I. TRUE OR FALSE
T 1. Polarization Index is a direct measure of the dryness and cleanliness of the insulation.
F 2. The insulation resistance is the ratio of the AC voltage applied between the winding and
ground to the resultant current. DC
F 3. The first two components of the voltage decay with time. CURRENT
T 4. Winding resistance test identifies short circuits, open circuit, ground faults, loose connections,
dirt accumulation at connections, and etc.
5. In DC High-potential test for a 4kV Motor, the maximum voltage requirement is 5000v. 9K
T 6. Stator Current fluctuation test is performed on an operating and loaded motor.
T 7. Hipot test is a nondestructive test used to evaluate the dielectric strength of the ground wall
insulation.
8. In surge testing, if the coil has an interturn fault or a phase-to-phase fault, the waveform
produced during the test could become stable. UNSTABLE
T 9. For a healthy motor, the resistance unbalance should be less than 10 percent if the test is
performed from the motor control center (MCC).
10. The main limitation of this test is that it can only be conducted on-line. OFF-LINE
T 11. In chemical cleaning of the heat exchanger, use a weak acid solution.
T 12. If the windings of the motor have serious damage, the motor should be rewound.
II. ENUMERATION
(13-15) Give at least 3 winding failures in three phase motor windings
Winding Shorted phase to phase Shorted connection
Winding Shorted turn to turn Winding damage due to overload
Winding with shorted coil Damage caused by a lock rotor
Winding grounded at the end of slot Winding damage by a voltage surge
Winding grounded in the slot
__________6. This test gives good indication about the presence of oil decay products.