Customer: AL FAYHAA Construction & Contracting

Project: Coastal Village (COV) infrastructure package


Notes: IP-EV13-MDB-2

Designer: Engr. Abuzer Banderkar

Rev. n°1 Date: 11/10/2021 Calculated by: DOC


Rev. n°2 Drafter:
Design.: File name:
Rev. n°3
REVISIONS Date: Signatures Approval: Record #:
Calculation and dimensioning criteria

Calculation method-standard IEC 60909-1

Standard for cable dimensioning IEC 60364

Overload Overload verifications are made according the following relations: IB <= In <= Iz and I2 <= 1.45*Iz

Legenda:

IB = the current for which the circuit is designed

In = nominal current of the protective device (For adjustable protective devices, the nominal current In is the current setting selected)

I2 = current ensuring effective operation in the conventional time of the protective device

Iz = cable carrying capacity according the chosen standard

Short Circuit Circuit breakers and fuses are dimensioned with a breaking capacity higher than the maximum short circuit current in the point of installation

Circuit breakers dimensioned according to IEC 60497-2 are also chosen with the making capacity Icm higher than the maximum peak current

The protection against short circuit must satisfy the rule I²t <= K²S²

Legenda:

I²t = let-through energy at the maximum short circuit current (defined by the producer)

S = section of the conductors

K = factor defined in IEC60364-4-43 table 43A and IEC60364-5-54 tables A.54.2, A.54.4 and A-54.5

Indirect contact TT systems: the verification is Idn * Ra <= Vo, or Im <= Ib min

TN systems: the verification is Im <= Ib min

Legenda:

Idn = sensitivity of the residual current device

Ra = earthing resistance

Uo = max admitted contact voltage

Im = tripping value of the protective device at time limit

Ib min = minimum short circuit current at line end

Discrimination and Back-up The discrimination and back-up values are determined by the producer with laboratory tests

Discrimination required in the installation (see indications on the single-line and the Discrimination report

Backup not required in the installation

Rev. n°1 Date: 11/10/2021 Description Customer: AL FAYHAA Construction & Contracting Drawing number:
Rev. n°2 Drafter: IP-EV13-MDB-2 Project: Coastal Village (COV) infrastructure package
Rev. n°3 Design.: Engr. Abuzer Banderkar File: Sheet: Next sheet: Sheets:
REVISIONS Date: Signatures Approval: Serial: 1 1
Short-circuit calculation hypothesis for IEC 60909-0

Calculation algorithm

The calculation of maximum and minimum, balanced and unbalanced, short-circuit currents is made by application of symmetrical components.

General conditions

The calculation of maximum and minimum short-circuit currents is based on the following simplifications.

a) For the duration of the short circuit, there is no change in the type of short circuit involved (a three-phase short circuit remains three-phase)

b) For the duration of the short circuit, there is no change in the network involved.

c) The impedance of the transformers is referred to the tap-changer in main position.

d) Arc resistances are not taken into account.

e) All line capacitances and shunt admittances and non-rotating loads, except those of the zero-sequence system, are neglected.

Maximum short-circuit currents

In the calculation of maximum short-circuit currents, the following conditions have been considered:

- it is applied the voltage factor cmax according to table 1, IEC 60909-0

- it is chosen the network configuration which leads to the maximum value of short-circuit current at the short-circuit location

- the contribution of asynchronous motors is considered if their contribution is higher than 5% of the initial short-circuit current calculated without motors

- resistance RL of lines (overhead lines and cables) are introduced at a temperature of 20°C

Minimum short-circuit currents

In the calculation of minimum short-circuit currents, the following conditions have been considered:

- it is applied the voltage factor cmin according to table 1, IEC 60909-0

- it is chosen the network confguration which lead to the minimum value of short-circuit current at the short-circuit location

- the contribution of asynchronous motors is neglected

- resistance RL of lines (overhead lines and cables) are introduced at a temperature of 250°C (EPR),160°C (PVC) or 140°C (PVC >300m²)

Rev. n°1 Date: 11/10/2021 Description Customer: AL FAYHAA Construction & Contracting Drawing number:
Rev. n°2 Drafter: IP-EV13-MDB-2 Project: Coastal Village (COV) infrastructure package
Rev. n°3 Design.: Engr. Abuzer Banderkar File: Sheet: Next sheet: Sheets:
REVISIONS Date: Signatures Approval: Serial: 1 1
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29

