LV product characteristics
Load Protection
Surge Arrester
General contents
Photovoltaic 21-25
1
Protection iPRF1 12.5r/PRF1 Master/ Protection iPRF1 12.5r/PRF1 Master/
Load protection Load protection
PRD1 25r/PRD1 Master PRD1 25r/PRD1 Master
Type 1 and 2 LV surge arresters Type 1 and 2 LV surge arresters (cont.)
The Type 1 range of surge arresters meets the iPRF1 12.5r/PRF1 Master/PRD1 25r/PRD1 Master
normative withstand capability of current wave type The Type 1 surge arrester is recommended for electrical installations in the service
10/350 μs (8/20 μs for Type 2 surge arresters). sector and industrial buildings protected by a lightning conductor or by a meshed
It is suitable for use with TT, TN-S, TN-C and 230 V IT cage.
earthing connection systems (neutral point It protects electrical installations against direct lightning strikes.
connection). It is used to conduct the direct lightning current, propagating from the earth
In addition, the PRF1 Master surge arrester covers the conductor to the network conductors.
400 V IT system. It must be installed with an upstream disconnection device, such as a fuse or
iPRF1 12.5r and PRD1 surge arresters are fitted with a circuit-breaker, whose breaking capacity must be at least equal to the maximum
remote transfer contact to send "end-of-life indication" prospective short-circuit current at the installation point.
information. iPRF1 12.5r and PRD1 25r surge arresters also provide Type 2 protection and
PRD1 surge arresters are fitted with easy-to-replace protect the electrical installation by finely clipping the lightning wave overvoltages.
withdrawable cartridges.
DB123384
DB118911
DB119039
DB119038
iPRF1 12.5r (1P+N, 3P+N) PRF1 Master (1P) iPRF1 12.5r (3P) PRF1 Master (2P, 3P, 4P)
DB122528
DB119036
DB119037
DB122527
DB122527
PB104260-35
PRD1 25r (1P+N, 3P+N) PRD1 Master (1P+N, 3P+N) PRD1 25r (1P) PRD1 25r (2P, 3P, 4P) PRD1 Master (2P, 3P, 4P)
Cartridge 1P+N 3P+N 1P 2P 3P 4P
surge arrester
PRD1 25r 16330 16332 TT, TN-S
T1 + T2
PRD1 25r 2 x 16329 4 x 16329 IT 230 V
16329 16331 TN-C, IT 230 V
PRD1 Master 16361 16363 TT, TN-S
T1
PB104264-35
PRD1 Master
2 3
Protection iPRF1 12.5r/PRF1 Master/ Protection iPRF1 12.5r/PRF1 Master/
Load protection Load protection
PRD1 25r/PRD1 Master PRD1 25r/PRD1 Master
Type 1 and 2 LV surge arresters (cont.) Type 1 and 2 LV surge arresters (cont.)
Type Nb. of Width I imp (kA) (10/350) I max (kA) In - kA Up - kV Un - V Uc - V Technical data
poles Impulse current (8/20) Rated Degree of Nominal Maximum iPRF1 12.5r PRF1 Master PRD1 25r PRD1 Master
Maximal discharge protection line steady Operating frequency 50 Hz 50/60 Hz 50 Hz 50 Hz
discharge current voltage state Degree of protection Front panel IP40 IP40 IP40 IP40
current voltage Terminals IP20 IP20 IP20 IP20
Impacts IK05 IK05 IK05 IK05
Fixed surge 9 mm Surge Surge arrester
Response time y 25 ns y 1 ms y 25 ns y 100 ns
arrester modules arrester + disconnector
End-of-life indication Green: correct operation - White: correct operation White: correct operation
iPRF1 12.5r Type 1 + 2 Red: at end of life - Red: at end of life Red: at end of life
1P+N 4 12.5/50 N/PE 50 25 1.5 230 350 A9L16632 Remote 1.5 A/250 V AC - 1 A/250 V AC. 1 A/250 V AC.
3P 8 12.5 50 25 1.5 230 / 400 350 A9L16633 notification 0.2 A/125 V DC 0.2 A/125 V DC
By tunnel terminal Rigid cable 10...35 mm² 10...50 mm² 2.5...35 mm² 10...35 mm²
3P+N 8 12.5/50 N/PE 50 25 1.5 230 / 400 350 A9L16634
Flexible 10...25 mm² 10...35 mm² 2.5...25 mm² 10...25 mm²
PRF1 Master Type 1 cable
1P 4 50 35 - 50 1.5 230 440 16630 Operating temperature -25°C to +60°C -40°C to +85°C -25°C to +60°C -25°C to +60°C
Withdrawable surge arrester Standards Type 1 IEC 61643-1 T1. IEC 61643-1 T1. IEC 61643-1 T1. IEC 61643-1 T1.
