You are on page 1of 12

SALVAVIDAS SISTEMAS CONTRA INC

25m. NTE DE PEDREGAL


SAN ANTONIO DE BELEN HEREDIA
COSTARICA
(506) 22931248

Job Name : CEDIS COYOL COSTA RICA


Building : PCI-14
Location : ALAJUELA SAN JOSE COSTA RICA
System : IN-RACK 32R
Contract : N/A
Data File : COY-S32R.WXF

Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
SALVAVIDAS SISTEMAS CONTRA INC Page 1
CEDIS COYOL COSTA RICA Date AUG.2018

HYDRAULIC CALCULATIONS
for

Project name: CEDIS COYOL


Location: ALAJUELA SAN JOSE COSTA RICA
Drawing no: PCI-14
Date: AUG. 2018

Design
Remote area number: IN-RACK 32R
Remote area location: IN-RACK SYSTEM 32R
Occupancy classification: UNCARTON EXPANDED PLASTIC
Density: 9,7
Area of application: 123.7
Coverage per sprinkler: 12.37
Type of sprinklers calculated: ESFR K22.4 165°F, PENDENT, 1"NPT
No. of sprinklers calculated: 10@120GPM
In-rack demand: 1254.881
Hose streams: 250
Total water required (including hose streams): 1504.881 - GPM @ 131.852
Type of system: WET
Volume of dry or preaction system: N/A - Gal

Water supply information


Date: AUG. 2018
Location: ALAJUELA COSTA RICA
Source: FIRE PUMP 2500GPM@145PSI, 290,000 GAL SUCTION TANK

Name of contractor: SALVAVIDAS SISTEMAS CONTRA INCENDIOS


Address: 75m NTE DE PEDREGAL, SAN ANTONIO DE BELEN HEREDIA COSTA RICA
Phone number: (506) 22931248
Name of designer: ING. MAURICIO MENESES
Authority having jurisdiction: FIRE DEPARTMENT OF COSTA RICA
Notes: (Include peaking information or gridded systems here.) FLOW AND PRESSURE SHOWN HERE
WERE CALCULATED AT THE PUMP'S DISCHARGE FLANGE

Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Water Supply Curve C
SALVAVIDAS SISTEMAS CONTRA INC Page 2
CEDIS COYOL COSTA RICA Date AUG.2018

Pump Data: Demand:


P1 - Pump Churn Pressure : 171.97 D1 - Elevation : 18.277
P2 - Pump Rated Pressure : 145 D2 - System Flow : 1254.88
P2 - Pump Rated Flow : 2500 D2 - System Pressure : 145.244
P3 - Pump Pressure @ Max Flow : 94.25 Hose ( Demand ) : 250
P3 - Pump Max Flow : 3750 D3 - System Demand : 1504.88
Safety Margin : 21.592

180 P1
168

156
D2 P2
P 144
D3
R 132

E 120

S 108
P3
S 96

U 84

R 72

E 60
48

36

24
D1
12

400 800 1200 1600 2000 2400 2800 3200 3600


FLOW ( N ^ 1.85 )

Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Fittings Used Summary
SALVAVIDAS SISTEMAS CONTRA INC Page 3
CEDIS COYOL COSTA RICA Date AUG.2018

Fitting Legend
Abbrev. Name ½ ¾ 1 1¼ 1½ 2 2½ 3 3½ 4 5 6 8 10 12 14 16 18 20 24

Aty Alarm Tyco AV-1 14 23 24 23


B NFPA 13 Butterfly Valve 0 0 0 0 0 6 7 10 0 12 9 10 12 19 21 0 0 0 0 0
E NFPA 13 90' Standard Elbow 1 2 2 3 4 5 6 7 8 10 12 14 18 22 27 35 40 45 50 61
Fsp Flow Switch Potter VSR Fitting generates a Fixed Loss Based on Flow
G NFPA 13 Gate Valve 0 0 0 0 0 1 1 1 1 2 2 3 4 5 6 7 8 10 11 13
S NFPA 13 Swing Check Valve 4 5 5 7 9 11 14 16 19 22 27 32 45 55 65 76 87 98 109 130
T NFPA 13 90' Flow thru Tee 3 4 5 6 8 10 12 15 17 20 25 30 35 50 60 71 81 91 101 121

Units Summary

Diameter Units Inches


Length Units Feet
Flow Units US Gallons per Minute
Pressure Units Pounds per Square Inch

Note: Fitting Legend provides equivalent pipe lengths for fittings types of various diameters.
Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFactors
of 120 except as noted with *. The fittings marked with a * show equivalent lengths values
supplied by manufacturers based on specific pipe diameters and CFactors and they require no
adjustment. All values for fittings not marked with a * will be adjusted in the calculation
for CFactors of other than 120 and diameters other than Sched 40 per NFPA.

Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Pressure / Flow Summary - STANDARD
SALVAVIDAS SISTEMAS CONTRA INC Page 4
CEDIS COYOL COSTA RICA Date AUG.2018

Node Elevation K-Fact Pt Pn Flow Density Area Press


No. Actual Actual Req.

R1 40.2 22.4 31.18 na 125.07 9.7 12.37 28.698


R2 40.2 22.4 31.19 na 125.1 9.7 12.37 28.698
R3 40.2 22.4 31.25 na 125.21 9.7 12.37 28.698
R4 40.2 22.4 31.35 na 125.41 9.7 12.37 28.698
R5 40.2 22.4 32.82 na 128.33 9.7 12.37 28.698
R6 40.2 22.4 32.36 na 127.43 9.7 12.37 28.698
R7 40.2 22.4 28.7 na 120.0 9.7 12.37 28.698
R8 40.2 22.4 28.98 na 120.59 9.7 12.37 28.698
R9 40.2 22.4 32.38 na 127.46 9.7 12.37 28.698
R10 40.2 22.4 33.82 na 130.27 9.7 12.37 28.698
R1A 39.6 34.45 na
R2A 39.6 34.46 na
R3A 39.6 34.52 na
R4A 39.6 34.63 na
R5A 39.6 36.24 na
R6A 39.6 35.74 na
R7A 39.6 31.74 na
R8A 39.6 32.06 na
R9A 39.6 35.75 na
R10A 39.6 37.33 na
A1 39.6 36.0 na
A2 39.6 36.01 na
A3 39.6 36.08 na
A4 39.6 36.19 na
A5 39.6 37.87 na
A6 48.39 62.0 na
A7 48.39 63.79 na
B1 39.6 37.38 na
B2 39.6 37.4 na
B3 39.6 39.04 na
B4 39.6 67.32 na
B5 39.6 69.09 na
M1 48.39 66.56 na
M2 48.39 67.97 na
M3 48.39 99.91 na
TR32 48.39 104.25 na
BR32 -2.13 131.85 na 250.0
LI15 -2.13 134.26 na
U15 -2.13 134.64 na
UN11 -9.0 139.89 na
UN12 -9.0 139.85 na
UN13 -9.0 139.74 na
UN14 -9.0 139.65 na
UN15 -9.0 139.54 na
UN16 -9.0 139.82 na
UN17 -9.0 141.48 na
UN18 -9.0 141.96 na
UN19 -9.0 142.94 na
UN20 -9.0 143.67 na
UN21 -9.0 143.69 na
UN22 -9.0 144.0 na
UN26 -9.0 144.64 na
UN2 -9.0 145.72 na
UN3 -9.0 145.27 na
UN4 -9.0 144.99 na
UN5 -9.0 144.63 na
UN6 -9.0 144.3 na
UN7 -9.0 143.82 na
UN8 -9.0 140.58 na
UN9 -9.0 140.26 na
UN10 -9.0 140.13 na
UN1 -9.0 146.78 na

Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Flow Summary - Standard
SALVAVIDAS SISTEMAS CONTRA INC Page 5
CEDIS COYOL COSTA RICA Date AUG.2018

Node Elevation K-Fact Pt Pn Flow Density Area Press


No. Actual Actual Req.