A
Un [V] 33000
Ik LLL [kA] 17.5
P [kW] 595.2
Q [kvar] 28.9


E -TM1
TR-1
Un2 = 400 V
Sn = 1000 kVA
Sec.: LLLN / TN-S


F -WC1
TR-1
12x(1x630)+2G630
Ib = 829.0 A
Iz = 2452.8 A
dV = 0.16 %
L = 30 m

G 
-QF1
E1.2N 1600 Ekip Touch LSIG 1600
TR-1
*

-B1
FU = 0.80
U=411.3 V
IB = 829.0 A
Cosphi = 1.00
I     Ik max = 23.1 kA
-QF2 -QF3 -QF4 -QF5 Ik LLL = 23.1 kA
T6S 630 PR221DS-LS/I 630A T6S 630 PR221DS-LS/I 630A T6S 630 PR221DS-LS/I 630A E1.2C 800 Ekip Touch LI 800
FP-502-RZ2-001 FP-501-RZ2-002 FP-502-RZ2-003 *
* * *

K    
-WC2 -WC5 -WC3 -WC4
FP-502-RZ2-001 FP-501-RZ2-002 FP-502-RZ2-003 2x 4G120/70
2x 5G185 2x 5G185 2x 5G185 IB = 493.6 A
Ib = 383.6 A Ib = 383.6 A Ib = 383.6 A Iz = 609.0 A
Iz = 829.9 A Iz = 829.9 A Iz = 829.9 A du = 0.21
dV = 1.63 % dV = 1.26 % dV = 1.47 % L = 20 m
L = 142 m L = 110 m L = 128 m
L    
-L1 -L3 -L2 -C1
FP-502-RZ2-001 FP-501-RZ2-002 FP-502-RZ2-003 Sn = 342.00 kVA
Sn = 265.80 [kVA] Sn = 265.80 [kVA] Sn = 265.80 [kVA] Q = 352.33 kvar
Cosphi (nominal) = 0.90 Cosphi (nominal) = 0.90 Cosphi (nominal) = 0.90 IB = 493.6 A
In = 383.6 [A] In = 383.6 [A] In = 383.6 [A]
U = 404.9 [V] U = 406.3 [V] U = 405.5 [V]
M dU = 0.00 % dU = 0.00 % dU = 0.00 %
P = 242.12 [kW] P = 243.00 [kW] P = 242.51 [kW]
Q = 117.27 [kvar] Q = 117.69 [kvar] Q = 117.45 [kvar]

T
Rev. n°1 Date: 11/10/2021 Description Customer: AL FAYHAA Construction & Contracting Drawing number:
Rev. n°2 Drafter: IP-EV13-MDB-2 Project: Coastal Village (COV) infrastructure package
Rev. n°3 Design.: Engr. Abuzer Banderkar File: Sheet: Next sheet: Sheets:
REVISIONS Date: Signatures Approval: Serial: 1 1
Distribution

Reference voltage [V] 33000 Symmetrical short circuit current LLL [kA] 17.50
Phases LLL Line-Neutral short circuit current LN [kA]
Distribution system IT Line-Ground short circuit current LPE [kA]

Active power P [kW] 595.21 Cmax 1.10


Reactive power Q [kvar] 28.93 Resistance at Reference voltage [mOhm] 239.580
Ib (A) [A] 10.43 Reactance at Reference voltage [mOhm] 2383.791
Power factor Cosphi 1.00 Impedance at Reference voltage [mOhm] 2395.800

Rev. n°1 Date: 11/10/2021 Description Customer: AL FAYHAA Construction & Contracting Drawing number:
Rev. n°2 Drafter: IP-EV13-MDB-2 Project: Coastal Village (COV) infrastructure package
Rev. n°3 Design.: Engr. Abuzer Banderkar File: Sheet: Next sheet: Sheets:
REVISIONS Date: Signatures Approval: Serial: 1 1
Transformers

-TM1 OIL Distr.Transf. MV-LV 33000/400V 1500kVA TR-1

Rated power [kVA] 1000 Winding Delta Star


Short-circuit voltage Usc [%] 6 Rated voltage Un [V] 33000 400
Losses [%] 1.20 No-load rated voltage [V] 415
Voltage regulator plug [%] 0.0
Cmax 1.10 Phases LLL LLLN
KT 1.009396 Distribution system IT TN-S
Resistance RT [mOhm] 13068.000 1.920
Reactance XT [mOhm] 64019.864 9.406
Impedance ZT [mOhm] 65340.000 9.600
Impedance Z x KT [mOhm] 65953.930 9.690

