You are on page 1of 8

Journal of Constructional Steel Research 62 (2006) 295–302

www.elsevier.com/locate/jcsr

A moment resisting connection for earthquake resistant structures


Sean Wilkinsona,∗, Gordon Hurdmanb, Adrian Crowtherb
a School of Civil Engineering and Geosciences, University of Newcastle, Newcastle upon Tyne, NE1 7RU, UK
b Arup (Newcastle Office) Central Square, Forth Street, Newcastle upon Tyne, NE1 3PL, UK

Received 24 January 2004; accepted 28 July 2005

Abstract

This paper proposes a new moment resisting detail for use in earthquake resistant structures. The wedge detail tested in this project is
a new design that builds upon the idea of inducing a plastic hinge away from the column face to dissipate the energy that would otherwise
yield the connection. The plastic capacity of the beam is locally reduced by decreasing the depth of the web and reforming the flange to the
new beam profile. This makes the section more plastic, so reducing the buckling problem suffered by other reduced section joints.
Laboratory testing shows that the joint is capable of plastic rotations greater than 0.05 rad without any significant loss of energy dissipation
capability, which is far in excess of the requirements for a joint given by the latest standards based on post-Northridge data.
© 2005 Elsevier Ltd. All rights reserved.
Keywords: Earthquake resistant; Moment resisting; Connection; Seismic detail; Experimental; Cyclic loading

1. Introduction occurred, the damage to the welded SMRF buildings was


so severe in some cases that all of the moment resisting
Earthquakes produce some of the most violent loading connections at one or more floors failed. Over 150 steel
situations that a structure can be subjected to and if a buildings have been identified as being damaged from the
structure fails under these loads then inevitably human life earthquake, most of which were built in accordance with the
is put at risk. One of the most common methods by which code and standards of practice at the time [1].
a structure fails under seismic loading is at the connection Post-Northridge, there was a significant loss of confi-
between beam and column. This type of failure can result in dence in the way in which steel moment resisting framed
a loss of structural integrity and the collapse of floors, if not buildings were designed and several alternatives to welded
whole buildings. connections for steel frames have been proposed. A welded
Before the Northridge earthquake on the 17th of January connection alone is no longer considered safe by most build-
1994, welded steel moment resisting frames (SMRF’s) were ing codes; instead there is a requirement for the designer to
commonplace in areas of seismic activity in the US. The demonstrate the adequacy of the connection detail by either
fully welded beam to column connection was used in full scale testing or calculations based on test data. This pa-
seismic areas not only because of its economic and versatile per discusses some of the joint detail alternatives in use and
nature but because it was assumed that the connection under consideration, highlighting their strengths and weak-
would possess a high plastic deformation capacity. In nesses. It then proposes and tests the seismic performance of
the Northridge earthquake this assumption was proved a new connection detail for steel moment resisting frames.
wrong when brittle cracking of the welded beam–column
connections was widely observed. Although no casualties 2. Standard connections
were sustained and no complete collapses of buildings
2.1. Welded connection

∗ Corresponding author. A typical pre-Northridge welded connection detail can


E-mail address: s.m.wilkinson@ncl.ac.uk (S. Wilkinson). be seen in Fig. 1. A hole in the beam web around each

0143-974X/$ - see front matter © 2005 Elsevier Ltd. All rights reserved.
doi:10.1016/j.jcsr.2005.07.011
296 S. Wilkinson et al. / Journal of Constructional Steel Research 62 (2006) 295–302

Since the Northridge earthquake, the assumption that


a welded connection possesses the required deformation
capacity has been proven to be inaccurate and welded
connections alone are now no longer considered safe in areas
prone to seismic activity.
2.2. Bolted end plate connections

