You are on page 1of 8

SV-0402-GB

Capacity control of screw compressors:


speed or slider control – a comparative study

Abridged version

There are different technologies to adapt the compressor’s cooling capacity


to the changing requirements of the A/C and refrigerant systems when
operating with screw compressors.
• Distribution of the requirements to several compressors
(parallel operation)
• Evaporation pressure control with hot gas bypass
• Internal bypass in the compressor
• Reduction of the compressor displacement by a control slider
• Variable compressor speed

The difference between the methods lies in the quality of the control – stepped or infi-
nite – and in the achievable part-load efficiencies.
The following comparison shows results from extensive measurings of two “modern”
methods of capacity control of a semi-hermetic compact-screw compressor, slider con-
trol, and speed control by frequency inverter.

Dipl. Ing. (FH) Rolf Blumhardt


Content 3 Test setup, components, refrigerants,
application range
1 Introduction
2 System description: The measurings were conducted on a test stand with gas
slider control / speed control circuit without refrigerant condensation. The heat equivalent
3 Test setup, components, refrigerants, of the required electric power is led out via a liquid cooled
application range heat exchanger. The operating points can be adjusted by a
4 Control ranges control valve (by the temperature of the coolant) and by the
5 Volume ratio refrigerant charge of the measuring circuit.
6 Results The suction gas flow is measured in order to get the cooling
7 Summary capacity. The electric current consumption is calculated from
the effective value of the current consumption and the tensi-
on. All relevant data, pressures and temperatures are recor-
ded electronically and are also analysed electronically. The
1 Introduction
measuring values shown are mean values of a measuring
time of 5 minutes.
There are different technologies to adapt the compressor’s
For the measuring a semi-hermetic compact screw compres-
cooling capacity to the changing requirements of the A/C
sor type CSH6561-60Y was used. The theoretical displace-
and refrigerant systems when operating with screw compres-
ment is 170 m3/h at 50 Hz, max. operating current
sors.
105 A. Slider position 100%, 75%, 50%, and 25%.
• Distribution of the requirements to several compressors
The frequency inverter, type 75FEP, used to regulate the
(parallel operation)
speed control, was set on a proportional tension frequency
• Evaporation pressure control with hot gas bypass line. The max. operating current is 145 A, the nominal capa-
city is 75 kW.
• Internal bypass in the compressor
The frequency variable operation was done by a standard
• Reduction of the compressor displacement by a control
motor for 400 Volts at 50 Hz. This means that when rising
slider
over 50 Hz operating frequencies, the compressor is opera-
• Variable compressor speed ted with increasing sub tension and proportionally increasing
operating current. The max. possible compressor speed is in
this case limited by the motor voltage rate.
The difference between the methods lies in the quality of the
control – stepped or infinite – and in the achievable part-load The application range of the compressor in connection with
efficiencies. The following comparison shows results from the refrigerant R407C is shown in figure 1. An evaporation
extensive measurings of two modern methods for capacity temperature range of +10°C to -10°C is examined, which
control of a semi-hermetic compact-screw compressor, slider covers the application in A/C systems with direct evaporati-
control, and speed control by frequency inverter. on, water- and brine chillers. The condensing temperature is
30, 40 and 50°C. The condensing and evaporation tempera-
tures are referring to the respective dew point temp. of the
mix-refrigerant R407C.
2 System description

Slider control
The slider control allows an adaptation of the compressor
displacement to the power requirement by shifting the start
70
of the compression process through an axial slide of the
control slider. At the same time the outlet window is adapted tc [°C]
to the newly developing displacement in this series. LI CR 75% CR 50%
60

CR 25%
Speed control 50

To regulate the speed, a frequency inverter was added to the


same compressor. The speed had been selected in such a 40
way that the same performance as for the slider control was
achieved in each measuring point.
30 CS(H)
R407C
∆toh = 10 K
20
-20 -15 -10 -5 0 5 10 to [°C] 20