Rated power [kVA] Winding


Short-circuit voltage Usc [%] Rated voltage Un [V]
Losses [%] No-load rated voltage [V]
Voltage regulator plug [%]
Cmax Phases
KT Distribution system
Resistance RT [mOhm]
Reactance XT [mOhm]
Impedance ZT [mOhm]
Impedance Z x KT [mOhm]

Rated power [kVA] Winding


Short-circuit voltage Usc [%] Rated voltage Un [V]
Losses [%] No-load rated voltage [V]
Voltage regulator plug [%]
Cmax Phases
KT Distribution system
Resistance RT [mOhm]
Reactance XT [mOhm]
Impedance ZT [mOhm]
Impedance Z x KT [mOhm]

Rev. n°1 Date: 11/10/2021 Description Customer: AL FAYHAA Construction & Contracting Drawing number:
Rev. n°2 Drafter: IP-EV13-MDB-2 Project: Coastal Village (COV) infrastructure package
Rev. n°3 Design.: Engr. Abuzer Banderkar File: Sheet: Next sheet: Sheets:
REVISIONS Date: Signatures Approval: Serial: 1 1
Short circuit calculation

Switchboard Ib LLL (kA) Ip LLL (kA) Ib LL (kA) Ip LL (kA) Ib LN (kA) Ip LN (kA) Ib LPE (kA) Ip LPE (kA)
IP-EV13-MDB-2 23.15 51.16 20.04 44.30 21.48 47.47 21.42 47.35

Rev. n°1 Date: 11/10/2021 Description Customer: AL FAYHAA Construction & Contracting Drawing number:
Rev. n°2 Drafter: IP-EV13-MDB-2 Project: Coastal Village (COV) infrastructure package
Rev. n°3 Design.: Engr. Abuzer Banderkar File: Sheet: Next sheet: Sheets:
REVISIONS Date: Signatures Approval: Serial: 1 1
Protection of Lv Cables

-WC1 TR-1
Phases - Distribution System LLLN / TN-S Overload: protected by -QF1 E1.2N 1600 Ekip Touch LSIG 1600
Load data

Voltage [V] 400


IB (A) [A] 1443.4
1 Short circuit at terminal 1 (current flowing downstream): protected by

Protection checks
Cosphi 1.00
Cable cross-sections 12x(1x630)+2G630
Conductor - Insulator Cu / EPR/XLPE Indirect touch at terminal 2 (current flowing downstream): protected by
Length (m) [m] 30 2
Cable

Iz (A) [A] 2452.8


1 Short circuit at terminal 2 (current flowing upstream): protected by
dU (%) 0.16
Work Temp (°C) [°C] 63.9
Power loss [W] 2158.40 Indirect touch at terminal 1 (current flowing upstream): protected by
K²S² [A2s] 8101917208 2

-WC2 FP-502-RZ2-001
Phases - Distribution System LLLN / TN-S Overload: protected by -QF2 T6S 630 PR221DS-LS/I 630A
Load data

Passed
Voltage [V] 400 IB (383.65[A]) <= Ith (554.40[A]) <= Iz (829.92[A]) and If (720.72[A]) <= 1.45*Iz (1203.38[A]); Uref=400V
IB (A) [A] 383.6
1 Short circuit at terminal 1 (current flowing downstream): protected by -QF2 T6S 630 PR221DS-LS/I 630A
Cosphi 0.88 Protection checks Passed
Protection guaranteed up to Ik LLL (23.15[kA]), Ik LN (21.48[kA]), Ik L-PE (21.42[kA]); Uref=400V
Cable cross-sections 2x 5G185
Conductor - Insulator Cu / EPR/XLPE Indirect touch at terminal 2 (current flowing downstream): protected by -QF2 T6S 630 PR221DS-LS/I 630A
Passed
Length (m) [m] 142 2 I@Max tripping time ( 1.04[kA])<=Ikmin L-PE ( 3.81[kA]); Trip time=5.00[s]; Uref=400V
Cable

