COMPARISION BETWEEN TAC AND OISD 116 RULES

TAC OISD 116


CLASSIFICATIONS OF OCCUPANCIES –(As given in F P Manual)
• LIGHT HAZARD OCCUPANCIES:
• ORDINARY HAZARD OCCUPANCIES:
• HIGH HAZARD OCCUPANCIES:
SUB-CATEGORY (A) SUB-CATEGORY (B).
HAND APPLIANCES SHALL BEAR ISI CERTIFICATION • Dry chemical powder fire extinguishers 25/50/75 kg
MARK. capacity: IS:10658/ UL299(in addition to 10kg DCP
Only meant for attacking small fires in their incipient stages requirement)
and are not intended to deal with large outbreaks of fires. • At least one fire extinguisher should be provided for every
one 9-litre water type extinguisher or 5 kg DCP extinguisher or 750 m2 of hazardous operating area.
2 4.5 KG CO2 extinguishers shall be provided for every • CO2 extinguishers 4.5/6.5/9.0/22.5 kg capacity
300m2 of floor area for ordinary and high hazard risks (and for (IS:2878/UL154)At least one fire extinguisher should be
every 450m2 in case of light hazard risks) provided for every 750 m2 of hazardous operating area.
The appliances shall be so distributed over the entire floor • To be located in substations, power stations, office
area, that a person has to travel not more than 15 m to reach building and control room. The number should be
the nearest appliance. determined based on the maximum traveling distance of
Generally, hand appliances shall be placed as near as 15 metre.
possible to exits or staircase landings. • At least one fire extinguisher shall be provided for every
Installation of Hand Appliances as per the Committee’s 250 m2 of hazardous operating area. There shall not be
Regulations is a prerequisite for any occupancy, other than less than 2nos.extinguishers at one designated location
storage occupancy e.g. control room.
• Portable clean agent extinguishers
• This should be as an alternate to CO2 extinguisher.
• To be located in control rooms, computer rooms,
laboratories and office buildings.
• Dry chemical powder (DCP)* fire Extinguishers -10 kg
capacity: IS:15683/UL299
• Extinguisher to be located in process units, pump houses,
pump area, LPG storage area, LPG bottling plant, Oil
separator, tank truck/ tank wagon loading areas,
substations, Work shops, laboratory, power station
buildings etc.
• The number should be determined based on the max.
Traveling distance of 15 M in above areas. At least one
fire extinguisher shall be provided for every 250 m2 of
hazardous operating area. There shall be not less than
two extinguishers at one designated location e.g. pump
house.
In place of 10 kg, 5 Kg DCP Extinguisher shall be provided at
elevated locations.
Small Bore Hose Reels: • Rubber hose reel (25mm)
This sort of protection is not deemed suitable for To be located in Process unit battery limits and other process
buildings/compartments containing electrical apparatus only or areas for quenching of incipient fires.
in respect of buildings/ compartments in which flammable
liquids are stored and/or used
no part of the floor SHOULD BE more than 6 m. distant from a
hose nozzle when the hose is fully extended
HYDRANTS/FIXED MONITORS: Fire hydrants around the tanks to be provided with 4” pumper
The stand posts shall be 80 mm in diameter for single headed connection.
hydrants. 100 mm for double-headed hydrants and monitors of Hydrants / Monitors shall be located with branch connections and
63 mm or 75 mm size and 150 mm for monitor of 100 mm not directly over main header
size.
N.B - Orifice plates of suitable design may be provided for
hydrants where the pressure exceeds 7 kg. /cm2
At least one hydrant post shall be provided for every 60 m of
external wall measurement in case of Light Hazard
Occupancy, for every 45 m in case of Ordinary Hazard
Occupancy and every 30 m of external wall measurement or
perimeter of unit battery limit in case of High Hazard

1
Occupancy.
NOTE: Notwithstanding the above, hydrants protecting utilities
and miscellaneous buildings in High hazard risks may be
spaced at 45 m.
No building shall be deemed to be protected by a hydrant The hydrants/monitors shall be located at a minimum Distance of
unless such hydrant is within 15 m of the building. Where any 15 M from the periphery of storage tank or hazardous equipment
part of a building is normally used for storage purpose or being protected
where hazardous processes are carried out, there shall be two this distance shall not be less than 5 M and more than 15 M from
single or one double headed hydrant within 15 m of the the face of building.
building. Hydrants / Monitors shall be located along road side berms for
In case of Buildings/Plants occupied for High Hazard process easy accesibility
or storages, the above-specified distance may be increased to
22.5 m.
All hydrant outlets shall be situated at a workable height of All hydrant outlets shall be situated at a workable height of about
about 1 metre above ground level. 1.2 metre above ground level.
In case of storeyed buildings, satisfactory access shall be Hydrants within buildings shall be in accordance with IS 3844.
provided to all parts of each floor by means of incombustible
internal or external staircases. Normally, a minimum of two Dry/Wet Risers with hydrants should be provided on each floor of
such staircases will be needed per compartment, but in case technological structures.
the area of the compartment exceeds 2,000 sq. m., an
additional staircase shall be provided for every additional
1,500 sq. m. or part thereof.
On the other hand, if a compartment has a floor area of less
than 500 sq. m., one access staircase shall be acceptable.
Tall columns, structure, towers and equipment will be A minimum of 2 monitors shall be provided for the protection of
considered as protected by hydrants at ground level, provided cluster of columns, heaters, gassifiers, etc., and where it is not
they are less than 15 m in height. When the height exceeds possible to approach the higher levels.
15 m, the concerned hydrants shall be replaced by monitors. Field adjustable variable flow monitors shall be installed atcritical
locations
Alternate hydrants for protection of loading unloading bays, The location of monitors shall not exceed 45 M from the hazard to
rail/truck gantries shall be replaced by water/foam monitors. be protected.
Tank Wagon & Tank Lorry loading/unloading gantry area shall be
provided with alternate water cum foam monitors having
multipurpose combination nozzles and fire hydrants located at a
spacing of 30 M on either sides of the gantry.
Storage of material in the open
Metals, Metallic goods, Machinery and other non-hazardous storage-
One single hydrant for every 60 m of storage periphery located beyond 2 m but within 15 m of storage area.
Coal or Coke-
One single hydrant for every 45 m of storage periphery located beyond 2 m but within 15 m of storage area