To test their compatibility for use in structures likely to


experience seismic events, the reliability and performance
of bolted end plate connections under cyclic loading have
also been examined. The bolted end plate connection allows
rapid construction on site, is cheap and is convenient.
Fig. 1. Pre-Northridge welded connection detail (after Roeder and Foutch [7] have carried out testing on end plate connections, the
[5]). experimental procedure for which has formed the basis of
the laboratory tests used in this project and is described in
flange allows access for welding equipment so that a full detail later.
penetration weld between the beam flange and column Three failure mechanisms for end plate connections are
flange can be provided. A shear tab is commonly used to outlined in [8].
connect the beam web to the column and is usually bolted to These failure mechanisms are defined as follows:
the beam web on site. This type of connection is simple to • Mode 1: plastic hinges form at the bolt line and the beam
fabricate and economical, and subsequently has been widely web.
used in America since the 1970’s. • Mode 2: plastic hinges form at the beam web followed by
Numerous failure modes were exhibited by the welded yielding of the bolts.
connections in the Northridge Earthquake. The most • Mode 3: yielding of the bolts whilst the end plate remains
common mode of failure was brittle fracture initiated within elastic.
the connection, usually in the full penetration weld between Mode 1 joints are expected to possess the highest ductility
the bottom flange of the beam and the column flange. To but the lowest stiffness and moment capacity. Mode 3 joints
the surprise of the engineers some of these fractures actually are expected to have the highest stiffness and moment
initiated whilst the structure remained in its elastic range [2]. capacity but are subject to sudden brittle fracture without
It is estimated that the buildings may have been designed warning. Mode 2 joints have an intermediate moment
to be 4–8 times the required strength in order to satisfy capacity, stiffness and ductility.
stringent storey drift ratios and, as such, plastic hinges could During the testing all three modes of failure were
not form in the beams under the loading scenario applied [1]. observed depending on the thickness of the end plate and
Each of the failure modes identified has been recreated the bolt grade and size used in each case.
under laboratory testing and the majority have been shown to The study concluded that the end plate connection is
be very brittle, with failure occurring before any significant suitable for use in areas of low to medium seismicity as
yielding of the connection [3]. This shocked designers, it possesses a stable cyclic response, but only has limited
who had assumed that the welded connection possessed moment capacity. The major failure mode in end plate
a high plastic deformation capacity. However, a statistical connections tested was slipping of the bolt threads.
analysis of all cyclic test data from 1970 to 1993 on welded
beam–column connections showed that they possessed an 2.3. Reinforced connections
average of 0.009 rad of plastic rotation capacity before
brittle fracture [3]. In the 1970’s this type of connection was Reinforcing the connection to prevent the brittle fractures
tested several times in the laboratory [4] with the conclusion found in welded connections is a method commonly used to
generally being that this connection showed good ductility combat the problem. The strengthened section of the beam
under cyclic loading. Later tests however, such as those forces the plastic hinge to form in the beam away from the
carried out by [5], have shown the connection to have poor column face and dissipate the energy from the earthquake
hysteretic behaviour [2]. away from the vital beam–column connection. Several types
Reasons for the poor performance of these welded of reinforcement detail have been proposed, both for use in
connections are cited as: upgrading existing welded connections and for use in new
buildings.
• Poor workmanship (weld defects).
• Poor detailing (producing stress concentrations at the root 2.3.1. The haunch
or toe of the weld). Perhaps the most common method of increasing stiffness
• Substandard materials (low toughness weld material). at joints, the haunch has become standard in steel frames to
• Unusually high seismic input (high strain rates) [6]. increase depth at beam to column connections.
S. Wilkinson et al. / Journal of Constructional Steel Research 62 (2006) 295–302 297

Fig. 2. Triangular haunch detail (after Naeim [9]).

Fig. 4. Column tree connection.

Fig. 3. Rib plates (after Naeim [9]).

