You are on page 1of 44

Form No: USM0408B - 60Hz

- 203-522Tons
INSTALLATION,
INSTALLATION, ®

OPERATION
OPERATION AND
AND Products That Perform . . .By People Who Care

MAINTENANCE
MAINTENANCE
MANUAL
MANUAL
AIR COOLED
ROTARY
SCREW
60 Hz FLOODED
CHILLERS

ACFX 200-6
ACFX 220-6
ACFX 250-6
ACFX 280-6
ACFX 300-6
ACFX 330-6
ACFX 360-6
ACFX 420-6
ACFX 450-6
ACFX 480-6
ACFX 500-6
ACFX 530-6
TABLE OF CONTENTS

DESCRIPTION PAGE NO
1.0 INTRODUCTION
1.1 Nomenclature............................................................................................................................................................. 4

2.0 INSTALLATION
2.1 General ........................................................................................................................................................................ 7
2.1.1
Application Precautions.................................................................................................................................... 7
2.1.2
Chilled Water Flow........................................................................................................................................... 7
2.2 Inspection.................................................................................................................................................................... 7
2.3 Rigging ........................................................................................................................................................................ 7
2.3.1 General.............................................................................................................................................................. 7
2.3.2 Rigging & Moving............................................................................................................................................ 7
2.4 Space Requirements and Clearance.................................................................................................................... 9
2.4.1 General.............................................................................................................................................................. 9
2.4.2 ACFX................................................................................................................................................................ 9
2.5 Foundation................................................................................................................................................................ 14
2.6 Vibration Isolation................................................................................................................................................. 14
2.7 Piping connections.................................................................................................................................................. 14
2.8 Electrical Wiring..................................................................................................................................................... 14
2.9 Controls..................................................................................................................................................................... 17
2.9.1 Connections .................................................................................................................................................... 17
2.9.2 Settings ........................................................................................................................................................... 17
2.10 Request For Start-Up Representative ............................................................................................................... 17

3.0 OPERATION
3.1 General ...................................................................................................................................................................... 18
3.2 Unit piping ................................................................................................................................................................ 18
3.3 System Water Flow Rate ...................................................................................................................................... 18
3.4 Standard Ambient Unit Operation (65°F Minimum Ambient)
Including Overnight Shut Down and Morning Restart............................................................................... 18
3.4.1 Air Cooled Package Chiller Start-Up ............................................................................................................. 18
3.5 System Start Up....................................................................................................................................................... 18
3.6 Shut-Down (Overnight Or Weekend)............................................................................................................... 22
3.7 Seasonal Shut-Down Procedure.......................................................................................................................... 22
3.8 Seasonal Start-up Procedure............................................................................................................................... 22
3.9 Safety Relief Valves................................................................................................................................................ 23
3.10 Refrigeration Cycle- Multiple Compressor ACFX........................................................................................ 23
3.11 Fan Cycling .............................................................................................................................................................. 23
3.12 Liquid Injection....................................................................................................................................................... 23
3.13 Hydraulic Capacity Control System.................................................................................................................. 23

4.0 ELECTRICAL
4.1 Electrical Data......................................................................................................................................................... 25
4.2 Wiring Diagram...................................................................................................................................................... 25
4.3 Typical Operation................................................................................................................................................... 25
4.4 Microcomputer Controller .................................................................................................................................. 31
4.4.1 To Display Data From The Menu ................................................................................................................... 31
4.4.2 To Reset All Control Points To Computer Control........................................................................................ 32
4.4.3 To Display Ala rms .......................................................................................................................................... 32
4.4.4 To Become Authorized ................................................................................................................................... 32
4.4.5 To Alter Setpoint Data.................................................................................................................................... 32
4.4.6 To Calibrate Temperature And Pressure Sensors ........................................................................................... 32
4.4.7 To Set Date And Time .................................................................................................................................... 33
4.4.8 To Display Data Without Accessing Menu .................................................................................................... 33
4.4.9 Unit Schedule Of Operation............................................................................................................................ 33
TABLE OF CONTENTS