Hydrants shall be protected if subject to mechanical damage

combustible/flammable liquid storage


Hydrants shall be located beyond 15 m, but within 35 m of tank shell as specified below -
Tanks upto 10 m dia.One double headed or two single headed hydrants.
Tanks above 10 m but upto 20 m dia.Two double headed or four single headed hydrants.
Tanks above 20 m dia.Three double headed or six single headed hydrants.

Protection of spheres/bullets,
Upto 50 m3 WATER CAPACITY-Three single hydrants (or one single + Two double headed hydrants)
Above 50 m3 but upto 150 m3-One monitor + two single (or one double headed hydrants)
Above 150 m3-Two monitors + four single hydrants (or two double headed hydrants)
Pump rooms shall be located 6 m away from all surrounding OISD
buildings and overhead structures. Firewater pumps shall be located as far away as possible (not less
N.B. for High Hazard (B) occupancies, the pump room shall be than 60 M) from hazardous areas
located 30 m clear of all equipment where flammable fluids
having flash point below 65o C are handled and/or stored
PUMPS:
Nos and Capacities of pumps are given in F p Manual in tabular form for different kinds of hazards
In calculating the number of hydrants in the system, a double headed hydrant shall be counted as two, a fixed monitor of 63 mm size
having nozzle bore of 32 mm shall be counted as three, a fixed monitor of 75 mm size having nozzle bore of 38 mm shall be counted

2
as four and a fixed monitor of 100 mm size having nozzle bore of 45 mm as six hydrant points
The diameter of the suction pipe shall be such that the rate of flow of water through it does not exceed 90 m. per minute when the
pump is delivering at its rated discharge. If, however, the pump is situated below the level of its water supply, the diameter of the
suction pipe/header shall be based upon a rate of flow not exceeding 120 m. per minute.
LIGHT HAZARD RISKS.
The pump delivery pressure will need to be 7 kg/cm2 if the highest floor of the risk is at a height exceeding 15 m above the
surrounding ground level.
Where the systems are hydraulically designed, The total pumping capacity need not be greater than 190 (683) irrespective of the
number of hydrant points.
ORDINARY HAZARD RISKS
Where the systems are hydraulically designed, the total pumping capacity need not be greater than 302 (1092) irrespective of the
number of hydrant points.Where the hydrant service consists of more than one pump, not more than half the total number (total
number + 1 in case of odd number) of pumps shall have prime movers of one type.
Where plants and other facilities are protected by sprinkler system tapped from the pressurised hydrant service
If the total water requirement for sprinkler system exceeds the requirement of the hydrant service as per Table 2, the pumping
capacity shall be equivalent to the former.
Where seawater is used or where the quality of water necessitates the use of special metals/alloys, the use of such metals or alloys
shall be insisted.
where the water demand for water spray and/or foam protection is in excess of that required for the hydrant system, the pumping
capacity shall be based on the higher water demand.
HIGH HAZARD RISKS
In case of High Hazard (B) risks where the aggregate pumping capacity required exceeds 1,640 m3/hr., larger capacity pumps are
acceptable provided the capacity of the largest pump does not exceed 25 % of the aggregate installed pumping capacity
where double headed hydrants are used throughout the risk a double headed hydrant may be regarded as a single hydrant only.
COMPRESSION IGNITION ENGINE DRIVEN PUMPS
Engines, shall have bare engine horsepower rating equivalent to the higher of the following two values
• 20 % in excess of the maximum brake horsepower required to drive the pump at its duty point.
• The brake horsepower required driving the pump at 150 % of its rated discharge.
FUEL TANK:
The tank shall be mounted above the engine fuel pump to give gravity feed. capacity of the tank shall be sufficient to allow the engine
to run on full load for –
Light Hazard-2 Hours
Ordinary Hazard- 4 Hours
High Hazard (A) -6 Hours
High Hazard (B) 8 Hours
PUMPS The capacity and number of main fire water pumps shall be fixed
Fire Pumps in High Hazard (B) category occupancies shall be based on design fire water rate,
provided with positive suction and automatic starting devices The capacity of each pump shall not be less than 400 m3/hr or
capable of sequential starting of the pumps. more than 1000 m3/hr.

When total number of Working pumps work out to be one or


two,100% standby pumps shall be provided.

ii) When total numbers of working pumps are more than two, 50%
standby pumps shall be provided.

