You are on page 1of 3

S5-60D,S5-120D REACTIVE POWER REGULATOR S5 SERIES

FEATURES
S5-60D for 6 steps requlator, S5-120D for 12 steps requlator.
Digital indication of power factor and specified installation data.
Automatic self adjustment for C/K value and operation frequency
50 or 60 Hz.
Three mode of operational sequence.
Switch for setting of individual parameters including target power
factor, switching time, step limit, etc.
Outside dimension according to DIN standard 144 144 mm

SPECIFICATION
Operation voltage range AC 220V 15%, & AC 380V 15%
Voltage burden 6 VA(S5-60D), 7.5 VA(S5-120D)
Input current range AC 0.05 ~ 5A, max. 6A
Current burden 0.5 VA
Power factor display Digital display, red LED, 14.2mm high, 0.01PF resolution
Power factor setting range CAP. 0.90 ~ IND. 0.90, PF. 0.98 be set on delivery from factory
C/K setting range Automatic self adjustment for C/K value
Operation time delay 10 ~ 240 sec. delay time 30 sec. be set on delivery from factory
Operation step setting 3 ~ 6 steps for S5-60D, 3 ~ 12 steps for S5-120D
Operation temperature range 0 ~ 60
Storage temperature range -10 ~ 70
Dielectric Strength AC 2KV, 60Hz, 1 minute, INPUT / OUTPUT/ GROUND
Withstandding impulse voltage According to IEC 1000-4-5
Electrical transient burst According to IEC 1000-4-4
Connection Plug-in terminal block
Weight About 1 Kg

TAIK Electric Co., Ltd. www.taik.com.tw TEL:886-2-2242-6825 FAX:886-2-2242-6827


S5-60D,S5-120D REACTIVE POWER REGULATOR S5 SERIES

OPERATION SEQUENCE

TAIK Electric Co., Ltd. www.taik.com.tw TEL:886-2-2242-6825 FAX:886-2-2242-6827


S5-60D,S5-120D REACTIVE POWER REGULATOR S5 SERIES

CONNECTION DIAGRAM

OUTSIDE DIMENSIONS ( UNIT : mm)

TAIK Electric Co., Ltd. www.taik.com.tw TEL:886-2-2242-6825 FAX:886-2-2242-6827