Various types of haunch have been suggested and tested


under laboratory conditions, the most promising of which
is the inverted T-section haunch. Rib plates have also
been used as a method for reducing stress on the welded
beam–column connection. These details are shown in Figs. 2
and 3 respectively.
Fig. 5. The cover plate method of strengthening beam to column connection.
2.3.2. The “column–tree” connection
The reinforced column–tree connection has reinforced
beam stubs attached to the column in the workshop and the
central section of the beam is added on site by welding or A welded beam to column connection is still preferred to a
bolting. The stub is reinforced by the addition of side and bolted one as this reduces the required thickness of the cover
cover plates as shown in Fig. 4. plates [9]. Although laboratory tests have been carried out on
connections using cover plates, and plastic rotations greater
2.3.3. Cover plates and flange plates than 0.03 rad have been obtained, about 20% of samples
Cover plates (as shown in Fig. 5) have become one of the failed to reach this target before brittle fracture around the
most common alternatives since the Northridge earthquake. welds [9].
The bottom flange of the beam is reinforced using a The flange plate connection is much the same as the
rectangular cover plate wider than the beam flange and the cover plate connection with the exception being that only
top flange is reinforced using a tapered cover plate thinner the flange plate is welded to the column face, not the beam.
than the beam flange. This enables down hand welding In this respect the flange plates are much thicker than the
(welding from above) to be carried out, in both cases leading cover plates but the bottom flange can be shop welded to the
to a stronger weld, and if the bottom plate is welded to the column. This removes the need for one of the on site welds,
column before the beam is offered up to the column then it which are linked to producing a notch effect connected with
can act as a construction seat speeding the erection process. brittle fractures such as those found at Northridge.
298 S. Wilkinson et al. / Journal of Constructional Steel Research 62 (2006) 295–302

Fig. 7. Tapered and circular (“dogbone”) flange profiles for reducing the
plastic moment capacity of the beam (after Naeim [9]).

Fig. 6. Post-tensioned connection with angles designed to be replaced after


1. Overall construction time will be significantly increased
yielding under seismic load (after Ricles et al. [2]). because of the complexity of the system (the time
required to fit and tension the cables) which will offset
any savings in terms of materials.
The problem with haunches and cover plates is that while
they increase the stiffness of the beam–column connection, 2. Tensioning of cables is dangerous and requires specialist
forcing a plastic hinge to form away from the column face, contractors.
this increase in stiffness also attracts increased moment 3. If every angle at every connection in the structure fails
to the column and connection, which in turn need to be then the structure essentially becomes a mechanism.
increased in size accordingly. 4. The cables will need to be serviced and re-tensioned
regularly in order to retain the required tensile force (lost
2.4. The post-tensioned connection in creep).
5. The holes drilled in the column to accommodate the steel
A more theoretical than practical design, the post- fibres weaken the column about the floor level where
tensioned method (shown in Fig. 6) utilises the tensile and the column experiences its greatest values of bending
rotational capacity of steel cables to provide a “safety net” moment. This increases the probability of failure in the
for the beam once a lightweight angle connection to the column, which is potentially more dangerous than a
column fails under earthquake loading. This lightweight failure of beam or connection.
angle can then be replaced and the building repaired quickly
and easily. 2.5. Reduced section beams (RBS)
Advantages of the PT steel connection are cited as:
1. Field welding is not required. The main problem with the stiffening of the joint is that
2. The connection is made with conventional materials and stiffness attracts moment and increasing the moment at the
skills. column could induce failure in the column (especially in the
3. The connection has initial stiffness similar to that of a case of a retrofit). Column failure is potentially more serious
typical welded connection. than the failure of the unimproved connection because it is
4. The connection is self-centring without residual deforma- more likely to lead to a collapse mechanism.
tion, so the SMRF will not have residual drift after an One of the provisions of a connection in a SMRF is that it
earthquake if significant residual deformation does not must possess sufficient strength to induce the plastic hinge in
occur at the base of the columns. the beam before it fails. Rather than stiffening the connection
5. The beams and columns remain essentially elastic while between the column and beam this can be achieved by
inelastic deformation (and damage) of the connection reducing the plastic capacity of the beam section away from
provides energy dissipation. the column face to induce the plastic hinge at a point chosen
6. Significant damage to the SMRF is contained to the by the designer rather than forcing it away using stiffeners.
angles of the connection. This will have the advantage of requiring less construction
7. These angles can be easily replaced [2]. time on site and using less material to produce a neater and
smaller connection. Two methods of reducing the plastic
However, there are many disadvantages of this type of moment of the beam have been suggested previously: cutting
system, such as: of the flanges as shown in Fig. 7 and drilling of the flanges.
S. Wilkinson et al. / Journal of Constructional Steel Research 62 (2006) 295–302 299

