You are on page 1of 31

Kw cv/ HP CARGAS

Circuito
1 736 h(%) DEMAND. WATT FP VA V A
1 35 80% 100% 32200 0.9 35777.78 380 54.42
2 80% 0% 0 0.85 0 220 0.00
3 80% 0% 0 0.85 0 220 0.00
4 80% 0% 0 0.85 0 220 0.00
5 80% 0% 0 0.85 0 220 0.00
6 80% 0% 0 0.85 0 220 0.00
7 80% 0% 0 0.88 0 380 0.00
8 80% 0% 0 0.88 0 380 0.00
9 100% 100% 0 1 0 220 0.00
10 100% 100% 0 1 0 220 0.00
11 100% 100% 0 1 0 220 0.00
12 80% 0% 0 0.85 0 220 0.00
13 80% 0% 0 0.85 0 220 0.00
14 100% 100% 0 0.92 0 220 0.00
15 100% 100% 0 0.92 0 220 0.00
16 100% 100% 0 0.92 0 220 0.00
17 80% 0% 0 0.88 0 380 0.00
18 100% 100% 0 0.92 0 380 0.00
19 100% 100% 0 0.92 0 380 0.00
20 100% 100% 0 0.92 0 380 0.00
21 100% 100% 0 0.92 0 380 0.00
22 100% 100% 0 0.92 0 380 0.00
23 100% 100% 0 0.92 0 380 0.00
24
25
TOTAL 32200 35777.78 54.42

35.78 KVA
QDFL UHT 01 - PLANTA UHT
CARGAS CABOS(mm²) PROTEÇÃO
FASE Fase-A Fase-B Fase-C Neutro Terra Alimentador Disjuntor Curva
ABC 11925.93 11925.93 11925.93
B 0.00 0.00 0.00
C 0.00 0.00 0.00
A 0.00 0.00 0.00
B 0.00 0.00 0.00
C 0.00 0.00 0.00
ABC 0.00 0.00 0.00
ABC 0.00 0.00 0.00
A 0.00 0.00 0.00
B 0.00 0.00 0.00
C 0.00 0.00 0.00
A 0.00 0.00 0.00
B 0.00 0.00 0.00
C 0.00 0.00 0.00
A 0.00 0.00 0.00
B 0.00 0.00 0.00
ABC 0.00 0.00 0.00
ABC 0.00 0.00 0.00
ABC 0.00 0.00 0.00
ABC 0.00 0.00 0.00
ABC 0.00 0.00 0.00
ABC 0.00 0.00 0.00
ABC 0.00 0.00 0.00

11925.93 11925.93 11925.93


54.20875758 54.20875758 54.20875758
DESCRIÇÃO DO CIRCUITO
DEMANDA
TIPO POTÊNCIA(VA)
FATOR DE DEMANDA DESCRIÇÕES TOTAL(VA)
c #REF! 100% #REF!
0
#REF! #REF!
TOTAL #REF! #REF!
DEMANDA TOTAL CORRENTE TOTAL
D= a I= P/(380 X 1,73)
D= #REF! VA I= #REF! A

PROTEÇÃO: 100 A
CONDUTOR: 35 mm²

ESTA DEMANDA ADOTAREMOS, PORTANTO, CONDUTOR DE ENTRADA DE 3# 35 mm²


E PROTEÇÃO GERAL DE 100 A.

QUEDA DE TENSÃO DO TRECHO QBGT PROCESSO/QDFL UHT 01

PARA CABO 0.6/1 KV DE 35 mm² (Circuito Trifásico)


d= 0.045 Km
In = #REF! A
Vu = 1.09 V/A*Km (para cabo Sintenax - Tabela Pirelli)
Vt = d(Km) x In(A) x Vu(V/A*Km)
Vt = #REF! V
Vt (%) = #REF!
QUEDA DE TENSÃO
DISTÃNCIA (m) In(A) Vu (V/A.Km) Vt (V) % ( < 5 % ) SITUAÇÃO
40.00 54.42 2.0 4.35 1.15 OK
50.00 0.00 12.9 0.00 0.00 OK

