Medium-Voltage Equipment
Selection and Ordering Data
R-HG11-172.tif
Contents Page
Equipment Selection 11
Ordering data and configuration example
Selection of basic types, circuit-breakers
12
13
2
Selection of secondary equipment 17
Selection of additional equipment 24
Accessories and spare parts 25
Technical Data 27
Electrical data, dimensions and weights
Circuit diagrams
28
42
3
Operating times, short-circuit protection
of motors, consumption data of releases 44
Annex 45
Inquiry form
Configuration instructions
46
47 4
Configuration aid Foldout page
R-HG11-173.tif
Contents Page
Description 5
General 6 1
Construction and mode of operation:
Switching medium 7
Pole assemblies 7
Operating mechanism box 7
Operating mechanism 7
Trip-free mechanism 7
Releases 8
Closing 8
Circuit-breaker tripping signal 8
Interlocking 8
Standards 8
R-HG11-174.tif
Maintenance-free design 8
Industrial application: Refinery Ambient conditions 9
Current carrying capacity 9
Dielectric strength 9
Product range overview 10
Basic equipment 10
Circuit-breakers must make and break all currents within controlling all fault conditions in the power system at the
R-HG11-216.tif
R-HG11-204.tif
The 3AH3 vacuum circuit-breaker is maintenance-free Due to its high capacity, the circuit-breaker is especially
throughout its entire service life. It is extremely powerful suitable for generator operation and industrial applications.
and controls up to 10,000 operating cycles. This circuit- The high-current and generator circuit-breakers 3AH37 and
breaker is used for high load currents up to 6300 A and high 3AH38 meet the requirements of IEEE Std C37.013.
short-circuit currents up to 72 kA. It covers the common
medium-voltage range from 7.2 kV to 36 kV.
Pole assemblies
The pole assemblies consist of the vacuum interrupters (6)
and the interrupter supports. The vacuum interrupters are
Circuit-breaker structure
air-insulated and freely accessible. This makes it possible to
clean the insulating parts easily in adverse ambient condi- 1 Pole assembly
tions. The vacuum interrupter is mounted rigidly to the upper 2 Operating mechanism box
3 Post insulator
interrupter support (5). The lower part of the interrupter is
4 Operating rod
guided in the lower interrupter support (7), allowing axial
5 Upper interrupter support
movement. The braces absorb the external forces resulting
6 Vacuum interrupter
from switching operations and the contact pressure. 7 Lower interrupter support
Trip-free mechanism
3AH3 vacuum circuit-breakers have a trip-free mechanism
according to IEC 62271-100. In the event of an opening
command being given after a closing operation has been
initiated, the moving contacts return to the open position
and remain there even if the closing command is sustained.
R-HG11-192.tif
Ambient conditions
The vacuum circuit-breakers are designed for the normal
operating conditions defined in IEC 62271-100.
Condensation can occasionally occur under the ambient
conditions shown opposite. 3AH3 vacuum circuit-breakers
are suitable for use in the following climatic classes
according to IEC 60721, Part 3-3:
40°C
1
Climatic ambient conditions: Class 3K4 1)
Biological ambient conditions: Class 3B1 max. 95% per day
max. 90% per month
Mechanical ambient conditions: Class 3M2 -5°C
Chemically-active substances: Class 3C2 2)
Mechanically-active substances: Class 3S2 3)
HG11-2515a_en eps
1) Low temperature limit: – 5 °C
2) Without icing and wind-driven precipitation
3) Restriction: Clean insulation parts
Dielectric strength
0
The dielectric strength of air insulation decreases with 10 20 30 40 50 60 °C 70
Ambient air temperature
increasing altitude due to low air density. According to
IEC 62271-1, the values of the rated lightning impulse
withstand voltage and the rated short-duration power-
frequency withstand voltage specified in the chapter
“Technical Data” apply to a site altitude of 1000 m above
sea level. For an altitude above 1000 m, the insulation level 1.50
voltages.
To select the devices, the following applies: 1.30
U W U0 x Ka
1.20
U Rated withstand voltage under reference atmosphere
U0 Rated withstand voltage requested for the place of installation
Ka Altitude correction factor according to the opposite diagram
HG11-2517c_en eps
1.10
Example
For a requested rated lightning impulse withstand voltage 1.00
1000 1500 2000 2500 3000 3500 m 4000
of 75 kV at an altitude of 2500 m, an insulation level of
Site altitude
90 kV under reference atmosphere is required as a minimum:
90 kV W 75 kV x 1.2
Rated short-
1 kV
7.2
kA
50
63
210
쐽
275
쐽
350 350 210
쐽
275
쐽
350 210
쐽
275
쐽
350 275
쐽
쐽
300 350 300 300
12 50 쐽 쐽 쐽 쐽
63 쐽 쐽 쐽 쐽
15 50 쐽 쐽 쐽 쐽
63 쐽 쐽 쐽 쐽
17.5 50 쐽 쐽 쐽 왖 쐽왖 왖 왖
63 쐽 쐽 쐽왖 쐽왖 왖 왖
72 왖 왖 왖 왖
24 40 쐽
50 쐽 왖 쐽 왖 왖 2) 왖 2)
63 왖 왖 왖 2) 왖 2)
72 왖 왖 왖 2) 왖 2)
36 31.5 쐽 쐽 쐽 쐽 쐽
40 쐽 쐽 쐽
40.5 1) 31.5 쐽 쐽 쐽 쐽 쐽
40 쐽 쐽 쐽
Basic equipment
Operating mechanism Electrical operating mecha- Manual operating mechanism Hand crank available
nism (hand crank not includ- (hand crank included in the scope of supply) as accessory
ed in the scope of supply)
Closing Closing solenoid and Manual electrical closing –
manual mechanical closing
1st release Shunt release None –
2nd release Without Shunt release, Max. 3 releases can be combined
undervoltage release, (for possible combinations,
c.t.-operated release refer to page 17)
3rd release Without Shunt release, Max. 3 releases can be combined
undervoltage release, (for possible combinations,
c.t.-operated release refer to page 17)
Varistor circuit Installed for ⱖ 60 V DC None For limiting switching overvoltages
due to inductive loads
Auxiliary switch 6 NO + 6 NC 12 NO + 12 NC –
Plug connector 24-pole terminal strip 24-pole plug, –
64-pole plug
Anti-pumping Available None –
Circuit-breaker Available None –
tripping signal
Operating cycle counter Available None –
“Spring charged” Available None –
signal and indication
Interlocking Without Mechanical interlocking –
Contents Page
Equipment Selection 11
Ordering data and configuration example 12
Voltage level 24 kV 16
2 Position:
a: alphabetical
1 2 3 4 5
n: numerical
6 7 – 8 9 10 11 12 – 13 14 15 16 Order codes
Order No.: 3 A H 3 n n n – n a a n n – n a a n – « n n n
Primary part
1st position Superior group
Switching devices
Secondary part
9th to 16th position Secondary equipment
Operating mechanism, releases, operating
voltages and further auxiliary equipment
Order codes
Group of 3 after the Order No.