Iz (A) [A] 829.9


1 Short circuit at terminal 2 (current flowing upstream): protected by
dU (%) 1.63
Work Temp (°C) [°C] 42.8
Power loss [W] 3423.12 Indirect touch at terminal 1 (current flowing upstream): protected by
K²S² [A2s] 698634710 2

-WC3 FP-502-RZ2-003
Phases - Distribution System LLLN / TN-S Overload: protected by -QF4 T6S 630 PR221DS-LS/I 630A
Load data

Passed
Voltage [V] 400 IB (383.65[A]) <= Ith (403.20[A]) <= Iz (829.92[A]) and If (524.16[A]) <= 1.45*Iz (1203.38[A]); Uref=400V
IB (A) [A] 383.6
1 Short circuit at terminal 1 (current flowing downstream): protected by -QF4 T6S 630 PR221DS-LS/I 630A
Protection checks

Cosphi 0.88 Passed


Protection guaranteed up to Ik LLL (23.15[kA]), Ik LN (21.48[kA]), Ik L-PE (21.42[kA]); Uref=400V
Cable cross-sections 2x 5G185
Conductor - Insulator Cu / EPR/XLPE Indirect touch at terminal 2 (current flowing downstream): protected by -QF4 T6S 630 PR221DS-LS/I 630A
Passed
Length (m) [m] 128 2 I@Max tripping time ( 2.05[kA])<=Ikmin L-PE ( 4.14[kA]); Trip time=5.00[s]; Uref=400V
Cable

Iz (A) [A] 829.9


1 Short circuit at terminal 2 (current flowing upstream): protected by
dU (%) 1.47
Work Temp (°C) [°C] 42.8
Power loss [W] 3085.63 Indirect touch at terminal 1 (current flowing upstream): protected by
K²S² [A2s] 698634710 2

Rev. n°1 Date: 11/10/2021 Description Customer: AL FAYHAA Construction & Contracting Drawing number:
Rev. n°2 Drafter: IP-EV13-MDB-2 Project: Coastal Village (COV) infrastructure package
Rev. n°3 Design.: Engr. Abuzer Banderkar File: Sheet: Next sheet: Sheets:
REVISIONS Date: Signatures Approval: Serial: 1 2 2
Protection of Lv Cables

-WC4
Phases - Distribution System LLL / TN-S Overload: protected by -QF5 E1.2C 800 Ekip Touch LI 800
Load data

Passed
Voltage [V] 400 IB (493.63[A]) <= Ith (528.80[A]) <= Iz (608.96[A]) and If (687.44[A]) <= 1.45*Iz (882.99[A]); Uref=400V
IB (A) [A] 705.9
1 Short circuit at terminal 1 (current flowing downstream): protected by -QF5 E1.2C 800 Ekip Touch LI 800

Protection checks
Cosphi 0.04 Passed
Protection guaranteed up to Ik LLL (23.15[kA]), Ik L-PE (21.42[kA]); Uref=400V
Cable cross-sections 2x 4G120/70
Conductor - Insulator Cu / EPR/XLPE Indirect touch at terminal 2 (current flowing downstream): protected by -QF5 E1.2C 800 Ekip Touch LI 800
Passed
Length (m) [m] 20 2 I@Max tripping time ( 1.32[kA])<=Ikmin L-PE (11.48[kA]); Trip time=5.00[s]; Uref=400V
Cable

Iz (A) [A] 609.0


1 Short circuit at terminal 2 (current flowing upstream): protected by
dU (%) 0.21
Work Temp (°C) [°C] 110.6
Power loss [W] 3141.69 Indirect touch at terminal 1 (current flowing upstream): protected by
K²S² [A2s] 293947110 2

-WC5 FP-501-RZ2-002
Phases - Distribution System LLLN / TN-S Overload: protected by -QF3 T6S 630 PR221DS-LS/I 630A
Load data

Passed
Voltage [V] 400 IB (383.65[A]) <= Ith (403.20[A]) <= Iz (829.92[A]) and If (524.16[A]) <= 1.45*Iz (1203.38[A]); Uref=400V
IB (A) [A] 383.6
1 Short circuit at terminal 1 (current flowing downstream): protected by -QF3 T6S 630 PR221DS-LS/I 630A
Cosphi 0.88 Protection checks Passed
Protection guaranteed up to Ik LLL (23.15[kA]), Ik LN (21.48[kA]), Ik L-PE (21.42[kA]); Uref=400V
Cable cross-sections 2x 5G185
Conductor - Insulator Cu / EPR/XLPE Indirect touch at terminal 2 (current flowing downstream): protected by -QF3 T6S 630 PR221DS-LS/I 630A
Passed
Length (m) [m] 110 2 I@Max tripping time ( 2.05[kA])<=Ikmin L-PE ( 4.67[kA]); Trip time=5.00[s]; Uref=400V
Cable

