Professional Documents
Culture Documents
The apparatus used for controlling, regulating and switching on or off the
electrical circuit in the electrical power system is known as switchgear. The
switches, fuses, circuit breaker, isolator, relays, current and potential
transformer, indicating instrument, lightning arresters and control panels are
examples of the switchgear devices.
The switchgear system is directly linked to the supply system. It is placed in both
the high and low voltage side of the power transformer. It is used for de-
energizing the equipment for testing and maintenance and for clearing the fault.
Overview
When the fault occurs in the power system, heavy current flow through equipment
due to which the equipment get damaged, and the service also get interrupted.
So to protect the lines, generators, transformers and other electrical equipment
from damage automatic protective devices or switchgear devices are required.
The automatic protective switchgear mainly consists of the relay and circuit
breaker. When the fault occurs in any section of the system, the relay of that
section comes into operation and close the trip circuit of the breaker which
disconnects the faulty section. The healthy section continues supplying loads as
usual, and thus there is no damage to equipment and no complete interruption of
supply.
The earliest central power stations used simple open knife switches, mounted on
insulating panels of marble or asbestos. Power levels and voltages rapidly
escalated, making opening manually operated switches too dangerous for
anything other than isolation of a de-energized circuit. Oil-filled switchgear
equipment allow arc energy to be contained and safely controlled. By the early
20th century, a switchgear line-up would be a metal-enclosed structure with
electrically operated switching elements, using oil circuit breakers. Today, oil-filled
equipment has largely been replaced by air-blast, vacuum, or SF6 equipment,
allowing large currents and power levels to be safely controlled by automatic
equipment.
High-voltage switchgear was invented at the end of the 19th century for
operating motors and other electric machines. The technology has been improved
over time and can now be used with voltages up to 1,100 kV.
Functions
One of the basic functions of switchgear is protection, which is interruption of
short-circuit and overload fault currents while maintaining service to unaffected
circuits. Switchgear also provides isolation of circuits from power supplies.
Switchgear is also used to enhance system availability by allowing more than one
source to feed a load.
Componenets
A switchgear assembly has two types of components:
VOLTAGE CONSIDERATION
If only one tap changer is required, manually operated tap points are
usually made on the high voltage (primary) or lower current winding of
the transformer to minimize the current handling requirements of the
contacts. However, a transformer may include a tap changer on each
winding if there are advantages to do so. For example, in power
distribution networks, a large step-down transformer may have an off-
load tap changer on the primary winding and an on- load automatic tap
changer on the secondary winding or windings. The high voltage tap is
set to match long term system profile on the high voltage network
(typically supply voltage averages) and is rarely changed. The low
voltage tap may be requested to change positions multiple times each
day, without interrupting the power delivery, to follow loading
conditio ns on the low-voltage (secondary winding) network.
To minimize the number of winding taps and thus reduce the physical size
of a tap changing transformer, a 'reversing' tap changer winding may be
used, which is a portion of the main winding able to be connected in its
opposite direction (buck) and thus oppose the voltage.
Apart from tap selection, the most important task of an OLTC is the break
function or current (load) transferring action. After transferring the
current, the contact which “breaks” must be capable of withstanding the
recovery voltage. The required switching capacity (the product of switched
current and recovery voltage) for a specific contact in an OLTC is based
on the relevant step voltage and cur- rent but is also determined by the
design and circuit of the OLTC. The switching capacity itself is primarily
a function of the contact design, contact speed and arc-quenching agent.
The OLTC design that is normally used for higher ratings and higher
voltages comprises a diverter switch (arcing switch) and a tap selector.
For lower ratings, OLTC designs in which the functions of the diverter
switch (arcing switch) and the tap selector are combined in a selector
switch (arcing tap switch) are used.
With an OLTC comprising a diverter switch (arcing switch) and a tap
selector, the tap-change operation takes place in two steps. The next tap is
first preselected by the tap selector at no load. The diverter switch then
transfers the load current from the tap in operation to the preselected
tap. The OLTC is operated by means of a drive mechanism. The tap
selector is operated by a gearing directly from the drive mechanism. At the
same time, a spring energy accumulator is tensioned, which operates the
diverter switch – after release at a very short time interval – independently
of the motion of the drive mechanism. The gearing ensures that this
diverter switch operation always takes place after the tap preselection
operation has finis hed. The switching time of a diverter switch is
between 40 and 60 Ms with today’s designs. During diverter switch
operation, transition resistors are inserted which are loaded for 20–30
Ms, i.e. the resistors can be designed for short-term loading. The
amount of resistor material required is therefore relatively small. The
total operation time of an OLTC is between 3 and 10 seconds, depending
on the respective design.
A selector switch (arcing tap switch) as shown in carries out the tap-
change in one step from the tap in service to the adjacent tap. The spring
energy accumulator, wound up by the drive mechanism actuates the
selector switch sharply after releasing.
Fig. oil type OLTC
(2) DESCRIPTION OF EQUIPMENTS
TAP CHANGER TYPE M
VERSATILITY:
REDUCED MAINTENANCE:
PROTECTIVE RELAYS:
Check that the operating positions of all columns are identical (tap-changer
head,
inspection window). Each one of the one-phase OLTCs must be in
the adjustment position.
Turn the upper gear unit of the tap-changer heads into the desired
installation position
and fix them there (tighten thrust collars and tab-lock the screws).
Take note of the arrow on the drive shaft flange below the punched
serial number. The direction of the arrow indicates the rotation
sense when crank- ing the motor drive clockwise and must be
identical on all gear units.
Operate the tap-changer poles separately by one step by rotating the
trunnions counter-
clockwise until the diverter switch operates once. Check coincidence of
operating positions of all tap-changer heads.
Mount the horizontal drive shaft between the tap- changer heads.
Return the OLTC set that is all tap-changer poles together, into the
adjustment position. The adjustment position is reached by turning
the drive shaft in clockwise direction.
Check simultaneous operation of all diverter switches. Check
coincidence of position of all tap- changer heads and the motor
drive unit.
Mount the vertical drive shaft.
Make sure that bevel gear serial number and on-load tap-changer
serial number are identica l. The horizontal drive shaft must be in
proper alignment with the trunnion in the tap-changer head.
After loosening the thrust collar (6 bolts M8, was. 13) the upper
gear unit can be swivelled (fig. 39). After adjusting the upper gear
unit, the thrust collar must be re-tightened (max. torque 15 Nm).
Tab-lock the screws. In case of bevel gears in special design and
intermediate bearings of the vertical or horizontal drive shaft above
instructions apply analogously.