Format: a n a
Configuration example
In order to simplify the selection of the correct order number
for the requested circuit-breaker type, you will find a con-
figuration example on each page of the chapter “Equipment
Selection”. For the selection of the secondary part, always the
last example of the primary part was taken over and continued, On the foldout page we offer a configuring aid.
so that at the end of the equipment selection (page 24) a Here you can fill in the order number you have deter-
completely configured circuit-breaker results as an example. mined for your circuit-breaker.
at 36 % DC component
Pole-centre distance
Rated short-circuit
Rated short-circuit
withstand voltage
withstand voltage
power-frequency
breaking current
making current
Rated voltage
See page 17
See page 18
See page 19
See page 20
See page 21
See page 22
See page 23
See page 23
See page 24
Ur Up Ud Isc Ima Ir
kV kV kV kA kA mm A
7.2 60 20 50 125/130 210 1250 3 A H 3 0 5 7 – 2
2500 3 A H 3 0 5 7 – 6
3150 3 A H 3 0 5 7 – 7
275 4000 1) 3 A H 3 0 7 7 – 8
63 160/164 275 1250 3 A H 3 0 7 8 – 2
2
2500 3 A H 3 0 7 8 – 6
3150 3 A H 3 0 7 8 – 7
4000 1) 3 A H 3 0 7 8 – 8
Special version (available for all 7.2 kV circuit-breakers)
Ud = 32 kV – Z E 1 6
12 kV
50/60 Hz
Ur Up Ud Isc Ima Ir
kV kV kV kA kA mm A
12 75 28 50 125/130 210 1250 3 A H 3 1 1 7 – 2
2500 3 A H 3 1 1 7 – 6
3150 3 A H 3 1 1 7 – 7
275 4000 1) 3 A H 3 1 2 7 – 8
63 160/164 275 1250 3 A H 3 1 2 8 – 2
2500 3 A H 3 1 2 8 – 6
3150 3 A H 3 1 2 8 – 7
4000 1) 3 A H 3 1 2 8 – 8
Special versions (available for all 12 kV circuit-breakers)
Ud = 42 kV – Z E 1 3
Isc = 57.8 kA
Ima = 145 kA (for 3AH3 117-.
circuit-breaker) – Z Y 0 3
Configuration example
3AH3 vacuum circuit-breaker 3 A H 3
Rated voltage Ur = 12 kV, 50/60 Hz
Rated lightning impulse withstand voltage Up = 75 kV
Rated short-circuit breaking current Isc = 50 kA
Pole-centre distance = 210 mm
Rated normal current Ir = 1250 A 1 1 7 – 2
at 36 % DC component
Pole-centre distance
Rated short-circuit
Rated short-circuit
withstand voltage
withstand voltage
power-frequency
breaking current
making current
Rated voltage
See page 17
See page 18
See page 19
See page 20
See page 21
See page 22
See page 23
See page 23
See page 24
Ur Up Ud Isc Ima Ir
kV kV kV kA kA mm A
15 95 36 50 125/130 210 1250 3 A H 3 1 6 7 – 2
2500 3 A H 3 1 6 7 – 6
3150 3 A H 3 1 6 7 – 7
275 4000 1) 3 A H 3 1 7 7 – 8
63 160/164 275 1250 3 A H 3 1 7 8 – 2
2
2500 3 A H 3 1 7 8 – 6
3150 3 A H 3 1 7 8 – 7
4000 1) 3 A H 3 1 7 8 – 8
Special version (available for all 15 kV circuit-breakers)
Ud = 42 kV – Z E 1 3
17.5 kV
50/60 Hz
Ur Up Ud Isc Ima Ir
kV kV kV kA kA mm A
17.5 95 38 50 125/130 210 1250 3 A H 3 2 1 7 – 2
2500 3 A H 3 2 1 7 – 6
3150 3 A H 3 2 1 7 – 7
275 4000 1) 3 A H 3 2 2 7 – 8
63 160/164 275 1250 3 A H 3 2 2 8 – 2
2500 3 A H 3 2 2 8 – 6
3150 3 A H 3 2 2 8 – 7
4000 1) 3 A H 3 2 2 8 – 8
Special version (available for all 17.5 kV circuit-breakers)
Ud = 42 kV – Z E 1 3
Configuration example
3AH3 vacuum circuit-breaker 3 A H 3
Rated voltage Ur = 17.5 kV, 50/60 Hz
Rated lightning impulse withstand voltage Up = 95 kV
Rated short-circuit breaking current Isc = 63 kA
Pole-centre distance = 275 mm
Rated normal current Ir = 4000 A 2 2 8 – 8
at 36 % DC component
Pole-centre distance
Rated short-circuit
Rated short-circuit
withstand voltage
withstand voltage
power-frequency
breaking current
making current
Rated voltage
See page 17
See page 18
See page 19
See page 20
See page 21
See page 22
See page 23
See page 23
See page 24
Ur Up Ud Isc Ima Ir
kV kV kV kA kA mm A
24 125 50 40 100/104 275 2500 3 A H 3 2 6 6 – 6
110 50 50 125/130 275 3150 3 A H 3 2 6 7 – 7
125 50 50 125/130 300 4000 1) 3 A H 3 3 6 7 – 8
36 kV
50/60 Hz
2
Ur Up Ud Isc Ima Ir
kV kV kV kA kA mm A
36 170 70 31.5 80/82 350 1250 3 A H 3 3 0 5 – 2
2000 3 A H 3 3 0 5 – 4
2500 3 A H 3 3 0 5 – 6
3150 3 A H 3 3 0 5 – 7
4000 1) 3 A H 3 3 0 5 – 8
40 100/104 350 2500 3 A H 3 3 0 6 – 6
3150 3 A H 3 3 0 6 – 7
4000 1) 3 A H 3 3 0 6 – 8
Special versions (available for all 36 kV circuit-breakers):
Up = 185 kV (only possible together) – Z E 1 4
and Ud = 85 kV + E 1 5
Up = 195 kV (only possible together) – Z E 2 4
and Ud = 95 kV + E 2 5
Ur = 40.5 kV (only possible together) – Z Y 0 9