Iz (A) [A] 829.9


1 Short circuit at terminal 2 (current flowing upstream): protected by
dU (%) 1.26
Work Temp (°C) [°C] 42.8
Power loss [W] 2651.71 Indirect touch at terminal 1 (current flowing upstream): protected by
K²S² [A2s] 698634710 2

Phases - Distribution System Overload: protected by


Load data

Voltage [V]
IB (A) [A]
1 Short circuit at terminal 1 (current flowing downstream): protected by
Protection checks

Cosphi
Cable cross-sections
Conductor - Insulator Indirect touch at terminal 2 (current flowing downstream): protected by
Length (m) [m] 2
Cable

Iz (A) [A]
1 Short circuit at terminal 2 (current flowing upstream): protected by
dU (%)
Work Temp (°C) [°C]
Power loss [W] Indirect touch at terminal 1 (current flowing upstream): protected by
K²S² [A2s] 2

Rev. n°1 Date: 11/10/2021 Description Customer: AL FAYHAA Construction & Contracting Drawing number:
Rev. n°2 Drafter: IP-EV13-MDB-2 Project: Coastal Village (COV) infrastructure package
Rev. n°3 Design.: Engr. Abuzer Banderkar File: Sheet: Next sheet: Sheets:
REVISIONS Date: Signatures Approval: Serial: 2 2
List of LV devices

Sign Part code Type RCD code RCD type User description 1 User description 2
-QF1 1SDA071516R1 E1.2N 1600 Ekip Touch LSIG 1600 TR-1
-QF2 1SDA060236R1 T6S 630 PR221DS-LS/I 630A FP-502-RZ2-001
-QF3 1SDA060236R1 T6S 630 PR221DS-LS/I 630A FP-501-RZ2-002
-QF4 1SDA060236R1 T6S 630 PR221DS-LS/I 630A FP-502-RZ2-003
-QF5 1SDA070754R1 E1.2C 800 Ekip Touch LI 800

Rev. n°1 Date: 11/10/2021 Description Customer: AL FAYHAA Construction & Contracting Drawing number:
Rev. n°2 Drafter: IP-EV13-MDB-2 Project: Coastal Village (COV) infrastructure package
Rev. n°3 Design.: Engr. Abuzer Banderkar File: Sheet: Next sheet: Sheets:
REVISIONS Date: Signatures Approval: Serial: 1 1
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

A
Report of LV circuit breakers

Circuit Breaker Thermomagnetic Electronic RCB device

B Sign Enclosure Poles In (A) Icu-Icn (kA) Ics (kA) Thermal (A) L I1 S I2 S2 I2-2 I G I4 R I5 InN/In (%) Id (A) Td (s)

Type User description 1 Magnetic (A) Curve L t1 Curve S t2 Curve S2 t2-2 I3 Curve G t4 t5 RCB type

C -QF1 IP-EV13-MDB-2
4P 1600 66.0 66.0 On 0.90 On 1.70 Off Off (null)

E1.2N 1600 Ekip Touch LSIG 1600 TR-1 IEC60947-2 52s t const. 0.11s 15.00 I2t const.

D -QF2 IP-EV13-MDB-2
3P 630 50.0 0.0 On 0.88 Off On (null)

T6S 630 PR221DS-LS/I 630A FP-502-RZ2-001 3s 1.50

E -QF3 IP-EV13-MDB-2
3P 630 50.0 0.0 On 0.64 Off On (null)

T6S 630 PR221DS-LS/I 630A FP-501-RZ2-002 3s 4.50

F -QF4 IP-EV13-MDB-2
3P 630 50.0 0.0 On 0.64 Off On (null)

T6S 630 PR221DS-LS/I 630A FP-502-RZ2-003 3s 4.50

G -QF5 IP-EV13-MDB-2
3P 800 50.0 0.0 On 0.66 On (null)

