Project Name: Drawing1
Location: BURO MILLA DE ORO, PISO 16,
Drawing Name: diseño piso 16 Calculation Date: 24/07/2019
Design
Remote Area Number:
Density: 0.100gpm/ft²
Area of Application: 1000.00ft² (Actual 801.05ft²)
Coverage per Sprinkler: 100.13ft²
Type of sprinklers calculated: Upright
No. of sprinklers calculated: 8
Name of Contractor:
Address: ,
Phone Number: Name of designer: ATEG INGENIERIAS
Notes:
Water Supply
Summary Sheet
Node: 10
Supply Analysis
Static Residual Flow Available Total Demand Required Pressure
Node Name @ @
(psi) (psi) (gpm) (psi) (gpm) (psi)
Node Analysis
Node Number Elevation (Meter) Node Type Pressure at Discharge at Notes
Node Node
(psi) (gpm)
1 3.00m 7.698
2 3.00m 9.838
3 3.00m 10.208
4 3.00m 12.235
5 3.00m 12.392
6 3.00m 12.815
7 3.00m 23.532
8 3.00m 24.404
9 3.00m 29.393
11 3.00m 7.519
12 3.00m 8.351
13 3.00m 9.044
14 3.00m 8.158
15 3.00m 10.883
16 3.00m 12.176
Pipe Information
Flow added Length C Factor Notes
Elev 1 Fittings & Total(Pt)
Node 1 K-Factor this step Nominal ID (Meter) Fitting/Device (Equivalent
(Meter) Devices
(q) Length)
Fitting
Pf Friction Elev(Pe) Fixed Pressure Losses, when
Equiv. (Meter) Loss Per Unit
Elev 2 Total Flow applicable, are added directly
Node 2 Actual ID Length Total
(Meter) (Q) (psi) to (Pf) and shown as a
(Meter) Friction(Pf)
(Meter) negative value.
0.188950
5 3.00m 76.75 2.0670
0.83m 0.157
0.378849
6 3.00m 111.79 2.0670
1.12m 0.423
0.410289
8 3.00m 130.57 2.1570
2.13m 0.872
10 380.57
Total(Pt) Route 1
Pipe Information
Flow added Length C Factor Notes
Elev 1 Fittings & Total(Pt)
Node 1 K-Factor this step Nominal ID (Meter) Fitting/Device (Equivalent
(Meter) Devices
(q) Length)
Fitting
Pf Friction Elev(Pe) Fixed Pressure Losses, when
Equiv. (Meter) Loss Per Unit
Elev 2 Total Flow applicable, are added directly
Node 2 Actual ID Length Total
(Meter) (Q) (psi) to (Pf) and shown as a
(Meter) Friction(Pf)
(Meter) negative value.
0.064840
1 3.00m 14.86 1.3800
2.75m 0.178
0.252049
13 3.00m 30.96 1.3800
2.75m 0.693
0.547077
3 3.00m 47.07 1.3800
2.13m 1.164
0.070121
12 3.00m 15.51 1.3800
2.75m 0.193
Pipe Information
Flow added Length C Factor Notes
Elev 1 Fittings & Total(Pt)
Node 1 K-Factor this step Nominal ID (Meter) Fitting/Device (Equivalent
(Meter) Devices
(q) Length)
Fitting
Pf Friction Elev(Pe) Fixed Pressure Losses, when
Equiv. (Meter) Loss Per Unit
Elev 2 Total Flow applicable, are added directly
Node 2 Actual ID Length Total
(Meter) (Q) (psi) to (Pf) and shown as a
(Meter) Friction(Pf)
(Meter) negative value.
Fittings Legend