Xi’’an Jianghe

Xi
Automatic Monitoring Component.Instrument

adopts spiral case differential pressure


General
measurement. To calculate the flow of turbine
It is a sort of intelligent digital instrument with according to the formula Q=K ∆P . In the
SCM for kernel disposal standard signal to formula Q:flow, K:spiral case flow coefficient,
flow monitoring device. The turbine ∆P: pressure difference between inside and
differential pressure discharge monitoring outside of the volute cross-section lateral flow
system is composed of the flow monitoring measured. The functional block diagram of
device,three- manifold valve and differential flow monitoring device refers to fig. 2.
pressure transmitter.
Technical parameters
Features
� Power supply: AC220V ± 10%, 50Hz
� Intelligent digital instrument with SCM for � Display range: instantaneous value: 0 ∼
disposal system. 9999.99 m3/s
� Setup and make amendment of handiness cumulative flow value: 0 ∼ 99999999 Km3
for sensor range,instrument range. � Accuracy: 0.5%FS / word
� Possess dump memory and parameters � Work environment:
automatic stop function. Temperature: 0 – 50°C
� Instantaneous flow rate and cumulative Humidity ≤ 90%RH
flow display to switch. � Setting for alarm: The alarm value can be
� The alarm value can be at discretion set, at discretion set, when the monitoring
adjustment convenience. value runs up to alarm setting value, alarm
� With standard signal output corresponding relay excite.
to instantaneous flow rate. � Analog output: 4-20mA
� Provide power supply 24VDC for sensor. Load resistance: ≥ 525 Ω
� The use of touch keys, elegant. � Output contact: two group normally
Principle of operation
Principle opened contacts
� Contact rating: 5A/250VAC, 5A/30VDC
The discharge measuring through turbine
� Power consumption: 12W

2
Fig. 1 LJZ-2 Intelligent Flow Monitoring Device Schematic Drawing

Installation and maintenance


� Operation panel details
1. 3-digit LED digital tube display window:
Display parameter
2. Ok attribute indicator light: Ok On,
indicates the device works normally
3. Button area: Set up instrument operation
parameter

Fig. 2 LJZ-2 Intelligent Flow Monitoring Device Operator Panel Description


� Terminals

Power Supply: AC Power supply


+24V: Transmitter power supply positive pole.
IN: Transmitter input signal.
COM: Transmitter power supply negative pole
+OUT-: 4-20mA current output terminal
J1-J2: Output contact terminal (SPST).
GND: Housing grounding line

Fig. 3 LJZ-2 Intelligent Flow Monitoring Device Wiring Terminal Description


Xi’’an Jianghe
Xi
Automatic Monitoring Component.Instrument

� Outline and opening dimensions

Mounting Plate Cutout Dimension:

Fig. 4 LJZ-2 Intelligent Flow Monitoring Device Mounting & Cutout Dimension
Operation instruction
Power on, type LJZ-2 flow monitoring device automatically enters into monitoring state,eight digit
nixie tube display the value of discharge measured.
� Parameters setup:
Press key “■” at least 3 seconds, the nixie tube shows “88888886”, press key “▲”, the nixie tube
shows “88888888” and enters into the parameter setting state. Press key “■”,the nixie tube shows
the setting value of the first numeral, by this time press key “▲” or “▼” to modify the setting value
of the first numeral. The setup of the first number is completed and press key “S” ingress the setup
of the second numeral. To release key “■”, the instrument automatically enters into the monitoring
state after 5 seconds.
At the same time press key “▲” and “▼” at least 3 seconds, the cumulative flow automatically
clear.
� Data setup description:
Instrument must be set homologous parameters before it is put into operation. If the showed value
and output value is unconformity in service, user should first check whether the setting of
parameters are correct.

Parameter Serial Number


Practical value

The meaning of parameter serial number 1 ∼ 6 as follows:


“1” --- the range of the differential pressure transmitter, the corresponding differential pressure
value when output value is 20mA.
“2” --- maximum flow, the corresponding flow value when instrument export 20mA,Unit: m3/s
4
Xi’’an Jianghe
Xi
Automatic Monitoring Component.Instrument
“3” --- alarm mode,
“00” – no alarm.
“01” - lower limit alarm. Alarm contact closure when flow is lower than the alarm setting.
“10” – high and low alarm mode. Alarm contact J1 closure when flow is lower than the lower
limit alarm setting value. Alarm contact J2 closure when flow is higher than the high limit alarm
setting value.
“11” - two-stage high limit alarm. Alarm contact closure when flow is higher than the alarm
setting.
“4” --- first stage alarm setting value
“5” --- second stage alarm setting value
Note: Spiral casing high/low voltage side current measuring lead shall correspond to spiral casing differential
pressure transmitter
Alarm Attribute Description:
1: High/High Limit Alarm:
Secondary Alarm Set-point Second Alarm Action
Primary Alarm Set-point First Alarm Action

2. Low/High Limit Alarm


Secondary Alarm Set-point Second Alarm Action
Primary Alarm Set-point First Alarm Action

3. Low/Low Limit Alarm


Secondary Alarm Set-point Second Alarm Action
Primary Alarm Set-point First Alarm Action

Reset Function
� Checking step
Wiring according to fig. 3.
Power on,instrument self-checking, if no signal of sensor, instrument should show disconnection
sign “HELP”.
To set instrument parameters according to the following table:
Serial number 1 2 3 4 5
Numerical value 100.00 100.00 11 40.00 70.00
To connect sensor and regulate input current according to the following table, check the instrument
display and output, if the showed value and numerical value in table is conformity, shows that
instrument is normally.
Input current 4mA 5mA 8mA 13mA 20mA
Display 0.00 25.00 50.00 75.00 100.00
Output 4mA 8mA 12mA 16mA 20mA
J1 No alarm No alarm Alarm Alarm Alarm
J2 No alarm No alarm No alarm Alarm Alarm
5
Xi’’an Jianghe
Xi
Automatic Monitoring Component.Instrument

� Fault checking
1) Power-on, no display
Check whether the power supply is good.
2) Signal disconnection indication
Check whether the wiring between sensor and instrument is exactness.
Check whether the power supply of sensor is 24VDC.
3) Showed value incorrectness
Check whether the instrument parameters setting are correct.
Check whether the sensor output signal is correct.
Re-calibration instrument.

Ordering Details

Designed Max. Flow

Spiral Casing Max. Differential Pressure Value (KPa)

Product Serial No.

Flow Monitoring Device