SEISMIC ANALYSIS OF 5-STOREY BUILDING

Design Considerations:
Unit weight of Concrete = 23.54 kN/m3
Unit weight of wall = 21.2 kN/m3
Wall thickness = 0.15 m
Slab thickness = 0.125 m
Height (1st Storey) = 5 m
Height (2nd -nth Storey) = 3.2 m
Height (Roof deck extension) = 1 m
Height (balcony, assumed as
wall) = 1 m

Dimension:
Column 0.5 x 0.5 m2
Beam 0.3 x 0.4 m2

Wall Perimeter:
Roof deck 81 m
Per Floor 154.5 m

Miscellaneous (balcony-assumed as wall):


Perimeter 31.5 m
Column
Length:
No. of Columns 24
Roof deck 0.9 m
5th Floor 3.2 m
4th Floor 3.2 m
3rd Floor 3.2 m
2nd Floor 3.2 m
1st Floor 5 m

Beam Length per Floor:


Beam Name No. Length
B1 28 4.5 m
B2 16 3.5 m
B3 8 2 m
Total 198 m

Computation of Loads:

W1
Beam:
Dimension: 0.3 x 0.4 m2
Total Length = 198 m
Unit Weight = 23.54 kN/m3
Total Weight = 559.3104 kN

Column:
Dimension: 0.5 x 0.5 m
Total Height = 60 m
Unit Weight = 23.54 kN/m3
Total Weight = 353.1 kN

Slab:
Area = 392 m2
Thickness = 0.125 m
Unit Weight = 23.54 kN/m3
Total Weight = 1153.46 kN

Wall:
Height(roof deck) = 1 m
Perimeter (roof
deck) = 81 m
Height = 1.6 m
Perimeter = 154.5 m
Thickness = 0.15 m
Unit Weight = 21.2 kN/m3
Total Weight = 1043.676 kN

Stair:
Area (Steps) = 0.3 x 1.75 m2
Height = 1.4 m
Unit Weight = 23.54 kN/m3
Total Weight = 17.3019 kN

W1 = 3126.848 kN

W2,W3,W4:
Beam:
Dimension: 0.3 x 0.4 m2
Total Length = 198 m
Unit Weight = 23.54 kN/m3
Total Weight = 559.3104 kN

Column:
Dimension: 0.5 x 0.5 m
Total Height = 76.8 m
Unit Weight = 23.54 kN/m3
Total Weight = 451.968 kN

Slab:
Area = 392 m2
Thickness = 0.125 m
Unit Weight = 23.54 kN/m3
Total Weight = 1153.46 kN
Wall:
Height = 3.2 m
Perimeter = 154.5 m
Thickness = 0.15 m
Unit Weight = 21.2 kN/m3
Total Weight = 1572.192 kN

Stair:
Area (Steps) = 0.3 x 1.75 m2
Height = 2.8 m
Unit Weight = 23.54 kN/m3
Total Weight = 34.6038 kN

Miscellaneous (Balcony-assumed as walls)


Thickness = 0.15 m
Height = 1 m
Length = 31.5 m
Unit Weight = 21.2 kN/m3
Total Weight = 100.17 kN

W2,W3,W4 = 3871.704 kN

W5
Beam:
Dimension: 0.3 x 0.4 m2
Total Length = 198 m
Unit Weight = 23.54 kN/m3
Total Weight = 559.3104 kN

Column:
Dimension: 0.5 x 0.5 m
Total Height = 98.4 m
Unit Weight = 23.54 kN/m3
Total Weight = 579.084 kN

Slab:
Area = 392 m2
Thickness = 0.125 m
Unit Weight = 23.54 kN/m3
Total Weight = 1153.46 kN

Wall:
Height = 4.1 m
Perimeter = 154.5 m
Thickness = 0.15 m
Unit Weight = 21.2 kN/m3
Total Weight = 2014.371 kN

Stair:
Area (Steps) = 0.3 x 1.75 m2
Height = 2.8 m
Unit Weight = 23.54 kN/m3
Total Weight = 34.6038 kN

Miscellaneous (Balcony-assumed as walls)


Thickness = 0.15 m
Height = 1 m
Length = 31.5 m
Unit Weight = 21.2 kN/m3
Total Weight = 100.17 kN