DESCRIPTION PAGE NO
4.5 Control Functions ................................................................................................................................................... 34
4.5.1 Chilled Water Pump Interlock And Flow Switch (CWP And CWFS)........................................................... 34
4.5.2 Customer Interlock.......................................................................................................................................... 34
4.5.3 Anti-Recycle Timer (Microcomputer)............................................................................................................ 34
4.5.4 Load Control (Microcomputer)....................................................................................................................... 34
4.5.5 Ramp Control (Microcomputer) ..................................................................................................................... 35
4.5.6 Current Limiting (Microcomputer)................................................................................................................. 36
4.5.7 Staging Control (Microcomputer)................................................................................................................... 36
4.5.8 Manual lead-Lag Control (Microcomputer) ................................................................................................... 36
4.5.9 Manual Load-Unload Control (Microcomputer) ............................................................................................ 36
4.5.10 Chilled Water Reset And Customer Control Interlock (Optional).................................................................. 36
4.5.11 Variable Fan Speed Control (Optional) .......................................................................................................... 37
4.5.12 Sump Heater Control....................................................................................................................................... 37

4.6 Safety Functions ...................................................................................................................................................... 37


4.6.1 Control Power Loss (Microcomputer)............................................................................................................ 37
4.6.2 Low Pressure Cut-Off (Microcomputer)......................................................................................................... 37
4.6.3 Evaporator Freeze Shutoff (Microcomputer).................................................................................................. 37
4.6.4 High Pressure Cut-Off (Microcomputer)........................................................................................................ 37
4.6.5 Oil Level Sensor (LS) ..................................................................................................................................... 37
4.6.6 High Oil Temperature Thermostat (12 TAS).................................................................................................. 38
4.6.7 Motor Temperature Protector (1TAS) ............................................................................................................ 38
4.6.8 Overload Protector (OL) ................................................................................................................................. 38
4.6.9 Phase Control Relay (PCR)............................................................................................................................. 38
4.6.10 Sensor Alarm (Microcomputer)...................................................................................................................... 38
4.6.11 No-Stop Alarm (Microcomputer) ................................................................................................................... 38
4.6.12 Low Differential Pressure Alarm (Microcomputer) ....................................................................................... 38

5.0 MAINTENANCE
5.1 General ...................................................................................................................................................................... 39
5.2 Periodic Inspection................................................................................................................................................. 39
5.3 Monthly Inspection................................................................................................................................................ 39
5.4 Vessel Maintenance................................................................................................................................................ 39
5.4.1
General............................................................................................................................................................ 39
5.4.2
Water Side Cleaning Of Cooler...................................................................................................................... 39
5.5 Air Cooled Condenser Cleaning ......................................................................................................................... 39
5.6 Electrical Malfunction .......................................................................................................................................... 41
5.7 Refrigerant Charge................................................................................................................................................ 41
5.8 Oil Charge ................................................................................................................................................................ 41
5.9 Troubleshooting ...................................................................................................................................................... 42
5.10 Sample Log Sheet ................................................................................................................................................... 43

SCHEMATIC DIAGRAM, GRAPH AND TABLE


DESCRIPTION PAGE NO DESCRIPTION PAGE NO
Figure 2.3.2 Typical Rigging.................................................... 8 Table 1.1 Physical Specifications..........................................5
Figure 2.4.1 Space Requirements.............................................. 9
Figure 2.4.2 Dimensional Data............................................... 11 Table 4.2 Control Data Sheet ..............................................31
Figure 2.5 Isolator Location ................................................ 15 Table 4.5.5 Sample Ramp Times (Minutes) .............................35
Figure 2.5A Isolator Location ................................................ 16
Figure 2.5B Isolator Point Load Data...................................... 16 Table 5.4.2 R-22 P ressure/Temperature Properties...................40
Figure 3.2 Typical Piping Schematic .................................... 19
Figure 3.3 Cooler Water Pressure Drop ................................ 21
Figure 3.13 Compressor Capacity Control Detail..................... 24
Figure 4.2 Typical Wiring Schematic................................... 27
1.0 INTRODUCTION

This manual is prepared to provide all the necessary information for


installation, operation and maintenance of the latest generation of the
Dunham-Bush medium screw compressor air-cooled packaged chillers.