EN 61643-11 Type 1 EN 61643-11 Type 1 EN 61643-11 Type 1 EN 61643-11 Type 1
PRD1 25r Type 1 + 2
Type 2 IEC 61643-1 T2. - IEC 61643-1 T2. -
1P 4 25 40 25 1.5 230 350 16329 EN 61643-11 Type 2 EN 61643-11 Type 2
1P+N 8 25/100 N/PE 40 25 1.5 230/400 350 16330 Certification CE KEMAKEUR, CE KEMAKEUR, CE CE
3P 12 25 40 25 1.5 230 350 16331
3P+N 16 25/100 N/PE 40 25 1.5 230/400 350 16332
PRD1 Master Type 1
1P 4 25 - 25 1.5 230 350 16360
1P+N 8 25/100 N/PE - 25 1.5 230/400 350 16361
3P 12 25 - 25 1.5 230 350 16362
3P+N 16 25/100 N/PE - 25 1.5 230/400 350 16363
Spare cartridge
C1 Master-350 - 4 - - - 25 1.5 - 350 16314
C1 25-350 - 23 mm - - - 25 1.5 - 350 16315
C2 40-350 - 12 mm - - - 20 1.4 - 350 16316
C1 Neutral-350 - 4 - - - - - - 350 16317
Accessories
DB123370
4 5
Protection iPRF1 12.5r/PRF1 Master/
Load protection
PRD1 25r/PRD1 Master
Type 1 and 2 LV surge arresters (cont.)
Dimensions (mm)
74
DB123928
DB123927
36 7 44 30
46.5 151.5
PRD1 Master
DB123930
PRD1 25r
6 7
Protection iPRD surge arresters Protection iPRD surge arresters
Load protection Type 2 or 3 LV withdrawable surge Load protection Type 2 or 3 LV withdrawable surge
arresters arresters (cont.)
DB122942
DB122943
replacement of damaged
cartridges.
Nominal discharge name of 9 mm voltage operating voltage
current (In) network
CM* DM* CM* DM*
Incoming Secondary 1P+N 3P+N 1P 2P 3P 4P L/t N/t L/N L/t N/t L/N
65 kA / 20 kA iPRD65
PB105274-35
Type Spare cartridges for Cat. no Type of surge arrester Associated circuit breaker
C 65-460 iPRD65r IT A9L16682 iPRD65 Curve C 50 A
C 65-340 iPRD65r A9L16681 iPRD40 Curve C 40 A
C 40-460 iPRD40r IT A9L16684 iPRD20 Curve C 25 A
C 40-340 iPRD40, iPRD40r A9L16685 iPRD8 Curve C 20 A
C 20-460 iPRD20r IT A9L16686
C 20-340 iPRD20, iPRD20r A9L16687
C 8-460 iPRD8r IT A9L16688
C 8-340 iPRD8, iPRD8r A9L16689
Cartridge C neutral All products A9L16691
8 9
Protection iPRD surge arresters Protection iPRD surge arresters
Load protection Type 2 or 3 LV withdrawable surge Load protection Type 2 or 3 LV withdrawable surge
arresters (cont.) arresters (cont.)
DB122945
DB122946
6.5 mm
2P 220
PZ2
3P 340
4P 450
iPRD 2 N.m 2.5 to 25 mm2 2.5 to 16 mm2
Dimensions (mm)
DB123596
Technical data
Main characteristics
Operating frequency 50/60 Hz
Operating voltage (Ue) 230/400 V AC
Permanent operating current (Ic) < 1 mA
Response time < 25 ns
1P 1P+N
End of life indication: by mechanical White In operation 2P
indicator Red At end of life
End of life remote indication By contact NO, NC 250 V / 0.25 A
Additional characteristics
Operating temperature -25°C to +60°C
Type of connection terminals Tunnel terminals, 2.5 to 35 mm²
Standards IEC 61643-1 T2 and EN 61643-11 Type 2
3P 3P+N
4P
10 11
Protection iPF surge arresters Protection iPF surge arresters
Load protection Type 2 or 3 LV surge arresters Load protection Type 2 or 3 LV surge arresters (cont.)
The iPF multi-pole single-piece surge arrester range is Each surge arrester in the range has a specific application:
adapted for earthing systems: TT, TN-S, TN-C. bb incoming protection (type 2):
Type 2 surge arresters are tested with a 8/20 μs current vv the iPF65(r) is recommended for a very high risk level (strongly exposed site)
wave. vv the iPF40(r) is recommended for a high risk level
Type 3 surge arresters are tested with a 12/50 μs and vv the iPF20 is recommended for a medium risk level
8/20 μs combined wave. bb secondary protection (type 2 or 3):
vv the iPF8 ensures secondary protection of loads to be protected and is placed in
cascade with the incoming surge arresters. This surge arrester is required when the
loads to be protected are at a distance of more than 30 m from the incoming surge
arrester.