W5 = 4440.9992 kN

Design
Parameters:
-consider the following:
Zone 4 z=0.4
Seismic source greater than 15KN
Soil source greater than 15KN
Soil profile type;
I= 1 Na= 4 Ca= 0.4
R= 8.5 Nv= 1 Cv= 0.56
Ct= 0.0731
Compute for Base shear, V

T=CtH3/4
T=0.0731(17.8)3/4
T= 0.633479

V = 1995.043 kN

But not to exceed,


V=

V= 2256.819

But not be less than,


V=

V= 1805.455 kN

or

V=

V= 844.0502
Use V= 1995.043 kN

Since T= 0.633479 <0.7


Thus, Ft=0

Level hx Wx h xW x Fx

5 17.8 3126.848 55657.89 0.264691 528.0695


4 14.6 3871.704 56526.88 0.268823 536.3143
3 11.4 3871.704 44137.43 0.209903 418.7659
2 8.2 3871.704 31747.97 0.150983 301.2176
1 5 4440.999 22205 0.1056 210.676
∑hxWx = 210275.2 1 1995.043

Lateral Loads

Frame 1,8: Frame 2-7:


5th Floor: 37.71925 kN 5th Floor: 75.4385 kN
4th Floor: 38.30816 kN 4th Floor: 76.61632 kN
3rd Floor: 29.91185 kN 3rd Floor: 59.8237 kN
2nd Floor: 21.51554 kN 2nd Floor: 43.03108 kN
1st Floor: 15.04828 kN 1st Floor: 30.09657 kN

Frame A: Frame B: Frame C:


5th Floor: 205.3604 kN 5th Floor: 264.0348 kN 5th Floor: 58.67439 kN
4th Floor: 208.5667 kN 4th Floor: 268.1571 kN 4th Floor: 59.59047 kN
3rd Floor: 162.8534 kN 3rd Floor: 209.383 kN 3rd Floor: 46.52955 kN
2nd Floor: 117.1402 kN 2nd Floor: 150.6088 kN 2nd Floor: 33.46862 kN
1st Floor: 81.92955 kN 1st Floor: 105.338 kN 1st Floor: 23.40844 kN
FRAME 1, 8:

4.310772 15.0877 15.0877 15.0877


37.719
15.0877 15.0877 30.1754 15.0877 15.0877

4.310772 9.429813 10.77693 18.85963 15.0877 9.429813 3.2

15.0877 12.99962 45.49867 30.1754 45.49867 45.49867 15.0877


38.3082
30.41097 45.49867 60.82193 45.49867 30.41097

17.31039 19.00685 43.27598 38.01371 60.58637 19.00685 3.2

30.41097 20.79619 72.78667 60.82193 72.78667 72.78667 30.41097


29.9119
42.37571 72.78667 84.75141 72.78667 42.37571

38.10658 26.48482 95.26646 52.96963 133.373 26.48482 3.2

42.37571 26.67361 93.35763 84.75141 93.35763 93.35763 42.37571


21.5155
50.98192 93.35763 101.9638 93.35763 50.98192

64.78019 31.8637 161.9505 63.7274 226.7307 31.8637 3.2

50.98192 40.01324 140.0464 101.9638 140.0464 140.0464 50.98192


15.0483
89.06443 140.0464 178.1289 140.0464 89.06443

104.7934 35.62577 261.9836 71.25155 366.777 35.62577 5

89.06443 178.1289 89.06443

7 2

LEGEND:
Column Shear
Column Moment
Girder Moment
Girder Shear
Column Axial
FRAME 2-7:

8.621543 30.1754 30.1754 30.1754


75.439
30.1754 30.1754 60.3508 30.1754 30.1754

8.621543 18.85963 21.55386 37.71925 30.1754 18.85963 3.2

30.1754 25.99924 90.99733 60.3508 90.99733 90.99733 30.1754


76.616
60.82193 90.99733 121.6439 90.99733 60.82193

34.62078 38.01371 86.55195 76.02741 121.1727 38.01371 3.2

60.82193 41.59238 145.5733 121.6439 145.5733 145.5733 60.82193


59.824
84.75141 145.5733 169.5028 145.5733 84.75141

76.21316 52.96963 190.5329 105.9393 266.7461 52.96963 3.2

84.75141 53.34722 186.7153 169.5028 186.7153 186.7153 84.75141


43.031
101.9638 186.7153 203.9277 186.7153 101.9638

129.5604 63.7274 323.901 127.4548 453.4613 63.7274 3.2

101.9638 80.02649 280.0927 203.9277 280.0927 280.0927 101.9638


30.097
178.1289 280.0927 356.2577 280.0927 178.1289

209.5869 71.25155 523.9672 142.5031 733.554 71.25155 5

178.1289 356.2577 178.1289

7 2

LEGEND:
Column Shear
Column Moment
Girder Moment
Girder Shear
Column Axial
FRAME A:

