You are on page 1of 12

SALVAVIDAS SISTEMAS CONTRA INC

25m. NTE DE PEDREGAL


SAN ANTONIO DE BELEN HEREDIA
COSTARICA
(506) 22931248

Job Name : CEDIS COYOL COSTA RICA


Building : PCI-14
Location : ALAJUELA SAN JOSE COSTA RICA
System : IN-RACK 30R
Contract : N/A
Data File : COY-S30R.WXF

Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
SALVAVIDAS SISTEMAS CONTRA INC Page 1
CEDIS COYOL COSTA RICA Date AUG.2018

HYDRAULIC CALCULATIONS
for

Project name: CEDIS COYOL


Location: ALAJUELA SAN JOSE COSTA RICA
Drawing no: PCI-14
Date: AUG. 2018

Design
Remote area number: IN-RACK 30R
Remote area location: IN-RACK SYSTEM 30R
Occupancy classification: UNCARTON EXPANDED PLASTIC
Density: 9,7
Area of application: 123.7
Coverage per sprinkler: 12.37
Type of sprinklers calculated: ESFR K22.4 165°F, PENDENT, 1"NPT
No. of sprinklers calculated: 10@120GPM
In-rack demand: 1258.057
Hose streams: 250
Total water required (including hose streams): 1508.057 - GPM @ 124.418
Type of system: WET
Volume of dry or preaction system: N/A - Gal

Water supply information


Date: AUG. 2018
Location: ALAJUELA COSTA RICA
Source: FIRE PUMP 2500GPM@145PSI, 290,000 GAL SUCTION TANK

Name of contractor: SALVAVIDAS SISTEMAS CONTRA INCENDIOS


Address: 75m NTE DE PEDREGAL, SAN ANTONIO DE BELEN HEREDIA COSTA RICA
Phone number: (506) 22931248
Name of designer: ING. MAURICIO MENESES
Authority having jurisdiction: FIRE DEPARTMENT OF COSTA RICA
Notes: (Include peaking information or gridded systems here.) FLOW AND PRESSURE SHOWN HERE
WERE CALCULATED AT THE PUMP'S DISCHARGE FLANGE

Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Water Supply Curve C
SALVAVIDAS SISTEMAS CONTRA INC Page 2
CEDIS COYOL COSTA RICA Date AUG.2018

Pump Data: Demand:


P1 - Pump Churn Pressure : 171.97 D1 - Elevation : 18.277
P2 - Pump Rated Pressure : 145 D2 - System Flow : 1258.06
P2 - Pump Rated Flow : 2500 D2 - System Pressure : 136.203
P3 - Pump Pressure @ Max Flow : 94.25 Hose ( Demand ) : 250
P3 - Pump Max Flow : 3750 D3 - System Demand : 1508.06
Safety Margin : 30.578

180 P1
168

156
P2
P 144 D2

R 132
D3
E 120

S 108
P3
S 96

U 84

R 72

E 60
48

36

24
D1
12

400 800 1200 1600 2000 2400 2800 3200 3600


FLOW ( N ^ 1.85 )

Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Fittings Used Summary
SALVAVIDAS SISTEMAS CONTRA INC Page 3
CEDIS COYOL COSTA RICA Date AUG.2018

Fitting Legend
Abbrev. Name ½ ¾ 1 1¼ 1½ 2 2½ 3 3½ 4 5 6 8 10 12 14 16 18 20 24

Aty Alarm Tyco AV-1 14 23 24 23


B NFPA 13 Butterfly Valve 0 0 0 0 0 6 7 10 0 12 9 10 12 19 21 0 0 0 0 0
E NFPA 13 90' Standard Elbow 1 2 2 3 4 5 6 7 8 10 12 14 18 22 27 35 40 45 50 61
Fsp Flow Switch Potter VSR Fitting generates a Fixed Loss Based on Flow
G NFPA 13 Gate Valve 0 0 0 0 0 1 1 1 1 2 2 3 4 5 6 7 8 10 11 13
S NFPA 13 Swing Check Valve 4 5 5 7 9 11 14 16 19 22 27 32 45 55 65 76 87 98 109 130
T NFPA 13 90' Flow thru Tee 3 4 5 6 8 10 12 15 17 20 25 30 35 50 60 71 81 91 101 121