Up = 195 kV + E 2 4
Ud = 95 kV + E 2 5
1) Higher rated normal currents on request
Configuration example
3AH3 vacuum circuit-breaker 3 A H 3
Rated voltage Ur = 36 kV, 50/60 Hz
Rated lightning impulse withstand voltage Up = 170 kV
Rated short-circuit breaking current Isc = 40 kA
Pole-centre distance = 350 mm
Rated normal current Ir = 2500 A 3 0 6 – 6
at 36 % DC component
Pole-centre distance
Rated short-circuit
Rated short-circuit
withstand voltage
withstand voltage
power-frequency
breaking current
making current
Rated voltage
See page 17
See page 18
See page 19
See page 20
See page 21
See page 22
See page 23
See page 23
See page 24
Ur Up Ud Isc Ima Ir
kV kV kV kA kA mm A
17.5 110 50 50 137 275 3150 3 A H 3 8 1 7 – 7
4000 3 A H 3 8 1 7 – 8
300 5000 3 A H 3 7 1 2 – 4
6300 1) 3 A H 3 7 1 2 – 5
63 173 275 3150 3 A H 3 8 1 8 – 7
2
4000 3 A H 3 8 1 8 – 8
300 5000 3 A H 3 7 1 3 – 4
6300 1) 3 A H 3 7 1 3 – 5
72 198 275 3150 3 A H 3 8 1 9 – 7 G 1 A
4000 3 A H 3 8 1 9 – 8 G 1 A
300 5000 3 A H 3 7 1 4 – 4
6300 1) 3 A H 3 7 1 4 – 5
24 kV
50/60 Hz/generator circuit-breaker acc. to IEEE Std C37.013
Ur Up Ud Isc Ima Ir
kV kV kV kA kA mm A
24 125 50 50 137 350 3150 3 A H 3 7 2 2 – 2
4000 3 A H 3 7 2 2 – 3
5000 3 A H 3 7 2 2 – 4
6300 1) 3 A H 3 7 2 2 – 5
63 173 350 3150 3 A H 3 7 2 3 – 2
4000 3 A H 3 7 2 3 – 3
5000 3 A H 3 7 2 3 – 4
6300 1) 3 A H 3 7 2 3 – 5
72 198 350 3150 3 A H 3 7 2 4 – 2
4000 3 A H 3 7 2 4 – 3
5000 3 A H 3 7 2 4 – 4
6300 1) 3 A H 3 7 2 4 – 5
1) Higher rated normal currents on request
Configuration example
3AH3 vacuum circuit-breaker 3 A H 3
Rated voltage Ur = 24 kV, 50/60 Hz
Rated lightning impulse withstand voltage Up = 125 kV
Rated short-circuit breaking current Isc = 72 kA
Pole-centre distance = 350 mm
Rated normal current Ir = 6300 A 7 2 4 – 5
C.t.-operated release
C.t.-operated release
C.t.-operated release
C.t.-operated release
with tripping pulse
ⱖ 0.1 Ws (20 c)
Closing solenoid
ⱖ 0.1 Ws (10 c)
See page 18
See page 19
See page 20
See page 21
See page 22
See page 23
See page 23
See page 24
0.5 A
1.0 A
n n M
n n n N
n n n N – Z F 1 51)
n n n n T
n n n n P
n n n n P – Z A 4 6
n n n2) Q
n n n R
n
n
n
n
n
n
n
n
n
n
n
n
n
n
S
S
U
U
–
–
Z
Z
A
A
4
4
6
6
2
n n n V
n n n V – Z A 4 5
1) With 3rd shunt release, voltage according to 13th position
2) Version with two c.t.-operated releases 0.5 A
Configuration example
3AH3 vacuum circuit-breaker 3 A H 3
(Ur = 36 kV, 50/60 Hz, Up = 170 kV, Isc = 40 kA, Ir = 2500 A,
pole-centre distance = 350 mm) 3 0 6 – 6
Closing solenoid, 1st shunt release, undervoltage release and
c.t.-operated release with a rated normal current of 1 A S – Z A 4 6
See page 19
See page 20
See page 21
See page 22
See page 23
See page 23
See page 24
Standard voltages Special voltages
2 125 V DC
127 V DC
240 V DC
Z
Z
Z
With order code
With order code
With order code
K
K
K
1 D
1 E
1 F
120 V AC 50/60 Hz 1) Z With order code K 1 K
125 V AC 50/60 Hz 1) Z With order code K 1 L
240 V AC 50/60 Hz 1) Z With order code K 1 M
Manual electrical closing at the circuit-breaker
24 V DC M
48 V DC N
60 V DC P
110 V DC Q
220 V DC R
100 V AC 50/60 Hz 1) T
110 V AC 50/60 Hz 1) U
230 V AC 50/60 Hz 1) V
30 V DC Z With order code K 2 A
32 V DC Z With order code K 2 B
120 V DC Z With order code K 2 C
125 V DC Z With order code K 2 D
127 V DC Z With order code K 2 E
240 V DC Z With order code K 2 F
120 V AC 50/60 Hz 1) Z With order code K 2 K
125 V AC 50/60 Hz 1) Z With order code K 2 L
240 V AC 50/60 Hz 1) Z With order code K 2 M
1) The AC frequency 50 or 60 Hz is selected at the 16th position of the
order number together with the language (see page 23)
Configuration example
3AH3 vacuum circuit-breaker 3 A H 3
(Ur = 36 kV, 50/60 Hz, Up = 170 kV, Isc = 40 kA, Ir = 2500 A,
pole-centre distance = 350 mm) 3 0 6 – 6 S
Manual electrical closing at the circuit-breaker,
operating voltage of the closing solenoid 32 V DC Z K 2 B
See page 20
See page 21
See page 22
See page 23
See page 23
See page 24
Standard voltages Special voltages
24 V DC 1
48 V DC 2
60 V DC 3
110 V DC 4
220 V DC 5
100 V AC 50/60 Hz 1) 6
110 V AC 50/60 Hz 1) 7
230 V AC 50/60 Hz 1) 8
30 V DC 9 With order code L 1 A
32 V DC 9 With order code L 1 B
120 V DC 9 With order code L 1 C