Fig. 1 Application range

2 Capacity control of screw compressors


4 Control ranges 6 Results

The slider of the compressor, starting from the full load posi- Fig. 2 shows the power consumption with frequency inverter
tion 100% had been positioned to nominal 75%, 50% and in comparison to direct net operation.
25%. The cooling capacity which results thereof can –
The higher power consumption at FI operation is based on
dependent on the pressure ratio – deviate from the nominal
the efficiency ratio of the FI, and by a smaller part, which
values.
cannot be defined by measuring technique, on the reduced
For the measurings with frequency inverter the operating fre- efficiency ratio of the electric motor, when supplied with the
quency of the compressor had been selected in such a way pulsed tension by the FI.
that in each measured operating point the cooling capacity
The further examinations are made for each single measu-
adjusted to a value that was identical with the slider position.
red condensing temperature of 30°C, 40°C, and 50°C.
In addition to the directly comparable measurings the opera-
At 30°C condensing temperature the relative power con-
ting frequency at the max. tension of 400 Volts was increa-
sumption shows a continuous curve for FI operation. The
sed so far over 50 Hz that the voltage limit of the motor was
relative power consumption at the slider control lies partly
achieved.
above, partly below the power consumption for FI operation.
This unsteady behaviour is caused by a volume ratio, defi-
ned in various slider positions. The results show that this
5 Volume ratio compressor is not optimised for the relatively low condensing
temperature of 30°C. This is quite common as air cooled A/C
systems do not work with such low condensing temperatu-
The volume ratio of the compressor is defined by the posi-
tion of the suction contour and the size of the discharge port.
The outlet window consists of an opening, which is axially
aligned in the discharge flange and a discharge port, which
Comparison of control with slider or FI
is radially integrated in the control slider. 110

The partial integration of the discharge port into the slider 100
leads to an automatic adaptation of the outlet window at part
Power consumption in [%]

load operation. The volume ratio stays at a constant level up 90

to 70% load. When further reducing the load (to 25%), an


80
independent Vi-control results, by which the volume ratio is
adapted to the lower condensing pressure, which is to be 70
expected in part load operation.
60
ideal
When operating in frequency variable ranges, the control sli- to = 0°C (S)
der stays at the 100% position. An adaptation of the volume 50
to = 0°C (FU)
ratio to the lower conditions at part load operation does not R407C
40
tc = 30°C
happen in this case.
30
30 40 50 60 70 80 90 100
Cooling capacity in [%]

Fig. 3 Curve of power consumption at 30°C condensing


temperature

Comparison of control with slider or FI


Relative power consumption in comparison 110
FI operation at 50Hz /net operation at full load
104,5 100
Power consumption in [%]
Relative power consumption

104,0
tc = 50°C 90
103,5
80
with FI [%]

103,0 ideal
tc = 40°C
102,5 70 to = 10°C (S)
to = 10°C (FI)
102,0 to = 0°C (S)
60
tc = 30°C to = 0°C (FI)
101,5 to = -10°C (S)
50 to = -10°C (FI)
101,0
-10 -5 0 5 10 R407C tc = 40°C
40
Evaporation temperature [°C] 30 40 50 60 70 80 90 100
Cooling capacity in [%]

Fig. 2 Relative power consumption in comparison FI-operation at Abb. 4 Curve of power consumption at 30°C condensing
50 Hz / net operation at full load temperature

Speed or slider control – a comparative study 3


res. (For water cooled systems compressors with accordingly possible condensing temperature in comparison to net ope-
adapted volume ratio are available). ration. Reason is the stronger heating of the motor at FI ope-
ration.
At 40°C condensing temperature the power consumption in
all operating points (to = -10°C, 0°C and +10°C) lies below
Operation of the compressor at frequencies above 50 Hz
the one at FI operation.
The data shown for the operation of the screw compressor
At 50°C condensing temperature (fig. 5) the ratio of the
were evaluated by the standard motor (400 V, 50 Hz) at a
power consumption of the compressors regulated by a slider
proportional characteristic curve of the frequency inverter.
is a little more favourable than at 40°C tc. At this operating
Operating frequencies above 50 Hz are possible at a con-
point the advantages of the slider control are obvious.
stant supply tension. In this range, the so called weakening
Moreover, the reduced peripheral velocity of the dental tops
of the field, the current consumption increases proportionally
has a negative effect on the performance – as well as on the
to the speed. The motor is therefore operated at an increa-
volumetric and isentropic efficiency of the compressor when
sing frequency with rising sub-tension. This operation is pos-
operated at low speed.
sible up to the max. current consumption of the compressor.
The current resources of the motor result from the relation of
the max. possible current consumption to the operating cur-
7 Comparison of application limits
rent for FI operation at the selected operating point.
Experiences show that the operating current must not
The full-load application limits for slider operation with fre- exceed 90% of the max. admissible operating current for
quency inverter are shown in fig. 6. The upper limit line is direct drive. The table shows some examples.
based on the max. admissible motor temperature. For opera-
tion with frequency inverter there is a restriction of the max.