Units Summary

Diameter Units Inches


Length Units Feet
Flow Units US Gallons per Minute
Pressure Units Pounds per Square Inch

Note: Fitting Legend provides equivalent pipe lengths for fittings types of various diameters.
Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFactors
of 120 except as noted with *. The fittings marked with a * show equivalent lengths values
supplied by manufacturers based on specific pipe diameters and CFactors and they require no
adjustment. All values for fittings not marked with a * will be adjusted in the calculation
for CFactors of other than 120 and diameters other than Sched 40 per NFPA.

Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Pressure / Flow Summary - STANDARD
SALVAVIDAS SISTEMAS CONTRA INC Page 4
CEDIS COYOL COSTA RICA Date AUG.2018

Node Elevation K-Fact Pt Pn Flow Density Area Press


No. Actual Actual Req.

R1 40.2 22.4 33.04 na 128.76 9.7 12.37 28.698


R2 40.2 22.4 29.31 na 121.26 9.7 12.37 28.698
R3 40.2 22.4 29.6 na 121.86 9.7 12.37 28.698
R4 40.2 22.4 33.06 na 128.79 9.7 12.37 28.698
R5 40.2 22.4 34.53 na 131.63 9.7 12.37 28.698
R6 40.2 22.4 32.36 na 127.43 9.7 12.37 28.698
R7 40.2 22.4 28.7 na 120.0 9.7 12.37 28.698
R8 40.2 22.4 28.98 na 120.59 9.7 12.37 28.698
R9 40.2 22.4 32.38 na 127.46 9.7 12.37 28.698
R10 40.2 22.4 33.82 na 130.27 9.7 12.37 28.698
R1A 39.6 36.48 na
R2A 39.6 32.41 na
R3A 39.6 32.72 na
R4A 39.6 36.5 na
R5A 39.6 38.1 na
R6A 39.6 35.74 na
R7A 39.6 31.74 na
R8A 39.6 32.06 na
R9A 39.6 35.75 na
R10A 39.6 37.33 na
A1 39.6 38.16 na
A2 39.6 38.17 na
A3 39.6 39.85 na
A4 39.6 68.15 na
A5 48.39 66.14 na
B1 39.6 37.38 na
B2 39.6 37.4 na
B3 39.6 39.04 na
B4 39.6 66.8 na
B5 48.39 64.76 na
M1 48.39 67.45 na
M2 48.39 68.88 na
M3 48.39 95.57 na
TR30 48.39 96.79 na
BR30 -2.13 124.42 na 250.0
LI14 -2.13 126.83 na
U14 -9.0 129.98 na
UN11 -9.0 130.6 na
UN12 -9.0 130.56 na
UN13 -9.0 130.44 na
UN14 -9.0 130.35 na
UN15 -9.0 130.6 na
UN16 -9.0 130.88 na
UN17 -9.0 132.51 na
UN18 -9.0 132.98 na
UN19 -9.0 133.94 na
UN20 -9.0 134.65 na
UN21 -9.0 134.68 na
UN22 -9.0 134.98 na
UN26 -9.0 135.6 na
UN2 -9.0 136.67 na
UN3 -9.0 136.2 na
UN4 -9.0 135.91 na
UN5 -9.0 135.53 na
UN6 -9.0 135.19 na
UN7 -9.0 134.69 na
UN8 -9.0 131.32 na
UN9 -9.0 130.99 na
UN10 -9.0 130.85 na
UN1 -9.0 137.74 na
LI1 -2.0 134.73 na
PH2 8.0 130.6 na

Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Flow Summary - Standard
SALVAVIDAS SISTEMAS CONTRA INC Page 5
CEDIS COYOL COSTA RICA Date AUG.2018

Node Elevation K-Fact Pt Pn Flow Density Area Press


No. Actual Actual Req.

