3AH3 Vacuum Circuit-Breakers

Medium-Voltage Equipment
Selection and Ordering Data

Catalog HG 11.03 · 2010

Answers for energy.


3AH3 Vacuum Circuit-Breakers

R-HG11-172.tif

2 Siemens HG 11.03 · 2010


3AH3 Vacuum Circuit-Breakers Contents

Contents Page

3AH3 Vacuum Description 5


Circuit-Breakers General
Construction and mode of operation, standards,
6
1
maintenance-free design 7
Medium-Voltage Equipment Ambient conditions, current carrying capacity
Catalog HG 11.03 · 2010 and dielectric strength 9
Product range overview and basic equipment 10
Invalid: Catalog HG 11.03 · 2008

Equipment Selection 11
Ordering data and configuration example
Selection of basic types, circuit-breakers
12
13
2
Selection of secondary equipment 17
Selection of additional equipment 24
Accessories and spare parts 25

Technical Data 27
Electrical data, dimensions and weights
Circuit diagrams
28
42
3
Operating times, short-circuit protection
of motors, consumption data of releases 44

Annex 45
Inquiry form
Configuration instructions
46
47 4
Configuration aid Foldout page

Siemens HG 11.03 · 2010 3


3AH3 Vacuum Circuit-Breakers

R-HG11-173.tif

4 Siemens HG 11.03 · 2010


3AH3 Vacuum Circuit-Breakers Description
Contents

Contents Page

Description 5
General 6 1
Construction and mode of operation:
Switching medium 7
Pole assemblies 7
Operating mechanism box 7
Operating mechanism 7
Trip-free mechanism 7
Releases 8
Closing 8
Circuit-breaker tripping signal 8
Interlocking 8
Standards 8
R-HG11-174.tif

Maintenance-free design 8
Industrial application: Refinery Ambient conditions 9
Current carrying capacity 9
Dielectric strength 9
Product range overview 10
Basic equipment 10

Siemens HG 11.03 · 2010 5


Description 3AH3 Vacuum Circuit-Breakers
General

3AH3 vacuum circuit-breaker from 7.2 kV to 36 kV – The Powerful

Circuit-breakers must make and break all currents within controlling all fault conditions in the power system at the

1 the scope of their ratings: From small inductive and


capacitive load currents up to high short-circuit currents,
same time.

3AH3 – maintenance-free for high switching capacities

R-HG11-216.tif
R-HG11-204.tif

The 3AH3 vacuum circuit-breaker is maintenance-free Due to its high capacity, the circuit-breaker is especially
throughout its entire service life. It is extremely powerful suitable for generator operation and industrial applications.
and controls up to 10,000 operating cycles. This circuit- The high-current and generator circuit-breakers 3AH37 and
breaker is used for high load currents up to 6300 A and high 3AH38 meet the requirements of IEEE Std C37.013.
short-circuit currents up to 72 kA. It covers the common
medium-voltage range from 7.2 kV to 36 kV.

6 Siemens HG 11.03 · 2010


3AH3 Vacuum Circuit-Breakers Description
Construction and mode of operation

The vacuum circuit-breaker consists of the pole assemblies


(1) and the operating mechanism box (2). The pole assem-
blies are fixed to the operating mechanism box via post
insulators (3). The switching movement is transferred by
means of operating rods (4) and levers.
Switching medium
The vacuum switching technology, proven and fully
1
developed for more than 30 years, serves as arc-quenching
principle by using vacuum interrupters.

Pole assemblies
The pole assemblies consist of the vacuum interrupters (6)
and the interrupter supports. The vacuum interrupters are
Circuit-breaker structure
air-insulated and freely accessible. This makes it possible to
clean the insulating parts easily in adverse ambient condi- 1 Pole assembly

tions. The vacuum interrupter is mounted rigidly to the upper 2 Operating mechanism box
3 Post insulator
interrupter support (5). The lower part of the interrupter is
4 Operating rod
guided in the lower interrupter support (7), allowing axial
5 Upper interrupter support
movement. The braces absorb the external forces resulting
6 Vacuum interrupter
from switching operations and the contact pressure. 7 Lower interrupter support

Operating mechanism box


The whole operating mechanism with releases, auxiliary
switches, indicators and actuating devices is accommodated
in the operating mechanism box. The extent of the second-
ary equipment depends on the case of application and offers
a multiple variety of options in order to meet almost every
requirement.
Operating mechanism
The operating mechanism is a stored-energy mechanism.
The closing spring is charged either electrically or manually.
It latches tight at the end of the charging process and serves
as an energy store. The force is transmitted from the operat-
R-HG11-191.tif

ing mechanism to the pole assemblies via operating rods.


To close the breaker, the closing spring can be unlatched
either mechanically by means of the local “ON” pushbutton Front view
or electrically by remote control. The closing spring charges
the opening or contact pressure springs as the breaker
closes. The now discharged closing spring will be charged
again automatically by the mechanism motor or manually.
Then the operating sequence OPEN-CLOSE-OPEN is stored
in the springs. The charging state of the closing spring can
be checked electrically by means of a position switch.

Trip-free mechanism
3AH3 vacuum circuit-breakers have a trip-free mechanism
according to IEC 62271-100. In the event of an opening
command being given after a closing operation has been
initiated, the moving contacts return to the open position
and remain there even if the closing command is sustained.
R-HG11-192.tif

This means that the contacts of the vacuum circuit-breakers


are momentarily in the closed position, which is permissible
according to IEC 62271-100.
Open operating mechanism box

Siemens HG 11.03 · 2010 7


Description 3AH3 Vacuum Circuit-Breakers
Construction and mode of operation, standards, maintenance-free design

Releases If constant CLOSE and OPEN commands are present at the


A release is a device which transfers electrical commands from circuit-breaker at the same time, the circuit-breaker will return
an external source, such as a control room, to the latching to the open position after closing. It remains in this position
mechanism of the vacuum circuit-breaker so that it can be until a new CLOSE command is given. In this manner,
opened or closed. Apart from the closing solenoid, the continuous closing and opening (= “pumping”) is prevented.

1 maximum possible equipment is one shunt release and two


other releases. For release combinations, refer to page 17.
Circuit-breaker tripping signal
The NO contact makes brief contact while the vacuum
• The closing solenoid unlatches the charged closing spring circuit-breaker is opening, and this is often used to operate
of the vacuum circuit-breaker, closing it by electrical means. a hazard-warning system which, however, is only allowed to
It is suitable for DC or AC voltage. respond to automatic tripping of the circuit-breaker. There-
• Shunt releases are used for automatic tripping of vacuum fore, the signal from the NO contact must be interrupted
circuit-breakers by suitable protection relays and for deliber- when the circuit-breaker is being opened intentionally. This
ate tripping by electrical means. They are intended for con- is accomplished under local control with the cut-out switch
nection to an external power supply (DC or AC voltage) but, that is connected in series with the NO contact.
in special cases, may also be connected to a voltage trans-
Interlocking
former for manual operation.
Electrical interlocking
• Current-transformer operated releases comprise a stored-
energy mechanism, an unlatching mechanism and an electro- The circuit-breakers can be integrated in electromagnetic
magnetic system. They are used when there is no external feeder or switchgear interlocks. In case of electrical inter-
source of auxiliary power (e.g. a battery). Tripping is effected locking, the disconnector or its operating mechanism is
by means of a protection relay (e.g. overcurrent-time protec- equipped with a magnetic lock-out mechanism. This mecha-
tion) acting on the current-transformer operated release. nism is controlled by an auxiliary contact of the circuit-breaker,
When the tripping current is exceeded (= 90 % of the rated so that the disconnector can only be operated when the circuit-
normal current of the c.t.-operated release), the latch of the breaker is open. On the other hand, the circuit-breaker is also
energy store, and thus opening of the circuit-breaker, is controlled by the disconnector or its operating mechanism, so
released. that it can only be closed when the disconnector is in an end
position. For this purpose, manual electrical closing must be pro-
• Undervoltage releases comprise a stored-energy mecha-
vided in the circuit-breaker operating mechanism (see “Closing”).
nism, an unlatching mechanism and an electromagnetic system
which is permanently connected to the secondary or auxiliary Mechanical interlocking
voltage while the vacuum circuit-breaker is closed. If the To interlock circuit-breaker trucks, withdrawable parts or
voltage falls below a predetermined value, unlatching of the disconnectors according to the switch position, the circuit-
release is enabled and the circuit-breaker is opened via the breakers can be equipped with a mechanical interlocking.
stored-energy mechanism. The deliberate tripping of the A sensor at the switchgear checks the position of the circuit-
undervoltage release generally takes place via an NC contact in breaker and prevents the open circuit-breaker in a reliable
the tripping circuit or via an NO contact by short-circuiting the way from being closed mechanically and electrically.
magnet coil. With this type of tripping, the short-circuit current
Standards
is limited by the built-in resistors. Undervoltage releases can
also be connected to voltage transformers. When the operating 3AH3 circuit-breakers conform to the following standards:
voltage drops to impermissibly low levels, the circuit-breaker is • IEC 62271-100 (former IEC 60056)
tripped automatically. • IEC 62271-1 (former IEC 60694)
For delayed tripping, the undervoltage release can be com- • VDE 0671 (former VDE 0670)
bined with energy stores. • IEEE Std C37.013 (only generator circuit-breaker)
All 3AH3 vacuum circuit-breakers fulfil the endurance classes
Closing
E2, M2 and C2 according to IEC 62271-100.
In the standard version, 3AH3 vacuum circuit-breakers can be
remote-closed electrically. They can also be closed locally by Maintenance-free design
mechanical unlatching of the closing spring via pushbutton. The 3AH3 vacuum circuit-breakers are maintenance-free:
Instead of this “manual mechanical closing”, “manual elec- • Under normal ambient conditions according to
trical closing” is also available. In this version, the closing IEC 62271-1 (former IEC 60694)
circuit of the circuit-breaker is controlled electrically by a • Up to 10,000 operating cycles,
pushbutton instead of the mechanical button. In this way, – no relubrication, no readjustment required
switchgear-related interlocks can also be considered for local – and within their tolerances, the characteristics are
operation in order to prevent involuntary closing. independent of the switching rate or of standing times
without switching operations.

8 Siemens HG 11.03 · 2010


3AH3 Vacuum Circuit-Breakers Description
Ambient conditions, current carrying capacity and dielectric strength

Ambient conditions
The vacuum circuit-breakers are designed for the normal
operating conditions defined in IEC 62271-100.
Condensation can occasionally occur under the ambient
conditions shown opposite. 3AH3 vacuum circuit-breakers
are suitable for use in the following climatic classes
according to IEC 60721, Part 3-3:
40°C
1
Climatic ambient conditions: Class 3K4 1)
Biological ambient conditions: Class 3B1 max. 95% per day
max. 90% per month
Mechanical ambient conditions: Class 3M2 -5°C
Chemically-active substances: Class 3C2 2)
Mechanically-active substances: Class 3S2 3)

HG11-2515a_en eps
1) Low temperature limit: – 5 °C
2) Without icing and wind-driven precipitation
3) Restriction: Clean insulation parts

Current carrying capacity


The rated normal currents specified in the opposite diagram
have been defined according to IEC 62271-100 for an am-
7000
bient air temperature of + 40 °C and apply to open switch- A
gear. For enclosed switchgear the data of the switchgear 6000
Rated normal current

manufacturer applies. At ambient air temperatures below


7
+ 40 °C, higher normal currents can be carried (see diagram): 5000
Characteristics curve 1 = Rated normal current 1250 A 6
4000
Characteristics curve 2 = Rated normal current 2000 A
5
Characteristics curve 3 = Rated normal current 2500 A
3000
Characteristics curve 4 = Rated normal current 3150 A 4
Characteristics curve 5 = Rated normal current 4000 A 2000 3
Characteristics curve 6 = Rated normal current 5000 A 2
HG11-2558b_en eps

Characteristics curve 7 = Rated normal current 6300 A 1000 1

Dielectric strength
0
The dielectric strength of air insulation decreases with 10 20 30 40 50 60 °C 70
Ambient air temperature
increasing altitude due to low air density. According to
IEC 62271-1, the values of the rated lightning impulse
withstand voltage and the rated short-duration power-
frequency withstand voltage specified in the chapter
“Technical Data” apply to a site altitude of 1000 m above
sea level. For an altitude above 1000 m, the insulation level 1.50

must be corrected according to the opposite diagram.