E1.2C 800 Ekip Touch LI 800 IEC60947-2 3s 1.50

Rev. n°1 Date: 11/10/2021 Description Customer: AL FAYHAA Construction & Contracting Drawing number:
N Rev. n°2 Drafter: IP-EV13-MDB-2 Project: Coastal Village (COV) infrastructure package
Rev. n°3 Design.: Engr. Abuzer Banderkar File: Sheet: Next sheet: Sheets:
REVISIONS Date: Signatures Approval: Serial: 1 1
List of Lv Cables

-WC1 TR-1
Phases - Distribution System LLLN / TN-S IB L1 [A] 829.0 R Ph 20°C [mOhm] 0.29
Voltage [V] 400 IB L2 [A] 829.0 R Ph 160-250°C [mOhm] 0.56
Cable cross-sections 12x(1x630)+2G630 IB L3 [A] 829.0 X Ph [mOhm] 1.85
Conductor - Insulator Cu / EPR/XLPE IB N [A] 0.0 R N 20°C [mOhm] 0.29
Method 31 Cosphi 1.00 R N 160-250°C [mOhm] 0.56
K factor 0.71 Iz (A) [A] 2452.8 XN [mOhm] 1.85
Length (m) [m] 30 dU (%) [%] 0.16 R PE 20°C [mOhm] 0.44
Ib max (kA) [kA] 25.59 Power Loss (W) [W] 2158.4 R PE 160-250°C [mOhm] 0.85
Ib min (kA) [kA] Work Temp (°C) [°C] 63.9 X PE [mOhm] 2.77

-WC2 FP-502-RZ2-001
Phases - Distribution System LLLN / TN-S IB L1 [A] 383.6 R Ph 20°C [mOhm] 7.10
Voltage [V] 400 IB L2 [A] 383.6 R Ph 160-250°C [mOhm] 13.64
Cable cross-sections 2x 5G185 IB L3 [A] 383.6 X Ph [mOhm] 6.30
Conductor - Insulator Cu / EPR/XLPE IB N [A] 0.0 R N 20°C [mOhm] 7.10
Method 31 Cosphi 0.88 R N 160-250°C [mOhm] 13.64
K factor 0.91 Iz (A) [A] 829.9 XN [mOhm] 6.30
Length (m) [m] 142 dU (%) [%] 1.63 R PE 20°C [mOhm] 14.21
Ib max (kA) [kA] 23.15 Power Loss (W) [W] 3423.1 R PE 160-250°C [mOhm] 27.28
Ib min (kA) [kA] 3.81 Work Temp (°C) [°C] 42.8 X PE [mOhm] 12.61

-WC3 FP-502-RZ2-003
Phases - Distribution System LLLN / TN-S IB L1 [A] 383.6 R Ph 20°C [mOhm] 6.40
Voltage [V] 400 IB L2 [A] 383.6 R Ph 160-250°C [mOhm] 12.29
Cable cross-sections 2x 5G185 IB L3 [A] 383.6 X Ph [mOhm] 5.68
Conductor - Insulator Cu / EPR/XLPE IB N [A] 0.0 R N 20°C [mOhm] 6.40
Method 31 Cosphi 0.88 R N 160-250°C [mOhm] 12.29
K factor 0.91 Iz (A) [A] 829.9 XN [mOhm] 5.68
Length (m) [m] 128 dU (%) [%] 1.47 R PE 20°C [mOhm] 12.81
Ib max (kA) [kA] 23.15 Power Loss (W) [W] 3085.6 R PE 160-250°C [mOhm] 24.59
Ib min (kA) [kA] 4.14 Work Temp (°C) [°C] 42.8 X PE [mOhm] 11.37

-WC4
Phases - Distribution System LLL / TN-S IB L1 [A] 493.6 R Ph 20°C [mOhm] 1.54
Voltage [V] 400 IB L2 [A] 493.6 R Ph 160-250°C [mOhm] 2.96
Cable cross-sections 2x 4G120/70 IB L3 [A] 493.6 X Ph [mOhm] 0.89
Conductor - Insulator Cu / EPR/XLPE IB N [A] R N 20°C [mOhm]
Method 31 Cosphi 0.04 R N 160-250°C [mOhm]
K factor 0.88 Iz (A) [A] 609.0 XN [mOhm]
Length (m) [m] 20 dU (%) [%] 0.21 R PE 20°C [mOhm] 2.64
Ib max (kA) [kA] 23.15 Power Loss (W) [W] 3141.7 R PE 160-250°C [mOhm] 5.08
Ib min (kA) [kA] 11.48 Work Temp (°C) [°C] 110.6 X PE [mOhm] 0.91