Number of diesel driven pumps shall be minimum 50% of the total


number of pumps (inclusive of standby pumps).
2 Jockey pumps (1working plus 1 standby) shall beprovided.

maximum water requirement for spray application should generally


not exceed 1200 m3/hr.
• Pressurised Storage vessels-10.2 lpm/m2
• Volatile product service pumps located under pipe racks-
20.4 LPM/m2
• Columns/Other extremely hazareas-10.2 LPM/m2
• LPG Pump house-20.4 LPM/m2
• LPG Truck/Wagon Loading gantries-10.2 LPM/m2
• LPG Bottling Plants/ Cold repair shops-10.2 LPM/m2
• Oil Truck/Wagon Loading gantries-10.2 LPM/m2
• Cable trays-10.2 LPM/m2
Transformers-10.2 LPM/m2

3
Floating roof storage tanks and floating-cum-fixed storage All the tank farms and other areas of installation where
tanks exceeding 30m in diameter and fixed roof storage tanks hydrocarbons are handled shall be fully covered by hydrant
containing products having flash point below 32o C shall be System.
considered as hydrant protected only if, supplementary
medium velocity water spray system or fixed/semi fixed foam 4.2.1 Fixed Water Spray on storage Tanks
system is also provided. • i) Class A Petroleum storage in above ground tanks shall
In case of foam system, there shall be additional protection by have fixed water spray system, whether floating roof or
water spray system in the form of a ring along the top edge of fixed roof.
the vertical face of the tank. Where tanks are protected by a • ii) Class 'B' Petroleum storage tanks of following
medium velocity water spray system tapped from the hydrant dimensions shall be provided with fixed water spray.
service, the water requirements of the spray system shall be • - Floating roof tanks of diameter larger than 30 M
calculated for tanks located in a common dyke which have the • - Fixed roof tanks of diameter larger than 20 M.
largest aggregate shell surface area at a rate of 10 litres
/minute/m2 of tank shell surface area except where the system Semi-fixed Foam system shall be provided for the following tanks:
has been designed to comply with the provisions contained in • - Floating roof tanks storing Class 'A' and Class 'B'
N.B 4 under rule 7.6.19 (mandatory protection) in which case petroleum products.
the rate of flow can be reduced to 3 lpm/m2). • - Fixed roof tanks storing Class 'A‘ and class 'B' petroleum
Even in the case of tanks located in separate dykes, the shell products.
surface area of all tanks located within a distance of 15 m (or • - Fixed roof tanks storing class 'C'petroleum products, of
the diameter of the larger tank if the same is more than 15m) diameter larger than 40 M.
shall be aggregated and the water demand of such cluster of •
tanks shall be calculated at the rate of flow indicated in the Automatic actuated rim seal fire detection and extinguishing
foregoing paragraph. system shall be provided on all existing aswell as new external
The water requirement of the spray system shall then be floating roof tanks storing Class A petroleum.
loaded for supplementary hose stream protection as under – Only those Rim seal protectionsystems, which use the linear
Where the largest tank in, in a dyke, has a diameter – heathollow metallic tube type detectorsshall be used.
Upto 10 m-1,150 LPM
More than 10 m and upto 20 m-2,250 LPM Water application rate
Over 20 m,-4500 LPM • Atmospheric storage Tanks
spheres/bullets • 3 Ipm/m2 of tank shell area for tank on fire
Taking into consideration the configuration of bullets/sphere, • 3 Ipm/m2 of tank shell area for exposure protection for
the one which has the largest number of other bullets/spheres tanks located within (R+30) M from centre of tank-onfire
within R +15 M of the centre thereof shall be selected. within the same dyke area.
The water demand shall then be worked out at the rate of 10 • 1 Ipm/m2 of tank shell area for exposure protection for
L/min/M2 of the aggregate shell surface area of the tanks located outside (R+30) metre from centre of tank-
bullet/spheres concerned and all bullets/spheres within R + 15 on-fire within the same dyke area.
M of the centre thereof.
The water requirement of the spray system worked out shall LPG and hydrogen Pressure storage vessels shall be provided with
then be loaded for supplementary hose stream protection as automatic water spraysystem.
under -
Upto and including 50 m3-1,750 LPM ii) Automatic water spray system shall be provided in LPG bottling
Above 50 m3 upto 150 m3-2,250 LPM stations, LPG loading/unloadinggantries and LPG pump
Above 150 m3-4,500 LPM andcompressor
plants and other facilities
Where the plants and other facilities are protected by medium Oil loading/unloading Tank Truck &Tank Wagon Gantries shall be
velocity water spray systems, tapped from hydrant service, provided with water spray and/or foam system.
water requirement of the spray system shall be loaded by In case automatic fixed water spray system is provided in TW
4,500 LPM for supplementary hose stream protection. gantry, the gantry may be divided into suitable number of segments
Transformers (each segment having min. length of 15 m length & width of 12 m)
Where transformers are protected by high velocity water spray and three largest segments operating at a time shall be considered
system tapped from hydrant system, water requirements of the as single risk for calculating the water requirement.
spray system shall be determined as per Committee's rules for
water spray system. Water requirement of the spray system HVWS system for Transformers/Cable Galleries
worked out as above shall then be loaded by 1,750 LPM for
supplementary hose stream protection. a provision shall be made to actuate the water spray system from a
safe approachable central location

