W8x18?

hanger plates to be
centered on existing
beam

URBANTECH CONSULTING ENGINEERING, PC


11 Broadway, Suite 410
New York, NY 10004
ACTION
Review is for general compliance
Submission is in general conformance
with contract documents. Sole
with design concept.
responsibility for correctness of
dimensions, details, quantities, Submission is in general conformance
and safety during fabrication and with design concept except as noted.
erection shall remain with the Submit record copy.
Contractor. Comments as noted. Revise and
X
resubmit.
Submission is rejected for non-
conformance with design concept.

By: TH Date: 09/13/2019

provide plan at all


other floors

ADDITIONAL COMMENTS SEE


DRAWING E-002
THIS PLATE TO BE
CENTERED AT
BEAM WEB (TYP.)

PROVIDE
CONNECTION
what is this BETWEEN
how to support connection between STRINGER AND URBANTECH CONSULTING ENGINEERING, PC
landing concrete? stair stringer and STEEL BEAM 11 Broadway, Suite 410
New York, NY 10004
need metal deck? landing beam? ACTION
Review is for general compliance
Submission is in general conformance
URBANTECH COMMENTS: with contract documents. Sole
with design concept.
responsibility for correctness of
1. ALL DIMENSIONS TO BE SHOWN AND dimensions, details, quantities, Submission is in general conformance
with design concept except as noted.
FIELD VERIFIED AND COORDINATED. and safety during fabrication and
Submit record copy.
erection shall remain with the
how to connect ARCHITECT TO APPROVE DIMENSIONS Contractor. Comments as noted. Revise and
stringer to landing X
is this metal deck? BEFORE CONSTRUCTION AND resubmit.
beam? TYPICAL Submission is rejected for non-
FABRICATION. conformance with design concept.
COMMENT 2. NO CONNECTION DETAILS BETWEEN By: TH Date: 09/13/2019
STAIR STRINGER AND W8x18 BEAMS IS
SHOWN. PROVIDE THESE DETAILS.
3. NOT CLEAR HOW LANDING IS
SUPPORTED AT EACH FLOOR. PROVIDE
METAL DECK AND DETAILS.
4. HANGER PLATES SHALL BE CENTERED
ON STEEL BEAM WEB.