LI1 -2.0 143.78 na


PH2 8.0 139.65 na
PH1 8.0 140.18 na
DSCH -2.0 144.83 na
FP -2.0 145.24 na

The maximum velocity is 27.52 and it occurs in the pipe between nodes M2 and M3

Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams
SALVAVIDAS SISTEMAS CONTRA INC Page 6
CEDIS COYOL COSTA RICA Date AUG.2018

Hyd. Qa Dia. Fitting Pipe Pt Pt


Ref. "C" or Ftng's Pe Pv ******* Notes ******
Point Qt Pf/Ft Eqv. Ln. Total Pf Pn

*ARM OVER
R1 125.07 2.215 2E 14.004 1.640 31.176 K Factor = 22.40
to 120.0 T 14.004 28.008 0.260
R1A 125.07 0.1015 0.0 29.648 3.009 Vel = 10.41
0.0
125.07 34.445 K Factor = 21.31
R2 125.10 2.215 2E 14.004 1.640 31.190 K Factor = 22.40
to 120.0 T 14.004 28.008 0.260
R2A 125.1 0.1015 0.0 29.648 3.010 Vel = 10.42
0.0
125.10 34.460 K Factor = 21.31
R3 125.21 2.215 2E 14.004 1.640 31.247 K Factor = 22.40
to 120.0 T 14.004 28.008 0.260
R3A 125.21 0.1017 0.0 29.648 3.015 Vel = 10.43
0.0
125.21 34.522 K Factor = 21.31
R4 125.41 2.215 2E 14.004 1.640 31.346 K Factor = 22.40
to 120.0 T 14.004 28.008 0.260
R4A 125.41 0.1020 0.0 29.648 3.024 Vel = 10.44
0.0
125.41 34.630 K Factor = 21.31
R5 128.33 2.215 2E 14.004 1.640 32.824 K Factor = 22.40
to 120.0 T 14.004 28.008 0.260
R5A 128.33 0.1064 0.0 29.648 3.156 Vel = 10.68
0.0
128.33 36.240 K Factor = 21.32
R6 127.43 2.215 2E 14.004 1.640 32.361 K Factor = 22.40
to 120.0 T 14.004 28.008 0.260
R6A 127.43 0.1050 0.0 29.648 3.114 Vel = 10.61
0.0
127.43 35.735 K Factor = 21.32
R7 120.00 2.215 2E 14.004 1.640 28.698 K Factor = 22.40
to 120.0 T 14.004 28.008 0.260
R7A 120.0 0.0940 0.0 29.648 2.787 Vel = 9.99
0.0
120.00 31.745 K Factor = 21.30
R8 120.59 2.215 2E 14.004 1.640 28.984 K Factor = 22.40
to 120.0 T 14.004 28.008 0.260
R8A 120.59 0.0948 0.0 29.648 2.812 Vel = 10.04
0.0
120.59 32.056 K Factor = 21.30
R9 127.46 2.215 2E 14.004 1.640 32.379 K Factor = 22.40
to 120.0 T 14.004 28.008 0.260
R9A 127.46 0.1051 0.0 29.648 3.116 Vel = 10.61
0.0
127.46 35.755 K Factor = 21.32
R10 130.27 2.215 2E 14.004 1.640 33.822 K Factor = 22.40
to 120.0 T 14.004 28.008 0.260
R10A 130.27 0.1094 0.0 29.648 3.244 Vel = 10.85

Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams
SALVAVIDAS SISTEMAS CONTRA INC Page 7
CEDIS COYOL COSTA RICA Date AUG.2018

Hyd. Qa Dia. Fitting Pipe Pt Pt


Ref. "C" or Ftng's Pe Pv ******* Notes ******
Point Qt Pf/Ft Eqv. Ln. Total Pf Pn