PH1 8.0 131.14 na


DSCH -2.0 135.79 na
FP -2.0 136.2 na

The maximum velocity is 27.59 and it occurs in the pipe between nodes M2 and M3

Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams
SALVAVIDAS SISTEMAS CONTRA INC Page 6
CEDIS COYOL COSTA RICA Date AUG.2018

Hyd. Qa Dia. Fitting Pipe Pt Pt


Ref. "C" or Ftng's Pe Pv ******* Notes ******
Point Qt Pf/Ft Eqv. Ln. Total Pf Pn

*ARM OVER
R1 128.76 2.215 2E 14.004 1.640 33.041 K Factor = 22.40
to 120.0 T 14.004 28.008 0.260
R1A 128.76 0.1071 0.0 29.648 3.175 Vel = 10.72
0.0
128.76 36.476 K Factor = 21.32
R2 121.26 2.215 2E 14.004 1.640 29.306 K Factor = 22.40
to 120.0 T 14.004 28.008 0.260
R2A 121.26 0.0959 0.0 29.648 2.842 Vel = 10.10
0.0
121.26 32.408 K Factor = 21.30
R3 121.86 2.215 2E 14.004 1.640 29.597 K Factor = 22.40
to 120.0 T 14.004 28.008 0.260
R3A 121.86 0.0967 0.0 29.648 2.868 Vel = 10.15
0.0
121.86 32.725 K Factor = 21.30
R4 128.79 2.215 2E 14.004 1.640 33.060 K Factor = 22.40
to 120.0 T 14.004 28.008 0.260
R4A 128.79 0.1071 0.0 29.648 3.176 Vel = 10.72
0.0
128.79 36.496 K Factor = 21.32
R5 131.63 2.215 2E 14.004 1.640 34.531 K Factor = 22.40
to 120.0 T 14.004 28.008 0.260
R5A 131.63 0.1115 0.0 29.648 3.307 Vel = 10.96
0.0
131.63 38.098 K Factor = 21.33
R6 127.43 2.215 2E 14.004 1.640 32.361 K Factor = 22.40
to 120.0 T 14.004 28.008 0.260
R6A 127.43 0.1050 0.0 29.648 3.114 Vel = 10.61
0.0
127.43 35.735 K Factor = 21.32
R7 120.00 2.215 2E 14.004 1.640 28.698 K Factor = 22.40
to 120.0 T 14.004 28.008 0.260
R7A 120.0 0.0940 0.0 29.648 2.787 Vel = 9.99
0.0
120.00 31.745 K Factor = 21.30
R8 120.59 2.215 2E 14.004 1.640 28.984 K Factor = 22.40
to 120.0 T 14.004 28.008 0.260
R8A 120.59 0.0948 0.0 29.648 2.812 Vel = 10.04
0.0
120.59 32.056 K Factor = 21.30
R9 127.46 2.215 2E 14.004 1.640 32.379 K Factor = 22.40
to 120.0 T 14.004 28.008 0.260
R9A 127.46 0.1051 0.0 29.648 3.116 Vel = 10.61
0.0
127.46 35.755 K Factor = 21.32
R10 130.27 2.215 2E 14.004 1.640 33.822 K Factor = 22.40
to 120.0 T 14.004 28.008 0.260
R10A 130.27 0.1094 0.0 29.648 3.244 Vel = 10.85

Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams
SALVAVIDAS SISTEMAS CONTRA INC Page 7
CEDIS COYOL COSTA RICA Date AUG.2018

Hyd. Qa Dia. Fitting Pipe Pt Pt


Ref. "C" or Ftng's Pe Pv ******* Notes ******
Point Qt Pf/Ft Eqv. Ln. Total Pf Pn