The iPF surge arresters with “r” indication have remote transfer of the information:
“surge arrester to be replaced”.
Rated discharge Type of protection Network Earthing Transfer Surge Width Up - (kV) Un - (V) Uc - (V)
current (Imax) / system arrester in mod. Voltage protection level Rated Maximum continuous
DB122942
DB122943
Nominal discharge name of 9 mm voltage operating voltage
current (In) network
CM* DM* CM* DM*
Incoming Secondary 1P+N 3P+N 1P 2P 3P 4P L/t N/t L/N L/t N/t L/N
(type 2 or 3)
65 kA / 20 kA iPF65
iPF65 A9L15683 TT & TN iPF65 1P 2 y 1.5 - - 230 340 - -
PB105278-35
12 13
Protection iPF surge arresters Protection iPF surge arresters
Load protection Type 2 or 3 LV surge arresters (cont.) Load protection Type 2 or 3 LV surge arresters (cont.)
DB122945
DB122946
PZ2 3P 335
4P 420
iPF8 / 20 Ph / N 1.2 N.m 16 mm2 max. 10 mm2 max.
t 2 N.m 25 mm2 max. 16 mm2 max.
DB123595
1P 1P+N 3P
2P 3P+N
4P
Technical data
Main characteristics
Operating frequency 50/60 Hz
Operating voltage (Ue) 230/400 V AC
Permanent operating current (Ic) < 1 mA
Response time < 25 ns
End of life indication: Green In operation
by green/red mechanical indicator Red At end of life
End of life remote indication By contact NO, NC 250 V / 0.25 A
Additional characteristics
Operating temperature -25°C to +60°C
Type of connection terminals Tunnel terminals, 2.5 to 35 mm²
Standards IEC 61643-1 T2 and EN 61643-11 Type 2
14 15
Protection iPRC, iPRI surge arresters Protection iPRC, iPRI surge arresters (cont.)
Load protection Load protection
Analogue telephone line protection: the iPRC surge arrester wired in series to the
private installation input protects the telephones, the PABX, the modems Connection
DB116619
DB122584
torque Rigid Flexible or ferrule
Country approval pictograms Protection for 2 low-current lines without common potential or 4 lines with 8 mm
common reference potential: the iPRI protects the measuring instrument and PLC
"sensor" inputs and the DC power supply inputs up to 53 V and AC power supply 3 mm
DB122945
DB122946
Protection against overvoltages related to lightning inputs up to 37 V.
strikes. The input current must not exceed 300 mA.
PB104270-35
DB122585
DB126523
10 4
L'1 L1 L'2 L2
DB123309
Technical data
Main characteristics
iPRC iPRI
Number of protected lines 2 2
A9L16337 A9L16339
Test category IEC/VDE C1, C2, C3, D1, B2 C1, C2, C3, D1, B2
Clip on DIN rail 35 mm.
Maximum continuous voltage (Uc) 180 V DC, 130 V AC 53 V DC, 37 V AC
Db122624
L'1 L1 L'2 L2
3 3 Limitation voltage (Up) 300 V 70 V
Rated discharge current (8/20) (In) 10 kA 10 kA
DB123300
Line L1 Cables 7-8 Line L1 Cables 5-6 Maximum discharge current (8/20) (Imax) 18 kA 10 kA
Line L2 Cables 11-12 Line L2 Cables 11-12 Response time < 500 ns y 1 ns
– – Line L’1 Cables 1-2 Nominal impulse current 100 A 70 A
– – Line L’2 Cables 7-8 Rated current (IN) 450 mA (up to 45°C) 300 mA (up to 45°C)
t Cable 3 t Cables 3-4-9-10 Series resistor 2.2 Ω 4.7 Ω
IN Ligne side IN Ligne side End-of-life information by Loss of dialling tone Loss of transmission
Catalogue numbers OUT Protected side OUT Protected side ± 30° vertical. Additional characteristics
Surge arresters iPRC iPRI Degree of protection Device only IP20 IP20
Mains voltage (Un) <130 V AC 48 V DC Device in modular IP40 IP40
Analogue telephone system bb – IP20 IP40 enclosure
DB123311
IK 05 05
Telephone transmitter bb – IK05 IK05 Operating temperature -25°C to +60°C -25°C to +60°C
Digital telephone system – bb
Storage temperature -40°C to +85°C -40°C to +85°C
Automation network – bb
VLV load power supply (12…48 V) – bb
xDSL compatibility bb –
Cat. no.. A9L16337 A9L16339
Width in 9 mm modules 2 2
Weight (g)
Diagrams Surge arresters
Type iPRC iPRI
DB122600
25 65
iPRC
3
Dimensions (mm)
66
DB122585
18 52
iPRI
Position
switches
90 45
iPRI
Analog
sensors
16 17
Protection iPRD-DC surge arresters Protection iPRD-DC surge arresters
Load protection Withdrawable surge arresters type 2 for Load protection Withdrawable surge arresters type 2 for
photovoltaic applications photovoltaic applications (cont.)