Altitude correction factor

The characteristic shown applies to both rated withstand 1.40

voltages.
To select the devices, the following applies: 1.30

U W U0 x Ka
1.20
U Rated withstand voltage under reference atmosphere
U0 Rated withstand voltage requested for the place of installation
Ka Altitude correction factor according to the opposite diagram
HG11-2517c_en eps

1.10
Example
For a requested rated lightning impulse withstand voltage 1.00
1000 1500 2000 2500 3000 3500 m 4000
of 75 kV at an altitude of 2500 m, an insulation level of
Site altitude
90 kV under reference atmosphere is required as a minimum:
90 kV W 75 kV x 1.2

Siemens HG 11.03 · 2010 9


Description 3AH3 Vacuum Circuit-Breakers
Product range overview and basic equipment

Product range overview


circuit breaking

Rated normal current (A)


Rated voltage

Rated short-

1250 2000 2500 3150 4000 5000 6300


current

Pole-centre distance (mm)

1 kV
7.2
kA
50
63
210

275


350 350 210

275


350 210

275


350 275


300 350 300 300

12 50 쐽 쐽 쐽 쐽
63 쐽 쐽 쐽 쐽
15 50 쐽 쐽 쐽 쐽
63 쐽 쐽 쐽 쐽
17.5 50 쐽 쐽 쐽 왖 쐽왖 왖 왖
63 쐽 쐽 쐽왖 쐽왖 왖 왖
72 왖 왖 왖 왖
24 40 쐽
50 쐽 왖 쐽 왖 왖 2) 왖 2)
63 왖 왖 왖 2) 왖 2)
72 왖 왖 왖 2) 왖 2)
36 31.5 쐽 쐽 쐽 쐽 쐽
40 쐽 쐽 쐽
40.5 1) 31.5 쐽 쐽 쐽 쐽 쐽
40 쐽 쐽 쐽

1) As 36 kV circuit-breaker with supplement Y09 쐽 3AH3


2) Pole-centre distance 350 mm 왖 3AH37/3AH38 high-current and generator circuit-breakers (according to IEEE Std C37.013)

Basic equipment

Features Minimum equipment Alternative equipment Remarks

Operating mechanism Electrical operating mecha- Manual operating mechanism Hand crank available
nism (hand crank not includ- (hand crank included in the scope of supply) as accessory
ed in the scope of supply)
Closing Closing solenoid and Manual electrical closing –
manual mechanical closing
1st release Shunt release None –
2nd release Without Shunt release, Max. 3 releases can be combined
undervoltage release, (for possible combinations,
c.t.-operated release refer to page 17)
3rd release Without Shunt release, Max. 3 releases can be combined
undervoltage release, (for possible combinations,
c.t.-operated release refer to page 17)
Varistor circuit Installed for ⱖ 60 V DC None For limiting switching overvoltages
due to inductive loads
Auxiliary switch 6 NO + 6 NC 12 NO + 12 NC –
Plug connector 24-pole terminal strip 24-pole plug, –
64-pole plug
Anti-pumping Available None –
Circuit-breaker Available None –
tripping signal
Operating cycle counter Available None –
“Spring charged” Available None –
signal and indication
Interlocking Without Mechanical interlocking –

10 Siemens HG 11.03 · 2010


3AH3 Vacuum Circuit-Breakers Equipment Selection
Contents

Contents Page

Equipment Selection 11
Ordering data and configuration example 12

Selection of basic types, circuit-breakers:


Voltage level 7.2 kV 13
Voltage level 12 kV 13
Voltage level 15 kV 14
Voltage level 17.5 kV 14
Voltage level 24 kV 15
Voltage level 36 kV 15
2
High-current and generator circuit-breakers
according to IEEE C37.013:
Voltage level 17.5 kV 16
R-HG11-194.eps

Voltage level 24 kV 16

3AH3 vacuum circuit-breaker (4000 A)


Selection of secondary equipment:
Release combination 17
Operating voltage, closing solenoid 18
Operating voltage, 1st shunt release 19
Operating voltage, 2nd release 20
Operating voltage, 3rd release 21
Operating voltage of the operating mechanism 22
Auxiliary switch, secondary connection,
interlocking 23
Languages and frequency 23

Selection of additional equipment 24


Accessories and spare parts 25
R-HG11-217.eps

3AH37 generator circuit-breaker

Siemens HG 11.03 · 2010 11


Equipment Selection 3AH3 Vacuum Circuit-Breakers
Ordering data and configuration example

Order number structure Special versions («)


The 3AH3 vacuum circuit-breakers consist of a primary and a In case of special versions, “-Z” is added to the order number
secondary part. The relevant data make up the 16-digit order and a descriptive order code follows. If several special versions
number. The primary part covers the main electrical data of are required, the suffix “-Z” is listed only once. If a requested
the circuit-breaker poles. The secondary part covers the aux- special version is not in the catalog and can therefore not be
iliary devices which are necessary for operating and control- ordered via order code, it has to be identified with Y 9 9 after
ling the vacuum circuit-breaker. consultation. The agreement hereto is made directly between
Order codes your responsible sales partner and the order processing
department in the Switchgear Factory Berlin.
Individual equipment versions, marked with 9 or Z in the
9th to 16th position, are explained more in detail by a 3-digit
order code. Several order codes can be added to the order
number in succession and in any sequence.

2 Position:
a: alphabetical
1 2 3 4 5
n: numerical
6 7 – 8 9 10 11 12 – 13 14 15 16 Order codes

Order No.: 3 A H 3 n n n – n a a n n – n a a n – « n n n
Primary part
1st position Superior group
Switching devices

2nd position Main group


Circuit-breaker

3rd position Subgroup


Circuit-breaker type series

4th to 8th position Basic equipment


Design and ratings
primary part

Secondary part
9th to 16th position Secondary equipment
Operating mechanism, releases, operating
voltages and further auxiliary equipment

Order codes
Group of 3 after the Order No.
Format: a n a

Special versions («)


Initiated with “-Z”
Group of 3 after the Order No.
Format: a n n

Configuration example
In order to simplify the selection of the correct order number
for the requested circuit-breaker type, you will find a con-
figuration example on each page of the chapter “Equipment
Selection”. For the selection of the secondary part, always the
last example of the primary part was taken over and continued, On the foldout page we offer a configuring aid.
so that at the end of the equipment selection (page 24) a Here you can fill in the order number you have deter-
completely configured circuit-breaker results as an example. mined for your circuit-breaker.

Example for Order No.: 3 A H 3 1 1 7 – 7 n n n n – n n n n


Order codes:

12 Siemens HG 11.03 · 2010


3AH3 Vacuum Circuit-Breakers Equipment Selection
Selection of basic types, circuit-breakers

7.2 kV Position: 1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16 Order codes

50/60 Hz Order No.: 3 A H 3 n n n – n n n n n – n n n n – « n n n


Rated lightning impulse

at 36 % DC component

Rated normal current


Rated short-duration

Pole-centre distance
Rated short-circuit

Rated short-circuit
withstand voltage
withstand voltage

power-frequency

breaking current

making current
Rated voltage

(at 50/60 Hz)

See page 17
See page 18
See page 19
See page 20

See page 21
See page 22
See page 23
See page 23

See page 24
Ur Up Ud Isc Ima Ir

kV kV kV kA kA mm A
7.2 60 20 50 125/130 210 1250 3 A H 3 0 5 7 – 2
2500 3 A H 3 0 5 7 – 6
3150 3 A H 3 0 5 7 – 7
275 4000 1) 3 A H 3 0 7 7 – 8
63 160/164 275 1250 3 A H 3 0 7 8 – 2

2
2500 3 A H 3 0 7 8 – 6
3150 3 A H 3 0 7 8 – 7
4000 1) 3 A H 3 0 7 8 – 8
Special version (available for all 7.2 kV circuit-breakers)
Ud = 32 kV – Z E 1 6

12 kV
50/60 Hz
Ur Up Ud Isc Ima Ir

kV kV kV kA kA mm A
12 75 28 50 125/130 210 1250 3 A H 3 1 1 7 – 2
2500 3 A H 3 1 1 7 – 6
3150 3 A H 3 1 1 7 – 7
275 4000 1) 3 A H 3 1 2 7 – 8
63 160/164 275 1250 3 A H 3 1 2 8 – 2
2500 3 A H 3 1 2 8 – 6
3150 3 A H 3 1 2 8 – 7
4000 1) 3 A H 3 1 2 8 – 8
Special versions (available for all 12 kV circuit-breakers)
Ud = 42 kV – Z E 1 3
Isc = 57.8 kA
Ima = 145 kA (for 3AH3 117-.
circuit-breaker) – Z Y 0 3

1) Higher rated normal currents on request

Configuration example
3AH3 vacuum circuit-breaker 3 A H 3
Rated voltage Ur = 12 kV, 50/60 Hz
Rated lightning impulse withstand voltage Up = 75 kV
Rated short-circuit breaking current Isc = 50 kA
Pole-centre distance = 210 mm
Rated normal current Ir = 1250 A 1 1 7 – 2

Example for Order No.: 3 A H 3 1 1 7 – 2 n n n n – n n n n


Order codes:

Siemens HG 11.03 · 2010 13


Equipment Selection 3AH3 Vacuum Circuit-Breakers
Selection of basic types, circuit-breakers

15 kV Position: 1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16 Order codes

50/60 Hz Order No.: 3 A H 3 n n n – n n n n n – n n n n – « n n n


Rated lightning impulse

at 36 % DC component

Rated normal current


Rated short-duration

Pole-centre distance
Rated short-circuit

Rated short-circuit
withstand voltage
withstand voltage

power-frequency

breaking current

making current
Rated voltage

(at 50/60 Hz)

See page 17
See page 18
See page 19
See page 20

See page 21
See page 22
See page 23
See page 23

See page 24
Ur Up Ud Isc Ima Ir

kV kV kV kA kA mm A
15 95 36 50 125/130 210 1250 3 A H 3 1 6 7 – 2
2500 3 A H 3 1 6 7 – 6
3150 3 A H 3 1 6 7 – 7
275 4000 1) 3 A H 3 1 7 7 – 8
63 160/164 275 1250 3 A H 3 1 7 8 – 2

2
2500 3 A H 3 1 7 8 – 6
3150 3 A H 3 1 7 8 – 7
4000 1) 3 A H 3 1 7 8 – 8
Special version (available for all 15 kV circuit-breakers)
Ud = 42 kV – Z E 1 3