125 V DC 9 With order code L 1 D
127 V DC
240 V DC
120 V AC 50/60 Hz 1)
9
9
9
With order code
With order code
With order code
L
L
L
1 E
1 F
1 K
2
125 V AC 50/60 Hz 1) 9 With order code L 1 L
240 V AC 50/60 Hz 1) 9 With order code L 1 M
Configuration example
3AH3 vacuum circuit-breaker 3 A H 3
(Ur = 36 kV, 50/60 Hz, Up = 170 kV, Isc = 40 kA, Ir = 2500 A,
pole-centre distance = 350 mm) 3 0 6 – 6 S Z
Operating voltage of the 1st shunt release 48 V DC 2
See page 21
See page 22
See page 23
See page 23
See page 24
Standard voltages Special voltages
2 120 V DC
125 V DC
127 V DC
9
9
9
With order code
With order code
With order code
M
M
M
1 C
1 D
1 E
240 V DC 9 With order code M 1 F
120 V AC 50/60 Hz 1) 9 With order code M 1 K
125 V AC 50/60 Hz 1) 9 With order code M 1 L
240 V AC 50/60 Hz 1) 9 With order code M 1 M
Special versions
To operate the 2nd release as an undervoltage release on an
energy store type AN 1902- (for DC) or AN 1901-2 (for AC),
both make Bender, the operating voltage must be defined –
and whether the energy store will be provided by the customer
or included in the scope of supply.
Energy store
Type In the scope
of supply
60 V DC AN 1902- no 9 With order code M 2 D
110 V DC AN 1902- no 9 With order code M 2 E
220 V DC AN 1902- no 9 With order code M 2 F
100/110/230 V AC AN 1901-2 no 9 With order code M 2 G
60 V DC AN 1902- yes 9 With order code M 3 D
110 V DC AN 1902- yes 9 With order code M 3 E
220 V DC AN 1902- yes 9 With order code M 3 F
100/110/230 V AC AN 1901-2 yes 9 With order code M 3 G
Configuration example
3AH3 vacuum circuit-breaker 3 A H 3
(Ur = 36 kV, 50/60 Hz, Up = 170 kV, Isc = 40 kA, Ir = 2500 A,
pole-centre distance = 350 mm) 3 0 6 – 6 S Z 2
2nd release as undervoltage release with operating voltage 32 V DC 9 M 1 B
See page 22
See page 23
See page 23
See page 24
Standard voltages Special voltages
Energy store
Type In the scope
of supply
60 V DC AN 1902- no 9 With order code N 2 D
110 V DC AN 1902- no 9 With order code N 2 E
220 V DC AN 1902- no 9 With order code N 2 F
100/110/230 V AC AN 1901-2 no 9 With order code N 2 G
60 V DC AN 1902- yes 9 With order code N 3 D
110 V DC AN 1902- yes 9 With order code N 3 E
220 V DC AN 1902- yes 9 With order code N 3 F
100/110/230 V AC AN 1901-2 yes 9 With order code N 3 G
Configuration example
3AH3 vacuum circuit-breaker 3 A H 3
(Ur = 36 kV, 50/60 Hz, Up = 170 kV, Isc = 40 kA, Ir = 2500 A,
pole-centre distance = 350 mm) 3 0 6 – 6 S Z 2 9 –
3rd release as c.t.-operated release 0
See page 23
See page 23
See page 24
Standard voltages Special voltages
2 125 V DC
127 V DC
240 V DC
Z
Z
Z
With order code
With order code
With order code
P
P
P
1 D
1 E
1 F
120 V AC 50/60 Hz 1) Z With order code P 1 K
125 V AC 50/60 Hz 1) Z With order code P 1 L
240 V AC 50/60 Hz 1) Z With order code P 1 M
1) The AC frequency 50 or 60 Hz is selected at the 16th position of the
order number together with the language (see page 23)
Configuration example
3AH3 vacuum circuit-breaker 3 A H 3
(Ur = 36 kV, 50/60 Hz, Up = 170 kV, Isc = 40 kA, Ir = 2500 A,
pole-centre distance = 350 mm) 3 0 6 – 6 S Z 2 9 – 0
Operating voltage of the operating mechanism 230 V AC, 50 Hz K
Auxiliary switch
terminal strip 2)
12 NO + 12 NC
64-pole plug 1)
24-pole plug 2)
6 NO + 6 NC
See page 24
interlocking
Mechanical
24-pole
n n A
n n E
n n G
n n C
n n M
n n n B
n n n F
n n n H
n n n D
n n n N
Special version
Auxiliary switch 12 NO + 12 NC and 24-pole plug (E or F)
Special versions gold-plated contacts and pins
– Z A 2 6 2
Auxiliary switch 6 NO + 6 NC and 24-pole terminal strip (G or H) – Z A 1 7
Auxiliary switch 12 NO + 12 NC and 24-pole terminal strip (M or N) – Z A 1 8
Auxiliary switch 6 NO + 6 NC and 64-pole plug (A or B) – Z A 2 0
Auxiliary switch 12 NO + 12 NC and 64-pole plug (C or D) – Z A 2 1
16th position
AC frequency of operating voltages
Languages of operating instructions and rating plate
Language selection Frequency selection
50 Hz and DC
60 Hz and DC
German
Spanish
English
French
50 Hz
60 Hz
DC
n n n n 0
n n n 1
n n n n 2
n n n 3
n n n n 4
n n n 5
n n n n 6
n n n 7
Other languages on request
Special versions
Additional information on the rating plate (only after consultation
with the order processing department at the Switchgear Factory Berlin).