10.43100305 23.46975687 10.43100305 23.46975687 10.43100305 23.46975687


205.36037
23.46975687 23.46975687 46.93951374 23.46975687 46.93951374 23.46975687 46.93951374

10.43100305 14.66859804 0 29.33719609 0 29.33719609 0

23.46975687 24.75362881 55.69566481 46.93951374 24.75362881 55.69566481 46.93951374 24.75362881 55.69566481


76.616322
32.22590795 55.69566481 64.45181589 55.69566481 64.45181589 55.69566481 64.45181589

35.18463186 20.14119247 0 40.28238493 0 40.28238493 0

32.22590795 31.68391581 71.28881057 64.45181589 31.68391581 71.28881057 64.45181589 31.68391581 71.28881057


59.823703
39.06290262 71.28881057 78.12580524 71.28881057 78.12580524 71.28881057 78.12580524

66.86854767 24.41431414 0 48.82862828 0 48.82862828 0

39.06290262 36.90828601 83.04364352 78.12580524 36.90828601 83.04364352 78.12580524 36.90828601 83.04364352


43.031085
43.9807409 83.04364352 87.9614818 83.04364352 87.9614818 83.04364352 87.9614818

103.7768337 27.48796306 0 54.97592612 0 54.97592612 0

43.9807409 52.47779365 118.0750357 87.9614818 52.47779365 118.0750357 87.9614818 52.47779365 118.0750357


30.096568
74.09429481 118.0750357 148.1885896 118.0750357 148.1885896 118.0750357 148.1885896

156.2546273 29.63771793 0 59.27543585 0 59.27543585 0

74.09429481 148.1885896 148.1885896

4.5 4.5 4.5

LEGEND:
Column Shear
Column Moment
Girder Moment
Girder Shear
Column Axial
FRAME A (cont.):

23.46975687 10.43100305 23.46975687 10.43100305 23.46975687 10.43100305 23.46975687


46.93951374 23.46975687 46.93951374 23.46975687 46.93951374 23.46975687 46.93951374

0 29.33719609 0 29.33719609 0 29.33719609 0

55.69566481 46.93951374 24.75362881 55.69566481 46.93951374 24.75362881 55.69566481 46.93951374 24.75362881 55.69566481
64.45181589 55.69566481 64.45181589 55.69566481 64.45181589 55.69566481 64.45181589

0 40.28238493 0 40.28238493 0 40.28238493 0

71.28881057 64.45181589 31.68391581 71.28881057 64.45181589 31.68391581 71.28881057 64.45181589 31.68391581 71.28881057
78.12580524 71.28881057 78.12580524 71.28881057 78.12580524 71.28881057 78.12580524

0 48.82862828 0 48.82862828 0 48.82862828 0

83.04364352 78.12580524 36.90828601 83.04364352 78.12580524 36.90828601 83.04364352 78.12580524 36.90828601 83.04364352
87.9614818 83.04364352 87.9614818 83.04364352 87.9614818 83.04364352 87.9614818

0 54.97592612 0 54.97592612 0 54.97592612 0

118.0750357 87.9614818 52.47779365 118.0750357 87.9614818 52.47779365 118.0750357 87.9614818 52.47779365 118.0750357
148.1885896 118.0750357 148.1885896 118.0750357 148.1885896 118.0750357 148.1885896

0 59.27543585 0 59.27543585 0 59.27543585 0

148.1885896 148.1885896 148.1885896

4.5 4.5 4.5

LEGEND:
Column Shear
Column Moment
Girder Moment
Girder Shear
Column Axial
FRAME A (cont.):