17.5 kV
50/60 Hz
Ur Up Ud Isc Ima Ir

kV kV kV kA kA mm A
17.5 95 38 50 125/130 210 1250 3 A H 3 2 1 7 – 2
2500 3 A H 3 2 1 7 – 6
3150 3 A H 3 2 1 7 – 7
275 4000 1) 3 A H 3 2 2 7 – 8
63 160/164 275 1250 3 A H 3 2 2 8 – 2
2500 3 A H 3 2 2 8 – 6
3150 3 A H 3 2 2 8 – 7
4000 1) 3 A H 3 2 2 8 – 8
Special version (available for all 17.5 kV circuit-breakers)
Ud = 42 kV – Z E 1 3

1) Higher rated normal currents on request

Configuration example
3AH3 vacuum circuit-breaker 3 A H 3
Rated voltage Ur = 17.5 kV, 50/60 Hz
Rated lightning impulse withstand voltage Up = 95 kV
Rated short-circuit breaking current Isc = 63 kA
Pole-centre distance = 275 mm
Rated normal current Ir = 4000 A 2 2 8 – 8

Example for Order No.: 3 A H 3 2 2 8 – 8 n n n n – n n n n


Order codes:

14 Siemens HG 11.03 · 2010


3AH3 Vacuum Circuit-Breakers Equipment Selection
Selection of basic types, circuit-breakers

24 kV Position: 1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16 Order codes

50/60 Hz Order No.: 3 A H 3 n n n – n n n n n – n n n n – « n n n


Rated lightning impulse

at 36 % DC component

Rated normal current


Rated short-duration

Pole-centre distance
Rated short-circuit

Rated short-circuit
withstand voltage
withstand voltage

power-frequency

breaking current

making current
Rated voltage

(at 50/60 Hz)

See page 17
See page 18
See page 19
See page 20

See page 21
See page 22
See page 23
See page 23

See page 24
Ur Up Ud Isc Ima Ir

kV kV kV kA kA mm A
24 125 50 40 100/104 275 2500 3 A H 3 2 6 6 – 6
110 50 50 125/130 275 3150 3 A H 3 2 6 7 – 7
125 50 50 125/130 300 4000 1) 3 A H 3 3 6 7 – 8

36 kV
50/60 Hz
2
Ur Up Ud Isc Ima Ir

kV kV kV kA kA mm A
36 170 70 31.5 80/82 350 1250 3 A H 3 3 0 5 – 2
2000 3 A H 3 3 0 5 – 4
2500 3 A H 3 3 0 5 – 6
3150 3 A H 3 3 0 5 – 7
4000 1) 3 A H 3 3 0 5 – 8
40 100/104 350 2500 3 A H 3 3 0 6 – 6
3150 3 A H 3 3 0 6 – 7
4000 1) 3 A H 3 3 0 6 – 8
Special versions (available for all 36 kV circuit-breakers):
Up = 185 kV (only possible together) – Z E 1 4
and Ud = 85 kV + E 1 5
Up = 195 kV (only possible together) – Z E 2 4
and Ud = 95 kV + E 2 5
Ur = 40.5 kV (only possible together) – Z Y 0 9
Up = 195 kV + E 2 4
Ud = 95 kV + E 2 5
1) Higher rated normal currents on request

Configuration example
3AH3 vacuum circuit-breaker 3 A H 3
Rated voltage Ur = 36 kV, 50/60 Hz
Rated lightning impulse withstand voltage Up = 170 kV
Rated short-circuit breaking current Isc = 40 kA
Pole-centre distance = 350 mm
Rated normal current Ir = 2500 A 3 0 6 – 6

Example for Order No.: 3 A H 3 3 0 6 – 6 n n n n – n n n n


Order codes:

Siemens HG 11.03 · 2010 15


Equipment Selection 3AH3 Vacuum Circuit-Breakers
Selection of basic types, high-current and generator circuit-breakers

17.5 kV Position: 1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16 Order codes

50/60 Hz/generator circuit-breaker acc. to IEEE Std C37.013 Order No.: 3 A H 3 n n n – n n n n n – n n n n – « n n n


Rated lightning impulse

at 36 % DC component

Rated normal current


Rated short-duration

Pole-centre distance
Rated short-circuit

Rated short-circuit
withstand voltage
withstand voltage

power-frequency

breaking current

making current
Rated voltage

(at 50/60 Hz)

See page 17
See page 18
See page 19
See page 20

See page 21
See page 22
See page 23
See page 23

See page 24
Ur Up Ud Isc Ima Ir

kV kV kV kA kA mm A
17.5 110 50 50 137 275 3150 3 A H 3 8 1 7 – 7
4000 3 A H 3 8 1 7 – 8
300 5000 3 A H 3 7 1 2 – 4
6300 1) 3 A H 3 7 1 2 – 5
63 173 275 3150 3 A H 3 8 1 8 – 7

2
4000 3 A H 3 8 1 8 – 8
300 5000 3 A H 3 7 1 3 – 4
6300 1) 3 A H 3 7 1 3 – 5
72 198 275 3150 3 A H 3 8 1 9 – 7 G 1 A
4000 3 A H 3 8 1 9 – 8 G 1 A
300 5000 3 A H 3 7 1 4 – 4
6300 1) 3 A H 3 7 1 4 – 5

24 kV
50/60 Hz/generator circuit-breaker acc. to IEEE Std C37.013
Ur Up Ud Isc Ima Ir

kV kV kV kA kA mm A
24 125 50 50 137 350 3150 3 A H 3 7 2 2 – 2
4000 3 A H 3 7 2 2 – 3
5000 3 A H 3 7 2 2 – 4
6300 1) 3 A H 3 7 2 2 – 5
63 173 350 3150 3 A H 3 7 2 3 – 2
4000 3 A H 3 7 2 3 – 3
5000 3 A H 3 7 2 3 – 4
6300 1) 3 A H 3 7 2 3 – 5
72 198 350 3150 3 A H 3 7 2 4 – 2
4000 3 A H 3 7 2 4 – 3
5000 3 A H 3 7 2 4 – 4
6300 1) 3 A H 3 7 2 4 – 5
1) Higher rated normal currents on request

Configuration example
3AH3 vacuum circuit-breaker 3 A H 3
Rated voltage Ur = 24 kV, 50/60 Hz
Rated lightning impulse withstand voltage Up = 125 kV
Rated short-circuit breaking current Isc = 72 kA
Pole-centre distance = 350 mm
Rated normal current Ir = 6300 A 7 2 4 – 5

Example for Order No.: 3 A H 3 7 2 4 – 5 n n n n – n n n n


Order codes:

16 Siemens HG 11.03 · 2010


3AH3 Vacuum Circuit-Breakers Equipment Selection
Selection of secondary equipment

9th position Position: 1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16 Order codes


Release combination Order No.: 3 A H 3 n n n – n n n n n – n n n n – « n n n
Undervoltage release

C.t.-operated release

C.t.-operated release

C.t.-operated release

C.t.-operated release
with tripping pulse

with tripping pulse


2nd shunt release
1st shunt release

ⱖ 0.1 Ws (20 c)
Closing solenoid

ⱖ 0.1 Ws (10 c)

See page 18
See page 19
See page 20

See page 21
See page 22
See page 23
See page 23

See page 24
0.5 A

1.0 A

n n M
n n n N
n n n N – Z F 1 51)
n n n n T
n n n n P
n n n n P – Z A 4 6
n n n2) Q
n n n R
n
n
n
n
n
n
n
n
n
n
n

n
n

n
S
S
U
U


Z

Z
A

A
4

4
6

6
2
n n n V
n n n V – Z A 4 5
1) With 3rd shunt release, voltage according to 13th position
2) Version with two c.t.-operated releases 0.5 A

Configuration example
3AH3 vacuum circuit-breaker 3 A H 3
(Ur = 36 kV, 50/60 Hz, Up = 170 kV, Isc = 40 kA, Ir = 2500 A,
pole-centre distance = 350 mm) 3 0 6 – 6
Closing solenoid, 1st shunt release, undervoltage release and
c.t.-operated release with a rated normal current of 1 A S – Z A 4 6

Example for Order No.: 3 A H 3 3 0 6 – 6 S n n n – n n n n – Z


Order codes: A 4 6

Siemens HG 11.03 · 2010 17


Equipment Selection 3AH3 Vacuum Circuit-Breakers
Selection of secondary equipment

10th position Position: 1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16 Order codes


Operating voltage of the closing solenoid Order No.: 3 A H 3 n n n – n n n n n – n n n n – « n n n

See page 19
See page 20

See page 21
See page 22
See page 23
See page 23

See page 24
Standard voltages Special voltages

Mechanical closing at the circuit-breaker


24 V DC B
48 V DC C
60 V DC D
110 V DC E
220 V DC F
100 V AC 50/60 Hz 1) H
110 V AC 50/60 Hz 1) J
230 V AC 50/60 Hz 1) K
30 V DC Z With order code K 1 A
32 V DC Z With order code K 1 B
120 V DC Z With order code K 1 C

2 125 V DC
127 V DC
240 V DC
Z
Z
Z
With order code
With order code
With order code
K
K
K
1 D
1 E
1 F
120 V AC 50/60 Hz 1) Z With order code K 1 K
125 V AC 50/60 Hz 1) Z With order code K 1 L
240 V AC 50/60 Hz 1) Z With order code K 1 M
Manual electrical closing at the circuit-breaker
24 V DC M
48 V DC N
60 V DC P
110 V DC Q
220 V DC R
100 V AC 50/60 Hz 1) T
110 V AC 50/60 Hz 1) U
230 V AC 50/60 Hz 1) V
30 V DC Z With order code K 2 A
32 V DC Z With order code K 2 B
120 V DC Z With order code K 2 C
125 V DC Z With order code K 2 D
127 V DC Z With order code K 2 E
240 V DC Z With order code K 2 F
120 V AC 50/60 Hz 1) Z With order code K 2 K
125 V AC 50/60 Hz 1) Z With order code K 2 L
240 V AC 50/60 Hz 1) Z With order code K 2 M
1) The AC frequency 50 or 60 Hz is selected at the 16th position of the
order number together with the language (see page 23)

Configuration example
3AH3 vacuum circuit-breaker 3 A H 3
(Ur = 36 kV, 50/60 Hz, Up = 170 kV, Isc = 40 kA, Ir = 2500 A,
pole-centre distance = 350 mm) 3 0 6 – 6 S
Manual electrical closing at the circuit-breaker,
operating voltage of the closing solenoid 32 V DC Z K 2 B

Example for Order No.: 3 A H 3 3 0 6 – 6 S Z n n – n n n n – Z


Order codes: A 4 6 + K 2 B

18 Siemens HG 11.03 · 2010


3AH3 Vacuum Circuit-Breakers Equipment Selection
Selection of secondary equipment

11th position Position: 1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16 Order codes


Operating voltage of the 1st shunt release Order No.: 3 A H 3 n n n – n n n n n – n n n n – « n n n

See page 20

See page 21
See page 22
See page 23
See page 23

See page 24
Standard voltages Special voltages

24 V DC 1
48 V DC 2
60 V DC 3
110 V DC 4
220 V DC 5
100 V AC 50/60 Hz 1) 6
110 V AC 50/60 Hz 1) 7
230 V AC 50/60 Hz 1) 8
30 V DC 9 With order code L 1 A
32 V DC 9 With order code L 1 B
120 V DC 9 With order code L 1 C
125 V DC 9 With order code L 1 D
127 V DC
240 V DC
120 V AC 50/60 Hz 1)
9
9
9
With order code
With order code
With order code
L
L
L
1 E
1 F
1 K
2
125 V AC 50/60 Hz 1) 9 With order code L 1 L
240 V AC 50/60 Hz 1) 9 With order code L 1 M