4
WATER SUPPLY Where rate of make up water supply is 50% or more, this storage
The effective capacity of the reservoir, shall be as indicated in capacity can be reduced to 3 hours aggregate working capacity of
the table 1. main pumps.
Reservoirs of and over 2,25,000 litres capacity shall be in two In case sea water or treated effluent water is used for firefighting
interconnected equal compartments purposes, the material of the pipe selected shall be suitable for the
Where the Fire pump(s) draw water from the reservoir under service.
suction lift conditions the two compartments shall be Suitable provisions shall be kept for make up firewater from various
connected to a common sump sources like ETP, Process from various sources like ETP,
ProcessCooling Water, river, ponds etc.
In case of dual purpose reservoirs, the tapping for the general
water pumps shall be taken at a higher level such that the
capacity of the reservoir between tappings is at least
equivalent to the requirements indicated in Table 1.
The capacity of the reservoir for ordinary and high hazard
class occupancies may be reduced by the quantum of inflow
of one hour in case of ordinary hazard, 90 minutes in case of
high hazard (A) and two hours in case of high hazard (B)
occupancies), from a reliable sources, but in no case shall the
reservoir capacity be less than 70 % of that mentioned above.
A terminal main of 80 mm diameter shall not feed more than one hydrant, that having a diameter of 100 mm shall not feed more
than two hydrants, that having a diameter of 125 mm shall not feed more than three hydrants and a main of 150 mm shall not feed
more than five hydrants.
In case where, owing to the size or layout of the building, or building being divided by internal walls, any point within the building is at
a distance of more than 45 m from an external fire hydrant, an internal hydrant system shall be provided so that no portion of the
floor is more than 45 m from an external hydrant or 30 m from an internal hydrant.
• N.B: Distance of 45 m indicated above shall be increased to 60 m for light hazard occupancies and reduced to 30 m for high
hazard occupancies.
Internal staircases shall be so located that atleast one of its enclosing walls is an external wall of the building.
Every opening from the staircase to any portion of the building or to a roof used as a floor shall be fitted with a single fireproof door.
N.B: The above rule will not apply to buildings, the upper floors of which are occupied by offices, air washer plants, rest rooms, cloak
rooms, canteen and the like.
For High Hazard occupancies, the hydrant system shall be Fire water distribution ring main shall be sized for 120% of the
hydraulically so designed that when half the aggregate design water rate.
pumping capacity is being discharged at the The fire water system shall be designed for a minimum residual
farthest/hydraulically most remote point and the other half in pressure of 7.0 kg/cm2g at the hydraulically remotest point of
the most vulnerable area enroute, a minimum running application at the designed flow rate at that point.
pressure of 5.25 kg/sq. cm is available at the former point and
the rate of flow of water does not exceed 5 m/second
anywhere in the system.
For Light and Ordinary Hazard Occupancies having more
than 55 points,
A single hydrant system may be installed provided, it is
hydraulically designed (where the highest hydrant is located
more than 20 m above ground level, pre calculated systems
shall not be accepted) as per the parameters indicated in N.B.
2 above, except that minimum running pressure shall be 3.5
kg/sq. cm. Instead of 5.25 kg/sq. cm
Hydrant MAINS: Pipes: Carbon Steel as per IS: 3589/ IS: 1239/IS:1978 or
Wrought or mild steel pipes (galvanised or un-galvanised) of Composite materials In case saline water/ treated effluent water is
‘Medium’ grade conforming to IS: 1239 or IS: 3589 having used. pipes made of composite materials as per API 15LR/API 15
welded joints and coated and wrapped as per IS: 10221 HR shall be used.
Holiday Testing for Wrapping and Coating is essential. Provision of hose boxes should be given at critical locations for
Un-plasticized PVC ‘Class 4’ pipes conforming to IS 4985 and housing hoses and nozzles.
HDPE pipes conforming to IS: 4984.
N.B. These pipes are permitted for use in Light Hazard
Occupancies for underground mains only.
As far as possible MS Steel pipes shall also be laid 1m below The main shall have at least 1.5 metre earth cushion under the
ground level. roads. In case of crane movement areas, pipes should be
Mains above ground shall be adequately supported at regular protected with concrete/steel encasement.These shall not be laid
intervals on masonry or RCC stools or pedestals and not on along with process piping on common sleepers.
pipe racks. piping should normally be laid above ground at a height of atleast
Such Pipes shall be run at least 6 m away from the face of the 300 mm above finished ground level. However, the fire water