23.46975687 10.43100305 23.46975687


46.93951374 23.46975687 23.46975687

0 29.33719609 10.43100305 14.66859804 3.2

55.69566481 46.93951374 24.75362881 55.69566481 23.46975687


64.45181589 55.69566481 32.22590795

0 40.28238493 35.18463186 20.14119247 3.2

71.28881057 64.45181589 31.68391581 71.28881057 32.22590795


78.12580524 71.28881057 39.06290262

0 48.82862828 66.86854767 24.41431414 3.2

83.04364352 78.12580524 36.90828601 83.04364352 39.06290262


87.9614818 83.04364352 43.9807409

0 54.97592612 103.7768337 27.48796306 3.2

118.0750357 87.9614818 52.47779365 118.0750357 43.9807409


148.1885896 118.0750357 74.09429481

0 59.27543585 156.2546273 29.63771793 5

148.1885896 74.09429481

4.5

LEGEND:
Column Shear
Column Moment
Girder Moment
Girder Shear
Column Axial
FRAME B:

13.41129 30.1754 13.41129 30.1754 13.41129 30.1754 13.41129 30.1754


264.035
30.1754 30.1754 60.3508 30.1754 60.3508 30.1754 60.3508 30.1754 60.3508 30.1754

13.41129 18.85963 0 37.71925 0 37.71925 0 37.71925 0 37.71925

30.1754 40.44326 90.99733 60.3508 40.44326 90.99733 60.3508 40.44326 90.99733 60.3508 40.44326 90.99733 60.3508
268.157
60.82193 90.99733 121.6439 90.99733 121.6439 90.99733 121.6439 90.99733 121.6439 90.99733

53.85455 38.01371 0 76.02741 0 76.02741 0 76.02741 0 76.02741

60.82193 64.69926 145.5733 121.6439 64.69926 145.5733 121.6439 64.69926 145.5733 121.6439 64.69926 145.5733 121.6439
209.383
84.75141 145.5733 169.5028 145.5733 169.5028 145.5733 169.5028 145.5733 169.5028 145.5733

118.5538 52.96963 0 105.9393 0 105.9393 0 105.9393 0 105.9393

84.75141 82.98456 186.7153 169.5028 82.98456 186.7153 169.5028 82.98456 186.7153 169.5028 82.98456 186.7153 169.5028
150.609
101.9638 186.7153 203.9277 186.7153 203.9277 186.7153 203.9277 186.7153 203.9277 186.7153

201.5384 63.7274 0 127.4548 0 127.4548 0 127.4548 0 127.4548

101.9638 124.4856 280.0927 203.9277 124.4856 280.0927 203.9277 124.4856 280.0927 203.9277 124.4856 280.0927 203.9277
105.338
178.1289 280.0927 356.2577 280.0927 356.2577 280.0927 356.2577 280.0927 356.2577 280.0927

326.024 71.25155 0 142.5031 0 142.5031 0 142.5031 0 142.5031

178.1289 356.2577 356.2577 356.2577 356.2577

4.5 4.5 4.5 4.5

LEGEND:
Column Shear
Column Moment
Girder Moment
Girder Shear
Column Axial
FRAME B (cont.):

30.1754 13.41129 30.1754 13.41129 30.1754 13.41129 30.1754


60.3508 30.1754 60.3508 30.1754 60.3508 30.1754 30.1754

0 37.71925 0 37.71925 0 37.71925 13.41129 18.85963 3.2

90.99733 60.3508 40.44326 90.99733 60.3508 40.44326 90.99733 60.3508 40.44326 90.99733 30.1754
121.6439 90.99733 121.6439 90.99733 121.6439 90.99733 60.82193

0 76.02741 0 76.02741 0 76.02741 53.85455 38.01371 3.2

145.5733 121.6439 64.69926 145.5733 121.6439 64.69926 145.5733 121.6439 64.69926 145.5733 60.82193
169.5028 145.5733 169.5028 145.5733 169.5028 145.5733 84.75141

0 105.9393 0 105.9393 0 105.9393 118.5538 52.96963 3.2

186.7153 169.5028 82.98456 186.7153 169.5028 82.98456 186.7153 169.5028 82.98456 186.7153 84.75141
203.9277 186.7153 203.9277 186.7153 203.9277 186.7153 101.9638

