Each tower shall be fitted with an approved anti-climbing device with gates which shall provide climbing facilities for use by authorized personnel. The height of the anti- climbing device above ground level shall be between 2.0m and 3.5m on the normal tower height. The anti-climbing devices could be of the "spikes" type or “barbed wire” type. Gates should be secured with an approved brass or galvanized steel padlock.
8.2.7.2 TOWER SIGNS
The OHL Sub CONTRACTOR shall furnish all materials for tower signs including all bolts, nuts, fibre washers front and back, brass eyelets fitted with the holes and sup- porting structures, if required, for attaching signs to the structure as specified in the structure list. The colours of figure and background shall be as described on the drawings and shall be weather-proof, baked enamel finish paint, vitreous or stove enamel. The OHL Sub CONTRACTOR is required to make provision in the tower members for attaching signs at the locations described hereunder. a) Circuit identification plates Circuit identification plates shall be fitted to all towers at convenient locations adjacent to the circuits concerned. One plate per circuit is required. b) Phase plates A set of three phase plates shall be attached about three meters from ground level and above the anti-climbing guards and be provided at all towers. One set of phase plates are required coloured red, yellow and blue. c) Danger plates Danger plates shall be attached about three meters from ground level and above anti- climbing guards and be provided at every tower. d) Number plates Number plates shall be provided one for each tower. e) Aircraft Warning Spheres and Warning Lights Aircraft Warning Spheres and Warning Lights on the 33 kV OHLs are to be provided according to statutory requirements.
8.2.7.3 STEP BOLTS
Each tower shall be provided with step bolts of an approved type on two diagonally opposite legs spaced alternately on the angle flanges at not more than 380 mm be- tween centres, starting immediately above the anti-climbing device and continuing to each earth wire. The minimum diameter of the step bolts shall be 16 mm. Step bolts shall not be used as connection bolts.
DOCUMENT TITLE: ADCO DOC. NO. 30.45.53.1617
EQUIPMENT SPECIFICATION FOR 33kV OVERHEAD LINES (STEEL LATTICE TYPE) Page 33 of 90
CONTRACTOR DOC. No. ADCO Project No. Rev. B Date : 14.AUG.2014