5
buildings and open storage areas in case of Light and network piping shall be laid below ground level at the Road
Ordinary Hazard Occupancies and 15 m. in case of High crossings.
Hazard Occupancies.
At least 10 % of all the welded joints shall be rediographically tested and half of the joints radiographed shall be the ‘field joints’.
The system shall be capable of withstanding for two hours a pressure equivalent to 150 % of the maximum working pressure. While
hydro-testing inclusion of cut-off valves in the mains to be tested should be avoided.
Mains shall be laid in rings and their sizes shall be as per Tables 3 & 3A.
Mains shall not be laid under buildings.
CUT OFF VALVES . Additional valves shall be provided in the segments where the
Cut-off valves shall conform to IS: 780, PN 1.0 length of the segment exceeds 300 M.
In case of system having working pressure in excess of 7 Flushing connections with isolation valves should be provided at
kg/cm2 PN- 1.6 rating would be necessary for valves suitable locations in the firewater ring main.
Cast Steel valves of class 150 are, however, acceptable
irrespective of the working pressure of the system.
Butterfly valves also can be accepted subject to the condition
that those exceeding 150 mm shall necessary be of gear
operated.
Fire Fighting staff
in no case shall be less than eight trained persons be available at any time during the day or night. Minimum number of trained
persons required may be further reduced to six in case of automatic pressurised hydrant systems.
REQUIREMENTS OF HOSE PIPES: i) For installation with hydrants upto 100 Nos: - One 15 mtrs hose
If hose is kept in central hose stations, for each of the first ten length/hydrant.
hydrants in the compound of the premises two lengths of hose ii) For installation with more than 100 hydrants: - One 15 metre
15 m each and an additional 15 m length for each hydrant in hose length/hydrant, for the first 100 hydrants; and, - One 15 M
excess of ten, shall be provided. hose length for every 10 hydrants above 100.
In case of system having more than 55 hydrant outlets, the The hose length so calculated shall be suitably divided into hose
total number of hose lengths required may be limited to 55 lengths of 15 M, 22.5 M or 30 M. Of the total Requirement of the
plus 20 percent of the number of hydrant outlets in excess of hoses, minimum 50% of hoses shall be of type B.
55. 4" Hoses of suitable length for feeding to large capacity monitors
Where a fire engine is maintained on the premises the number wherever installed.
of hose, pipes required (including those on the engine) would
be 55 plus 10 percent of the number of outlets in excess of 55.
REQUIREMENTS OF NOZZLES:
The number of nozzles to be provided shall be equivalent to
half the number of hose pipes installed on the premises.
Where storage tanks are protected by a fixed foam system OISD
connected to the hydrant service, water requirement for the In determining total solution flow requirements, potential
foam system shall be equivalent to that required by the largest foamlosses from wind and other factorsshall be considered.
protected tank at a rate of 5 litres/minute/m2 of liquid surface For cone roof tanks containing liquid hydrocarbons, the foam
area for fixed roof tanks and 12.2 lpm/m2 of rim seal in case of solution delivery rate shall beat least 5 Ipm/m2 of liquid surface
floating roof tanks. area of the tank to be protected.
conditions regarding supplementary hose stream protection, For floating roof tanks containing liquid hydrocarbons foam solution
pumping capacity remain the same as for water spray delivery rate shall be at least 12 Ipm/m2 of seal area with foam
protection. dam height of 600 mm of the tank to be protected.
In case of floating roof sinking, the rate considered should be 8.1
Ipm/m2 of liquid surface areas.
FOAM COMPOUND: OISD
The stock of foam compound to be maintained shall be • Foam compound: (IS: 4989 (Part-III)
equivalent to at least two times the requirement of the tank • Higher of the quantities in :
needing maximum quantity of foam. Foam Compound shall be • 1. 60,000 litre (excluding that in foam tender) for
chemically neutral (PH 6.5 to 7.5) installation having largest tank of diameter as 60 M.
• 2. 77,000 litre for installation having largest tank of
diameter as 79 M.
• Minimum of 90% of storage of foam compound shall be of
AFFF type. Minimum life of foam compound shall be
taken as per manufacturer's data.
• Foam compound should be tested periodically for
ensuring its quality and the deteriorated quantity replaced.
- Quantity of foam compound equal to 100% of requirement
should be stored in the Installation, subjected to a
minimum of 60,000 litres. However, for installations
having tankages larger than 60 M diameter, minimum of

6
77000 liters foam should be stored
- 4000 kg for the DCP tender plus 500 kg for additional
requirement.
Electric supply for fire pumps OISD
A direct feeder without any tappings shall be laid from the sub- A direct feeder dedicated only to fire water pumps shall belaid from
station to the pump house. The feeder shall consist of an the sub-station to ensure reliable power supply. The direct feeder
armoured cable buried underground and shall not pass under line shall not run along with other HT cables.
any building or permanent structure. The system shall ensure auto start of the standby pump in case a
The electric supply to the pumping set(s) shall be entirely pump in sequence failed to take start.
independent of all other equipment in the premises i.e. even Power supply to the electric driven pumps should be from two
when the power throughout the entire premises is switched off, separate feeders.
the supply to the pump shall continue to be available un-
interrupted.
Transformer cubicles inside these sub-stations shall be
separated from H.T. and L.T. cubicles and from each other by
blank walls of bricks/stone/concrete blocks of 355 mm
thickness or of R.C.C of 200 mm with door openings, if any
therein, protected by single fireproof doors. The sub-station(s)
and D.G. house(s) shall also be separated from each other as
above.
Baffle walls of bricks/stone/concrete blocks of 355 mm
thickness or of R.C.C. of 200 mm thickness shall be
constructed between two transformers and these walls shall
be extended horizontally 600 mm beyond the extremities of
the transformers and vertically 600 mm above the highest
point of the transformers.
The fire pump circuit shall be protected at the origin by an
automatic circuit breaker Further, the under voltage
release/`no volt’ coil of the circuit breaker shall be removed.
The motor rating shall be equivalent to the horsepower
required to drive the pump at 150 % of its rated discharge
The sub-station(s) and/or D.G. house(s)-supplying power to
the fire pump(s) shall be located at least 6 m away from all
surrounding buildings.
Where this is not feasible, all door and window openings of the
surrounding buildings within 6 m of the sub-station(s) and/or
D.G. house(s) shall be protected by single fireproof doors and
6 mm thick wired glasses in steel framework respectively. The
above provisions shall also apply when the sub-station(s) and
D.G. house(s) are within 6 m of each other.
SPECIAL DISPENSATIONS FOR ELECTRICAL GENERATING STATIONS
WATER SUPPLY:
The fore bay supplying water to the thermal power station fed by canals from perennial water sources like rivers, rivulets, dams etc.
may be accepted as firewater reservoir
The cooling water pond (s) may also be accepted as firewater reservoir
NOTE: Cooling water basins shall not be acceptable as equivalent to cooling water ponds.
PUMPS:
Higher capacity pumps not exceeding 410 m3/hr and 88 m head may be acceptable. In order to achieve the minimum pressure of
3.5 Kg./cm2 at higher elevation, booster pump(s) with a capacity of 137 m3/Hr., having requisite rated head may be acceptable.
Electrically driven booster pump(s) shall in addition to the normal supply be connected to the emergency power supply also.
ABOVE GROUND HYDRANT MAINS:
In case of practical difficulties in maintaining the stipulated distance from the face of the building in case of above ground over head
mains, warranted under demanding circumstances in specific areas, for example between Boiler House and TG Building and
between Transformer and T.G. Building, the same may be permitted provided the mains installed in such areas form part of sub-ring
only.
STAIRCASES FOR STOREYED TG HALL/BOILER HOUSE/MILL BAY:
At least 50 % of the number of staircases thus arrived at shall conform to Rules 7.6.15.1, 7.6.15.2 and 7.6.15.3.
REQUIREMENT OF HOSE PIPES IN T.G.HALL/BOILLER HOUSE/MILL BAY:
For use with each hydrant on staircase landing two lengths of hoses 15 m each and a nozzle with attached branch pipe shall be
provided in hose box alongside each landing valve.
TAC SPL RULINGS
Piers, Wharfs and Jetties - to be classified normally under ordinary hazard category unless Category III of list of hazardous materials

