Professional Documents
Culture Documents
PART 1 GENERAL
1. Building Wire.
2. Power Cable.
3. Control Cable.
4. Instrumentation Cable.
5. Wire Connectors.
6. Insulating Tape.
7. Pulling’s Lubricants
2. WC 70/S-95-658, Non-Shielded Power Cables Rated 2000 Volts or Less for the
Distribution of Electrical Energy.
2. 262, Standard Method of Test for Flame Travel and Smoke of Wires and Cables for
Use in Air-Handling Spaces.
4. 486A, Standard for Safety Wire Connectors and Soldering Lugs for use with Copper
Conductors.
6. 510, Standard for Safety Polyvinyl Chloride, Polyethylene and Rubber Insulating Tape.
7. 1277, Standard for Safety Electrical Power and Control Tray Cables with Optional
Optical-Fiber Members.
1.4 SUBMITTALS
A. Submittals shall be in accordance with the Contract Documents and with applicable
requirements of Specification Section 01 00 00 - General Requirements in addition to those
listed below.
B. Product Data: Manufacturer's data sheets and detail drawings for each product to be used,
including:
3. Product literature.
4. Installation methods.
A. All work performed and all materials used shall be in accordance with the National Electrical
Code, and with applicable local regulations and ordinances. Equipment assemblies,
materials, and equipment shall be listed and labeled by Underwriter’s Laboratories or by a
testing agency acceptable to authorities having jurisdiction and marked for intended use.
B. Product Requirements:
1. Source Limitations: Obtain cable tray components through one source from a single
manufacturer.
a. The Terms "Classified" pertaining to cable trays (rather than "Listed") and
"Labeled": As defined in NFPA 70, Article 100.
3. Comply with NFPA 70, National Electrical Code, Article 392: Cable Trays; provide UL
Classification and labels.
4. Comply with IEC 61537, Cable Tray Systems and Cable Ladder Systems for Cable
Management.
5. Comply with NEMA VE 1/CSA C22.2 No. 126.1, Metal Cable Tray Systems, for
materials, sizes, and configurations; provide cCSAus Certificate and labels.
8. Structural Performance: Cable trays shall be tested and rated for load carrying
capacity and safety factors.
A. Avoid breakage, denting and scoring finishes. Damaged products shall not be installed.
Store cable and accessories in original cartons and in clean dry space; protect from weather
and construction traffic. Wet materials will be unpacked and dried before storage.
PART 2 PRODUCTS
1.8 MANUFACTURERS
A. Subject to compliance with the Contract Documents, the following manufacturers are
acceptable:
a. Southwire Company.
c. Okonite Company.
d. General Cable.
f. Alphawire.
2. Instrumentation cable.
a. Belden Inc.
b. General Cable.
c. Alphawire.
3. Wire Connectors.
a. Burndy Corporation.
b. Buchanan.
c. Ideal.
d. Ilsco.
e. 3M Co.
h. Phoenix Contact.
a. 3M Co.
PART 2
A. Building Wire:
2. Conductors shall be stranded, except for conductors used in lighting and receptacle
circuits which may be stranded or solid.
2. Surface mark with manufacturer's name or trademark, conductor size, insulation type
and UL label.
2) #14 AWG – Used for PT’s and all other wiring, SIS grey wire
b. Field Wiring after Control Boards Terminal Blocks and before Field Equipment
2) #12 AWG or 19/25 – Used for PT’s and other control and indication
functions
c. Standard BWP control cables come in 2c, 3c, 4c, and 6c.
C. Control Cable:
2. Surface mark with manufacturer's name or trademark, conductor size, insulation type
and UL label.
6. Conform to NFPA 70 Type TC and IEEE 1202, CSA FT-4 or NFPA 262.
2) #14 AWG – Used for PT’s and all other wiring, SIS grey wire
b. Field Wiring after Control Boards Terminal Blocks and before Field Equipment
2) #12 AWG or 19/25 – Used for PT’s and other control and indication
functions
c. Standard BWP control cables come in 2c, 3c, 4c, and 6c.
