Mutuality
Single focus
– commercial property
FM Global
FM Global-Engineering
~1,800 engineers
148 countries
Loss Prevention Solutions
- Consistent
- Practical and cost effective
- Scientific proven
FM Global
– Ignition source
– Catastrophic failure of controlled equipment
– Business Interruption
FM Global
F
R
Environment E
Q
Operating U
conditions E
N
Age/history C
Maintenance Y
Operator training
Very
Low Severe
SEVERITY
Operator training, contingency plan, safety device
FM Global
Safety Device
FM Global
– Instrument
– Relay
– Control wire
– Trip coil
– Battery
– Etc.
FM Global
Quarterly Check the specific gravity Check the pilot cell Check the internal
for lead-antimony electrolyte ohmic values and
batteries*, and the temperature negative terminal
temperature of 10% of the temperature of 10% of
cells… the cells…
Annually Check the specific gravity check all inter-cell Check the inter-cell
of all the cells for lead- resistances … resistance and the
antinomy batteries as well amount of AC ripple in
as all inter-cell the charger waveform,
resistances … charger alarm
accuracy…
FM Global
Sources:
DS 5-19: Switchgear and Circuit Breakers
DS 5-20: Electrical Testing
FM Global
Case Study #1
Site Information
12 kV
480 V
FM Global
Case Study #1
Damage Investigation
Case Study #1
Damage investigation
Case Study #1
Conclusion
Case Study #2
Site Information
Case Study #2
Site Electrical system:
– Utility power: 69 kV
– 480V feeder
Case Study #2
Electrical PM
– Annual IR scan
– Annual transformer oil sample – screen & DGA
– 3 year switchgear PM
FM Global
Case Study #2
The incident
Case Study #2
Damage investigation
Case Study #2
Damage investigation
─ GFP
• Unknown setting of GFP
• No electrical study to identify setting
• No recorded testing/maintenance
Case Study #2
Conclusion
Questions