cover 175A, and then some, is 208A, which
indicates a 75 KVA Transformer, shown in the next over vertical column to the left.

See pages 3 & 4 of document 7400HO9501 "Looking for Low Voltage Transformer
Solutions" for more information and conversion tables.

https://www.schneider-electric.us/en/faqs/FA101694/