0.0
130.27 37.326 K Factor = 21.32
*REMOTE BRACH LINE 1
R1A 125.07 2.215 T 14.004 1.290 34.445
to 120.0 0.0 14.004 0.0
A1 125.07 0.1015 0.0 15.294 1.553 Vel = 10.41
0.0
125.07 35.998 K Factor = 20.85
R2A 125.10 2.215 T 14.004 1.290 34.460
to 120.0 0.0 14.004 0.0
A2 125.1 0.1015 0.0 15.294 1.552 Vel = 10.42
0.0
125.10 36.012 K Factor = 20.85
R3A 125.21 2.215 T 14.004 1.290 34.522
to 120.0 0.0 14.004 0.0
A3 125.21 0.1017 0.0 15.294 1.556 Vel = 10.43
0.0
125.21 36.078 K Factor = 20.85
R4A 125.41 2.215 T 14.004 1.290 34.630
to 120.0 0.0 14.004 0.0
A4 125.41 0.1021 0.0 15.294 1.561 Vel = 10.44
0.0
125.41 36.191 K Factor = 20.85
R5A 128.33 2.215 T 14.004 1.290 36.240
to 120.0 0.0 14.004 0.0
A5 128.33 0.1064 0.0 15.294 1.628 Vel = 10.68
0.0
128.33 37.868 K Factor = 20.85
*REMOTE BRACH LINE 2
R6A 127.43 2.215 T 14.004 1.690 35.735
to 120.0 0.0 14.004 0.0
B1 127.43 0.1051 0.0 15.694 1.649 Vel = 10.61
0.0
127.43 37.384 K Factor = 20.84
R7A 120.00 2.215 0.0 3.310 31.745
to 120.0 0.0 0.0 0.0
R8A 120.0 0.0940 0.0 3.310 0.311 Vel = 9.99
R8A 120.59 2.215 T 14.004 1.690 32.056
to 120.0 0.0 14.004 0.0
B2 240.59 0.3404 0.0 15.694 5.343 Vel = 20.03
0.0
240.59 37.399 K Factor = 39.34
R9A 127.46 2.215 T 14.004 1.640 35.755
to 120.0 0.0 14.004 0.0
B2 127.46 0.1051 0.0 15.644 1.644 Vel = 10.61
0.0
127.46 37.399 K Factor = 20.84

Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams
SALVAVIDAS SISTEMAS CONTRA INC Page 8
CEDIS COYOL COSTA RICA Date AUG.2018

Hyd. Qa Dia. Fitting Pipe Pt Pt


Ref. "C" or Ftng's Pe Pv ******* Notes ******
Point Qt Pf/Ft Eqv. Ln. Total Pf Pn

R10A 130.27 2.215 T 14.004 1.690 37.326


to 120.0 0.0 14.004 0.0
B3 130.27 0.1094 0.0 15.694 1.717 Vel = 10.85
0.0
130.27 39.043 K Factor = 20.85
*REMOTE IN.RACK MAIN 1
A1 125.07 4.316 0.0 3.740 35.998
to 120.0 0.0 0.0 0.0
A2 125.07 0.0037 0.0 3.740 0.014 Vel = 2.74
A2 125.10 4.316 0.0 4.620 36.012
to 120.0 0.0 0.0 0.0
A3 250.17 0.0143 0.0 4.620 0.066 Vel = 5.49
A3 125.21 4.316 0.0 3.740 36.078
to 120.0 0.0 0.0 0.0
A4 375.38 0.0302 0.0 3.740 0.113 Vel = 8.23
A4 125.42 4.316 T 28.063 4.620 36.191
to 120.0 0.0 28.063 0.0
A5 500.8 0.0513 0.0 32.683 1.677 Vel = 10.98
A5 128.33 4.316 T 28.063 329.000 37.868
to 120.0 0.0 28.063 -3.807
A6 629.13 0.0782 0.0 357.063 27.939 Vel = 13.80
A6 0.0 4.316 E 14.032 8.790 62.000
to 120.0 0.0 14.032 0.0
A7 629.13 0.0783 0.0 22.822 1.786 Vel = 13.80
A7 0.0 4.316 T 28.063 7.410 63.786
to 120.0 0.0 28.063 0.0
M1 629.13 0.0783 0.0 35.473 2.776 Vel = 13.80
0.0
629.13 66.562 K Factor = 77.11
B1 127.43 4.316 0.0 3.740 37.384
to 120.0 0.0 0.0 0.0
B2 127.43 0.0040 0.0 3.740 0.015 Vel = 2.79
B2 368.05 4.316 T 28.063 4.620 37.399
to 120.0 0.0 28.063 0.0
B3 495.48 0.0503 0.0 32.683 1.644 Vel = 10.87
B3 130.27 4.316 T 28.063 336.900 39.043
to 120.0 0.0 28.063 0.0
B4 625.75 0.0775 0.0 364.963 28.275 Vel = 13.72
B4 0.0 4.316 E 14.032 8.790 67.318
to 120.0 0.0 14.032 0.0
B5 625.75 0.0775 0.0 22.822 1.768 Vel = 13.72
B5 0.0 4.316 T 28.063 6.620 69.086
to 120.0 0.0 28.063 -3.807
M2 625.75 0.0775 0.0 34.683 2.687 Vel = 13.72
0.0
625.75 67.966 K Factor = 75.90
M1 629.13 4.316 0.0 17.940 66.562
to 120.0 0.0 0.0 0.0
M2 629.13 0.0783 0.0 17.940 1.404 Vel = 13.80

Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams
SALVAVIDAS SISTEMAS CONTRA INC Page 9
CEDIS COYOL COSTA RICA Date AUG.2018

Hyd. Qa Dia. Fitting Pipe Pt Pt


Ref. "C" or Ftng's Pe Pv ******* Notes ******
Point Qt Pf/Ft Eqv. Ln. Total Pf Pn

M2 625.75 4.316 T 28.063 85.760 67.966


to 120.0 0.0 28.063 0.0
M3 1254.88 0.2807 0.0 113.823 31.948 Vel = 27.52
M3 0.0 6.357 2E 35.205 66.630 99.914
to 120.0 0.0 35.205 0.0
TR32 1254.88 0.0426 0.0 101.835 4.337 Vel = 12.68
TR32 0.0 6.357 B 12.573 50.520 104.251
to 120.0 Aty 30.176 60.352 22.880 * * Fixed Loss = 1
BR32 1254.88 0.0426 Fsp 0.0 110.872 4.721 Vel = 12.68
E 17.603
BR32 250.00 6.357 T 37.72 2.600 131.852 Qa = 250
to 120.0 0.0 37.720 0.0
LI15 1504.88 0.0596 0.0 40.320 2.403 Vel = 15.21
LI15 0.0 10.4 T 79.716 7.130 134.255
to 140.0 G 7.972 87.688 0.0
U15 1504.88 0.0041 0.0 94.818 0.386 Vel = 5.68
U15 0.0 9.42 2E 49.22 225.450 134.641
to 150.0 T 55.931 105.151 2.975
UN15 1504.88 0.0058 0.0 330.601 1.921 Vel = 6.93
0.0
1504.88 139.537 K Factor = 127.40
UN11 -581.48 9.42 0.0 39.370 139.891
to 150.0 0.0 0.0 0.0
UN12 -581.48 -0.0010 0.0 39.370 -0.040 Vel = 2.68
UN12 0.0 9.42 0.0 110.680 139.851
to 150.0 0.0 0.0 0.0
UN13 -581.48 -0.0010 0.0 110.680 -0.110 Vel = 2.68
UN13 0.0 9.42 G 5.593 87.500 139.741
to 150.0 0.0 5.593 0.0
UN14 -581.48 -0.0010 0.0 93.093 -0.093 Vel = 2.68
UN14 0.0 9.42 0.0 110.330 139.648
to 150.0 0.0 0.0 0.0
UN15 -581.48 -0.0010 0.0 110.330 -0.111 Vel = 2.68
UN15 1504.88 9.42 G 5.593 114.150 139.537
to 150.0 0.0 5.593 0.0
UN16 923.4 0.0024 0.0 119.743 0.282 Vel = 4.25
UN16 0.0 9.42 E 24.61 682.700 139.819
to 150.0 0.0 24.609 0.0
UN17 923.4 0.0024 0.0 707.309 1.665 Vel = 4.25
UN17 0.0 9.42 E 24.61 176.670 141.484
to 150.0 0.0 24.609 0.0
UN18 923.4 0.0023 0.0 201.279 0.473 Vel = 4.25
UN18 0.0 9.42 E 24.61 389.070 141.957
to 150.0 G 5.593 30.202 0.0
UN19 923.4 0.0024 0.0 419.272 0.987 Vel = 4.25
UN19 0.0 9.42 E 24.61 282.280 142.944
to 150.0 0.0 24.609 0.0
UN20 923.4 0.0024 0.0 306.889 0.722 Vel = 4.25

Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams
SALVAVIDAS SISTEMAS CONTRA INC Page 10
CEDIS COYOL COSTA RICA Date AUG.2018

Hyd. Qa Dia. Fitting Pipe Pt Pt


Ref. "C" or Ftng's Pe Pv ******* Notes ******
Point Qt Pf/Ft Eqv. Ln. Total Pf Pn