Information in clear text. – Z Y 1 2
Configuration example
3AH3 vacuum circuit-breaker 3 A H 3
(Ur = 36 kV, 50/60 Hz, Up = 170 kV, Isc = 40 kA, Ir = 2500 A,
pole-centre distance = 350 mm) 3 0 6 – 6 S Z 2 9 – 0 K
Auxiliary switch 6 NO + 6 NC, 64-pole plug and with mechanical interlocking B
Auxiliary switch contacts and pins of the plug connector gold-plated – Z A 2 0
Frequency 50 Hz or DC, operating instructions and rating plate in English 2
Options
Configuration example
3AH3 vacuum circuit-breaker 3 A H 3
Rated voltage Ur = 36 kV (50/60 Hz)
Rated lightning impulse withstand voltage Up = 170 kV
Rated short-circuit breaking current Isc = 40 kA
Pole-centre distance = 350 mm
Rated normal current Ir = 2500 A 3 0 6 – 6
Closing solenoid, 1st shunt release, undervoltage release
and c.t.-operated release with a rated normal current of 1 A S – Z A 4 6
Manual electrical closing at the circuit-breaker,
operating voltage of the closing solenoid 32 V DC Z K 2 B
Operating voltage of the 1st release 48 V DC 2
2nd release as undervoltage release with operating voltage 32 V DC 9 – M 1 B
3rd release as c.t.-operated release 0
Operating voltage of the operating mechanism 230 V AC, 50 Hz K
Auxiliary switch 6 NO + 6 NC, 64-pole plug and with mechanical interlocking B
Auxiliary switch contacts and pins of the plug connector gold-plated – Z A 2 0
Frequency 50 Hz or DC, operating instructions and rating plate in English 2
Routine test certificate enclosed – Z F 2 0
On request, we will be pleased to send you an overview Accessories for the plug connector
of accessories and spare parts, as well as the spare pole Included in the scope of supply of the basic equipment for
assemblies available. Please consider the following infor- 3AH3 vacuum circuit-breakers:
mation for your purchase order.
For 24-pole plug connector
Remark for orders – Lower part of plug
The order numbers in the spare part overview are applicable – Crimp sockets according to number of contacts
to vacuum circuit-breakers of current manufacture. When – Upper part of plug with screwed contacts
mounting parts or spare parts are being ordered for an (no crimp sockets required)
existing vacuum circuit-breaker, always quote the type For 64-pole plug connector
designation, serial number and the year of manufacture of
– Lower part of plug
the circuit-breaker to be sure to get the correct delivery.
– Upper part of plug
Retrofitting – Crimp sockets according to number of contacts
When releases/solenoids are retrofitted, the order numbers
of the mounting parts must also be specified. For other addi- Data on the rating plate
tional equipment, the required mounting parts are included
in the delivery.
HG11-2588c_en eps
the type designation, serial number and year of manufacture
of the circuit-breaker. All data is given on the rating plate.
Note:
For any query regarding spare parts,
subsequent deliveries, etc. the following
three details are necessary:
– Type designation
– Serial No.
– Year of manufacture
R-HG11-205.tif
Contents Page
Technical Data 27
Electrical data, dimensions and weights:
Voltage level 7.2 kV 28
Voltage level 12 kV 28
Voltage level 15 kV 30
Voltage level 17.5 kV 32
Voltage level 24 kV 34
Voltage level 36 kV 36
Circuit diagrams 42
Vacuum interrupter Operating times 44
Short-circuit protection of motors 44
Consumption data of releases 44
3
R-HG11-197.tif
Pole-centre distance
Minimum clearance,
Minimum clearance,
DC component in %
withstand voltage
(can be ordered)
phase-to-phase
phase-to-earth
phase-to-earth
(at 50/60 Hz)
interrupter
Order No.
Weights
Ir tk Isc Ima Up Ud
A mm s kA % kA kA kV kV mV mm mm mm mm kg
125/
3AH3 057-2 … 1250 210 n 3 50 36 56.1 60 20 1.8 160 230 80 130 180 S_325 00415 1 1
130
125/
3AH3 057-6 … 2500 210 n 3 50 36 56.1 60 20 1.8 160 230 80 130 180 S_325 00417 1 1
130
125/
3AH3 057-7 … 3150 210 n 3 50 36 56.1
130
60 20 1.8 160 230 80 130 180 S_325 00001 1 1
125/
3AH3 077-8 … 4000 275 n 3 50 36 56.1 60 20 1.4 160 170 71 130 308 S_325 00004 1 3
130
160/
3AH3 078-2 … 1250 275 n 3 63 36 70.7
164
60 20 1.8 160 170 71 130 196 S_325 00003 2 2
160/
3AH3 078-6 … 2500 275 n 3 63 36 70.7 60 20 1.8 160 170 71 130 196 S_325 00003 2 2
164
160/
3AH3 078-7 … 3150 275 n 3 63 36 70.7
164
60 20 1.8 160 170 71 130 196 S_325 00003 2 2
160/
3AH3 078-8 … 4000 275 n 3 63 36 70.7 60 20 1.4 160 170 71 130 308 S_325 00004 2 3
164
3 12 kV
Ir tk Isc Ima Up Ud
50/60 Hz A mm s kA % kA kA kV kV mV mm mm mm mm kg
125/
3AH3 117-2 … 1250 210 n 3 50 36 56.1
130
75 28 1.8 160 230 80 130 180 S_325 00415 1 1
125/
3AH3 117-6 … 2500 210 n 3 50 36 56.1 75 28 1.8 160 230 80 130 180 S_325 00417 1 1
130
125/
3AH3 117-7 … 3150 210 n 3 50 36 56.1 75 28 1.8 160 230 80 130 180 S_325 00001 1 1
130
125/
3AH3 127-8 … 4000 275 n 3 50 36 56.1 75 28 1.4 160 170 71 130 308 S_325 00004 1 3
130
160/
3AH3 128-2 … 1250 275 n 3 63 36 70.7 75 28 1.8 160 170 71 130 196 S_325 00003 2 2
164
160/
3AH3 128-6 … 2500 275 n 3 63 36 70.7 75 28 1.8 160 170 71 130 196 S_325 00003 2 2
164
160/
3AH3 128-7 … 3150 275 n 3 63 36 70.7
164
75 28 1.8 160 170 71 130 196 S_325 00003 2 2
160/
3AH3 128-8 … 4000 275 n 3 63 36 70.7 75 28 1.4 160 170 71 130 308 S_325 00004 2 3
164
500
200
100
75
50
HG11-2564b_en eps
2
20
1
10
1 2 5 10 20 kA 50 63 100
Breaking current (r.m.s. value)
3
105
105
211 211
668
494
494
668
HG11-2560 eps
HG11-2561 eps
70
105
571 610
601 776
Dimension drawing 1
Dimension drawing 2
694 750
275 275
105
211
494
733
170
HG11-2562 eps
694 776
Dimension drawing 3
Pole-centre distance
Minimum clearance,
Minimum clearance,
DC component in %
withstand voltage
(can be ordered)
phase-to-phase
phase-to-earth
phase-to-earth
(at 50/60 Hz)
interrupter
Order No.