0 127.4548 0 127.4548 0 127.4548 201.5384 63.7274 3.2

280.0927 203.9277 124.4856 280.0927 203.9277 124.4856 280.0927 203.9277 124.4856 280.0927 101.9638
356.2577 280.0927 356.2577 280.0927 356.2577 280.0927 178.1289

0 142.5031 0 142.5031 0 142.5031 326.024 71.25155 5

356.2577 356.2577 356.2577 178.1289

4.5 4.5 4.5

LEGEND:
Column Shear
Column Moment
Girder Moment
Girder Shear
Column Axial
FRAME C:

2.980287 6.705645 2.980287 6.705645 2.980287 6.705645 2.980287 6.705645


58.6744
6.705645 6.705645 13.41129 6.705645 13.41129 6.705645 13.41129 6.705645 13.41129 6.705645

2.980287 4.191028 0 8.382056 0 8.382056 0 8.382056 0 8.382056

6.705645 8.987391 20.22163 13.41129 8.987391 20.22163 13.41129 8.987391 20.22163 13.41129 8.987391 20.22163 13.41129
59.5905
13.51598 20.22163 27.03197 20.22163 27.03197 20.22163 27.03197 20.22163 27.03197 20.22163

11.96768 8.44749 0 16.89498 0 16.89498 0 16.89498 0 16.89498

13.51598 14.37761 32.34963 27.03197 14.37761 32.34963 27.03197 14.37761 32.34963 27.03197 14.37761 32.34963 27.03197
46.5295
18.83365 32.34963 37.66729 32.34963 37.66729 32.34963 37.66729 32.34963 37.66729 32.34963

26.34529 11.77103 0 23.54206 0 23.54206 0 23.54206 0 23.54206

18.83365 18.44101 41.49228 37.66729 18.44101 41.49228 37.66729 18.44101 41.49228 37.66729 18.44101 41.49228 37.66729
33.4686
22.65863 41.49228 45.31726 41.49228 45.31726 41.49228 45.31726 41.49228 45.31726 41.49228

44.7863 14.16165 0 28.32329 0 28.32329 0 28.32329 0 28.32329

22.65863 27.66348 62.24282 45.31726 27.66348 62.24282 45.31726 27.66348 62.24282 45.31726 27.66348 62.24282 45.31726
23.4084
39.58419 62.24282 79.16838 62.24282 79.16838 62.24282 79.16838 62.24282 79.16838 62.24282

72.44978 15.83368 0 31.66735 0 31.66735 0 31.66735 0 31.66735

39.58419 79.16838 79.16838 79.16838 79.16838

4.5 4.5 4.5 4.5

LEGEND:
Column Shear
Column Moment
Girder Moment
Girder Shear
Column Axial
FRAME C (cont.):

6.705645 2.980287 6.705645 2.980287 6.705645 2.980287 6.705645


13.41129 6.705645 13.41129 6.705645 13.41129 6.705645 6.705645

0 8.382056 0 8.382056 0 8.382056 2.980287 4.191028 3.2

20.22163 13.41129 8.987391 20.22163 13.41129 8.987391 20.22163 13.41129 8.987391 20.22163 6.705645
27.03197 20.22163 27.03197 20.22163 27.03197 20.22163 13.51598

0 16.89498 0 16.89498 0 16.89498 11.96768 8.44749 3.2

32.34963 27.03197 14.37761 32.34963 27.03197 14.37761 32.34963 27.03197 14.37761 32.34963 13.51598
37.66729 32.34963 37.66729 32.34963 37.66729 32.34963 18.83365

0 23.54206 0 23.54206 0 23.54206 26.34529 11.77103 3.2

41.49228 37.66729 18.44101 41.49228 37.66729 18.44101 41.49228 37.66729 18.44101 41.49228 18.83365
45.31726 41.49228 45.31726 41.49228 45.31726 41.49228 22.65863

0 28.32329 0 28.32329 0 28.32329 44.7863 14.16165 3.2

62.24282 45.31726 27.66348 62.24282 45.31726 27.66348 62.24282 45.31726 27.66348 62.24282 22.65863
79.16838 62.24282 79.16838 62.24282 79.16838 62.24282 39.58419

0 31.66735 0 31.66735 0 31.66735 72.44978 15.83368 5

79.16838 79.16838 79.16838 39.58419

4.5 4.5 4.5

LEGEND:
Column Shear
Column Moment
Girder Moment
Girder Shear
Column Axial