UN20 0.0 9.42 0.0 11.020 143.666


to 150.0 0.0 0.0 0.0
UN21 923.4 0.0024 0.0 11.020 0.026 Vel = 4.25
UN21 0.0 9.42 G 5.593 125.000 143.692
to 150.0 0.0 5.593 0.0
UN22 923.4 0.0024 0.0 130.593 0.308 Vel = 4.25
UN22 0.0 9.42 2E 49.22 215.580 144.000
to 150.0 G 5.593 54.813 0.0
UN26 923.4 0.0024 0.0 270.393 0.636 Vel = 4.25
UN26 0.0 9.42 2E 49.22 349.960 144.636
to 150.0 T 55.931 110.744 0.0
UN2 923.4 0.0024 G 5.593 460.704 1.084 Vel = 4.25
UN2 -1504.88 9.42 2E 49.22 395.660 145.720
to 150.0 G 5.593 54.813 0.0
UN3 -581.48 -0.0010 0.0 450.473 -0.450 Vel = 2.68
UN3 0.0 9.42 E 24.61 249.960 145.270
to 150.0 G 5.593 30.202 0.0
UN4 -581.48 -0.0010 0.0 280.162 -0.280 Vel = 2.68
UN4 0.0 9.42 T 55.931 299.140 144.990
to 150.0 G 5.593 61.524 0.0
UN5 -581.48 -0.0010 0.0 360.664 -0.361 Vel = 2.68
UN5 0.0 9.42 E 24.61 300.950 144.629
to 150.0 G 5.593 30.202 0.0
UN6 -581.48 -0.0010 0.0 331.152 -0.331 Vel = 2.68
UN6 0.0 9.42 4E 98.439 379.620 144.298
to 150.0 0.0 98.439 0.0
UN7 -581.48 -0.0010 0.0 478.059 -0.479 Vel = 2.68
UN7 0.0 9.42 18E 442.977 2782.800 143.819
to 150.0 2G 11.186 454.163 0.0
UN8 -581.48 -0.0010 0.0 3236.963 -3.238 Vel = 2.68
UN8 0.0 9.42 3E 73.829 236.890 140.581
to 150.0 G 5.593 79.422 0.0
UN9 -581.48 -0.0010 0.0 316.312 -0.316 Vel = 2.68
UN9 0.0 9.42 E 24.61 114.130 140.265
to 150.0 0.0 24.609 0.0
UN10 -581.48 -0.0010 0.0 138.739 -0.139 Vel = 2.68
UN10 0.0 9.42 2E 49.22 124.540 140.126
to 150.0 T 55.931 110.744 0.0
UN11 -581.48 -0.0010 G 5.593 235.284 -0.235 Vel = 2.68
0.0
-581.48 139.891 K Factor = -49.16
UN2 1504.88 9.42 E 24.61 158.360 145.720
to 150.0 0.0 24.609 0.0
UN1 1504.88 0.0058 0.0 182.969 1.063 Vel = 6.93
UN1 0.0 10.4 0.0 7.000 146.783
to 140.0 0.0 0.0 -3.032
LI1 1504.88 0.0041 0.0 7.000 0.029 Vel = 5.68
LI1 0.0 10.42 E 26.62 10.000 143.780
to 120.0 0.0 26.620 -4.331
PH2 1504.88 0.0054 0.0 36.620 0.197 Vel = 5.66

Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams
SALVAVIDAS SISTEMAS CONTRA INC Page 11
CEDIS COYOL COSTA RICA Date AUG.2018

Hyd. Qa Dia. Fitting Pipe Pt Pt


Ref. "C" or Ftng's Pe Pv ******* Notes ******
Point Qt Pf/Ft Eqv. Ln. Total Pf Pn

PH2 0.0 10.42 3E 79.861 20.000 139.646


to 120.0 0.0 79.861 0.0
PH1 1504.88 0.0054 0.0 99.861 0.536 Vel = 5.66
PH1 0.0 10.42 B 22.99 10.000 140.182
to 120.0 E 26.62 49.610 4.331
DSCH 1504.88 0.0054 0.0 59.610 0.320 Vel = 5.66
DSCH 0.0 10.42 S 66.551 10.000 144.833
to 120.0 0.0 66.551 0.0
FP 1504.88 0.0054 0.0 76.551 0.411 Vel = 5.66
0.0
1504.88 145.244 K Factor = 124.87

Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087

You might also like