Drilling of the flanges involves, as its name implies,


simply drilling material out of the flange around where the
hinge is to be induced to give an overall section with the
same dimensions as previously but with less cross sectional
area.
Both of the above methods reduce the plastic capacity
of the beam section through a reduction in the areas of
the flange. This has the desired effect of inducing a plastic
hinge away from the column face and thus preventing
a failure at the connection. However, in addition to the
reduction in plastic capacity there is also a reduction in
the in-plane stiffness of the beam, decreasing the lateral
torsional stability of the section about that point and hence
buckling may become a significant problem. This has been
proven to be the case and “the reduced beam section usually
experiences web local buckling first, followed by lateral
torsional buckling and finally flange local buckling” [9].
Although this may seem to prove that lateral torsional Fig. 8. Geometry of the wedge detail.
stiffness is not the major contributor to buckling for
reduced section beams (RBS), the problem of lateral where σ y is the yield stress of the material. So if the section
stability becomes much more apparent in the jumbo sections depth is reduced to induce the plastic hinge, this has the
employed to limit storey drift in tall buildings in seismic advantage of reducing the plastic moment capacity of the
regions. The amplitude of the lateral torsional buckling tends section much faster than when tapering the flanges and with
to be larger when the RBS is used, giving rise to twisting in less change in the overall properties of the beam under
the columns, which when jumbo sized can be more prone normal loading situations. The beam is also made more
to twisting than smaller, compact ones. Ref. [9] suggests compact and thus less likely to undergo lateral torsional
that in these cases lateral bracing around the RBS should buckling, one of the problems associated with the “dogbone”
be provided. connection detail.
Hence the proposed joint detail will take the form of a
beam with a wedge removed from the web and the flange
3. A proposal for a new connection detail—the wedge reattached to produce a profile such as that shown in Fig. 8.
design The geometry of the beam was chosen such that the hinge
point would be located at a distance equal to the beam
From the previous discussion it can be seen that the depth away from the column face. The depth of the section
most common way of providing resistance to seismic load was therefore designed for the moment at this location. By
is increasing the stiffness of the beam–column connection, equating the moment at the desired hinge point with the
such as by the addition of a haunch or plates. This type equation for plastic moment capacity of the section, the
of detail is recommended in Eurocode 8 [8] on design for reduced depth can be calculated. Since the beam stub tested
seismic activity. The proposed connection method, like the for this paper was a 254 × 102 × 22 UB and was tested in the
“dogbone” style of connection, uses a reduced beam section configuration of a cantilever of 1.5 m length, the appropriate
to induce a plastic hinge away from the column face before depth of the section at a distance equal to 254 mm away from
the connection reaches its ultimate moment. This has the the column face is 200 mm.
advantage of reducing the complexity of the connection, The actual geometry of the wedge detail used in the
hence reducing construction time and potentially cost. experiment is shown in Fig. 8.
Unlike the “dogbone” connection, which reduces the
flange width to reduce the plastic moment capacity of the
4. Experimentation
beam section, the proposed design will reduce the depth
of the web at the point where the plastic hinge will be
The wedge beams were constructed using the following
induced. The plastic modulus of a universal beam section is
procedure.
proportional to the square of the depth of the section but only
As the removed flange section was being shaped to fit
linearly proportional to the width of the flange. Therefore,
the web of the wedged beam, a provision for the shortening
reducing the depth of the section has a greater effect on the
of the flange was provided (i.e. the wedge was cut 20 mm
plastic modulus than reducing the width of the section.
further into the beam web than was required). Thus the beam
The plastic moment capacity of the section is given in
could be cut at the end of the wedge and the end plate fitted
Eq. (1):
flush with the end of the beam with the full beam depth at
M p = Z p σy (1) the bottom flange.
300 S. Wilkinson et al. / Journal of Constructional Steel Research 62 (2006) 295–302