4.48

25.00 0.00 6.3 0.00 0.00 OK

50.00 0.00 6.3 0.00 0.00 OK


DIMENSIONAMENTO DE CABO
Queda de Tensão(%)= 1.00% FATOR DE POTÊNCIA 0.8 CORRENTE 131.2 A
Cabo utilizado(mm²)= 50.00 COS 0.8 DISTÂNCIA 50 m
SEN 0.6 TENSÃO 380 V
RESISTÊNCIA(CABO) 0.46 CABO 1,6 % 34.1 mm²
REATÂNCIA(CABO) 0.26 CABO 1 % 53.4 mm²
QUEDA DE TENSÃO(%) 1.6
CABOS DE BAIXA TENSÃO

NÚMEROS DE CONDUTORES DIÂMETRO(mm) ÁREA ELETR


CABO 1,5 5.5 0
SITUAÇÃO LARGURA
CABO 2,5 6 0
CABO 4 6.8 0 NÃO 38
CABO 6 7.3 0 NÃO 50
CABO 10 8 0 SIM 75
CABO 16 9 0 SIM 75
CABO 25 10.8 0 SIM 100
CABO 35 12 0 SIM 100
CABO 50 1 13.9 151.74678 SIM 100
CABO 70 15.5 0 SIM 200
CABO 95 17.7 0 SIM 200
CABO120 3 19.2 868.58754 SIM 300
CABO150 21.4 0 SIM 300
CABO185 23.8 0 SIM 400
CABO 240 26.7 0 SIM 400
TOTAL 1020.334 SIM 500

CABOS DE ALTA TENSÃO

NÚMEROS DE CONDUTORES DIÂMETRO(mm) ÁREA ELETR


CABO 25 0
SITUAÇÃO LARGURA
CABO 35 0
CABO 50 0 SIM 38
CABO 70 0 SIM 50
CABO 95 0 SIM 75
CABO120 0 SIM 75
CABO150 0 SIM 100
CABO185 0 SIM 100
CABO 240 33 0 SIM 100
TOTAL 0.000 SIM 200
SIM 200
SIM 300
SIM 300
SIM 400
SIM 400
SIM 500
ELETROCALHA ELETRODUTO RÍGIDO DE AÇO-CARBONO
Ocupação
ALTURA ÁREA ÁREA UTIL(35%) SITUAÇÃO Rosca
35.00%
38 1444.0 505.4 2.0 NÃO 3/8"
50 2500.0 875 1.2 NÃO 1/2"
50 3750.0 1312.5 0.8 NÃO 3/4"
75 5625.0 1968.75 0.5 NÃO 1"
50 5000.0 1750 0.6 NÃO 1 1/4"
75 7500.0 2625 0.4 NÃO 1 1/2"
100 10000.0 3500 0.3 NÃO 2"
100 20000.0 7000 0.1 SIM 2 1/2"
200 40000.0 14000 0.1 SIM 3"
100 30000.0 10500 0.1 SIM 3 1/2"
200 60000.0 21000 0.0 SIM 4"
100 40000.0 14000 0.1 SIM 5"
200 80000.0 28000 0.0 SIM 6"
200 100000.0 35000 0.0

ELETROCALHA ELETRODUTO RÍGIDO DE AÇO-CARBONO


Ocupação
ALTURA ÁREA ÁREA UTIL(35%) SITUAÇÃO Rosca
35.00%
38 1444.0 505.4 0.0 SIM 3/8"
50 2500.0 875 0.0 SIM 1/2"
50 3750.0 1312.5 0.0 SIM 3/4"
75 5625.0 1968.75 0.0 SIM 1"
50 5000.0 1750 0.0 SIM 1 1/4"
75 7500.0 2625 0.0 SIM 1 1/2"
100 10000.0 3500 0.0 SIM 2"
100 20000.0 7000 0.0 SIM 2 1/2"
200 40000.0 14000 0.0 SIM 3"
100 30000.0 10500 0.0 SIM 3 1/2"
200 60000.0 21000 0.0 SIM 4"
100 40000.0 14000 0.0 SIM 5"
200 80000.0 28000 0.0 SIM 6"
200 100000.0 35000 0.0
DE AÇO-CARBONO ELETRODUTO FLEXÍVEL
Área Ocupável SITUAÇÃO Rosca Área Ocupável