Weights
Ir tk Isc Ima Up Ud
A mm s kA % kA kA kV kV mV mm mm mm mm kg
125/
3AH3 167-2 … 1250 210 n 3 50 36 56.1 95 36 1.8 160 230 110 130 184 S_325 00416 3 4
130
125/
3AH3 167-6 … 2500 210 n 3 50 36 56.1 95 36 1.8 160 230 110 130 184 S_325 00418 3 4
130
125/
3AH3 167-7 … 3150 210 n 3 50 36 56.1
130
95 36 1.8 160 230 110 130 184 S_325 00002 3 4
125/
3AH3 177-8 … 4000 275 n 3 50 36 56.1 95 36 1.4 160 170 135 130 310 S_325 00006 3 6
130
160/
3AH3 178-2 … 1250 275 n 3 63 36 70.7
164
95 36 1.8 160 170 71 130 196 S_325 00005 4 5
160/
3AH3 178-6 … 2500 275 n 3 63 36 70.7 95 36 1.8 160 170 71 130 196 S_325 00005 4 5
164
160/
3AH3 178-7 … 3150 275 n 3 63 36 70.7
164
95 36 1.8 160 170 71 130 196 S_325 00005 4 5
160/
3AH3 178-8 … 4000 275 n 3 63 36 70.7 95 36 1.4 160 170 71 130 308 S_325 00006 4 6
164
500
200
100
75
50
HG11-2565b_en eps
3
20
4
10
1 2 5 10 20 kA 50 63 100
Breaking current (r.m.s. value)
3
105
105
211 211
668
494
494
668
HG11-2560 eps
HG11-2561 eps
70
105
571 610
601 776
Dimension drawing 4
Dimension drawing 5
694 750
275 275
105
211
494
733
170
HG11-2562 eps
694 776
Dimension drawing 6
Pole-centre distance
Minimum clearance,
Minimum clearance,
DC component in %
withstand voltage
(can be ordered)
phase-to-phase
phase-to-earth
phase-to-earth
(at 50/60 Hz)
interrupter
Order No.
Weights
Ir tk Isc Ima Up Ud
A mm s kA % kA kA kV kV mV mm mm mm mm kg
125/
3AH3 217-2 … 1250 210 n 3 50 36 56.1 95 38 1.8 160 230 110 130 184 S_325 00416 5 4
130
125/
3AH3 217-6 … 2500 210 n 3 50 36 56.1 95 38 1.8 160 230 110 130 184 S_325 00418 5 4
130
125/
3AH3 217-7 … 3150 210 n 3 50 36 56.1
130
95 38 1.8 160 230 110 130 184 S_325 00002 5 4
125/
3AH3 227-8 … 4000 275 n 3 50 36 56.1 95 38 1.4 160 170 135 130 310 S_325 00006 5 6
130
160/
3AH3 228-2 … 1250 275 n 3 63 36 70.7
163.8
95 38 1.8 160 170 145 130 198 S_325 00005 6 5
160/
3AH3 228-6 … 2500 275 n 3 63 36 70.7 95 38 1.8 160 170 145 130 198 S_325 00005 6 5
163.8
160/
3AH3 228-7 … 3150 275 n 3 63 36 70.7
163.8
95 38 1.8 160 170 145 130 198 S_325 00005 6 5
160/
3AH3 228-8 … 4000 275 n 3 63 36 70.7 95 38 1.4 160 170 135 130 310 S_325 00006 6 6
163.8
500
200
100
50
HG11-2566b_en eps
30
20 6
5
10
1 2 5 10 20 kA 50 63 100
Breaking current (r.m.s. value)
3
105
105
211 211
668
494
494
668
HG11-2560 eps
HG11-2561 eps
70
105
571 610
601 776
Dimension drawing 4
Dimension drawing 5
694 750
275 275
105
211
494
733
170
HG11-2562 eps
694 776
Dimension drawing 6
34
Order No.
50/60 Hz
24 kV
3AH3 367-8 …
3AH3 267-7 …
3AH3 266-6 …
Ir
A
Rated normal current
Technical Data
Pole-centre distance
4000 300
2500 275
2500 275
mm
n
n
n
O - 3 min - CO - 3 min - CO
O - 0.3 s - CO - 3 min - CO
O - 0.3 s - CO - 15 s - CO
3
3
3
tk
Rated duration of short-circuit
Electrical data, dimensions and weights
Isc
kA
Rated short-circuit breaking current
50
50
40
DC component in %
36
36
36
of the rated short-circuit breaking current
Asymmetrical breaking current
kA
56.1
56.1
44.9
kA
Ima
130
130
104
125/
125/
100/
(at 50/60 Hz)
Up
kV
Rated lightning impulse withstand voltage
125
110
125
Ud
kV
50
50
50
withstand voltage
Voltage drop ΔU between connections
1.5
1.5
2.0
mV
(according to IEC 62271-1 at DC 100 A)
Minimum creepage distance,
interrupter
Minimum creepage distance,
phase-to-earth
Minimum clearance,
phase-to-phase
161 207 440 197 Minimum clearance,
161 170 228 180
360 226 245 173
mm mm mm mm
phase-to-earth
Weights
kg
350
198
168
9
9
7
500
200
100
50
HG11-2567d_en eps
7
20
8 9
10
1 2 5 10 20 31.5 40 50 kA 100
Breaking current (r.m.s. value)
211
3
105
494
668
210
900
1030
778
494
max.70
HG11-2755 eps
194
HG11-2568 eps
599,5 776
645 704
1051 750
736,5 300 300
80
211
105
494
733
1180
max.60
HG11-2756 eps
824
Dimension drawing 9
Pole-centre distance
Minimum clearance,
Minimum clearance,
DC component in %
withstand voltage
(can be ordered)
phase-to-phase
phase-to-earth
phase-to-earth
(at 50/60 Hz)
interrupter
Order No.