these deflections for two cycles for each value of plastic


rotation required. Plastic rotation was measured using the
same method as in [7], i.e. the assumption was made that
after the formation of the plastic hinge the predominant
form of displacement would be in rotation about a plastic
hinge at the reduced section and that bending of the beam
would be negligible. Thus tip deflection could be used as an
appropriate form of measurement for rotation.
Loading proceeded with two cycles being performed for
each specified rotation until local buckling at the hinge point
became extremely severe, after which the beam was loaded
upward to ultimate failure and testing ceased. Testing of the
beam is shown in Fig. 10.

Fig. 9. Basic experimental set-up (jack shown in both positions). Numbers


represent the approximate positions of the LVDT’s used. 5. Results

The full hysteretic response curve for specimen 2 can be


The experimental apparatus is shown in Fig. 9 and seen in Fig. 11. The points labelled on this graph are referred
includes a reaction frame, two single-acting hydraulic to in the following text using terms in square brackets,
jacks, a load cell, linearly variable differential transform- e.g. [H].
ers (LVDT’s, displacement gauges) and a data logging com- With the beam stabilised from lateral failure modes the
puter. LVDT’s measured displacements at four locations. performance of the stub with respect to local yielding could
Two LVDT’s were used in unison to measure tip displace- be observed. At the minimum required plastic rotation for
ments (1 and 3) because the range of displacement at the acceptability as a connection for use in seismic areas (of
tip was in excess of the range of measurement of a single 0.03 rad) there was little local deformation of the beam.
LVDT. One LVDT measured displacement at the mid-span [A] The beam web showed signs of slight straining with the
of the beam past the hinge point (2) and one measured dis- beginnings of web buckling, but of minimal magnitude.
placement above the position of the plastic hinge (4). In the first cycle of rotation to 0.04 rad [B], local buckling
After the Northridge earthquake the AISC Seismic of the beam web was observed as shown in Figs. 12 and 13.
Provisions were changed to require that [9]: This is thought to be the result of additional compressive
1. The design of beam–column joints and connections in force applied to the beam web as the wedge form undergoes
SMFs must be based on qualifying tests of at least two “pinching” at the peak of the removed section.
specimens. When the loading case was reversed and the beam was
2. Each connection must develop a plastic rotation of 0.03 pushed upward to a rotation of 0.04 rad this buckling was
rad. corrected as the wedge detail was stretched out [C].
In the second cycle of plastic rotation at 0.04 rad the
Thus the experimental program tested two identical buckling was much more severe. Local buckling of the
samples of universal beam sections with the wedge bottom flange of the beam at the peak of the wedge detail
removed. Each sample was cyclically tested to values of tip (“pinching”) occurred, increasing the web buckling [D].
displacement that are estimated to produce plastic rotation Buckling of the top flange of the beam began in the final
with an increasing increment of 0.01 rad. The results loading scenario of the second 0.04 plastic rotation cycle as
were collected using a data logging device that recorded shown in Fig. 14 and point [F] on Fig. 11. In the first and
each LDVT and the load cell at 2 s intervals. Load and only cycle of plastic rotation past 0.04 rad, the buckling of
displacement data were recorded for the duration of the test. top and bottom flanges and of the web became much more
prominent, to the extent that a full plastic region had formed
4.1. Testing of the connection and further testing would have been without gain as the
beam began to behave in a manner that would be unrealistic
Once the instrumentation was in place and had been in a building. The rotation of the beam was of such great
calibrated, the first specimen was tested. The elastic capacity magnitude that to approach anywhere near that degree of
of the beam around the hinge location was calculated and rotation in a real structure the columns would have had to
the beam stub was subjected to this load in a trial test run. undergo plastic deformation.
From the data obtained in this test, the tip deflection after
which the beam became plastic could be estimated. This 6. Conclusions
subsequently allowed the tip deflections necessary for each
increment of plastic rotation to be obtained. The beam stub The three criteria for a connection in an SMRF in a
was then subjected to cyclic loading that produced each of seismic area are:
S. Wilkinson et al. / Journal of Constructional Steel Research 62 (2006) 295–302 301

Fig. 10. Loading of the beam from above.