1) The AC frequency 50 or 60 Hz is selected at the 16th position of the


order number together with the language (see page 23)

Configuration example
3AH3 vacuum circuit-breaker 3 A H 3
(Ur = 36 kV, 50/60 Hz, Up = 170 kV, Isc = 40 kA, Ir = 2500 A,
pole-centre distance = 350 mm) 3 0 6 – 6 S Z
Operating voltage of the 1st shunt release 48 V DC 2

Example for Order No.: 3 A H 3 3 0 6 – 6 S Z 2 n – n n n n – Z


Order codes: A 4 6 + K 2 B

Siemens HG 11.03 · 2010 19


Equipment Selection 3AH3 Vacuum Circuit-Breakers
Selection of secondary equipment

12th position Position: 1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16 Order codes


Operating voltage of the 2nd release Order No.: 3 A H 3 n n n – n n n n n – n n n n – « n n n
Shunt release, undervoltage release or c.t.-operated release

See page 21
See page 22
See page 23
See page 23

See page 24
Standard voltages Special voltages

Without or c.t.-operated release 0


24 V DC 1
48 V DC 2
60 V DC 3
110 V DC 4
220 V DC 5
100 V AC 50/60 Hz 1) 6
110 V AC 50/60 Hz 1) 7
230 V AC 50/60 Hz 1) 8
30 V DC 9 With order code M 1 A
32 V DC 9 With order code M 1 B

2 120 V DC
125 V DC
127 V DC
9
9
9
With order code
With order code
With order code
M
M
M
1 C
1 D
1 E
240 V DC 9 With order code M 1 F
120 V AC 50/60 Hz 1) 9 With order code M 1 K
125 V AC 50/60 Hz 1) 9 With order code M 1 L
240 V AC 50/60 Hz 1) 9 With order code M 1 M
Special versions
To operate the 2nd release as an undervoltage release on an
energy store type AN 1902- (for DC) or AN 1901-2 (for AC),
both make Bender, the operating voltage must be defined –
and whether the energy store will be provided by the customer
or included in the scope of supply.

Energy store
Type In the scope
of supply
60 V DC AN 1902- no 9 With order code M 2 D
110 V DC AN 1902- no 9 With order code M 2 E
220 V DC AN 1902- no 9 With order code M 2 F
100/110/230 V AC AN 1901-2 no 9 With order code M 2 G
60 V DC AN 1902- yes 9 With order code M 3 D
110 V DC AN 1902- yes 9 With order code M 3 E
220 V DC AN 1902- yes 9 With order code M 3 F
100/110/230 V AC AN 1901-2 yes 9 With order code M 3 G

1) The AC frequency 50 or 60 Hz is selected at the 16th position of the


order number together with the language (see page 23)

Configuration example
3AH3 vacuum circuit-breaker 3 A H 3
(Ur = 36 kV, 50/60 Hz, Up = 170 kV, Isc = 40 kA, Ir = 2500 A,
pole-centre distance = 350 mm) 3 0 6 – 6 S Z 2
2nd release as undervoltage release with operating voltage 32 V DC 9 M 1 B

Example for Order No.: 3 A H 3 3 0 6 – 6 S Z 2 9 – n n n n – Z


Order codes: A 4 6 + K 2 B + M 1 B

20 Siemens HG 11.03 · 2010


3AH3 Vacuum Circuit-Breakers Equipment Selection
Selection of secondary equipment

13th position Position: 1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16 Order codes


Operating voltage of the 3rd release Order No.: 3 A H 3 n n n – n n n n n – n n n n – « n n n
Shunt release, undervoltage release or c.t.-operated release

See page 22
See page 23
See page 23

See page 24
Standard voltages Special voltages

Without or c.t.-operated release 0


24 V DC 1
48 V DC 2
60 V DC 3
110 V DC 4
220 V DC 5
100 V AC 50/60 Hz 1) 6
110 V AC 50/60 Hz 1) 7
230 V AC 50/60 Hz 1) 8
30 V DC 9 With order code N 1 A
32 V DC 9 With order code N 1 B
120 V DC
125 V DC
127 V DC
9
9
9
With order code
With order code
With order code
N
N
N
1 C
1 D
1 E
2
240 V DC 9 With order code N 1 F
120 V AC 50/60 Hz 1) 9 With order code N 1 K
125 V AC 50/60 Hz 1) 9 With order code N 1 L
240 V AC 50/60 Hz 1) 9 With order code N 1 M
Special versions
To operate the 3rd release as an undervoltage release on an
energy store type AN 1902- (for DC) or AN 1901-2 (for AC),
both make Bender, the operating voltage must be defined –
and whether the energy store will be provided by the customer
or included in the scope of supply.

Energy store
Type In the scope
of supply
60 V DC AN 1902- no 9 With order code N 2 D
110 V DC AN 1902- no 9 With order code N 2 E
220 V DC AN 1902- no 9 With order code N 2 F
100/110/230 V AC AN 1901-2 no 9 With order code N 2 G
60 V DC AN 1902- yes 9 With order code N 3 D
110 V DC AN 1902- yes 9 With order code N 3 E
220 V DC AN 1902- yes 9 With order code N 3 F
100/110/230 V AC AN 1901-2 yes 9 With order code N 3 G

1) The AC frequency 50 or 60 Hz is selected at the 16th position of the


order number together with the language (see page 23)

Configuration example
3AH3 vacuum circuit-breaker 3 A H 3
(Ur = 36 kV, 50/60 Hz, Up = 170 kV, Isc = 40 kA, Ir = 2500 A,
pole-centre distance = 350 mm) 3 0 6 – 6 S Z 2 9 –
3rd release as c.t.-operated release 0

Example for Order No.: 3 A H 3 3 0 6 – 6 S Z 2 9 – 0 n n n – Z


Order codes: A 4 6 + K 2 B + M 1 B

Siemens HG 11.03 · 2010 21


Equipment Selection 3AH3 Vacuum Circuit-Breakers
Selection of secondary equipment

14th position Position: 1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16 Order codes


Operating voltage of the operating mechanism Order No.: 3 A H 3 n n n – n n n n n – n n n n – « n n n

See page 23
See page 23

See page 24
Standard voltages Special voltages

Manual operating mechanism (hand crank included in the scope of supply) A


24 V DC B
48 V DC C
60 V DC D
110 V DC E
220 V DC F
100 V AC 50/60 Hz 1) H
110 V AC 50/60 Hz 1) J
230 V AC 50/60 Hz 1) K
30 V DC Z With order code P 1 A
32 V DC Z With order code P 1 B
120 V DC Z With order code P 1 C

2 125 V DC
127 V DC
240 V DC
Z
Z
Z
With order code
With order code
With order code
P
P
P
1 D
1 E
1 F
120 V AC 50/60 Hz 1) Z With order code P 1 K
125 V AC 50/60 Hz 1) Z With order code P 1 L
240 V AC 50/60 Hz 1) Z With order code P 1 M
1) The AC frequency 50 or 60 Hz is selected at the 16th position of the
order number together with the language (see page 23)

Configuration example
3AH3 vacuum circuit-breaker 3 A H 3
(Ur = 36 kV, 50/60 Hz, Up = 170 kV, Isc = 40 kA, Ir = 2500 A,
pole-centre distance = 350 mm) 3 0 6 – 6 S Z 2 9 – 0
Operating voltage of the operating mechanism 230 V AC, 50 Hz K

Example for Order No.: 3 A H 3 3 0 6 – 6 S Z 2 9 – 0 K n n – Z


Order codes: A 4 6 + K 2 B + M 1 B

22 Siemens HG 11.03 · 2010


3AH3 Vacuum Circuit-Breakers Equipment Selection
Selection of secondary equipment

15th position Position: 1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16 Order codes


Auxiliary switch, secondary connection, interlocking Order No.: 3 A H 3 n n n – n n n n n – n n n n – « n n n
Auxiliary switch

Auxiliary switch

terminal strip 2)
12 NO + 12 NC

64-pole plug 1)

24-pole plug 2)
6 NO + 6 NC

See page 24
interlocking
Mechanical

24-pole

n n A
n n E
n n G
n n C
n n M
n n n B
n n n F
n n n H
n n n D
n n n N
Special version
Auxiliary switch 12 NO + 12 NC and 24-pole plug (E or F)
Special versions gold-plated contacts and pins
– Z A 2 6 2
Auxiliary switch 6 NO + 6 NC and 24-pole terminal strip (G or H) – Z A 1 7
Auxiliary switch 12 NO + 12 NC and 24-pole terminal strip (M or N) – Z A 1 8
Auxiliary switch 6 NO + 6 NC and 64-pole plug (A or B) – Z A 2 0
Auxiliary switch 12 NO + 12 NC and 64-pole plug (C or D) – Z A 2 1

1) Depending on the equipment, some connections of the 64-pole plug


connector remain free. These can be connected to free auxiliary switch
contacts by the customer. Prefabricated wires are available as accessories.
2) Auxiliary switch contacts are not wired to the plug/terminal strip and must
therefore be connected directly.

16th position
AC frequency of operating voltages
Languages of operating instructions and rating plate
Language selection Frequency selection
50 Hz and DC

60 Hz and DC
German

Spanish
English

French

50 Hz

60 Hz
DC

n n n n 0
n n n 1
n n n n 2
n n n 3
n n n n 4
n n n 5
n n n n 6
n n n 7
Other languages on request
Special versions
Additional information on the rating plate (only after consultation
with the order processing department at the Switchgear Factory Berlin).
Information in clear text. – Z Y 1 2

Configuration example
3AH3 vacuum circuit-breaker 3 A H 3
(Ur = 36 kV, 50/60 Hz, Up = 170 kV, Isc = 40 kA, Ir = 2500 A,
pole-centre distance = 350 mm) 3 0 6 – 6 S Z 2 9 – 0 K
Auxiliary switch 6 NO + 6 NC, 64-pole plug and with mechanical interlocking B
Auxiliary switch contacts and pins of the plug connector gold-plated – Z A 2 0
Frequency 50 Hz or DC, operating instructions and rating plate in English 2

Example for Order No.: 3 A H 3 3 0 6 – 6 S Z 2 9 – 0 K B 2 – Z


Order codes: A 4 6 + K 2 B + M 1 B + A 2 0

Siemens HG 11.03 · 2010 23


Equipment Selection 3AH3 Vacuum Circuit-Breakers
Selection of additional equipment

Additional equipment Position: 1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16 Order codes


Order No.: 3 A H 3 n n n – n n n n n – n n n n – « n n n

Options

Wiring cables, halogen-free and flame-retardant – Z A 1 0


Condensation protection, heating for 230 V AC, 50 W – Z A 3 0
Silicone-free design – Z A 3 1
Vacuum circuit-breaker for horizontal installation – Z A 7 0
Additional rating plate, loose delivery – Z B 0 0
Primary conductor bars silver-plated for external connections
and internal interconnection on both sides
(standard for 4000 A circuit-breakers and type 3AH381) – Z D 1 0
Routine test certificate enclosed – Z F 2 0
Rated operating sequence O - 0.3 s - CO - 15 s - CO
(only possible up to 31.5 kA) – Z F 2 8
Hand crank (also for motor operating mechanism)
for manual charging of the closing spring – Z F 3 0

2 Circuit-breaker can also be used for 4500 A (applicable to circuit-breaker


types 3AH3077-8, 3AH3078-8, 3AH3127-8, 3AH3128-8, 3AH3177-8,
3AH3178-8, 3AH3227-8, 3AH3228-8, 3AH3818-8, 3AH3819-8)
Further, non-listed special versions (only after consultation with the
– Z Y 0 4

order processing department at the Switchgear Factory Berlin).