Weights
Ir tk Isc Ima Up Ud
A mm s kA % kA kA kV kV mV mm mm mm mm kg
80/
3AH3 305-2 … 1250 350 n 3 31.5 36 35.4 170 70 2.3 360 330 314 260 170 S_325 00008 8 10
82
80/
3AH3 305-4 … 2000 350 n 3 31.5 36 35.4 170 70 2.3 360 330 314 260 175 S_325 00008 8 10
82
80/
3AH3 305-6 … 2500 350 n 3 31.5 36 35.4
82
170 70 2.3 360 330 314 260 175 S_325 00009 8 11
80/
3AH3 305-7 … 3150 350 n 3 31.5 36 35.4 170 70 1.9 366 430 309 270 350 S_325 00057 8 12
82
80/
3AH3 305-8… 4000 350 n 3 31.5 36 35.4
82
170 70 1.9 366 430 309 270 350 S_325 00057 8 12
100/
3AH3 306-6 … 2500 350 n 3 40 36 44.9 170 70 2.0 360 330 314 260 175 S_325 00009 7 11
104
100/
3AH3 306-7… 3150 350 n 3 40 36 44.9
104
170 70 1.9 366 430 309 270 350 S_325 00058 7 12
100/
3AH3 306-8… 4000 350 n 3 40 36 44.9 170 70 1.9 366 430 309 270 350 S_325 00058 7 12
104
500
200
100
50
HG11-2567d_en eps
7
20
8 9
10
1 2 5 10 20 31.5 40 50 kA 100
Breaking current (r.m.s. value)
3
105
105
211 211
1000
1000
791
494
734
494
234
234
HG11-2570 eps
HG11-2569 eps
1012 870
679 268,5 350 350
ca.105
211
1126,5
986,5
494
max.70
HG11-2781 eps
920
Dimension drawing 12
Pole-centre distance
Minimum clearance,
Minimum clearance,
DC component in %
withstand voltage
(can be ordered)
phase-to-phase
O - 30 min - CO
according to IEEE C37.013
phase-to-earth
phase-to-earth
(at 50/60 Hz)
interrupter
Order No.
Weights
Ir tk Isc Ima Up Ud
A mm s kA % kA kA kV kV mV mm mm mm mm kg
3AH3 712-4 … 5000 300 n 3 50 75 73 137 110 50 1.4 160 230 230 230 470 S_325 00587 14
3AH3 712-5 … 6300 300 n 3 50 75 73 137 110 50 1.4 160 230 230 230 500 S_325 00587 14
3AH3 713-4 … 5000 300 n 3 63 65 86 173 110 50 1.4 160 230 230 230 470 S_325 00588 15
3AH3 713-5 … 6300 300 n 3 63 65 86 173 110 50 1.4 160 230 230 230 500 S_325 00588 15
3AH3 714-4 … 5000 300 n 3 72 65 96 198 110 50 1.4 160 230 230 230 470 S_325 00589 15
3AH3 714-5 … 6300 300 n 3 72 65 96 198 110 50 1.4 160 230 230 230 500 S_325 00589 15
3AH3 817-7 … 3150 275 n 3 50 75 73 137 110 50 1.4 160 170 145 130 230 S_325 00592 13
3AH3 817-8 … 4000 275 n 3 50 75 73 137 110 50 1.4 160 170 135 130 320 S_325 00593 14
3 3AH3 818-7 …
3AH3 818-8 …
3150 275
4000 275
n
n
3
3
63
63
65
65
86
86
173
173
110
110
50
50
1.4
1.4
160 170 145 130
320
S_325 00019
S_325 00030
16
14
3AH3 819-7 … 3150 275 n 3 72 65 96 198 110 50 1.4 160 170 145 130 250 S_325 00019 16
3AH3 819-8 … 4000 275 n 3 72 65 96 198 110 50 1.4 160 170 135 130 320 S_325 00030 14
433 600
269,5 109 275 275 271,5 211 275 275
80 80
211 211
ca.90
104
668
494
494
900
733
HG11-2571 eps
1000
HG11-2572 eps
max.70
max.70
119
840
356 410 300 300
211
3
104
494
1180
915
HG11-2573 eps
max. 60
Dimension drawing 15
433
269,5 109 275 275
80
211
104
668
494
900
HG11-2574 eps
59
119
Dimension drawing 16
Pole-centre distance
Minimum clearance,
Minimum clearance,
DC component in %
withstand voltage
(can be ordered)
phase-to-phase
O - 30 min - CO
according to IEEE C37.013
phase-to-earth
phase-to-earth
(at 50/60 Hz)
interrupter
Order No.
Weights
Ir tk Isc Ima Up Ud
A mm s kA % kA kA kV kV mV mm mm mm mm kg
3AH3 722-2 … 3150 300 n 3 50 75 73 137 125 50 1.6 160 220 538 170 350 S_325 00913 9
3AH3 722-3 … 4000 300 n 3 50 75 73 137 125 50 1.6 160 220 538 170 350 S_325 00597 9
3AH3 722-4 … 5000 300 n 3 50 75 73 137 125 50 1.6 160 207 293 170 470 S_325 00914 15
3AH3 722-5 … 6300 300 n 3 50 75 73 137 125 50 1.6 160 207 293 170 500 S_325 00910 15
3AH3 723-2 … 3150 300 n 3 63 65 86 173 125 50 1.6 160 220 538 170 350 S_325 00915 9
3AH3 723-3 … 4000 300 n 3 63 65 86 173 125 50 1.6 160 220 538 170 350 S_325 00909 9
3AH3 723-4 … 5000 300 n 3 63 65 86 173 125 50 1.6 160 207 293 170 470 S_325 00916 15
3AH3 723-5 … 6300 300 n 3 63 65 86 173 125 50 1.6 160 207 293 170 500 S_325 00911 15
3 3AH3 724-2 …
3AH3 724-3 …
3150 300
4000 300
n
n
3
3
72
72
65
65
96
96
198
198
125
125
50
50
1.6
1.6
160 220 538 170
350
S_325 00917
S_325 00918
9
3AH3 724-4 … 5000 300 n 3 72 65 96 198 125 50 1.6 160 207 293 170 470 S_325 00919 15
3AH3 724-5 … 6300 300 n 3 72 65 96 198 125 50 1.6 160 207 293 170 500 S_325 00920 15
1051 750
736,5 300 300
80
211
105
494
733
1180
max.60
HG11-2756 eps
824
Dimension drawing 9
356
840
410 300 300
3
211
104
494
1180
915
HG11-2573 eps
max.60
Dimension drawing 15
Circuit diagrams
The circuit diagrams shown here are examples from the manifold possibilities of circuit-breaker wiring.
