2 | Air Humidifiers

Air Humidifier DVX


For DV Air Handling Units

• High humidification efficiency


• Maximum performance with minimum operating cost
• Simple to install and easy to service

Operating principle Construction


The operating characteristics of DVX series HEF2 are standard components
based on the natural effect of water evaporation when air • Water basin, side and top frames
stream passes over a wet surface. Air picks up water • Automatic float water filling valve
vapour which decreases the air temperature since the • Overflow and deconcentration device
heat of evaporation comes from the air. This principle • Drain and overflow nozzles
ensures that a gas to air mixture occurs without any liquid • Water pump
water being released. Only when carry over occurs, water • Water level (pneumatic/electric) switch
droplets would be released to the air stream. This is the • Watering & bleed-off piping
major difference between the media pad and water spray • Water flows control valves
humidifiers; providing a correct air velocity or mounting • Evaporative media pad cassettes.
integral droplets separator will handle this.
Operating data
Media pad • Minimum size of air handling unit
DVX humidifiers are available with two different media pad • Process airflow: N1, m3/h
materials: • Humidification efficiency: N2, %
• The CelPad are basically cellulose paper impregnated • Pressure drop: N3, Pa.
with chemicals to provide stability and wettability. The
corrugated and cross channels configuration ensures an
expanded surface in contact with the air for water
­evaporation, together with minimum air resistance. The
material is combustible but it represents an economically
priced option.
• HU-CELL pads are fibreglass sheets with wetting agents
and water adsorbent additives. Using the same corru­
gated and cross channel configuration as the CelPad; the
media has a compact structure maintaining optimum
­performance at low pressure drop. As HU-CELL pads are
inorganic, they are incombustible. It’s inorganic compound
makes it odourless. HU-CELL media contains a small
amount of silver ion which acts as a biocide to prevent
fungus and also helps any water deposits to release from
the media allowing it to stay clean.

Both types of pads are assembled in sheet steel frames


with an integral watering system and handle to enable
them to be easily serviced.
Air Humidifiers | 3

Installation example

Into an air handling unit


The DVX evaporative humidifier
series HEF2 is usually incorporated
into an air handling unit after the pre-
heating coil and before the cooling
coil, as illustrated in the photo. The
humidifier is serviced down stream.

Modular system
The DVX humidifier can be delivered
in modules to build any size of
“humidification bank” into a large air
handling unit for big airflows,
as illu­strated in the photo.

Main typical applications


• Comfort air conditioning systems in office buildings, hotels, shops, etc.
• Air evaporative coolers for industrial halls summer refrigeration.
4 | Air Humidifiers

DV Air handling unit


with single heating coil

DV Air handling unit with single heating coil 1. The air is heated up from -3 °C and 40% RH through
The performance control can be achieved by an ON-OFF the rotary heat exchanger and furthermore through the
hygrostat acting on the pump motor contactor. heating coil until the desired temperature is reached.

The evaporative process into the Mollier chart 2. N


 ow the air has a RH of 3% and a temperature of 40 °C.
The illustration on page 5 shows an example of the usual As the air passes through the humidifier, the saturated
design process for humidification into the Mollier chart: pads of the humidifier pass on the moisture to the air.
Starting from outside air at -3 ºC and 40% RH to achieve This changes both the humidity of the air as well as the
air at 22 ºC and 50% RH. temperature.

Single heating coil + humidification 3. E


 nding with 22 °C and 50% RH by following the
See illustration with 1-2-3 on page 5. enthalpy lines in the Mollier chart.