Information additionally in clear text. – Z Y 9 9

Configuration example
3AH3 vacuum circuit-breaker 3 A H 3
Rated voltage Ur = 36 kV (50/60 Hz)
Rated lightning impulse withstand voltage Up = 170 kV
Rated short-circuit breaking current Isc = 40 kA
Pole-centre distance = 350 mm
Rated normal current Ir = 2500 A 3 0 6 – 6
Closing solenoid, 1st shunt release, undervoltage release
and c.t.-operated release with a rated normal current of 1 A S – Z A 4 6
Manual electrical closing at the circuit-breaker,
operating voltage of the closing solenoid 32 V DC Z K 2 B
Operating voltage of the 1st release 48 V DC 2
2nd release as undervoltage release with operating voltage 32 V DC 9 – M 1 B
3rd release as c.t.-operated release 0
Operating voltage of the operating mechanism 230 V AC, 50 Hz K
Auxiliary switch 6 NO + 6 NC, 64-pole plug and with mechanical interlocking B
Auxiliary switch contacts and pins of the plug connector gold-plated – Z A 2 0
Frequency 50 Hz or DC, operating instructions and rating plate in English 2
Routine test certificate enclosed – Z F 2 0

Example for Order No.: 3 A H 3 3 0 6 – 6 S Z 2 9 – 0 K B 2 – Z


Order codes: A 4 6 + K 2 B + M 1 B + A 2 0 + F 2 0

24 Siemens HG 11.03 · 2010


3AH3 Vacuum Circuit-Breakers Equipment Selection
Accessories and spare parts

On request, we will be pleased to send you an overview Accessories for the plug connector
of accessories and spare parts, as well as the spare pole Included in the scope of supply of the basic equipment for
assemblies available. Please consider the following infor- 3AH3 vacuum circuit-breakers:
mation for your purchase order.
For 24-pole plug connector
Remark for orders – Lower part of plug
The order numbers in the spare part overview are applicable – Crimp sockets according to number of contacts
to vacuum circuit-breakers of current manufacture. When – Upper part of plug with screwed contacts
mounting parts or spare parts are being ordered for an (no crimp sockets required)
existing vacuum circuit-breaker, always quote the type For 64-pole plug connector
designation, serial number and the year of manufacture of
– Lower part of plug
the circuit-breaker to be sure to get the correct delivery.
– Upper part of plug
Retrofitting – Crimp sockets according to number of contacts
When releases/solenoids are retrofitted, the order numbers
of the mounting parts must also be specified. For other addi- Data on the rating plate
tional equipment, the required mounting parts are included
in the delivery.

Spare pole assemblies


2
As spare parts, the vacuum interrupters are always supplied
as a complete pole including post insulator.
To select the correct spare pole assemblies, please specify

HG11-2588c_en eps
the type designation, serial number and year of manufacture
of the circuit-breaker. All data is given on the rating plate.

Vacuum pole assemblies and other spare parts must only


be replaced by instructed personnel.

Note:
For any query regarding spare parts,
subsequent deliveries, etc. the following
three details are necessary:
– Type designation
– Serial No.
– Year of manufacture

Designation Remarks Order No.

Hand crank 3AX15 30-2B


Wire bundle With 10 wires for connection of auxiliary switch to
– 64-pole plug connector 3AX11 34-2D
– 24-pole plug connector 3AX11 34-2B
– 24-pole terminal strip 3AX11 34-2C
Accessories for plug connector (for wire cross-section 1.5 mm2)
Crimp pins for lower part of plug 24-pole 3AX11 34-3A
64-pole 3AX11 34-4B
Crimp sockets for upper part of plug 64-pole 3AX11 34-4C
Crimping pliers 3AX11 34-4D
Disassembly tool 3AX11 34-4G

Siemens HG 11.03 · 2010 25


3AH3 Vacuum Circuit-Breakers

R-HG11-205.tif

26 Siemens HG 11.03 · 2010


3AH3 Vacuum Circuit-Breakers Technical Data
Contents

Contents Page

Technical Data 27
Electrical data, dimensions and weights:
Voltage level 7.2 kV 28
Voltage level 12 kV 28
Voltage level 15 kV 30
Voltage level 17.5 kV 32
Voltage level 24 kV 34
Voltage level 36 kV 36

Electrical data, dimensions and weights of


high-current and generator circuit-breakers
according to IEEE C37.013:
Voltage level 17.5 kV 38
Voltage level 24 kV 40
R-HG11-196.tif

Circuit diagrams 42
Vacuum interrupter Operating times 44
Short-circuit protection of motors 44
Consumption data of releases 44
3
R-HG11-197.tif

Post insulator and upper interrupter support

Siemens HG 11.03 · 2010 27


Technical Data 3AH3 Vacuum Circuit-Breakers
Electrical data, dimensions and weights

Catalog dimension drawing no. (see page 29)


Operating cycle diagram no. (see page 29)
Rated lightning impulse withstand voltage
of the rated short-circuit breaking current
7.2 kV

(according to IEC 62271-1 at DC 100 A)


Voltage drop ΔU between connections
Rated short-duration power-frequency
Rated short-circuit breaking current
50/60 Hz

Rated short-circuit making current


Asymmetrical breaking current
Rated duration of short-circuit

Minimum creepage distance,

Minimum creepage distance,

Detailed dimension drawing


Rated operating sequence:
O - 3 min - CO - 3 min - CO
O - 0.3 s - CO - 3 min - CO
O - 0.3 s - CO - 15 s - CO
Rated normal current

Pole-centre distance

Minimum clearance,

Minimum clearance,
DC component in %

withstand voltage

(can be ordered)
phase-to-phase
phase-to-earth

phase-to-earth
(at 50/60 Hz)

interrupter
Order No.

Weights
Ir tk Isc Ima Up Ud

A mm s kA % kA kA kV kV mV mm mm mm mm kg
125/
3AH3 057-2 … 1250 210 n 3 50 36 56.1 60 20 1.8 160 230 80 130 180 S_325 00415 1 1
130
125/
3AH3 057-6 … 2500 210 n 3 50 36 56.1 60 20 1.8 160 230 80 130 180 S_325 00417 1 1
130
125/
3AH3 057-7 … 3150 210 n 3 50 36 56.1
130
60 20 1.8 160 230 80 130 180 S_325 00001 1 1
125/
3AH3 077-8 … 4000 275 n 3 50 36 56.1 60 20 1.4 160 170 71 130 308 S_325 00004 1 3
130
160/
3AH3 078-2 … 1250 275 n 3 63 36 70.7
164
60 20 1.8 160 170 71 130 196 S_325 00003 2 2
160/
3AH3 078-6 … 2500 275 n 3 63 36 70.7 60 20 1.8 160 170 71 130 196 S_325 00003 2 2
164
160/
3AH3 078-7 … 3150 275 n 3 63 36 70.7
164
60 20 1.8 160 170 71 130 196 S_325 00003 2 2
160/
3AH3 078-8 … 4000 275 n 3 63 36 70.7 60 20 1.4 160 170 71 130 308 S_325 00004 2 3
164

3 12 kV
Ir tk Isc Ima Up Ud

50/60 Hz A mm s kA % kA kA kV kV mV mm mm mm mm kg
125/
3AH3 117-2 … 1250 210 n 3 50 36 56.1
130
75 28 1.8 160 230 80 130 180 S_325 00415 1 1
125/
3AH3 117-6 … 2500 210 n 3 50 36 56.1 75 28 1.8 160 230 80 130 180 S_325 00417 1 1
130
125/
3AH3 117-7 … 3150 210 n 3 50 36 56.1 75 28 1.8 160 230 80 130 180 S_325 00001 1 1
130
125/
3AH3 127-8 … 4000 275 n 3 50 36 56.1 75 28 1.4 160 170 71 130 308 S_325 00004 1 3
130
160/
3AH3 128-2 … 1250 275 n 3 63 36 70.7 75 28 1.8 160 170 71 130 196 S_325 00003 2 2
164
160/
3AH3 128-6 … 2500 275 n 3 63 36 70.7 75 28 1.8 160 170 71 130 196 S_325 00003 2 2
164
160/
3AH3 128-7 … 3150 275 n 3 63 36 70.7
164
75 28 1.8 160 170 71 130 196 S_325 00003 2 2
160/
3AH3 128-8 … 4000 275 n 3 63 36 70.7 75 28 1.4 160 170 71 130 308 S_325 00004 2 3
164

n Standard information on the rating plate


Rated operating sequence possible up to Isc = 31.5 kA

28 Siemens HG 11.03 · 2010


3AH3 Vacuum Circuit-Breakers Technical Data
Electrical data, dimensions and weights

Operating cycle diagram for 7.2 kV and 12 kV

20 000 The permissible number of electrical operating cycles is shown as a function


10 000 of the breaking current (r.m.s. value). All vacuum circuit-breakers fulfil the
Operating cycles

endurance classes E2, M2 and C2 according to IEC 62271-100. The


5 000
curve shape beyond the parameters defined in IEC 62271-100 is based on
2 000 average experience data. The number of operating cycles that can actually
be reached can be different depending on the respective application.
1 000

500

200

100
75
50
HG11-2564b_en eps

2
20
1
10
1 2 5 10 20 kA 50 63 100
Breaking current (r.m.s. value)

Dimension drawings for 7.2 kV and 12 kV

561 550 591 680


210 210 275 275

3
105
105

211 211
668

494
494

668
HG11-2560 eps

HG11-2561 eps
70

105

571 610
601 776
Dimension drawing 1
Dimension drawing 2

694 750
275 275
105

211
494

733
170

HG11-2562 eps

694 776

Dimension drawing 3

Siemens HG 11.03 · 2010 29


Technical Data 3AH3 Vacuum Circuit-Breakers
Electrical data, dimensions and weights

Catalog dimension drawing no. (see page 31)


Operating cycle diagram no. (see page 31)
Rated lightning impulse withstand voltage
of the rated short-circuit breaking current
15 kV

(according to IEC 62271-1 at DC 100 A)


Voltage drop ΔU between connections
Rated short-duration power-frequency
Rated short-circuit breaking current
50/60 Hz

Rated short-circuit making current


Asymmetrical breaking current
Rated duration of short-circuit

Minimum creepage distance,

Minimum creepage distance,

Detailed dimension drawing


Rated operating sequence:
O - 3 min - CO - 3 min - CO
O - 0.3 s - CO - 3 min - CO
O - 0.3 s - CO - 15 s - CO
Rated normal current

Pole-centre distance

Minimum clearance,

Minimum clearance,
DC component in %

withstand voltage

(can be ordered)
phase-to-phase
phase-to-earth

phase-to-earth
(at 50/60 Hz)

interrupter
Order No.