DB124057
UTE C 61740-51 T2 Rigid Flexible or ferrule
Country approval pictograms 14 mm
prEN 50539-11 T2 6.5 mm
DB122945
DB122946
PZ2
PB107585-40
iPRD-DC direct current surge arresters are designed to protect against overvoltages iPRD-DC 2 N.m 2.5 to 25 mm2 2.5 to 16 mm2
due to a lightning strike: of the "DC" input to the inverter and of photovoltaic panels.
DB124049
Catalogue numbers
Internal diagram Imax (kA) In (kA) Up (kV) UCPV (V) (1) Width in Cat. no.
Maximum Nominal Protection level Maximum steady state module of
discharge discharge voltage 9 mm
current current
L+/t L-/t L+/L- L+/t L-/t L+/L-
iPRD-DC40r 600PV
40 15 1.6 1.6 2.8 600 600 840 6 A9L16434 10 m iPRD-DC
DB124051
Generator
Conversion
iPRD-DC40r 1000PV
40 15 3.9 3.9 3.9 1000 1000 1000 6 A9L16436
DB124052
iPRD-DC
2
10 m
(1) Ucpv u 1.2 x Uoc stc (Uoc stc: maximum no-load voltage of the photovoltaic generator "photovoltaic module manufacturer's data")
Replacement cartridges
PB107586-30
PB107587-30
Replacement cartridges
18 19
Protection iPRD-DC surge arresters Practical Advice Photovoltaic
Load protection Withdrawable surge arresters type 2 for Examples of installation architectures
photovoltaic applications (cont.)
Technical data The examples of photovoltaic installation architectures presented in this document
DB123310
illustrate the use of direct current circuit breakers dedicated to protection of the
Main characteristics modules and cables of the PV strings, to protect against overloads and short circuits.
Type of network Isolated direct current To ensure the safety of the photovoltaic installation it is necessary, in the cases
Temps de réponse < 25 ns described below, to combine the C60PV-DC circuit breaker with other protective or
fault detection devices on the DC side.
Short circuit current (ISCPV) 30 A
Type of surge arresters Type 2
Clip on DIN rail 35 mm. End-of-life indication mode Circuit opened by integrated thermal
disconnector
Additional characteristics
Installation from 10 to 100 kW - Ue y 800 V DC
DB123312
DB404761
By the NO/NC remote indication contact 250 V AC / 0.25 A Private domain Public domain
Indifferent position of installation. Operating temperature -25°C to +60°C Earthing TT TNS IT
Storage temperature -40°C to +85°C systems PV PV modules protective DC protective
Inverter
Tropicalization (IEC 60068-1) Treatment 2 (relative humidity b b - modules enclosure enclosure AC protective enclosure
integral
transformer C60PV-DC iDPN Vigi
2P
Installation at Without
DC end earthed C60PV-DC
polarity
Weight (g) Insulation - iPRD PV-DC iPRD PV-DC
monitoring
Surge arresters device
iDPN Vigi
C60PV-DC C60NA-DC 2P
C60PV-DC
C60PV-DC
20 21
Practical Advice Photovoltaic (cont.) Practical Advice Photovoltaic (cont.)
Examples of installation architectures Examples of installation architectures
DB404764
Installation from 10 to 100 kW - Ue y 800 V DC Earthing TT TNS IT
PV PV modules DC protective
systems Inverter AC protective enclosure
modules protective enclosure enclosure
In the case of a PV architecture without an earthed polarity on the DC side and with a PV inverter or with galvanic isolation, it is necessary to:
bb protect each string of photovoltaic modules with a C60PV-DC installed in the junction box near the PV modules;
b b -
C60PV-DC
IMD IM20
C60PV-DC
22 23
Practical Advice Photovoltaic (cont.) Practical Advice Photovoltaic (cont.)
Examples of installation architectures Examples of installation architectures
DB404765
C60PV-DC Earthing TT TNS IT modules protective enclosure DC protective enclosure
Inverter With integral systems
Installation at
transformer
Without
C60PV-DC
NSX100-
200NA DC-PV
NSX80-
200DC-PV
- -
b C60PV-DC NSX80-200DC PV
iPRD PV-DC
C60PV-DC
C60PV-DC NSX80-200DC PV
NSX100- NSX80-
C60PV-DC
200NA DC-PV 200DC-PV
NSX100-
C60PV-DC 200NA
C60PV-DC DC PV
C60PV-DC
iPRD PV-DC
iPRD PV-DC
24 25