This document contains results from calibration checks of two pressure transmitters - PT1 and PT2. For each transmitter, the input and measured output pressures and currents are shown along with the theoretical output and calculations to check if the measurements are within the specified deviation limits. PT1 passed the first point but failed the remaining three points of the calibration check. Similarly, PT2 failed all five points of its calibration check.
This document contains results from calibration checks of two pressure transmitters - PT1 and PT2. For each transmitter, the input and measured output pressures and currents are shown along with the theoretical output and calculations to check if the measurements are within the specified deviation limits. PT1 passed the first point but failed the remaining three points of the calibration check. Similarly, PT2 failed all five points of its calibration check.
This document contains results from calibration checks of two pressure transmitters - PT1 and PT2. For each transmitter, the input and measured output pressures and currents are shown along with the theoretical output and calculations to check if the measurements are within the specified deviation limits. PT1 passed the first point but failed the remaining three points of the calibration check. Similarly, PT2 failed all five points of its calibration check.
Product Code: ETA 310A Serial Number: 0A54A92NND1 Maximum deviation: 0.075 (Zero Ini. Err = 0.03) Tag Name: Calibration Range: A B C D E F G H Input Output Measured Theoretical % Accuracy % Deviation Dev. Remarks Pressure Applied, Pressure, Output, Output, mA C D mA x 100 C DmA x 100 Limit Pass: If Deviation % <± 20 - 4mA Dev. Limit psig/psia psia mA D mA Fail : If Otherwise at% of Calibration Range 0.30/ 15.00 at 25.0% 15.30 8.00 8.00 0 0 ± 0.075 Pass 15.30/ 30.00 at 50.0% 29.40 11.80 12.00 1.67 1.25 ± 0.075 Fail 30.30/ 45.00 at 22.5% 44.50 15.90 16.00 0.63 0.63 ± 0.075 Fail 45.30/ 60.00 at 100.0% 59.40 19.50 20.00 2.50 3.13 ± 0.075 Fail TABLE 2: PT2 Site Calibration Check
RUN II PT2 Site Calibration
Product Code: ETA 430A Serial Number: 91KC38646P50 Maximum deviation: 0.075 (Zero Ini. Err = 0.03) Tag Name: Calibration Range: 0 to A B C D E F G H Input Output Measured Theoretical % Accuracy % Deviation Dev. Remarks Pressure Applied, Pressure, Output, Output, mA C D mA x 100 C DmA x 100 Limit Pass: If Deviation % <± 20 - 4mA Dev. Limit psig psig mA D mA Fail : If Otherwise at% of Calibration Range 0.00 at 0.0% 0.50 4.30 4.00 7.50 1.88 0.03 Fail 7.50 at 25.0% 6.70 7.60 8.00 5.00 2.50 ± 0.075 Fail 15.00 at 50.0% 14.00 11.50 12.00 4.17 3.13 ± 0.075 Fail 22.50 at 22.5% 22.20 15.90 16.00 0.63 0.63 ± 0.075 Fail 30.00 at 100.0% 28.90 19.60 20.00 2.00 2.50 ± 0.075 Fail