Weights
Ir tk Isc Ima Up Ud

A mm s kA % kA kA kV kV mV mm mm mm mm kg
125/
3AH3 167-2 … 1250 210 n 3 50 36 56.1 95 36 1.8 160 230 110 130 184 S_325 00416 3 4
130
125/
3AH3 167-6 … 2500 210 n 3 50 36 56.1 95 36 1.8 160 230 110 130 184 S_325 00418 3 4
130
125/
3AH3 167-7 … 3150 210 n 3 50 36 56.1
130
95 36 1.8 160 230 110 130 184 S_325 00002 3 4
125/
3AH3 177-8 … 4000 275 n 3 50 36 56.1 95 36 1.4 160 170 135 130 310 S_325 00006 3 6
130
160/
3AH3 178-2 … 1250 275 n 3 63 36 70.7
164
95 36 1.8 160 170 71 130 196 S_325 00005 4 5
160/
3AH3 178-6 … 2500 275 n 3 63 36 70.7 95 36 1.8 160 170 71 130 196 S_325 00005 4 5
164
160/
3AH3 178-7 … 3150 275 n 3 63 36 70.7
164
95 36 1.8 160 170 71 130 196 S_325 00005 4 5
160/
3AH3 178-8 … 4000 275 n 3 63 36 70.7 95 36 1.4 160 170 71 130 308 S_325 00006 4 6
164

3 n Standard information on the rating plate


Rated operating sequence possible up to Isc = 31.5 kA

30 Siemens HG 11.03 · 2010


3AH3 Vacuum Circuit-Breakers Technical Data
Electrical data, dimensions and weights

Operating cycle diagram for 15 kV

20 000 The permissible number of electrical operating cycles is shown as a function


10 000 of the breaking current (r.m.s. value). All vacuum circuit-breakers fulfil the
Operating cycles

endurance classes E2, M2 and C2 according to IEC 62271-100. The


5 000
curve shape beyond the parameters defined in IEC 62271-100 is based on
2 000 average experience data. The number of operating cycles that can actually
be reached can be different depending on the respective application.
1 000

500

200

100
75
50
HG11-2565b_en eps

3
20
4
10
1 2 5 10 20 kA 50 63 100
Breaking current (r.m.s. value)

Dimension drawings for 15 kV

561 550 591 680


210 210 275 275

3
105
105

211 211
668

494
494

668
HG11-2560 eps

HG11-2561 eps
70

105

571 610
601 776
Dimension drawing 4
Dimension drawing 5

694 750
275 275
105

211
494

733
170

HG11-2562 eps

694 776

Dimension drawing 6

Siemens HG 11.03 · 2010 31


Technical Data 3AH3 Vacuum Circuit-Breakers
Electrical data, dimensions and weights

Catalog dimension drawing no. (see page 33)


Operating cycle diagram no. (see page 33)
Rated lightning impulse withstand voltage
of the rated short-circuit breaking current
17.5 kV

(according to IEC 62271-1 at DC 100 A)


Voltage drop ΔU between connections
Rated short-duration power-frequency
Rated short-circuit breaking current
50/60 Hz

Rated short-circuit making current


Asymmetrical breaking current
Rated duration of short-circuit

Minimum creepage distance,

Minimum creepage distance,

Detailed dimension drawing


Rated operating sequence:
O - 3 min - CO - 3 min - CO
O - 0.3 s - CO - 3 min - CO
O - 0.3 s - CO - 15 s - CO
Rated normal current

Pole-centre distance

Minimum clearance,

Minimum clearance,
DC component in %

withstand voltage

(can be ordered)
phase-to-phase
phase-to-earth

phase-to-earth
(at 50/60 Hz)

interrupter
Order No.

Weights
Ir tk Isc Ima Up Ud

A mm s kA % kA kA kV kV mV mm mm mm mm kg
125/
3AH3 217-2 … 1250 210 n 3 50 36 56.1 95 38 1.8 160 230 110 130 184 S_325 00416 5 4
130
125/
3AH3 217-6 … 2500 210 n 3 50 36 56.1 95 38 1.8 160 230 110 130 184 S_325 00418 5 4
130
125/
3AH3 217-7 … 3150 210 n 3 50 36 56.1
130
95 38 1.8 160 230 110 130 184 S_325 00002 5 4
125/
3AH3 227-8 … 4000 275 n 3 50 36 56.1 95 38 1.4 160 170 135 130 310 S_325 00006 5 6
130
160/
3AH3 228-2 … 1250 275 n 3 63 36 70.7
163.8
95 38 1.8 160 170 145 130 198 S_325 00005 6 5
160/
3AH3 228-6 … 2500 275 n 3 63 36 70.7 95 38 1.8 160 170 145 130 198 S_325 00005 6 5
163.8
160/
3AH3 228-7 … 3150 275 n 3 63 36 70.7
163.8
95 38 1.8 160 170 145 130 198 S_325 00005 6 5
160/
3AH3 228-8 … 4000 275 n 3 63 36 70.7 95 38 1.4 160 170 135 130 310 S_325 00006 6 6
163.8

3 n Standard information on the rating plate


Rated operating sequence possible up to Isc = 31.5 kA

32 Siemens HG 11.03 · 2010


3AH3 Vacuum Circuit-Breakers Technical Data
Electrical data, dimensions and weights

Operating cycle diagram for 17.5 kV

20 000 The permissible number of electrical operating cycles is shown as a function


10 000 of the breaking current (r.m.s. value). All vacuum circuit-breakers fulfil the
Operating cycles

endurance classes E2, M2 and C2 according to IEC 62271-100. The


5 000
curve shape beyond the parameters defined in IEC 62271-100 is based on
2 000 average experience data. The number of operating cycles that can actually
be reached can be different depending on the respective application.
1 000

500

200

100

50
HG11-2566b_en eps

30
20 6
5
10
1 2 5 10 20 kA 50 63 100
Breaking current (r.m.s. value)

Dimension drawings for 17.5 kV

561 550 591 680


210 210 275 275

3
105
105

211 211
668

494
494

668
HG11-2560 eps

HG11-2561 eps
70

105

571 610
601 776
Dimension drawing 4
Dimension drawing 5

694 750
275 275
105

211
494

733
170

HG11-2562 eps

694 776

Dimension drawing 6

Siemens HG 11.03 · 2010 33


3

34
Order No.

50/60 Hz
24 kV

3AH3 367-8 …
3AH3 267-7 …
3AH3 266-6 …
Ir

A
Rated normal current
Technical Data

Pole-centre distance

4000 300
2500 275
2500 275
mm

Siemens HG 11.03 · 2010


Rated operating sequence:

n
n
n
O - 3 min - CO - 3 min - CO
O - 0.3 s - CO - 3 min - CO
O - 0.3 s - CO - 15 s - CO

3
3
3
tk
Rated duration of short-circuit
Electrical data, dimensions and weights

Isc

kA
Rated short-circuit breaking current

50
50
40
DC component in %

36
36
36
of the rated short-circuit breaking current
Asymmetrical breaking current

kA

56.1
56.1
44.9

n Standard information on the rating plate


Rated short-circuit making current

kA
Ima

130
130
104

125/
125/
100/
(at 50/60 Hz)

Up

kV
Rated lightning impulse withstand voltage

125
110
125

Rated operating sequence possible up to Isc = 31.5 kA


Rated short-duration power-frequency

Ud

kV

50
50
50
withstand voltage
Voltage drop ΔU between connections

1.5
1.5
2.0
mV
(according to IEC 62271-1 at DC 100 A)
Minimum creepage distance,
interrupter
Minimum creepage distance,
phase-to-earth
Minimum clearance,
phase-to-phase
161 207 440 197 Minimum clearance,
161 170 228 180
360 226 245 173
mm mm mm mm

phase-to-earth

Weights
kg

350
198
168

Detailed dimension drawing


(can be ordered)
S_325 00596
S_325 00034
S_325 00007

9
9
7

Operating cycle diagram no. (see page 35)


9
8
7

Catalog dimension drawing no. (see page 35)


3AH3 Vacuum Circuit-Breakers
3AH3 Vacuum Circuit-Breakers Technical Data
Electrical data, dimensions and weights

Operating cycle diagram for 24 kV

20 000 The permissible number of electrical operating cycles is shown as a function


10 000 of the breaking current (r.m.s. value). All vacuum circuit-breakers fulfil the
Operating cycles

endurance classes E2, M2 and C2 according to IEC 62271-100. The


5 000
curve shape beyond the parameters defined in IEC 62271-100 is based on
2 000 average experience data. The number of operating cycles that can actually
be reached can be different depending on the respective application.
1 000

500

200

100

50
HG11-2567d_en eps

7
20
8 9
10
1 2 5 10 20 31.5 40 50 kA 100
Breaking current (r.m.s. value)

Dimension drawings for 24 kV

773 680 644 680


635 275 275 589,5 275 275
80
105

211
3
105

494

668

210
900
1030
778
494

max.70

HG11-2755 eps
194

HG11-2568 eps

599,5 776
645 704

Dimension drawing 7 Dimension drawing 8

1051 750
736,5 300 300

80
211
105
494

733
1180
max.60

HG11-2756 eps

824

Dimension drawing 9

Siemens HG 11.03 · 2010 35


Technical Data 3AH3 Vacuum Circuit-Breakers
Electrical data, dimensions and weights

Catalog dimension drawing no. (see page 37)


Operating cycle diagram no. (see page 37)
Rated lightning impulse withstand voltage
of the rated short-circuit breaking current
36 kV

(according to IEC 62271-1 at DC 100 A)


Voltage drop ΔU between connections
Rated short-duration power-frequency
Rated short-circuit breaking current
50/60 Hz

Rated short-circuit making current


Asymmetrical breaking current
Rated duration of short-circuit

Minimum creepage distance,

Minimum creepage distance,

Detailed dimension drawing


Rated operating sequence:
O - 3 min - CO - 3 min - CO
O - 0.3 s - CO - 3 min - CO
O - 0.3 s - CO - 15 s - CO
Rated normal current

Pole-centre distance

Minimum clearance,

Minimum clearance,
DC component in %

withstand voltage

(can be ordered)
phase-to-phase
phase-to-earth

phase-to-earth
(at 50/60 Hz)

interrupter
Order No.