3. Surface mark with manufacturer's name or trademark, conductor size, insulation type
and UL label.
E. Instrumentation Cable:
1. Surface mark with manufacturer's name or trademark, conductor size, insulation type
and UL label.
2. Analog cable:
c. Twisted with 100 percent foil shield coverage with drain wire.
f. Conform to IEEE 1202 or CSA FT-4 or NFPA 262, UL 2250, UL 1581 and NFPA
70 Type ITC.
3. Digital cable:
c. Conform to IEEE 1202 or CSA FT-4 or NFPA 262 and NFPA 70 Type ITC.
1. Twist/screw on type:
a. Twist/screw type shall not be used on power control cables, control cables,
electric equipment control wire, and instrumentation cable.
d. 600 V rated.
a. 600 V rated.
2. Premium grade.
6. Color:
PART 3 EXECUTION
2.2 EXAMINATION
A. Examine substrates for compliance with requirements for installation tolerances and other
conditions affecting performance of cable. Do not proceed with installation until
unsatisfactory conditions have been corrected.
2.3 PREPARATION
B. Prepare surfaces using the methods recommended by the manufacturer for achieving the
best result for the substrate under the project conditions.
D. Minimum Wire Size: #12 awg for power and lighting circuits, #14 awg for control circuits. In
the case of “homeruns” over 125 feet in length, no conductor smaller than a No. 10 wire shall
be used. The tap conductor from the J-box in the ceiling to the receptacle may be No. 12.
Each 120-volt phase conductor shall have a neutral conductor of the same size. The sizing
of all wire except remote control wire shall be accomplished in the case of both feeder and
branch circuits by conforming to the following provisions. Only lighting circuits may share
grounding conductors. All lighting circuits with shared grounding conductors shall be #10
AWG minimum.
A. Service Entrance: Type XHHW, or type THHN/THWN up to and including 600 kcmil, single
conductors in conduit.
B. Exposed Feeders: Type THHN/THWN for all sizes up to and including 600 kcmil, single
conductors in conduit.
C. Feeders Concealed in Ceilings, Walls, Partitions, and Crawlspaces: Type XHHW for #2 awg
and larger, or type THHN/THWN for all sizes up to and including 600 kcmil, single
conductors in conduit.
D. Feeders Concealed in Concrete, below Slabs-on-Grade, and underground: Type XHHW for
#2 awg and larger, single conductors in conduit.
F. Branch Circuits Concealed in Ceilings, Walls, and Partitions: Type XHHW, single conductors
in conduit.
H. Cord Drops and Portable Appliance Connections: Type SO, hard service cord with
I. Recessed or Semi-recessed Lighting Fixture Whips: Type THHN-THWN (90 deg C), single
conductors in FMC in lengths not to exceed six (6) feet.
A. Splices in feeder circuits shall be avoided unless necessitated by the length of the run more
than 500 feet. Locations of all splices shall be approved by the University’s Chief Electrician
and made in Code sized splice box with the word “SPLICE” permanently labeled on cover.
B. Conductors may be run parallel from sizes 250 kcmil up to and including 600 kcmil provided
all paralleled conductors are of the same size, manufacturer, length and type of insulation
E. Use pulling means; including fish tape, cable, rope, and basket-weave wire/cable grips that
will not damage cables or conduit.
2.7 CONNECTIONS
B. Make splices and taps that are compatible with conductor material and that possess
equivalent or better mechanical strength and insulation ratings than unspliced conductors.
C. Wiring at Outlets: Install conductor at each outlet or junction box with at least 6 inches (150
mm) of slack.
2.8 FIRESTOPPING
1. After installing conductors and cables and before electrical circuitry has been
energized, test service entrance and feeder conductors, and conductors feeding the
following critical equipment and services for compliance with requirements.
2. Perform each visual and mechanical inspection and electrical test stated in NETA
Acceptance Testing Specification. Certify compliance with test parameters.
3. Test results that do not comply with requirements and corrective action taken to
achieve compliance with requirements.
D. Remove and replace non-compliant cables or wires and retest as specified above.
END OF SECTION