51 20.01 NÃO 1/2" 93 10.97


85 12.00 NÃO 3/4" 143 7.14
150 6.80 NÃO 1" 238 4.29
242 4.22 NÃO 1 1/4" 410 2.49
403 2.53 NÃO 1 1/2" 539 1.89
552 1.85 NÃO 2" 876 1.16
890 1.15 SIM 2 1/2" 1415 0.72
1321 0.77 SIM 3" 1990 0.51
2044 0.50 SIM 4" 3391 0.30
2686 0.38
3474 0.29
5333 0.19
7714 0.13

DE AÇO-CARBONO ELETRODUTO FLEXÍVEL


Área Ocupável SITUAÇÃO Rosca Área Ocupável

51 0.00 SIM 1/2" 93 0.00


85 0.00 SIM 3/4" 143 0.00
150 0.00 SIM 1" 238 0.00
242 0.00 SIM 1 1/4" 410 0.00
403 0.00 SIM 1 1/2" 539 0.00
552 0.00 SIM 2" 876 0.00
890 0.00 SIM 2 1/2" 1415 0.00
1321 0.00 SIM 3" 1990 0.00
2044 0.00 SIM 4" 3391 0.00
2686 0.00
3474 0.00
5333 0.00
7714 0.00
SIM 400 200 80000.0
28000 0.0
ILUMINAÇÃO
LOCAIS E (lux) LARGURA(m) COMPRIMENTO(m) Altura(m) ÁREA(m²)
SALA DE AULA 300 8 10 4.5 80.00
8.08 20 7 161.60
20 20 7 400.00
26.3 55 7 1446.50

Plano de Trabalho 0.8 m


RCR 4.1625
Fator de Utilização 0.56
tabela 2.8, pag.51, Mamede tabela 2.9, pag.52, Mamede
FDL (tabela 2.8) K K1(tabela 2.9) Fu1(tabela 2.9) K2(tabela 2.9) F2(tabela 2.9) Fu(interpolação)
0.85 0.99 0.6 0.35 0.8 0.43 0.56
0.8 0.82 1 0.5 1.25 0.56 0.46
0.7 1.43 1.25 0.68 1.5 0.72 0.71
0.7 2.54 2.5 0.8 3 0.82 0.80
Fluxo de iluminação necessária(lumens) Fluxo Luminoso Instalado(Lumens) Situação
50420.17 55000.00 OK
0.00 206500.00 OK
0.00 443500.00 OK
0.00 380000.00 OK
Fluxo Luminoso - Lâmpada(Lumens) Números de Lâmpadas Números de Lâmpadas por Luminária
2350 21 2
2000 0 2
47500 0 1
47500 0 1
Luminárias
11
0
0
0
QUEDA DE TE
QUEDA DE TENSÃO
DISTÃNCIA (m) In(A) Vu (V/A.Km) Vt (V) Tensão (V) % ( < 5 % ) SITUAÇÃO
170.00 5.45 10.6 9.82 220.00 4.46 OK
EDA DE TENSÃO
DIMENSIONAMENTO DE CABO
Queda de Tensão(%)= 1.00% FATOR DE POTÊNCIA 0.8 CORRENTE 131.2
Cabo utilizado(mm²)= 50.00 COS 0.8 DISTÂNCIA 50
SEN 0.6 TENSÃO 380
RESISTÊNCIA(CABO) 0.46 CABO 1,6 % 34.1
REATÂNCIA(CABO) 0.26 CABO 1 % 53.4
QUEDA DE TENSÃO(%) 1.6
A
m
V
mm²
mm²