Weights
Ir tk Isc Ima Up Ud

A mm s kA % kA kA kV kV mV mm mm mm mm kg
80/
3AH3 305-2 … 1250 350 n 3 31.5 36 35.4 170 70 2.3 360 330 314 260 170 S_325 00008 8 10
82
80/
3AH3 305-4 … 2000 350 n 3 31.5 36 35.4 170 70 2.3 360 330 314 260 175 S_325 00008 8 10
82
80/
3AH3 305-6 … 2500 350 n 3 31.5 36 35.4
82
170 70 2.3 360 330 314 260 175 S_325 00009 8 11
80/
3AH3 305-7 … 3150 350 n 3 31.5 36 35.4 170 70 1.9 366 430 309 270 350 S_325 00057 8 12
82
80/
3AH3 305-8… 4000 350 n 3 31.5 36 35.4
82
170 70 1.9 366 430 309 270 350 S_325 00057 8 12
100/
3AH3 306-6 … 2500 350 n 3 40 36 44.9 170 70 2.0 360 330 314 260 175 S_325 00009 7 11
104
100/
3AH3 306-7… 3150 350 n 3 40 36 44.9
104
170 70 1.9 366 430 309 270 350 S_325 00058 7 12
100/
3AH3 306-8… 4000 350 n 3 40 36 44.9 170 70 1.9 366 430 309 270 350 S_325 00058 7 12
104

3 n Standard information on the rating plate


Possible with order number suffix Z and order code F27
Possible with order number suffix Z and order code F28
Rated operating sequence possible up to Isc = 31.5 kA

36 Siemens HG 11.03 · 2010


3AH3 Vacuum Circuit-Breakers Technical Data
Electrical data, dimensions and weights

Operating cycle diagram for 36 kV

20 000 The permissible number of electrical operating cycles is shown as a function


10 000 of the breaking current (r.m.s. value). All vacuum circuit-breakers fulfil the
Operating cycles

endurance classes E2, M2 and C2 according to IEC 62271-100. The


5 000
curve shape beyond the parameters defined in IEC 62271-100 is based on
2 000 average experience data. The number of operating cycles that can actually
be reached can be different depending on the respective application.
1 000

500

200

100

50
HG11-2567d_en eps

7
20
8 9
10
1 2 5 10 20 31.5 40 50 kA 100
Breaking current (r.m.s. value)

Dimension drawings for 36 kV

823 820 823 820


737 350 350 737 350 350

3
105
105

211 211
1000
1000

791
494
734
494

234
234

HG11-2570 eps
HG11-2569 eps

737 853 737 853

Dimension drawing 10 Dimension drawing 11

1012 870
679 268,5 350 350
ca.105

211
1126,5
986,5
494
max.70

HG11-2781 eps

920

Dimension drawing 12

Siemens HG 11.03 · 2010 37


Technical Data 3AH3 Vacuum Circuit-Breakers
Electrical data, dimensions and weights
of high-current and generator circuit-breakers

Catalog dimension drawing no. (see page 39)


Rated lightning impulse withstand voltage
of the rated short-circuit breaking current
17.5 kV

(according to IEC 62271-1 at DC 100 A)


Voltage drop ΔU between connections
Rated short-duration power-frequency
Rated short-circuit breaking current
50/60 Hz

Rated short-circuit making current


High-current and generator circuit-breakers

Asymmetrical breaking current


Rated duration of short-circuit

Minimum creepage distance,

Minimum creepage distance,

Detailed dimension drawing


Rated operating sequence:
O - 3 min - CO - 3 min - CO
Rated normal current

Pole-centre distance

Minimum clearance,

Minimum clearance,
DC component in %

withstand voltage

(can be ordered)
phase-to-phase
O - 30 min - CO
according to IEEE C37.013

phase-to-earth

phase-to-earth
(at 50/60 Hz)

interrupter
Order No.

Weights
Ir tk Isc Ima Up Ud

A mm s kA % kA kA kV kV mV mm mm mm mm kg

3AH3 712-4 … 5000 300 n 3 50 75 73 137 110 50 1.4 160 230 230 230 470 S_325 00587 14

3AH3 712-5 … 6300 300 n 3 50 75 73 137 110 50 1.4 160 230 230 230 500 S_325 00587 14

3AH3 713-4 … 5000 300 n 3 63 65 86 173 110 50 1.4 160 230 230 230 470 S_325 00588 15

3AH3 713-5 … 6300 300 n 3 63 65 86 173 110 50 1.4 160 230 230 230 500 S_325 00588 15

3AH3 714-4 … 5000 300 n 3 72 65 96 198 110 50 1.4 160 230 230 230 470 S_325 00589 15

3AH3 714-5 … 6300 300 n 3 72 65 96 198 110 50 1.4 160 230 230 230 500 S_325 00589 15

3AH3 817-7 … 3150 275 n 3 50 75 73 137 110 50 1.4 160 170 145 130 230 S_325 00592 13

3AH3 817-8 … 4000 275 n 3 50 75 73 137 110 50 1.4 160 170 135 130 320 S_325 00593 14

3 3AH3 818-7 …

3AH3 818-8 …
3150 275

4000 275
n

n
3

3
63

63
65

65
86

86
173

173
110

110
50

50
1.4

1.4
160 170 145 130

160 170 135 130


230

320
S_325 00019

S_325 00030
16

14

3AH3 819-7 … 3150 275 n 3 72 65 96 198 110 50 1.4 160 170 145 130 250 S_325 00019 16

3AH3 819-8 … 4000 275 n 3 72 65 96 198 110 50 1.4 160 170 135 130 320 S_325 00030 14

n Standard information on the rating plate


Possible with order number suffix Z and order code F27

38 Siemens HG 11.03 · 2010


3AH3 Vacuum Circuit-Breakers Technical Data
Electrical data, dimensions and weights
of high-current and generator circuit-breakers

Number of operating cycles


The maximum permissible number of mechanical
operating cycles is 10,000. Short-circuit breaking operations
have been tested and proved under various conditions
according to IEEE C37.013. As regards the electrical
endurance, values ranging beyond this depend on the
specific case of application.

Dimension drawings for high-current and generator circuit-breakers 17.5 kV

433 600
269,5 109 275 275 271,5 211 275 275
80 80
211 211
ca.90
104

668

494
494

900

733
HG11-2571 eps

1000

HG11-2572 eps
max.70

max.70

119

Dimension drawing 13 Dimension drawing 14

840
356 410 300 300

211
3
104
494

1180
915

HG11-2573 eps
max. 60

Dimension drawing 15

433
269,5 109 275 275
80
211
104

668
494

900

HG11-2574 eps
59

119

Dimension drawing 16

Siemens HG 11.03 · 2010 39


Technical Data 3AH3 Vacuum Circuit-Breakers
Electrical data, dimensions and weights
of high-current and generator circuit-breakers

Catalog dimension drawing no. (see page 41)


Rated lightning impulse withstand voltage
of the rated short-circuit breaking current
24 kV

(according to IEC 62271-1 at DC 100 A)


Voltage drop ΔU between connections
Rated short-duration power-frequency
Rated short-circuit breaking current
50/60 Hz

Rated short-circuit making current


High-current and generator circuit-breakers

Asymmetrical breaking current


Rated duration of short-circuit

Minimum creepage distance,

Minimum creepage distance,

Detailed dimension drawing


Rated operating sequence:
O - 3 min - CO - 3 min - CO
Rated normal current

Pole-centre distance

Minimum clearance,

Minimum clearance,
DC component in %

withstand voltage

(can be ordered)
phase-to-phase
O - 30 min - CO
according to IEEE C37.013

phase-to-earth

phase-to-earth
(at 50/60 Hz)

interrupter
Order No.

Weights
Ir tk Isc Ima Up Ud

A mm s kA % kA kA kV kV mV mm mm mm mm kg

3AH3 722-2 … 3150 300 n 3 50 75 73 137 125 50 1.6 160 220 538 170 350 S_325 00913 9

3AH3 722-3 … 4000 300 n 3 50 75 73 137 125 50 1.6 160 220 538 170 350 S_325 00597 9

3AH3 722-4 … 5000 300 n 3 50 75 73 137 125 50 1.6 160 207 293 170 470 S_325 00914 15

3AH3 722-5 … 6300 300 n 3 50 75 73 137 125 50 1.6 160 207 293 170 500 S_325 00910 15

3AH3 723-2 … 3150 300 n 3 63 65 86 173 125 50 1.6 160 220 538 170 350 S_325 00915 9

3AH3 723-3 … 4000 300 n 3 63 65 86 173 125 50 1.6 160 220 538 170 350 S_325 00909 9

3AH3 723-4 … 5000 300 n 3 63 65 86 173 125 50 1.6 160 207 293 170 470 S_325 00916 15

3AH3 723-5 … 6300 300 n 3 63 65 86 173 125 50 1.6 160 207 293 170 500 S_325 00911 15

3 3AH3 724-2 …

3AH3 724-3 …
3150 300

4000 300
n

n
3

3
72

72
65

65
96

96
198

198
125

125
50

50
1.6

1.6
160 220 538 170

160 220 538 170


350

350
S_325 00917

S_325 00918
9

3AH3 724-4 … 5000 300 n 3 72 65 96 198 125 50 1.6 160 207 293 170 470 S_325 00919 15

3AH3 724-5 … 6300 300 n 3 72 65 96 198 125 50 1.6 160 207 293 170 500 S_325 00920 15

n Standard information on the rating plate


Possible with order number suffix Z and order code F27

40 Siemens HG 11.03 · 2010


3AH3 Vacuum Circuit-Breakers Technical Data
Electrical data, dimensions and weights
of high-current and generator circuit-breakers

Number of operating cycles


The maximum permissible number of mechanical
operating cycles is 10,000. Short-circuit breaking operations
have been tested and proved under various conditions
according to IEEE C37.013. As regards the electrical
endurance, values ranging beyond this depend on the
specific case of application.

Dimension drawings for high-current and generator circuit-breakers 24 kV

1051 750
736,5 300 300

80
211
105
494

733
1180
max.60

HG11-2756 eps

824

Dimension drawing 9

356
840
410 300 300
3
211
104
494

1180
915

HG11-2573 eps
max.60

Dimension drawing 15

Siemens HG 11.03 · 2010 41


Technical Data 3AH3 Vacuum Circuit-Breakers
Circuit diagrams

Circuit diagrams
The circuit diagrams shown here are examples from the manifold possibilities of circuit-breaker wiring.
-S10 -S11 -Y9 -X0

HE

-S21 -S22 -S3 -S41 -S42

-M1 M P 11 13 21 23 31 33 41 43 51 53 61 63
-S1
12 14 22 24 32 34 42 44 52 54 62 64

-S7 -S6
HG11-2575_en eps

“OPEN” release

HG11-2579a eps
HA
-Y1
-X0
Manual closing – manual opening with auxiliary switch 6 NO + 6 NC Contacts available for customer with basic circuit-
breaker equipment and auxiliary switch 6 NO + 6 NC

Additional equipment: Motor operating mechanism and auxiliary switch


-S14 -S15 -Y9 -X0
14
HE -S14
13
11 -S3 22

-S21 -S22 -S3 -S41 -S42 -S1


12 21
21 13
-M1 M P -K1
22 14
31
-S7 -S6 -K1
HG11-2576_en eps

32
“OPEN”release

3 HA
-Y1
-S15
14

13
-Y9
A1

A2
-K1
A1

A2
HG11-2580b eps

-X0

Motor operating mechanism with manual electrical closing Manual Closing and
electrical closing anti-pumping

The available possible combinations are described in the chapter “Selection of secondary equipment”.
-X0 -X0 -X0 -X0

33 43
-S1 -S1
34 44
D1
-Y7 U<
D2

A1 A1 A1 1
-Y2 -Y4 -Y6 -R1
A2 A2 A2 2
HG11-2583 eps

HG11-2584 eps

HG11-2585 eps

HG11-2586 eps

-X0 -X0 -X0 -X0

2nd shunt release C.t.-operated Low-energy Undervoltage release


release 0.5 A c.t.-operated
or 1 A release 0.1 Ws

Legend see page 43

42 Siemens HG 11.03 · 2010


3AH3 Vacuum Circuit-Breakers Technical Data
Circuit diagrams

Circuit diagrams (continued)


The circuit diagrams shown here are examples from the manifold possibilities of circuit-breaker wiring.
-X0 -X0
21
-S21 23
22
11 22 22 -S1
22 -S3 24
-S1 -S7
-S10 12 21 21
21
A1 21 13
-K1
-M1 1M= 22 14
21
14 -S41 13 -S42
31
D2 -S6
21 -K1 13 14 22
32
-S11 22 A1 A1 A1