0.0
130.27 37.326 K Factor = 21.32
*REMOTE BRACH LINE 1
R1A 128.76 2.215 T 14.004 1.690 36.476
to 120.0 0.0 14.004 0.0
A1 128.76 0.1071 0.0 15.694 1.681 Vel = 10.72
0.0
128.76 38.157 K Factor = 20.84
R2A 121.26 2.215 0.0 3.310 32.408
to 120.0 0.0 0.0 0.0
R3A 121.26 0.0958 0.0 3.310 0.317 Vel = 10.10
R3A 121.87 2.215 T 14.004 1.690 32.725
to 120.0 0.0 14.004 0.0
A2 243.13 0.3471 0.0 15.694 5.448 Vel = 20.24
0.0
243.13 38.173 K Factor = 39.35
R4A 128.79 2.215 T 14.004 1.640 36.496
to 120.0 0.0 14.004 0.0
A2 128.79 0.1072 0.0 15.644 1.677 Vel = 10.72
0.0
128.79 38.173 K Factor = 20.85
R5A 131.63 2.215 T 14.004 1.690 38.098
to 120.0 0.0 14.004 0.0
A3 131.63 0.1116 0.0 15.694 1.751 Vel = 10.96
0.0
131.63 39.849 K Factor = 20.85
*REMOTE BRACH LINE 2
R6A 127.43 2.215 T 14.004 1.690 35.735
to 120.0 0.0 14.004 0.0
B1 127.43 0.1051 0.0 15.694 1.649 Vel = 10.61
0.0
127.43 37.384 K Factor = 20.84
R7A 120.00 2.215 0.0 3.310 31.745
to 120.0 0.0 0.0 0.0
R8A 120.0 0.0940 0.0 3.310 0.311 Vel = 9.99
R8A 120.59 2.215 T 14.004 1.690 32.056
to 120.0 0.0 14.004 0.0
B2 240.59 0.3404 0.0 15.694 5.343 Vel = 20.03
0.0
240.59 37.399 K Factor = 39.34
R9A 127.46 2.215 T 14.004 1.640 35.755
to 120.0 0.0 14.004 0.0
B2 127.46 0.1051 0.0 15.644 1.644 Vel = 10.61
0.0
127.46 37.399 K Factor = 20.84
R10A 130.27 2.215 T 14.004 1.690 37.326
to 120.0 0.0 14.004 0.0
B3 130.27 0.1094 0.0 15.694 1.717 Vel = 10.85

Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams
SALVAVIDAS SISTEMAS CONTRA INC Page 8
CEDIS COYOL COSTA RICA Date AUG.2018

Hyd. Qa Dia. Fitting Pipe Pt Pt


Ref. "C" or Ftng's Pe Pv ******* Notes ******
Point Qt Pf/Ft Eqv. Ln. Total Pf Pn

0.0
130.27 39.043 K Factor = 20.85
*REMOTE IN.RACK MAIN 1
A1 128.76 4.316 0.0 3.740 38.157
to 120.0 0.0 0.0 0.0
A2 128.76 0.0043 0.0 3.740 0.016 Vel = 2.82
A2 371.92 4.316 T 28.063 4.620 38.173
to 120.0 0.0 28.063 0.0
A3 500.68 0.0513 0.0 32.683 1.676 Vel = 10.98
A3 131.63 4.316 T 28.063 330.240 39.849
to 120.0 0.0 28.063 0.0
A4 632.31 0.0790 0.0 358.303 28.299 Vel = 13.87
A4 0.0 4.316 E 14.032 8.790 68.148
to 120.0 0.0 14.032 -3.807
A5 632.31 0.0790 0.0 22.822 1.803 Vel = 13.87
A5 0.0 4.316 T 28.063 6.620 66.144
to 120.0 0.0 28.063 0.0
M2 632.31 0.0790 0.0 34.683 2.739 Vel = 13.87
0.0
632.31 68.883 K Factor = 76.19
B1 127.43 4.316 0.0 3.740 37.384
to 120.0 0.0 0.0 0.0
B2 127.43 0.0040 0.0 3.740 0.015 Vel = 2.79
B2 368.05 4.316 T 28.063 4.620 37.399
to 120.0 0.0 28.063 0.0
B3 495.48 0.0503 0.0 32.683 1.644 Vel = 10.87
B3 130.27 4.316 T 28.063 330.240 39.043
to 120.0 0.0 28.063 0.0
B4 625.75 0.0775 0.0 358.303 27.759 Vel = 13.72
B4 0.0 4.316 E 14.032 8.790 66.802
to 120.0 0.0 14.032 -3.807
B5 625.75 0.0775 0.0 22.822 1.768 Vel = 13.72
B5 0.0 4.316 T 28.063 6.620 64.763
to 120.0 0.0 28.063 0.0
M1 625.75 0.0775 0.0 34.683 2.687 Vel = 13.72
M1 0.0 4.316 0.0 18.500 67.450
to 120.0 0.0 0.0 0.0
M2 625.75 0.0775 0.0 18.500 1.433 Vel = 13.72
M2 632.31 4.316 T 28.063 66.560 68.883
to 120.0 0.0 28.063 0.0
M3 1258.06 0.2820 0.0 94.623 26.684 Vel = 27.59
M3 0.0 6.357 E 17.603 11.080 95.567
to 120.0 0.0 17.603 0.0
TR30 1258.06 0.0428 0.0 28.683 1.227 Vel = 12.72
TR30 0.0 6.357 B 12.573 50.520 96.794
to 120.0 Aty 30.176 60.352 22.880 * * Fixed Loss = 1
BR30 1258.06 0.0428 Fsp 0.0 110.872 4.744 Vel = 12.72
E 17.603

Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams
SALVAVIDAS SISTEMAS CONTRA INC Page 9
CEDIS COYOL COSTA RICA Date AUG.2018

Hyd. Qa Dia. Fitting Pipe Pt Pt


Ref. "C" or Ftng's Pe Pv ******* Notes ******
Point Qt Pf/Ft Eqv. Ln. Total Pf Pn

BR30 250.00 6.357 T 37.72 2.600 124.418 Qa = 250


to 120.0 0.0 37.720 0.0
LI14 1508.06 0.0598 0.0 40.320 2.412 Vel = 15.24
LI14 0.0 10.4 E 35.075 7.000 126.830
to 140.0 0.0 35.075 2.975
U14 1508.06 0.0041 0.0 42.075 0.172 Vel = 5.70
U14 0.0 10.4 T 79.716 3.000 129.977
to 140.0 G 7.972 87.688 0.0
UN14 1508.06 0.0041 0.0 90.688 0.371 Vel = 5.70
0.0
1508.06 130.348 K Factor = 132.09
UN11 -594.18 9.42 0.0 39.370 130.601
to 150.0 0.0 0.0 0.0
UN12 -594.18 -0.0010 0.0 39.370 -0.041 Vel = 2.74
UN12 0.0 9.42 0.0 110.680 130.560
to 150.0 0.0 0.0 0.0
UN13 -594.18 -0.0010 0.0 110.680 -0.115 Vel = 2.74
UN13 0.0 9.42 G 5.593 87.500 130.445
to 150.0 0.0 5.593 0.0
UN14 -594.18 -0.0010 0.0 93.093 -0.097 Vel = 2.74
UN14 1508.06 9.42 0.0 110.330 130.348
to 150.0 0.0 0.0 0.0
UN15 913.88 0.0023 0.0 110.330 0.255 Vel = 4.21
UN15 0.0 9.42 G 5.593 114.150 130.603
to 150.0 0.0 5.593 0.0
UN16 913.88 0.0023 0.0 119.743 0.277 Vel = 4.21
UN16 0.0 9.42 E 24.61 682.700 130.880
to 150.0 0.0 24.609 0.0
UN17 913.88 0.0023 0.0 707.309 1.633 Vel = 4.21
UN17 0.0 9.42 E 24.61 176.670 132.513
to 150.0 0.0 24.609 0.0
UN18 913.88 0.0023 0.0 201.279 0.464 Vel = 4.21
UN18 0.0 9.42 E 24.61 389.070 132.977
to 150.0 G 5.593 30.202 0.0
UN19 913.88 0.0023 0.0 419.272 0.968 Vel = 4.21
UN19 0.0 9.42 E 24.61 282.280 133.945
to 150.0 0.0 24.609 0.0
UN20 913.88 0.0023 0.0 306.889 0.709 Vel = 4.21
UN20 0.0 9.42 0.0 11.020 134.654
to 150.0 0.0 0.0 0.0
UN21 913.88 0.0023 0.0 11.020 0.025 Vel = 4.21
UN21 0.0 9.42 G 5.593 125.000 134.679
to 150.0 0.0 5.593 0.0
UN22 913.88 0.0023 0.0 130.593 0.302 Vel = 4.21
UN22 0.0 9.42 2E 49.22 215.580 134.981
to 150.0 G 5.593 54.813 0.0
UN26 913.88 0.0023 0.0 270.393 0.624 Vel = 4.21
UN26 0.0 9.42 2E 49.22 349.960 135.605
to 150.0 T 55.931 110.744 0.0
UN2 913.88 0.0023 G 5.593 460.704 1.064 Vel = 4.21

Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams
SALVAVIDAS SISTEMAS CONTRA INC Page 10
CEDIS COYOL COSTA RICA Date AUG.2018

Hyd. Qa Dia. Fitting Pipe Pt Pt


Ref. "C" or Ftng's Pe Pv ******* Notes ******
Point Qt Pf/Ft Eqv. Ln. Total Pf Pn

UN2 -1508.06 9.42 2E 49.22 395.660 136.669


to 150.0 G 5.593 54.813 0.0
UN3 -594.18 -0.0010 0.0 450.473 -0.469 Vel = 2.74
UN3 0.0 9.42 E 24.61 249.960 136.200
to 150.0 G 5.593 30.202 0.0
UN4 -594.18 -0.0010 0.0 280.162 -0.292 Vel = 2.74
UN4 0.0 9.42 T 55.931 299.140 135.908
to 150.0 G 5.593 61.524 0.0
UN5 -594.18 -0.0010 0.0 360.664 -0.375 Vel = 2.74
UN5 0.0 9.42 E 24.61 300.950 135.533
to 150.0 G 5.593 30.202 0.0
UN6 -594.18 -0.0010 0.0 331.152 -0.345 Vel = 2.74
UN6 0.0 9.42 4E 98.439 379.620 135.188
to 150.0 0.0 98.439 0.0
UN7 -594.18 -0.0010 0.0 478.059 -0.498 Vel = 2.74
UN7 0.0 9.42 18E 442.977 2782.800 134.690
to 150.0 2G 11.186 454.163 0.0
UN8 -594.18 -0.0010 0.0 3236.963 -3.370 Vel = 2.74
UN8 0.0 9.42 3E 73.829 236.890 131.320
to 150.0 G 5.593 79.422 0.0
UN9 -594.18 -0.0010 0.0 316.312 -0.329 Vel = 2.74
UN9 0.0 9.42 E 24.61 114.130 130.991
to 150.0 0.0 24.609 0.0
UN10 -594.18 -0.0010 0.0 138.739 -0.145 Vel = 2.74
UN10 0.0 9.42 2E 49.22 124.540 130.846
to 150.0 T 55.931 110.744 0.0
UN11 -594.18 -0.0010 G 5.593 235.284 -0.245 Vel = 2.74
0.0
-594.18 130.601 K Factor = -51.99
UN2 1508.06 9.42 E 24.61 158.360 136.669
to 150.0 0.0 24.609 0.0
UN1 1508.06 0.0058 0.0 182.969 1.067 Vel = 6.94
UN1 0.0 10.4 0.0 7.000 137.736
to 140.0 0.0 0.0 -3.032
LI1 1508.06 0.0041 0.0 7.000 0.029 Vel = 5.70
LI1 0.0 10.42 E 26.62 10.000 134.733
to 120.0 0.0 26.620 -4.331
PH2 1508.06 0.0054 0.0 36.620 0.197 Vel = 5.67
PH2 0.0 10.42 3E 79.861 20.000 130.599
to 120.0 0.0 79.861 0.0
PH1 1508.06 0.0054 0.0 99.861 0.539 Vel = 5.67
PH1 0.0 10.42 B 22.99 10.000 131.138
to 120.0 E 26.62 49.610 4.331
DSCH 1508.06 0.0054 0.0 59.610 0.321 Vel = 5.67
DSCH 0.0 10.42 S 66.551 10.000 135.790
to 120.0 0.0 66.551 0.0
FP 1508.06 0.0054 0.0 76.551 0.413 Vel = 5.67
0.0

Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams
SALVAVIDAS SISTEMAS CONTRA INC Page 11
CEDIS COYOL COSTA RICA Date AUG.2018

Hyd. Qa Dia. Fitting Pipe Pt Pt


Ref. "C" or Ftng's Pe Pv ******* Notes ******
Point Qt Pf/Ft Eqv. Ln. Total Pf Pn

1508.06 136.203 K Factor = 129.22

Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087