7
are handled.
In case of new systems where the number of hydrants is expected to be between 100 and 150; and where further extension of the
system beyond 150 hydrants is not anticipated, a single pump of 410 m3/hr capacity at 7/8.8 Kgs./cm2 may be permitted.
Likewise in case of old installations where the system is extended beyond 100 hydrants but not exceeding 150 hydrants; and where
further extension beyond 150 hydrants is not anticipated, an additional pump of 171 M3/hr. at 7 Kgs./Cm2 may be permitted.
Where spray system/sprinkler system is provided for the protection of equipment/plant the water demand of such a system should be
worked out and compared to the water demand of tanks of 10 M, 20 M and beyond 20 M dia. and he supplementary hose stream
protection indicated for the equivalent tank diameter shall be provided
Where hydrant/monitors located along one longer side of a storage area are more than 90 m from those along the other longer side,
monitors having jets of longer reach may be accepted
ADDITIONAL OISD RULES
PETROLEUM PRODUCTS
Class 'A' Petroleum: Liquids having flash point below 23 degrees C.
Class 'B' petroleum: Liquids havingflash point of 23 degrees C and above but below 65 degrees C.
Class 'C' petroleum : Liquids having flash point of 65 degrees C and above but below 93 degrees C.
Excluded Petroleum: Liquids having flash point of 93 degrees C and above.
b) Classification for heated products :
At locations where the handling temperatures are higher than the flash point of the product in circumstances where product handled
is artificially heated to above its flash point, class 'C' product shall be considered as Class 'B' product and Class 'B'product shall be
considered as Class 'A' product.
OISD
Fixed Remote / Manual operated High Volume Long Range Water cum Foam Monitors
They shall be provided in
• i) Tank farm area. (all the tanks in the installation shall be within the horizontal range of foam throw.)
• ii) Inaccessible areas such as column, reactor, compressor house etc in critical units like CCRU, DHDS, HCU, Hydrogen,
FCCU, DCU, CDU
• iii) Critical equipments at higher locations (above 45 mtrs.)
• The electrical or hydraulic remote control mechanism shall be in line with Hazardous Area Classification.
Number and capacity of monitor shall be provided in such a way that foam application rate from the monitors meet requirement of
foam application rate (8.1 LPM/m2) for full surface tank fire
Water Spray System in Process Unit shall be provided for hazardousareas like

Un-insulated vessels having capacity larger than 50 m3 and containing class A or B flammable liquid.

Vessels inaccessible to fire tender/ mobile equipment, fire hydrants

Pumps handling petroleum products class 'A' under pipe racks.

Pumps handling products above auto-ignition temperature underpipe racks

Air fin coolers in hydrocarbon service located above pipe racks /elevated location.

Water spray rings for columns of height more than 45 M shall be provided
Building/sheds storing combustible and flammable materials.- to be sprinkler protected
FIREWATER FLOW RATE
Several combinations of flow requirements shall be assumed for design of network.
Also whenever firewater demand increases due to addition of plant & facilities or extensive extension of network, fresh Hydraulic
analysis shall be carried out.
The fire water system in an installation shall be designed to meetthe fire water flow requirement forfighting two fires simultaneously
or single fire for largest floating roof tank roof sinking case, whichever requiring largest water demand.
Two of the largest flow rates calculated for different sections as shown below shall be added and that shall be taken as design flow
rate.
i) Fire Water flow rate for tank farm shall be aggregate of the following:
Water flow calculated for cooling atank-on-fire at a rate of 3 Ipm/m2of tank shell area.
Water flow calculated for all other tanks falling within a radius of (R+30m) from the center of the tank on fire at a rate of 3 Ipm/m2 of
tank shell area.
Water flow calculated for all other tanks falling outside a radius of (R+30) M from centre of the tank on fire and situated in the
samedyke area at a rate of 1 Ipm/m2 of tank shell area.
Water flow required for applying foam into a single largest coneroof or floating roof tank (after the roof has sunk) burning surface
area of oil, by way of fixed foam system, where provided or by useof water/foam monitors.
Fire water flow rate for supplementary stream, shall be based on using 4 single hydrantoutlets and 1 HVLR 1000GPM)