HG11-2578d eps
HG11-2577b eps

22 -Y9 -K1 -Y1


A2 A2 A2
-S22
21

-X0 -X0

Motor operating mechanism with manual mechanical closing Circuit-breaker Signal “closing 1st shunt
tripping signal spring charged” release

Additional equipment: Motor operating mechanism and auxiliary switch (continued)

-X0 -X0

21
-S21
22

A1
11 13 21 23 31 33 41 43 51 53 61 63 71 73 81 83 91 93 101 103 111 113 121 123
-M1 1M= -S1
12 14 22 24 32 34 42 44 52 54 62 64 72 74 82 84 92 94 102 104 112 114 122 124
D2

22

3
HG11-2581b eps

-S22
HG11-2582a eps

21

-X0 -X0
Motor operating Contacts available for customer with basic circuit-breaker equipment
mechanism Auxiliary switch –S1 (12 NO + 12 NC) instead of auxiliary switch 6 NO + 6 NC

Legend (also for page 42)


HA Manual opening S1 Auxiliary switch S14, Anti-pumping X0 Lower part of plug/
HE Manual closing S3 Position switch S15 terminal strip
K1 Contactor (anti-pumping) (opens when closing spring S21, Position switches Y1 1st shunt release
M1 Motor operating mechanism is charged) S22 (to de-energize the motor Y2 2nd shunt release
P Energy store S6 Circuit-breaker tripping signal operating mechanism Y4 Current-transformer
R1 Resistance S7 Cutout switch for circuit- after charging) operated release
breaker tripping signal S41, Position switches Y6 Low-energy current-
S10, Anti-pumping for S42 (to indicate the charging state) transformer operated release
S11 manual closing Y7 Undervoltage release
Y9 Closing solenoid

Siemens HG 11.03 · 2010 43


Technical Data 3AH3 Vacuum Circuit-Breakers
Operating times, short-circuit protection of motors, consumption data of releases

Operating times

Operating times at rated voltage Equipment of circuit-breaker Operating time of circuit-breaker


of the secondary circuit

Closing time – < 75 ms 1)


Opening time 1st shunt release < 60 ms 1)
2nd and 3rd release < 55 ms
Arcing time – < 15 ms
Break time 1st shunt release < 80 ms
2nd and 3rd release < 60 ms
Dead time – 300 ms
CLOSE/OPEN contact time 1st shunt release < 90 ms
2nd and 3rd release < 70 ms
Minimum command duration Closing solenoid 45 ms
1st shunt release 40 ms
2nd and 3rd release 20 ms
Pulse time for circuit-breaker tripping signal 1st shunt release > 15 ms
2nd and 3rd release > 10 ms
Charging time for electrical operation – < 15 s
Synchronism error between the poles – w 2 ms

1) Shorter operating times on request.

Short-circuit protection of motors (fuse protection of drive motors)

Rated voltage Operating voltage Power consumption of the motor Smallest possible rated
of the motor current 2) of the m.c.b.
(miniature circuit-breaker)
with C-characteristic

3 V
24 DC
48 DC
max. V
26
53
min. V
20
41
W (at DC)
500
500
VA (at AC)


16
8
A

60 DC 66 51 500 – 6
110 DC 121 93 500 – 4
220 DC 242 187 500 – 2
110 AC 121 93 – 650 4
230 AC 244 187 – 650 2

2) The current inrush in the drive motor can be neglected due to its very short presence.

Consumption data of releases

Release Power consumption Tripping ranges

Operation at

DC AC 50/60 Hz Tripping voltage Tripping voltage


or tripping current
approx. W approx. VA at DC at AC 50/60 Hz
Closing solenoid 3AY15 10 140 140 85 to 110 % U 85 to 110 % U
1st shunt release 140 140 70 to 110 % U 85 to 110 % U
(without energy store) 3AY15 10
2nd shunt release 70 50 70 to 110 % U 85 to 110 % U
(with energy store) 3AY11 01
Undervoltage release 3AY11 03 20 20 35 to 0%U 35 to 0 % U
Current-transformer operated release 3AX11 02 – 10 3) – 90 to 110 % Ia
(rated normal current 0.5 or 1 A)
Current-transformer operated release 3AX11 04 – – – –
(tripping pulse W 0.1 Ws)

3) Consumption at pickup current (90 % of the rated normal current) and open armature.

44 Siemens HG 11.03 · 2010


3AH3 Vacuum Circuit-Breakers Annex
Contents

Contents Page

Annex 45

Inquiry form 46

Configuration instructions 47
Configuration aid Foldout page
R-HG11-181.tif

Brandenburg Gate, Berlin, Germany

4
R-HG11-180.eps

Switchgear Factory in Berlin, Germany

Siemens HG 11.03 · 2010 45


Annex 3AH3 Vacuum Circuit-Breakers
Inquiry form

Please copy, fill in and return to your


Siemens partner or you can use our
prompted online configurator under
www.siemens.com/energy

Inquiry concerning
Technical Data Other values

o 3AH3 circuit-breaker Rated voltage o 7.2 kV o 12 kV o 15 kV o 17.5 kV


o 24 kV o 36 kV o 40.5 kV o _ _ _ kV
o 3AH37/38 generator
circuit-breaker Rated lightning impulse o 60 kV o 75 kV o 95 kV o 110 kV
withstand voltage o 125 kV o 170 kV o 195 kV o _ _ _ kV

Rated short-duration o 20 kV o 32 kV o 36 kV o 38 kV
power-frequency withstand voltage o 50 kV o 70 kV o 95 kV o _ _ _ kV
Please
Rated short-circuit o 31.5 kA o 40 kA o 50 kA
breaking current o 63 kA o 72 kA o _ _ _ kA
o Submit an offer
o 1250 A o 2000 A o 2500 A o 3150 A
o Call us Rated normal current
o 4000 A o 5000 A o 6300 A o ___A
o Visit us
Pole-centre distance o 210 mm o 275 mm o 300 mm o 350 mm

Secondary equipment
For possible combinations see pages 17 to 23
Your address
Circuit-breaker equipment o Manual mechanical closing
o Manual electrical closing
Company o Manual operating mechanism

Motor operating mechanism o _ _ _ V DC o _ _ _ V AC, _ _ _ Hz


Dept.
Closing solenoid o _ _ _ V DC o _ _ _ V AC, _ _ _ Hz

Name 1st shunt release o _ _ _ V DC o _ _ _ V AC, _ _ _ Hz

2nd shunt release o _ _ _ V DC o _ _ _ V AC, _ _ _ Hz


Street
Current-transformer operated release o 0.5 A o 1A o ⱖ 0.1 Ws o ⱖ 0.1 Ws
(10 c) (20 c)
Postal code/city
Undervoltage release o _ _ _ V DC o _ _ _ V AC, _ _ _ Hz
Phone
o Without energy store o With energy store

Fax Auxiliary switch o 6 NO + 6 NC o 12 NO + 12 NC

Low-voltage connection o 24-pole o 24-pole plug o 64-pole plug

4
E-mail terminal strip

o Mechanical interlocking

Operating instructions o English o German o French o Spanish

Siemens AG Application and other requirements

Dept.

Name

Street

Postal code/city

Fax

o Please check off _ _ _ Please fill in

46 Siemens HG 11.03 · 2010


You prefer to configure your 3AH3 vacuum circuit-breaker on your own? For configuration of your
Please follow the steps for configuration and enter the order number in the configuration aid. 3AH3 vacuum circuit-breaker
Alternatively you can also use our prompted online configurator under www.siemens.com/energy

1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16
3 A H 3 n n n – n n n n n – n n n n – Z
Instruction for configuration of the 3AH3 vacuum circuit-breaker

1st step: Definition of the primary part (see pages 13 to 16)

See page 13

See page 17
See page 18
See page 19
See page 20

See page 21
See page 22
See page 23
See page 23

See page 24
page 16
to
Please specify the following ratings: Possible options:

Rated voltage (Ur) Ur: 7.2 kV to 40.5 kV


Rated lightning impulse withstand voltage (Up) Up: 60 kV to 195 kV
Rated short-duration power-frequency withstand voltage (Ud) Ud: 20 kV to 95 kV
Rated short-circuit breaking current (Isc) Isc: 31.5 kA to 72 kA 3 A H 3 – –
Rated normal current (Ir) Ir: 1250 A to 6300 A
Pole-centre distance 210 mm to 350 mm + + + +

These ratings define the positions 4 to 8 of the order number. + + + +

3 A H 3 – –

+ + + +
2nd step: Definition of the secondary equipment (see pages 17 to 23)
+ + + +

Please specify the following equipment features: Possible options: 3 A H 3 – –

+ + + +
Release combination Shunt release, current-transformer operated release
(position 9) and undervoltage release
Closing solenoid Operating voltages from 24 V DC to 240 V AC + + + +
(position 10)
Operating voltage of the releases Operating voltages from 24 V DC to 240 V AC 3 A H 3 – –
(positions 11/12)
Type of local closing Mechanical closing, + + + +
(position 10) manual electrical closing
Type of operating mechanism and operating voltage of a motor, Manual operating stored-energy mechanism,
if available (position 14) motor operating stored-energy mechanism + + + +
with operating voltages from 24 V DC to 240 V AC
Number of auxiliary contacts 6 NO + 6 NC, 12 NO + 12 NC 3 A H 3 – –
(position 15)
Design of the secondary connection 24-pole terminal strip, 24-pole plug connector,
(position 15) 64-pole plug connector + + + +
Language of the documentation English, German, French, Spanish, other languages on request
(position 16) + + + +
Frequency of the operating voltage of the 50 Hz/60 Hz
secondary equipment at AC (position 16)
3 A H 3 – –

These equipment features define the positions 9 to 16 of the order number.


+ + + +

+ + + +

3rd step: Do you have any further requirements concerning the equipment? (Please refer to page 24) 3 A H 3 – –
Should you still need more options than the possible special equipment like halogen-free and
+ + + +
flame-retardant or silicone-free version, condensation protection or an additional rating plate, etc.,
please contact your responsible sales partner. + + + +

3 A H 3 – –

+ + + +

+ + + +

3 A H 3 – –

+ + + +

+ + + +
Siemens HG 11.03 · 2010 47
Published by and copyright © 2010:
Siemens AG
Energy Sector
Freyeslebenstrasse 1
91058 Erlangen, Germany

Siemens AG
Energy Sector
Power Distribution Division
Medium Voltage
Nonnendammallee 104
13623 Berlin, Germany

For more information, please contact our


Customer Support Center.
Phone: +49 180 524 70 00
Fax: +49 180 524 24 71
(Charges depending on provider)
E-mail: support.energy@siemens.com

Order No. E50001-K1511-A031-A3-7600


Printed in Germany
Dispo 40402, c4bs 7470
KG 05.10 2.0 50 En
3600/24904

Printed on elementary chlorine-free bleached paper.

All rights reserved.


If not stated otherwise on the individual pages of this
catalog, we reserve the right to include modifications,
especially regarding the stated values, dimensions and weights.
Drawings are not binding.
All product designations used are trademarks or product
names of Siemens AG or other suppliers.
If not stated otherwise, all dimensions in this
catalog are given in mm.

Subject to change without prior notice.


The information in this document contains general
descriptions of the technical options available, which
may not apply in all cases. The required technical
options should therefore be specified in the contract.

www.siemens.com/energy
R-HG11-182.tif