-S10 -S11 -Y9 -X0
HE
-M1 M P 11 13 21 23 31 33 41 43 51 53 61 63
-S1
12 14 22 24 32 34 42 44 52 54 62 64
-S7 -S6
HG11-2575_en eps
OPEN release
HG11-2579a eps
HA
-Y1
-X0
Manual closing – manual opening with auxiliary switch 6 NO + 6 NC Contacts available for customer with basic circuit-
breaker equipment and auxiliary switch 6 NO + 6 NC
32
OPENrelease
3 HA
-Y1
-S15
14
13
-Y9
A1
A2
-K1
A1
A2
HG11-2580b eps
-X0
Motor operating mechanism with manual electrical closing Manual Closing and
electrical closing anti-pumping
The available possible combinations are described in the chapter “Selection of secondary equipment”.
-X0 -X0 -X0 -X0
33 43
-S1 -S1
34 44
D1
-Y7 U<
D2
A1 A1 A1 1
-Y2 -Y4 -Y6 -R1
A2 A2 A2 2
HG11-2583 eps
HG11-2584 eps
HG11-2585 eps
HG11-2586 eps
HG11-2578d eps
HG11-2577b eps
-X0 -X0
Motor operating mechanism with manual mechanical closing Circuit-breaker Signal “closing 1st shunt
tripping signal spring charged” release
-X0 -X0
21
-S21
22
A1
11 13 21 23 31 33 41 43 51 53 61 63 71 73 81 83 91 93 101 103 111 113 121 123
-M1 1M= -S1
12 14 22 24 32 34 42 44 52 54 62 64 72 74 82 84 92 94 102 104 112 114 122 124
D2
22
3
HG11-2581b eps
-S22
HG11-2582a eps
21
-X0 -X0
Motor operating Contacts available for customer with basic circuit-breaker equipment
mechanism Auxiliary switch –S1 (12 NO + 12 NC) instead of auxiliary switch 6 NO + 6 NC
Operating times
Rated voltage Operating voltage Power consumption of the motor Smallest possible rated
of the motor current 2) of the m.c.b.
(miniature circuit-breaker)
with C-characteristic
3 V
24 DC
48 DC
max. V
26
53
min. V
20
41
W (at DC)
500
500
VA (at AC)
–
–
16
8
A
60 DC 66 51 500 – 6
110 DC 121 93 500 – 4
220 DC 242 187 500 – 2
110 AC 121 93 – 650 4
230 AC 244 187 – 650 2
2) The current inrush in the drive motor can be neglected due to its very short presence.
Operation at
3) Consumption at pickup current (90 % of the rated normal current) and open armature.
Contents Page
Annex 45
Inquiry form 46
Configuration instructions 47
Configuration aid Foldout page
R-HG11-181.tif
4
R-HG11-180.eps
Inquiry concerning
Technical Data Other values
Rated short-duration o 20 kV o 32 kV o 36 kV o 38 kV
power-frequency withstand voltage o 50 kV o 70 kV o 95 kV o _ _ _ kV
Please
Rated short-circuit o 31.5 kA o 40 kA o 50 kA
breaking current o 63 kA o 72 kA o _ _ _ kA
o Submit an offer
o 1250 A o 2000 A o 2500 A o 3150 A
o Call us Rated normal current
o 4000 A o 5000 A o 6300 A o ___A
o Visit us
Pole-centre distance o 210 mm o 275 mm o 300 mm o 350 mm
Secondary equipment
For possible combinations see pages 17 to 23
Your address
Circuit-breaker equipment o Manual mechanical closing
o Manual electrical closing
Company o Manual operating mechanism
4
E-mail terminal strip
o Mechanical interlocking
Dept.
Name
Street
Postal code/city
Fax
1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16
3 A H 3 n n n – n n n n n – n n n n – Z
Instruction for configuration of the 3AH3 vacuum circuit-breaker
See page 13
See page 17
See page 18
See page 19
See page 20
See page 21
See page 22
See page 23
See page 23
See page 24
page 16
to
Please specify the following ratings: Possible options:
3 A H 3 – –
+ + + +
2nd step: Definition of the secondary equipment (see pages 17 to 23)
+ + + +
+ + + +
Release combination Shunt release, current-transformer operated release
(position 9) and undervoltage release
Closing solenoid Operating voltages from 24 V DC to 240 V AC + + + +
(position 10)
Operating voltage of the releases Operating voltages from 24 V DC to 240 V AC 3 A H 3 – –
(positions 11/12)
Type of local closing Mechanical closing, + + + +
(position 10) manual electrical closing
Type of operating mechanism and operating voltage of a motor, Manual operating stored-energy mechanism,
if available (position 14) motor operating stored-energy mechanism + + + +
with operating voltages from 24 V DC to 240 V AC
Number of auxiliary contacts 6 NO + 6 NC, 12 NO + 12 NC 3 A H 3 – –
(position 15)
Design of the secondary connection 24-pole terminal strip, 24-pole plug connector,
(position 15) 64-pole plug connector + + + +
Language of the documentation English, German, French, Spanish, other languages on request
(position 16) + + + +
Frequency of the operating voltage of the 50 Hz/60 Hz
secondary equipment at AC (position 16)
3 A H 3 – –
+ + + +
3rd step: Do you have any further requirements concerning the equipment? (Please refer to page 24) 3 A H 3 – –
Should you still need more options than the possible special equipment like halogen-free and
+ + + +
flame-retardant or silicone-free version, condensation protection or an additional rating plate, etc.,
please contact your responsible sales partner. + + + +
3 A H 3 – –
+ + + +
+ + + +
3 A H 3 – –
+ + + +
+ + + +
Siemens HG 11.03 · 2010 47