Rev. n°1 Date: 11/10/2021 Description Customer: AL FAYHAA Construction & Contracting Drawing number:
Rev. n°2 Drafter: IP-EV13-MDB-2 Project: Coastal Village (COV) infrastructure package
Rev. n°3 Design.: Engr. Abuzer Banderkar File: Sheet: Next sheet: Sheets:
REVISIONS Date: Signatures Approval: Serial: 1 2 2
List of Lv Cables

-WC5 FP-501-RZ2-002
Phases - Distribution System LLLN / TN-S IB L1 [A] 383.6 R Ph 20°C [mOhm] 5.50
Voltage [V] 400 IB L2 [A] 383.6 R Ph 160-250°C [mOhm] 10.57
Cable cross-sections 2x 5G185 IB L3 [A] 383.6 X Ph [mOhm] 4.88
Conductor - Insulator Cu / EPR/XLPE IB N [A] 0.0 R N 20°C [mOhm] 5.50
Method 31 Cosphi 0.88 R N 160-250°C [mOhm] 10.57
K factor 0.91 Iz (A) [A] 829.9 XN [mOhm] 4.88
Length (m) [m] 110 dU (%) [%] 1.26 R PE 20°C [mOhm] 11.01
Ib max (kA) [kA] 23.15 Power Loss (W) [W] 2651.7 R PE 160-250°C [mOhm] 21.13
Ib min (kA) [kA] 4.67 Work Temp (°C) [°C] 42.8 X PE [mOhm] 9.77

Phases - Distribution System IB L1 [A] R Ph 20°C [mOhm]


Voltage [V] IB L2 [A] R Ph 160-250°C [mOhm]
Cable cross-sections IB L3 [A] X Ph [mOhm]
Conductor - Insulator IB N [A] R N 20°C [mOhm]
Method Cosphi R N 160-250°C [mOhm]
K factor Iz (A) [A] XN [mOhm]
Length (m) [m] dU (%) [%] R PE 20°C [mOhm]
Ib max (kA) [kA] Power Loss (W) [W] R PE 160-250°C [mOhm]
Ib min (kA) [kA] Work Temp (°C) [°C] X PE [mOhm]

Phases - Distribution System IB L1 [A] R Ph 20°C [mOhm]


Voltage [V] IB L2 [A] R Ph 160-250°C [mOhm]
Cable cross-sections IB L3 [A] X Ph [mOhm]
Conductor - Insulator IB N [A] R N 20°C [mOhm]
Method Cosphi R N 160-250°C [mOhm]
K factor Iz (A) [A] XN [mOhm]
Length (m) [m] dU (%) [%] R PE 20°C [mOhm]
Ib max (kA) [kA] Power Loss (W) [W] R PE 160-250°C [mOhm]
Ib min (kA) [kA] Work Temp (°C) [°C] X PE [mOhm]

Phases - Distribution System IB L1 [A] R Ph 20°C [mOhm]


Voltage [V] IB L2 [A] R Ph 160-250°C [mOhm]
Cable cross-sections IB L3 [A] X Ph [mOhm]
Conductor - Insulator IB N [A] R N 20°C [mOhm]
Method Cosphi R N 160-250°C [mOhm]
K factor Iz (A) [A] XN [mOhm]
Length (m) [m] dU (%) [%] R PE 20°C [mOhm]
Ib max (kA) [kA] Power Loss (W) [W] R PE 160-250°C [mOhm]
Ib min (kA) [kA] Work Temp (°C) [°C] X PE [mOhm]

Rev. n°1 Date: 11/10/2021 Description Customer: AL FAYHAA Construction & Contracting Drawing number:
Rev. n°2 Drafter: IP-EV13-MDB-2 Project: Coastal Village (COV) infrastructure package
Rev. n°3 Design.: Engr. Abuzer Banderkar File: Sheet: Next sheet: Sheets:
REVISIONS Date: Signatures Approval: Serial: 2 2
Discrimination

Upstream device Downstream device

Sign Model User description 1 Sign Model User description 1 Check

Guaranteed up to 50.00[kA] >= requested value (23.15[kA]); Uref=400V


-QF1 E1.2N 1600 Ekip Touch LSIG 1600 TR-1 -QF2 T6S 630 PR221DS-LS/I 630A FP-502-RZ2-001 Passed