Oper. point current cons. Imax max. freq. for Imax = 94,5 A
Comparison of control with slider or FI
110 -10°C/40°C 69,1 A 105 A 78 Hz

-10°C/50°C 71,4 A 105 A 66 Hz


100
Power consumption in [%]

0°C/40°C 62,9 A 105 A 75 Hz


90
0°C/50°C 74,5 A 105 A 63 Hz

80 ideal
to = 10°C (S)
For the operating point to = 0°C, tc = 45°C the operating
to = 10°C (FU) behaviour of the compressor has been recorded for operati-
70 to = 0°C (S) on with FI. The maximum frequency resulted in 74 Hz.
to = 0°C (FU)
R407C tc = 50°C Fig. 7 shows the FI increase of the cooling capacity and the
60
COP above the speed. Both values do not behave proportio-
50 60 70 80 90 100
nally to the speed increase.
Cooling capacity in [%]

Abb. 5 Curve of the power consumption at 50°C condensing


temperature

Measured application limits CSH6561-60Y


(with and without frequency inverter) Cooling capacity at over-synchroised operation (net: 400 V - 50 Hz)
80 1

70 0,98
Condensing temperature [°C]

Slider (100%)
0,96
Relative capacity and COP

60
Qo
FI (50Hz) 0,94
50
0,92

40 0,9
COP
30 0,88

0,86
20 R407C (dew points)
∆toh = 10 K (50Hz) 0,84
50 55 60 65 70 75
10
-25 -20 -15 -10 -5 0 5 10 15 Operating frequency [Hz]
Evaporation temperature [°C]

Abb. 6 Application limits Abb. 7 Relative curve of capacity and COP at frequencies above
50Hz

4 Capacity control of screw compressors


The relative cooling capacity related to frequency is still
Relative values
approx. 92% for 40 Hz. Reasons are an enlarged slip of the 50 Hz 60 Hz
for 60 Hz
motor caused by sub-tension when operating above 50 Hz,
and the increasing throttling losses in the compressor cau- Cooling capacity [kW] 116,9 139,4 99%
sed by the increasing refrigerant mass flow. When the speed
increases due to higher peripheral speed of the rotors, the Power consumption [kW] 41,9 49,3 98%
back flow losses are reduced and cannot compensate this
COP 2,79 2,83 1,014
effect.
The COP shows a similar behaviour. The sub-tension, rising
The cooling capacity increases sub-proportionally to 99%
proportionally to the frequency, causes a lower magnetizati-
relative value. The power consumption also increases sub-
on of the motor and thus a reduction of the efficiency ratio.
proportionally to 98% relative value. This leads to a 1,4%
At the max. possible frequency of 74 Hz the performance
increase of the COP.
drops 14%.
Due to the higher flow losses at increasing mass flow in the
Provided that the max. frequency is only needed to cover the
compressor, the cooling capacity increases sub-proportional-
peak loads – for a few days a year – the reduction of the
ly to the speed increase. The relative reduction of the power
COP value becomes less important. Especially important is
consumption results from the lower back flow losses of the
the capacity increase at higher compressor frequencies – for
compressor at higher frequencies. The COP increases to
this operating point – 36% from 117 to 159 kW.
1,4%. With the 400 V motor the COP dropped to 97% at this
Alternatively to the selected motor voltage of 400 V, 50 Hz operating point, as already mentioned. This result shows that
the compressor can also be equipped with a motor of 230 V, systems, which are primarily operated at frequencies above
50 Hz. In this case the frequency inverter is able to provide a 50 Hz should be equipped with a motor, which allows a pro-
tension which is proportional to the frequency over the entire portional increase of voltage and frequency in this range as
speed range. Thus, the performance and COP losses for well. This is a motor selected for 230 V, 3 PH, 50 Hz. In this
operation with sub-tension mentioned before can be avoided. case it must be paid attention to the fact that the frequency
The respective operating data had been measured with the inverter has to be selected for higher currents when using
available motor at an intensified voltage, proportionally to the 230 V motors.
frequency (50 Hz, 390 V to 60 Hz, 460 V). With respect to
motor efficiency and speed the results are comparable to
those of the motor 230V, 50Hz. The operating point to = 0°C, Performance curve with frequency inverter (27 to 74 Hz)
tc = 45°C was selected.
The diagram shows the part load behaviour with frequency
inverter for 0°C / 45°C with R407 C. The red curve repre-
sents the part load behaviour for proportional change of ten-
sion and frequency. For frequencies above 50 Hz the curve
comes close to the curve of the proportional line. The
distance to the proportional line, which is still obvious, is due
to the efficiency ratio of the frequency inverter. The measu-
rings had been conducted up to 60 Hz. For higher frequen-
cies the efficiency of the inverter is almost compensated by
the better isentropic efficiency of the compressor developing
at higher speed. This positive effect is partly neutralized by
the increasing throttling losses of the compressor.

