ROUTINE TEST CERTIFICATE

OUTDOOR OIL COOLED CURRENT TRANSFORMER


CUSTOMER
SERIAL No.
H.SV 36 KV R.I.L. : 36/70/170 KV
FREQUENCY 50 Hz S.T.R. : 25 KA / 3SEC.
RATIO 600-300-150 / 1 -1 A REF.STANDARD : IS 2705 / 1992
CORE – I : PROTECTION 30 VA, 5P15 @ 600A CORE – II - METERING - 5 VA, 0.2S @ 600A
1. Verification of Terminal Markings & Polarity Checked OK
2. High Voltage Power Frequency Test :
a) A HV of 70 KV is applied on Primary for 1 Minute WithStood
with Secondary’s Earthed
b) A HV of 3 KV is applied for 1 Minute on Secondary’s
WithStood
with Primary Earthed
3. I.R Value
a) Between Primary and Earth Above 5000 MΩ
b) Between Secondary and Earth Above 200 MΩ
c) Between Primary and Secondary Above 5000 MΩ
4. Over Voltage Interturn Test WithStood
5. RATIO ERROR AND PHASE DISPLACEMENT TEST:
CORE -I / PROTECTION / 5P 15 / 600-300-150/1-1A
ADOPTED RATIO 600/1A (1S1-1S4) BURDEN - 30 VA
600 A @ 0.8 P.F, 30 VA

ERROR Ratio Error Phase Disp VsecL Iexc SECONDARY RESISTANCE COMPOSITE ERROR
(Volts) (Amps) (Ω)

(%) (minutes)
Limit ±1.0 ±60 Ambient 5%
Actual At 75 ͦC
ADOPTED RATIO 300/1A (1S1-1S3) BURDEN - 15 VA
300 A @ 0.8 P.F, 15 VA
ERROR VsecL Iexc SECONDARY RESISTANCE COMPOSITE ERROR
Ratio Error Phase Disp (Volts) (Amps) (Ω)

(%) (minutes)
Limit ±1.0 ±60 Ambient 5%
Actual At 75 ͦC
ADOPTED RATIO 150/1A (1S1-1S2) BURDEN - 7.5 VA
150A @ 0.8 P.F, 7.5 VA
VsecL Iexc SECONDARY RESISTANCE
ERROR (Volts) (Amps) (Ω) COMPOSITE ERROR
Ratio Error Phase Disp
(%) (minutes)
Limit ±1.0 ±60 Ambient 5%
Actual At 75 ͦC

CONTINUED
CORE -II / METERING / 0.2S / 600-300-150/1-1A
ADOPTED RATIO 600/1A (2S1-2S4) BURDEN - 5 VA
100% BURDEN, 0.8 P.F @ ADOPTED RATIO
120% 100% 20% 5% 1%
ERROR Ratio Error Phase Disp. Ratio Error Phase Disp. Ratio Error Phase Disp. Ratio Error Phase Disp. Ratio Error Phase Disp.
(%) (Min) (%) (Min) (%) (Min) (%) (Min) (%) (Min)
Limit ±0.2 ±10 ±0.2 ±10 ±0.2 ±10 ±0.35 ±15 ±0.75 ±30
Actual
25% BURDEN, UNITY P.F @ ADOPTED RATIO
120% 100% 20% 5% 1%
ERROR Ratio Error Phase Disp. Ratio Error Phase Disp. Ratio Error Phase Disp. Ratio Error Phase Disp. Ratio Error Phase Disp.
(%) (Min) (%) (Min) (%) (Min) (%) (Min) (%) (Min)
Limit ±0.2 ±10 ±0.2 ±10 ±0.2 ±10 ±0.35 ±15 ±0.75 ±30
Actual

ADOPTED RATIO 300/1A (2S1-2S3) BURDEN - 2.5 VA


100% BURDEN, 0.8 P.F @ ADOPTED RATIO
120% 100% 20% 5% 1%
ERROR Ratio Error Phase Disp. Ratio Error Phase Disp. Ratio Error Phase Disp. Ratio Error Phase Disp. Ratio Error Phase Disp.
(%) (Min) (%) (Min) (%) (Min) (%) (Min) (%) (Min)
Limit ±0.2 ±10 ±0.2 ±10 ±0.2 ±10 ±0.35 ±15 ±0.75 ±30
Actual
25% BURDEN, UNITY P.F @ ADOPTED RATIO
120% 100% 20% 5% 1%
ERROR Ratio Error Phase Disp. Ratio Error Phase Disp. Ratio Error Phase Disp. Ratio Error Phase Disp. Ratio Error Phase Disp.
(%) (Min) (%) (Min) (%) (Min) (%) (Min) (%) (Min)
Limit ±0.2 ±10 ±0.2 ±10 ±0.2 ±10 ±0.35 ±15 ±0.75 ±30
Actual

ADOPTED RATIO 150/1A (2S1-2S2) BURDEN - 1.25 VA


100% BURDEN, 0.8 P.F @ ADOPTED RATIO
120% 100% 20% 5% 1%
ERROR Ratio Error Phase Disp. Ratio Error Phase Disp. Ratio Error Phase Disp. Ratio Error Phase Disp. Ratio Error Phase Disp.
(%) (Min) (%) (Min) (%) (Min) (%) (Min) (%) (Min)
Limit ±0.2 ±10 ±0.2 ±10 ±0.2 ±10 ±0.35 ±15 ±0.75 ±30
Actual
25% BURDEN, UNITY P.F @ ADOPTED RATIO
120% 100% 20% 5% 1%
ERROR Ratio Error Phase Disp. Ratio Error Phase Disp. Ratio Error Phase Disp. Ratio Error Phase Disp. Ratio Error Phase Disp.
(%) (Min) (%) (Min) (%) (Min) (%) (Min) (%) (Min)
Limit ±0.2 ±10 ±0.2 ±10 ±0.2 ±10 ±0.35 ±15 ±0.75 ±30
Actual

Tested by

ENERGY TEC