8
simultaneously. Capacity of each hydrant outlet as 36 m3/hr and of each monitor as 228 m3/hr shall be considered
ii) Fire water flow rate for LPG sphere storage area shall be aggregate of the following:
Water flow calculated for cooling LPG sphere on fire at a rate of 10.2 Ipm/ m2 of sphere surface area.
Water flow calculated for all other spheres falling within a radius of (R+30) metre from centre of the sphere on fire at the rate of
10.2Ipm/ m2 of surface area.
Water flow for supplementarystream shall be considered as 372 m3/hr as indicated under item (i).
iv) Water flow rate requirements for fire fighting in other major areas shall be calculated based on criteria in terms of lpm/ m2 given
elsewhere.
In cases where two sets of firewater storage and pumps are provided, the number of pumps at each location shall be according to
hydraulic analysis of piping network
The capacity of jockey pumps shall be 5% minimum and maximum 10% of the design fire waterrate. Its head shall be higher than
themain fire water pumps. Auto cut-in /cut-off facility should be provided for jockey pumps
OISD
FOLLOWING PORTABLE EQUIPMENTS SHALL BE MAINTAINED

• Portable water-cum-foam monitor.


• Minimum 2 no. for Petroleum refinery and 1 no. for Gas Processing Plant
• Water Mist cum Compressed air Foam Technology:
• Minimum of one trolley type should be provided as an alternate to existing DCP system at each critical locations such as hot
pumps handling fluids above auto ignition temperature, like column bottom pumps at CDU, VDU, Coker,FCCU & HCU units
and minimum one back pack at critical high temperature column & exchangers in these units.
• Filling capacity - 35 to 50 litres for trolley mounted & 9 litres for backpack system.
• The exact number of fire tenders shall be higher of the items (a) or (b):
• (a) The quantities firmed up in each case based on two simultaneous major fires taking into Consideration the size, location
of the plant and statutory requirements.
• (b) The quantities indicated below.
• i) 3 nos. of foam tenders out of which two are for fire fighting one for spill/ standby. The foam tender should have foam tank
capacity of 3000/3600 Iitre and the pump capacity of minimum 4000 Ipm at 8.5 kg/cm2.
• a Multipurpose fire fighting skid should be used in lieu of one foam tender/ DCP tender as described
• Minimum 2 nos. of foam tank trailers with field adjustable variable flow water cum foam monitors having foam tank capacity
of 500-1000 liters and monitors capacity of minimum 1000 GPM
• Minimum 2 nos. of Trolley mounted water cum foam monitors of capacity of minimum 2000 GPM with field adjustable
variable flow
• iii) 1 to 2 numbers of Foam Nurser with foam compound tank of 7000 – 16000 litre capacity with suitable pump for foam
transfer.
iv) 1 to 2 nos. of portable/ trailer fire pumps of capacity ranging from 1800 to 2250 Ipm at discharge pressure of 7 kg/cm2 g.
FOAM QUANTITY
REQUIREMENT AS PER OISD
• should be calculated as sum total indicated below under items (i), (ii) and (iii) for a minimum period of 65 minutes.
• Foam solution application at the rate of 5 Ipm/m2 for the liquid surface of the single largest cone roof tank or at the rate of
12 Ipm/m2 of rim seal area of the single largest floating roof tank whichever is higher.
• However, a foam solution application rate of 8.1 Ipm/m2 of the liquid surface of the largest floating roof tank for 65 minutes
shall be considered for a roof sinking case.
• ii) One portable foam monitor of 4500 Ipm foam solution capacity.
• iii) Two hose streams of foam each with a capacity of 1140 Ipm of foam solution.
LOW EXPANSION FOAM: Foam expansion ratio can be up to 50 to 1, but usually between 5:1 to 15:1 as produced by self
aspirating foam branch pipes.
• The low expansion foam contains more water and has better resistant to fire. It is suitable for hydrocarbon liquid fires and is
widely used in oil refinery, oil platforms, petrochemical and other chemical industries.
HIGH EXPANSION FOAM: Foam expansion ratio vary from 501:1 to 1500:1, usually between 750:1 to 1000:1 is typically produced
by foam generators with air fans. This foam is used for protection of hydrocarbon gases stored under cryogenic conditions and for
warehouse protection.
PROTEIN BASE FOAM:
• The concentrate forms a thick foam blanket and is suitable for hydrocarbon liquid fires, but not on water miscible liquids.
FLUORO PROTEIN FOAM:
• . The foam is very effective on deep pools of low flash point fuels which have had lengthy pre burn time but not on water
miscible liquids
AQUEOUS FILM FORMING FOAM (AFFF):
• This can be used with fresh water as well as with sea water.It produces very fluid foam, which flows freely on liquid surface.
The aqueous film produced suppresses the liquid vapour quickly.
MULTIPURPOSE AFFF:

9
• Multipurpose AFFF concentrate is synthetic, foaming liquid designed specially for fire protection of water soluble solvents .
This can be used either with fresh water of sea water.The foam is also suitable for deep pool fires because of superior
drainage rate and more resistive to hot fuels/radiant heat. The 3% induction rate is suitable for liquid hydrocarbon fires and
5% for water miscible solvents.
• The process of adding or injecting thefoam to water is called proportioning.The mixture of water and foamcompound (foam
solution) is then mixed with air in a foam maker for onward transmission to burning surface.
FOAM CONVEYING SYSTEMS
• The system consists of an adequate water supply, supply of foamconcentrate, suitable proportioning equipment, a proper
piping system, foam makers and discharge devices
• There are three types of systems:
• i) Fixed
• ii) Semifixed
• iii) Mobile
Fixed foam conveying systemcomprises of fixed piping for water supply at adequate pressure, foam concentrate tank, eductor,
suitable proportioning equipment for drawing foam concentrate and making foam solution, fixed piping system for onward conveying
to foam makers for making foam, vapour seal box, and foam pourer.
Semifixed Foam System
• Semi-fixed foam system gets supply of foam solution through the mobile foam tender. A fixed piping system connected to
foam makers cum vapour seal box in case of cone roof tanks and foam maker and foam pourers in the case of floating roof
tanks conveys foam to the surface of tank.
Mobile Foam System
• Mobile system includes foam producing unit mounted on wheels which can be self propelled or towed by a vehicle. These
units supply foam through monitors/foam towers to the burning surface.
• Sub-surface foam injection
• This comprises of high back pressure foam generator connected near the bottom of the tank.
• Under the Seal Foam application:
• Foam travels through a flexible pipe inside the tank upto the center of the tank roof and exits at the seal rim of the floating
roof where the fire is located .
Automatic Actuated Foam Flooding system:
All the components and ingredients including premix solution are contained within the system. Such systems usually have a premix
solution supply tank pressurised by air or inert gas. The automatic sensing of fire releases this pressure and places the system into
operation.
Floating roof protection
foam shall be poured at the foam dam to blanket the roof’s rim seal.
Foam makers/foam pourers shall be located not more than 24 M apart on the shell perimeter based on 600 mm foam dam
height. The height of foam dam shall be at least 51 mm above the top of metallic secondary seal.
iv) A minimum of two foam pourers shall be provided.
FIXED ROOF TANK PROTECTION USING FOAM
a vapour seal chamber is required before the foam discharge outlet. to prevent entrance of vapour into the foam conveying
piping system
Tanks should be provided with foam discharge outlets/ vapour seal chambers as indicated below:
• Tank Dia in M. Minimum number of foam outlet
• upto 20 2
• >20 upto 25 3
• >25 upto 30 4
• >30 upto 35 5
• >35 upto 40 6
• >40 upto 45 8
• >45 upto 50 10
• It is based on pourer capacity of 1000 Ipm at a pressure of 7 Kg/cm2 upstream of eductor.
FLOATING CUM FIXED ROOF TANK PROTECTION
Protection facilities shall be provided as required for fixed roof tank.
DURATION OF FOAM DISCHARGE
• Tanks containing liquid
hdrocarbons - Class 'C'
petroleum .... 30 minutes.
• ii) Tanks containing Class 'A' & 'B'
Petroleum or liquids heated
above their flash points --- 65 minutes
• iii) Where the system's primary purpose is
for spill fire protection. --- 30 minutes.

10
DYKE AREA/ SPILLS/ OIL SEPARATOR PROTECTION USING FOAM
Portable monitors/ Medium Expansion foam generator/ foam hose streams shall be considered for fighting fires in dyke area, spills
and oil separator.
Clean Agent system is required for Control rooms & Satellite Rack Room (SRR) and Computer/Server rooms
DETECTION SYSTEM AND
ALARM
A flammable gas detector is designed to give a warning of the presence of flammable gases or vapours in air, well before they reach
explosive concentrations. Normally, the detector provides visible and audible alarm signals, but frequently it performs a further
function by initiating control action such as increasing ventilation or shutting off the source of gas. A flammable gas detector can also
be used for tracing leaks and checking that vessels or tunnels are gas free before entering.
AREAS TO BE COVERED WITH
DETECTORS
• - Light hydrocarbon pumps in process units.
• - Process cooling tower top platform in the units having pressurised cooling water return.
• - Fuel gas knock out drum
• - Suction side of forced draft air blowers if located where hydrocarbon vapours can be present.
• - Light hydrocarbon pump stations if located below grade level.
• - LPG Horton spheres
• - LPG pump house
• - LPG bulk truck loading area
• - LPG bulk wagon loading area
• LPG bottling, storage, repair sheds.
• - Gas compressor
• - Air-intake point for control room,
Following areas shall be provided with Smoke/ Flame / Heat detectors with alarm and/or system to actuate relevant fire
suppression system:
• - LPG spheres
• - LPG filling sheds
• - LPG pumps/compressors
• - LPG loading/unloading, both in tank truck and tank wagon gantry
• Hydrocarbon detectors shall be installed near all potential leak source
• of class-A e.g. tank dykes, tank manifolds, pump house manifold etc.
• following areas should also be provided with suitable detectors:
• - Extremely hazardous area in process units
• - Computer room, Server room,
• Process control rooms, Record room
• - Unmanned electric substations /MCC rooms
• - Cable galleries
• - Chemical Storage.
The fire alarm systems includes manualcall points (break glass), automatic gas/smoke/heat detectors, release &inhibit switches for
fire suppressing clean agent and conventional or microprocessor based data gathering panels viz. central fire alarm panel,
mimicpanels & associated equipments.
Manual Call Points shall be provided atsuitable locations like access point, approach roads, walkways etc. to cover the critical areas.
These manual call points activate the audio-visual alarm in the Central fire alarm panel installed in fire station and in the repeater
panel installed in the respective area control room(s). The location of these points shall be conspicuously marked on the
annunciation panel for proper identification. These manual call points should also have suitably wired telephone handset to facilitate
communication with respective area control room and fire station.