You are on page 1of 5

Hydratec Incorporated

64 Haverhill Road
Route 111
Windham, NH 03087
603-434-0502

Job Name : Calculo rociadores casa de bombas


Drawing :
Location :
Remote Area :
Contract :
Data File : CALCULO ROCIADORES CASA DE BOMBAS AREA 1.wxtmp

Computer Programs by Hydratec Inc. Revision: 50.5520.727


Water Supply Curve
Hydratec Incorporated Page 1
Calculo rociadores casa de bombas Date

Pump Data: Demand:


P1 - Pump Churn Pressure : 97.9 D1 - Elevation : 4.855
P2 - Pump Rated Pressure : 89 D2 - System Flow : 96.972
P2 - Pump Rated Flow : 100 D2 - System Pressure : 32.510
P3 - Pump Pressure @ Max Flow : 57.85 Hose ( Demand ) : _______
P3 - Pump Max Flow : 150 D3 - System Demand : 96.972
Safety Margin : 57.170

150

140

130

P 120

R 110
P1
E 100
P2
S 90

S 80

U 70
P3
R 60

E 50
40 D2
30

20

10
D1
20 40 60 80 100 120 140 160 180
FLOW ( N ^ 1.85 )

Computer Programs by Hydratec Inc. Revision: 50.5520.727


Fittings Used Summary
Hydratec Incorporated Page 2
Calculo rociadores casa de bombas Date

Fitting Legend
Abbrev. Name ½ ¾ 1 1¼ 1½ 2 2½ 3 3½ 4 5 6 8 10 12 14 16 18 20 24

Avc Alarm Vic 751 0 0 0 0 3 9 8 17 0 21 0 22 50 0 0 0 0 0 0 0


Ball B Ball Milw BB-SC100 2.25 2 2.5 2.25 10
E NFPA 13 90' Standard Elbow 1 2 2 3 4 5 6 7 8 10 12 14 18 22 27 35 40 45 50 61
T NFPA 13 90' Flow thru Tee 3 4 5 6 8 10 12 15 17 20 25 30 35 50 60 71 81 91 101 121

Units Summary

Diameter Units Inches


Length Units Feet
Flow Units US Gallons per Minute
Pressure Units Pounds per Square Inch

Note: Fitting Legend provides equivalent pipe lengths for fittings types of various diameters.
Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFactors
of 120 except as noted with *. The fittings marked with a * show equivalent lengths values
supplied by manufacturers based on specific pipe diameters and CFactors and they require no
adjustment. All values for fittings not marked with a * will be adjusted in the calculation
for CFactors of other than 120 and diameters other than Sched 40 per NFPA.

Computer Programs by Hydratec Inc. Revision: 50.5520.727


Flow Summary - NFPA
Hydratec Incorporated Page 3
Calculo rociadores casa de bombas Date

SUPPLY ANALYSIS

Node at Static Residual Available


Source Pressure Pressure Flow Pressure Total Demand Required Pressure

PUMP See Information on Pump Curve 89.68 96.97 32.51

NODE ANALYSIS

Pressure Discharge
Node Tag Elevation Node Type at Node at Node Notes

1 11.21 8 7.0 21.17 0.15 120


2 10.72 8 8.37 23.15 0.15 120
3 10.59 9.62
4 9.0 15.18
5 9.0 20.85
TOR 9.0 21.63
BOR 2.0 26.73
9 2.0 30.84
PUMP 0.0 32.51
6 11.21 8 9.94 25.23 0.15 120
7 10.72 8 11.76 27.43 0.15 120
8 10.59 15.01

Computer Programs by Hydratec Inc. Revision: 50.5520.727


Final Calculations : Hazen-Williams
Hydratec Incorporated Page 4
Calculo rociadores casa de bombas Date

Node1 Elev1 K Qa Nom Fitting Pipe CFact Pt


to or Ftngs Pe ******* Notes ******
Node2 Elev2 Fact Qt Act Eqiv Len Total Pf/Ft Pf

1 11.21 8.00 21.17 1 8.020 120 7.000


to 0.212
2 10.72 21.17 1.049 8.020 0.1445 1.159 Vel = 7.86
2 10.72 8.00 23.14 1 2.100 120 8.371
to 0.056
3 10.59 44.31 1.049 2.100 0.5671 1.191 Vel = 16.45
3 10.59 0.0 1 E 2.0 1.600 120 9.618
to T 5.0 7.000 0.689
4 9 44.31 1.049 8.600 0.5670 4.876 Vel = 16.45
4 9 0.0 1 10.000 120 15.183
to 0.0
5 9 44.31 1.049 10.000 0.5669 5.669 Vel = 16.45
5 9 52.66 2 E 5.0 3.770 120 20.852
to 5.000 0.0
TOR 9 96.97 2.067 8.770 0.0888 0.779 Vel = 9.27
TOR 9 0.0 2 E 5.0 7.000 120 21.631
to Avc 9.0 16.250 3.032
BOR 2 96.97 2.067 Ball 2.25 23.250 0.0887 2.063 Vel = 9.27
BOR 2 0.0 2 4E 20.0 26.380 120 26.726
to 20.000 0.0
9 2 96.97 2.067 46.380 0.0888 4.117 Vel = 9.27
9 2 0.0 2 E 5.0 4.020 120 30.843
to 5.000 0.866
PUMP 0 96.97 2.067 9.020 0.0888 0.801 Vel = 9.27
0.0
PUMP 96.97 32.510 K Factor = 17.01
System Demand Pressure 32.510
Safety Margin 57.170
Continuation Pressure 89.680
6 11.21 8.00 25.23 1 8.020 120 9.943
to 0.212
7 10.72 25.23 1.049 8.020 0.2000 1.604 Vel = 9.37
7 10.72 8.00 27.43 1 E 2.0 2.100 120 11.759
to 2.000 0.056
8 10.59 52.66 1.049 4.100 0.7802 3.199 Vel = 19.55
8 10.59 0.0 1 T 5.0 1.600 120 15.014
to 5.000 0.689
5 9 52.66 1.049 6.600 0.7802 5.149 Vel = 19.55
0.0
5 52.66 20.852 K Factor = 11.53

Computer Programs by Hydratec Inc. Revision: 50.5520.727

You might also like