Professional Documents
Culture Documents
Ejemplo PDF
Ejemplo PDF
Other Dimensions
Inside centerline longitudinal dimension of finished branch opening = [ D ob - 2 (T b - A ) ] / sin α d1 = 4.402 in.
Half width of reinf. zone = d 1 or (T b - A )+(T h -A ) + d 1 / 2, whichever is greater, but not more than D oh d2 = 4.402 in.
Reinf. zone height outside of run pipe, for ring or saddle = 2.5 (T h - A ) or 2.5 (T b - A ) + t nr , whichever is less Lr = 0.234 in.
Reinf. zone height outside of run pipe, for integrally reinforced fitting = 2.5 (T h - A ) Li = 0.000 in.
Reinf. zone height outside of run pipe = L r + L i L4 = 0.234 in.
Outside dimension of reinforcing ring or saddle (along run) = 2 w r + [ (D ob ) ( 2 - sin α ) ] Dr = 6.250 in.
Minimum throat of fillet weld at saddle-to-branch = (smaller of t nb or t nr ) ---[weld reference para. 127.4.8(B)] t min = 0.000 in.
Min. throat of weld at branch periphery (except saddle or integrally reinf.) = smaller of 6.0 mm (1/4") or 0.7 t nb tc = 0.166 in.
Minimum leg of weld at branch periphery (except saddle or integrally reinf.) = t c / 0.707 W 1(min) = 0.235 in.
Leg height of weld at branch periphery (except saddle or integrally reinf.) = greater of W 1(min) or W 1s W1 = 0.235 in.
Minimum leg of weld at outer edge of ring, pad, or saddle = 0.5 t nr / 0.707 W 2(min) = 0.228 in.
Leg height of weld at outer edge of ring, pad, or saddle = greater of W 2(min) , or W 2s , but W2 = 0.228 in.
not more than smaller of t nr or L 4 (must fit within the reinf. zone)
Minimum leg height of fillet weld at saddle-to-branch periphery = 0.7t min /0.707 W 3(min) = 0.000 in.
Leg height of fillet weld at saddle-to-branch periphery = greater of W 3(min) or W 3s W3 = 0.000 in.
Maximum width of ring, pad, or saddle which would apply = d 2 - (D ob / 2 ) / sin α WR max = 2.152 in.
Reinforcement height (except weld) = lesser of ( t nr or L 4 ) , or lesser of ( t r i or L 4 ), as applicable Rh = 0.234 in.
Reinforcement width (except weld) = (lesser of w r or WR max ), or (lesser of w r i or t ri ) tan 30, as applicable Rw = 0.875 in.
Count of Welds Within Reinforcement Zone
Factor for complete fillet welds, other than on ring, pad, or saddle edge, which will fit within the reinf. zone height N wh = 0
Factor for complete fillet welds on ring, pad, or saddle edge which will fit within reinforcement zone width N ww = 2
Strength Correction Factors
Factor for strength correction of branch area = 1 if SE b > SE h , or = (SE b / SE h ) if SE b <= SE h Fb = 1.000
Strength correction factor for reinforcing material = 1 if SE r > SE h , or = (SE r / SE h ) if SE r <= SE h Fr = 1.000
Strength correction factor for welds, F w = lesser of F b or F r Fw = 1.000
Areas
Pressure design area expected at end of service life = (t mhr - A ) d 1 A6 = 0.412 in.^2
Required reinforcement area = A 6 (2 - sin α ) A7 = 0.412 in.^2
Area of excess thickness in run pipe wall = (2 d 2 - d 1 ) (T h - t mhr ) A1 = 0.000 in.^2
Area of excess thickness in branch pipe wall = 2 L 4 (T b - t mb ) / sin α A2 = 0.000 in.^2
2 2 2
Total area of welds within zone = (N wh / 2)(W 1 )+(N wh / 2)(W 3 )+(N ww / 2)(W 2 ) A3 = 0.052 in.^2
Area of added reinforcement metal, except welds, within the reinforcement zone = 2 x R h x R w A4 = 0.409 in.^2
Area provided in B31.1 integrally reinforced fitting [See Fig. 104.3.1(D), Example B], = R h x R w A 4i = 0.000 in.^2
Total contributing area (with strength correction for added metal within the reinf. zone) Ac = 0.461 in.^2
A c = A 1 + (A 2 )(F b ) + (A 3 )(F w ) + (A 4 + A 4i )(F r )
Percent of area replaced = A c / A 7 % This branch has sufficient reinforcement. % Area 112%