This example has absolute humidity increase How to choose in SystemairCAD


from 1.5 g/kg to 8 g/kg. When choosing the design with one heating coil, it can be
difficult to reach 100% accurate end temperature and
With a single heating coil you will need to heat up the air humidity. If this is the chosen solution you may have to
to a high starting temperature before the humidification. change the CelPad thickness or even change the media
This will allow you to end up with the desired air charac- pad to a HU-CELL material. This will always be a balance
teristics. of choosing the correct humidifier material and the correct
starting temperature before humidification. The selection
can be made in the SystemairCAD and calculated instantly
to find the leaving air conditions of the AHU.
Air Humidifiers | 5

1 2 3

Mollier chart for moist air for p = 1 bar


40000

20000

00

00
00

00

00
1600

100

00
120
140

80
90

70
5

Relative humidity [%]


80

1,00

00
60
10
70

00
15 55

60
1,05
20
00
50
50
30

2
1,10 00
40 45
40
50

60
0
70 400
1,1530 80
Density [kg/m3]

90

3
100

3500
20 70
65
1,20 60
55 ]
50 h[ kJ/kg
alpy
45
ific enth
40 Spec 3000
10
35
1,25 30
25
20
0 2500
15
Air temperature [°C]

10
1,30
5

-10
1 -5
0 2000

-16

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
10 1500
Water vapour content [g/kg] -10 0 00
00
Mollier chart for moist air for p = 1 bar
6 | Air Humidifiers

DV Air handling unit


with two heating coils

The evaporative process into the Mollier chart 2. N


 ow the air has a RH of 4% and a temperature of 34 °C.
The illustration on page 7 shows an example of the usual As the air passes through the humidifier, the saturated
design process for humidification into the Mollier chart pads of the humidifier pass on the moisture to the air.
with 2 heating coils (pre- and post heating): Starting from This changes both the humidity of the air as well at the
outside air at –3 °C and 40% RH to achieve air at 22 ºC temperature.
and 50% RH.
3. E
 nding with 17 °C and 70% RH by following the
Pre-heating + humidification + post heating enthalpy lines in the Mollier chart.
See illustration with 1-2-3-4 on page 7.
4. After passing through the post heating coil the tempe­
This example has absolute humidity increase from rature rises to the end conditions of 22 °C and 50% RH.
1.5 g/kg to 8 g/kg.
How to choose in SystemairCAD
With two heating coils you can accept a lower starting If this is the chosen solution you may have to change the
temperature before the humidification. The reason is that CelPad thickness or even change the media pad to a
if the air temperature is lower after the humidification HU-CELL material. You will also have the possibility to
than desired, you have the possibility to heat up the air in change the starting temperature to reach your desired
order to end up with the desired air characteristics. leaving air conditions. Here you will have the possibility
not only to change the humidifier material but also the
1. The air is heated up from -3 ºC and 40% RH through temperatures. This solution ensures you more possibilities.
the rotary heat exchanger and furthermore through the However, it is also more demanding for the control
pre-heating coil until the desired temperature is ­system. The selection can be made in the SystemairCAD
reached. and calculated instantly to find the leaving air conditions
of the AHU.
Air Humidifiers | 7

1 2 3 4

Mollier chart for moist air for p = 1 bar


40000

20000

00

00
00

00

00
1600

100

00
120
140

80
90

70
5

Relative humidity [%]


80

1,00

00
60
10
70

00
15 55

60
1,05
20
00
50
50
30

1,10 00
40 45
40

2
50

60
0
70 400
1,1530 80
Density [kg/m3]

90

4
100

3500
20 70
65
1,20 60
55 ]
50 h[ kJ/kg
alpy

3
45
ific enth
40 Spec 3000
10
35
1,25 30
25
20
0 2500
15
Air temperature [°C]

10
1,30
5

1
-10 0 2000
-5
-16

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
10 1500
Water vapour content [g/kg] -10 0 00
00
Mollier chart for moist air for p = 1 bar
EC_ventilatorer.dk.06.2011-V2
AirHumidifiers_uk_02_2014-V1-90935100

Systemair A/S
Ved Milepælen 7
DK-8361 Hasselager

Avedøreholmen 50
DK-2650 Hvidovre

Tel. +45 87 38 75 00

mail@systemair.dk
www.systemair.dk

You might also like