Guaranteed up to 50.00[kA] >= requested value (23.15[kA]); Uref=400V


-QF1 E1.2N 1600 Ekip Touch LSIG 1600 TR-1 -QF3 T6S 630 PR221DS-LS/I 630A FP-501-RZ2-002 Passed

Guaranteed up to 50.00[kA] >= requested value (23.15[kA]); Uref=400V


-QF1 E1.2N 1600 Ekip Touch LSIG 1600 TR-1 -QF4 T6S 630 PR221DS-LS/I 630A FP-502-RZ2-003 Passed

Guaranteed up to 50.00[kA] >= requested value (23.15[kA]); Uref=400V


-QF1 E1.2N 1600 Ekip Touch LSIG 1600 TR-1 -QF5 E1.2C 800 Ekip Touch LI 800 Passed

Rev. n°1 Date: 11/10/2021 Description Customer: AL FAYHAA Construction & Contracting Drawing number:
Rev. n°2 Drafter: IP-EV13-MDB-2 Project: Coastal Village (COV) infrastructure package
Rev. n°3 Design.: Engr. Abuzer Banderkar File: Sheet: Next sheet: Sheets:
REVISIONS Date: Signatures Approval: Serial: 1 1
List of Loads

-L1 FP-502-RZ2-001
Phases - Distribution System LLLN / TN-S Utilization factor [%] 100 Computed voltage [V] 404.9
Rated voltage [V] 400 Active power P [kW] 242.12 Max allowed voltage drop by Standard [%] 4.0
IB [A] 383.6 Reactive power Q [kvar] 117.27 Max allowed voltage drop by user [%] 4.0
Cosphi 0.90 Computed voltage drop [%] 0.00

-L2 FP-502-RZ2-003
Phases - Distribution System LLLN / TN-S Utilization factor [%] 100 Computed voltage [V] 405.5
Rated voltage [V] 400 Active power P [kW] 242.51 Max allowed voltage drop by Standard [%] 4.0
IB [A] 383.6 Reactive power Q [kvar] 117.45 Max allowed voltage drop by user [%] 4.0
Cosphi 0.90 Computed voltage drop [%] 0.00

-L3 FP-501-RZ2-002
Phases - Distribution System LLLN / TN-S Utilization factor [%] 100 Computed voltage [V] 406.3
Rated voltage [V] 400 Active power P [kW] 243.00 Max allowed voltage drop by Standard [%] 4.0
IB [A] 383.6 Reactive power Q [kvar] 117.69 Max allowed voltage drop by user [%] 4.0
Cosphi 0.90 Computed voltage drop [%] 0.00

Phases - Distribution System Utilization factor [%] Computed voltage [V]


Rated voltage [V] Active power P [kW] Max allowed voltage drop by Standard [%] 4.0
IB [A] Reactive power Q [kvar] Max allowed voltage drop by user [%]
Cosphi Computed voltage drop [%]

Phases - Distribution System Utilization factor [%] Computed voltage [V]


Rated voltage [V] Active power P [kW] Max allowed voltage drop by Standard [%] 4.0
IB [A] Reactive power Q [kvar] Max allowed voltage drop by user [%]
Cosphi Computed voltage drop [%]

Phases - Distribution System Utilization factor [%] Computed voltage [V]


Rated voltage [V] Active power P [kW] Max allowed voltage drop by Standard [%] 4.0
IB [A] Reactive power Q [kvar] Max allowed voltage drop by user [%]
Cosphi Computed voltage drop [%]

Phases - Distribution System Utilization factor [%] Computed voltage [V]


Rated voltage [V] Active power P [kW] Max allowed voltage drop by Standard [%] 4.0
IB [A] Reactive power Q [kvar] Max allowed voltage drop by user [%]
Cosphi Computed voltage drop [%]

Rev. n°1 Date: 11/10/2021 Description Customer: AL FAYHAA Construction & Contracting Drawing number:
Rev. n°2 Drafter: IP-EV13-MDB-2 Project: Coastal Village (COV) infrastructure package
Rev. n°3 Design.: Engr. Abuzer Banderkar File: Sheet: Next sheet: Sheets:
REVISIONS Date: Signatures Approval: Serial: 1 1