Curve of cooling cap. at over-synchr. operation (net: 50 Hz - 400 V)


180 Performance curve with FI (27 bis 74 Hz)

160
170
Cooling capacity [kW]

Qo (proportional)
160 140
Power consumption [%]

150 120
Qo (Measurement)
140 100
Umax = 400V
130 80 f/I = prop.
proportional
120 60

110 40
50 55 60 65 70 75 50 60 70 80 90 100 110 120 130 140
Cooling capacity [%]
Operating frequency [Hz]

Fig. 8 Curve of the cooling capacity at over-synchronic operation Fig. 9 Curve of the cooling capacity with FI

Speed or slider control – a comparative study 5


The blue curve shows the part load behaviour for compres-
sor operation from 50 Hz with increasing sub-tension. It is
obvious that the power consumption increases superpropor-
tionally to the increasing frequency. This characteristic, which
is achieved by the 400 Volts standard motor, should be used
only when this high performance is needed temporarily.

7 Summary

• Due to the efficiency of the frequency inverter, the COP


achieved by this system in the respective control range is
always lower than it is for direct net operation.
• The application range of the compressor is reduced when
operating with a frequency inverter. This leads to a slight
reduction of the maximal possible condensing temperatu-
re. A very suitable alternative for applications with higher
condensing temperatures is provided by the refrigerant
R134a.
• The possibility to increase the compressor’s performance
by operating over 50 Hz and then using smaller compres-
sors, increases the efficiency of such systems.
• For systems, which are primarily operated above 50 Hz,
one should check, if the application of a motor with 230 V
would be an economically efficient solution.
• If there are requirements of the power companies concer-
ning restrictions of the staring currents, these might also
be met by using frequency inverters. Separate soft star-
ters are not necessary.
• Both systems, slider control and variable frequency opera-
tion are suitable to adapt the compressor capacity to the
required performance. The decision, which system to use,
can be made only after a calculation of the system confi-
guration, taking into account the performance, capacity
ratio and the investment costs.
• Net impedance, sinus filter and the load on the frequency
inverter can significantly reduce the blind current at fre-
quency inverter operation. The priority of each measure-
ment has to be specified more precisely by further tests.

6 Capacity control of screw compressors


Speed or slider control – a comparative study 7
Bitzer Kühlmaschinenbau GmbH
Subject to change 03.06

Eschenbrünnlestr. 15
7 10 65 Sindelfingen, Germany
fon +49 (0) 70 31 9 32-0
fax +49 (0) 70 3 9 32-1 46 & -1 47
www.bitzer.de • www.bitzer-corp.com
bitzer@bitzer.de

You might also like