Fig. 11. Hysteretic response curve for specimen 2. Rotation based on corrected tip displacement.

1. The connection must possess sufficient strength to of the end plate to provide a fully rigid connection (the
develop the full plastic moment of the beam. end plate was used in this test as a convenient method of
2. The connection must possess sufficient stiffness to satisfy switching between beam specimens on the same column).
the assumption that it is a fully rigid connection. Finally, the hysteretic response curves for the specimens
3. The connection must have a large post-yield deformation show that the post-yield deformation capacity of the joint
capacity without significant loss of strength. is very large, with plastic rotations up to 0.05 rad being
observed without any loss of energy dissipation capacity.
In reducing the plastic modulus of the beam near the Furthermore, following the AISC guidelines for a joint
beam–column connection, these criteria are effectively met to be considered safe for use in a seismic area, at least two
by transferring the plastic hinge from the connection to the samples of the joint have been tested, with both samples
beam. The wedge detail induces a plastic hinge away from easily surpassing the minimum requirements of plastic
the column face, thus satisfying the first criterion. The end rotations of 0.03 rad.
plate connection is already assumed to be semi-rigid and The connection is simple to construct and has excellent
has been used for many years in moment resisting frames. seismic resistance properties. Furthermore it is particularly
Alternatively, a welded connection could be used in place useful for retrofitting of buildings as it does not increase
302 S. Wilkinson et al. / Journal of Constructional Steel Research 62 (2006) 295–302

Fig. 14. Buckled top flange under >0.05 rad plastic rotation upwards. [F].

in resisting lateral torsional buckling, as it has superior


torsional rigidity.
Fig. 12. Pinching of the wedge as seen in the second plastic rotation of 0.04
rad. References

[1] Mahin SA. Lessons from damage to steel buildings during the
Northridge earthquake. Engineering Structures 1998;20(4–6):261–70.
[2] Ricles JM, Sause R, Garlock MM, Zhao C. Post-tensioned
seismic-resistant connections for steel frames. Journal of Structural
Engineering, ASCE 2001;127(2):120.
[3] Stojadinovic B, Goel SC, Lee K-Y. Welded steel moment connections –
old and new. In: Avent RR, Alawady M, editors. Structural engineering
in the 21st century [Proceedings of the 1999 structures congress].
Structural Engineering Institute of ASCE; 1999.
[4] Popov EP, Stephen RM. Cyclic loading of full size steel connections.
Bulletin No. 21. Washington, (DC): American Iron and Steel Institute;
1972.
[5] Roeder CW, Foutch DA. Experimental results for seismic resistant steel
moment frame connections. Journal of Structural Engineering 1996;
122(6):581–8.
[6] Dubina D, Ciutina A, Stratan A. Cyclic tests of double-sided beam-to-
column joints. Journal of Structural Engineering, ASCE 2001;127(2):
129.
Fig. 13. Web buckling above the wedge peak. [7] Broderick BM, Thomson AW. The response of flush end-plate joints
under earthquake loading. Journal of Constructional Steel Research
the moment in the connected column (as with reinforced 2001.
[8] European committee for standardisation. Eurocode 3: Part 1.1 Revised
connections) and only requires access to the bottom flange
Annex J: Joints in building frames, ENV 1993-1-1: 1992/A2: 1998.
of the beam. Finally the wedge detail will be superior to [9] Naeim F. The seismic design handbook. 2nd ed. Kluwer Academic
a dogbone section with the same plastic moment capacity Publishers; 2001. p. 418.

You might also like