To utilize this manual effectively, you must first identify your unit
model from the unit nameplate.

Your Dunham-Bush package has been manufactured under a careful


quality control system. If the package is installed, operated and
maintained with care and attention to the instructions contained herein,
it will yield many years of satisfactory service.

It is assumed that the user of this manual and those who install, operate
and maintain this equipment are experienced and qualified air
conditioning equipment personnel.

1.1 NOMENCLATURE

AC F X 250 - 6 S R

Air Cooled Chiller


Blank - R22
R - R134a
Flooded Evaporator

Screw Compressor
S - Standard Unit
Q - Special Unit
Nominal Tons
Twin Compressors = 200, 220, 250,
280, 300, 330,
360
Three Compressors = 420, 450, 480, 5 = 50Hz
500, 530 6 = 60Hz
1.0 INTRODUCTION

TABLE 1.1 PHYSICAL SPECIFICATIONS


MODEL ACFX 200-6 ACFX 220-6 ACFX 250-6 ACFX 280-6 ACFX 300-6 ACFX 330-6

COMPRESSOR

MODEL (QTY) MSC1210(2) MSC 1210(1) MSC 1212(2) MSC 1212(1) MSC 1215(2) MSC 1215(1)
MSC 1212(1) MSC 1215(1) MSC 1218(1)

RPM 3500 3500 3500 3500 3500 3500

OIL CHARGE (QTY) GAL 10.50 (2) 10.50 (1) 10.25 (2) 10.25 (1) 12.50 (2) 12.50 (2)
10.25 (1) 12.50 (1)

SUMP HEATER (QTY) kW 0.4 (2) 0.4 (2) 0.4 (2) 0.4 (2) 0.4 (2) 0.4 (2)

NOMINAL CAPACITY TR 203.3 222.4 250.2 274.9 301.1 326.7

COMPRESSOR KWI 216.8 238.7 259.7 282.3 306.6 339.1

FAN KWI 22.8 26.6 30.4 30.4 30.4 34.2

UNIT EER 10.18 10.06 10.35 10.55 10.72 10.50

MIN. % UNIT CAPACITY 12.50% 13.30% 12.50% 13.20% 12.50% 13.00%


REDUCTION

EVAPORATOR

MODEL (QTY) EF14102M EF16102M EF18102M EF18102M EF18102M EF18102M


076KAG (2) 098KAG (2) 128KAG (2) 128KAG (2) 128KAG (2) 144KAG(2)

WATER CONNECTOR INCH 6 6 8 8 8 8

NOM. WATER FLOW (GPM)/ PD 501 / 556 / 617 / 684 / 760 / 828/
(FT IN WG) (7.9 X 2) (6.2 X 2) (4.4 X 2) (5.3 X 2) (6.5 X 2) (6.2 X 2)

MIN/MAX WATER FLOW (GPM) 222 / 886 288 / 1150 378 / 1500 378/ 1500 378/ 1500 425/ 1680

MIN/MAX WATER PD (FT IN WG) (1.8/ 22.0) (1.9/ 24.0) (1.8/ 22.2) (1.8/ 22.2) (1.8/ 22.2) (1.8/ 22.5)
X2 X2 X2 X2 X2 X2

CONDENSER

COIL ROWS DEEP/ TOTAL FA 3 / 282.3 3 / 329.4 3 / 376.4 3 / 188.2 4 / 376.4 4/423.5
FT² 4 / 188.2

NO OF FAN 12 14 16 16 16 18

FAN DIA (QTY) INCH 31.5 (12) 31.5 (14) 31.5 (16) 31.5 (16) 31.5 (16) 31.5 (9),
31.5 (9)

FLA , AMP (QTY) 3.6 (12) 3.6 (14) 3.6 (16) 3.6 (16) 3.6 (16) 3.6 (18)

*MIN. AMBIENT TEMPERATURE 65 65 65 65 65 65


(°F) AT MIN. LOAD

GENERAL

UNIT LENGTH INCH 322.5 365 402 402 402 444

UNIT WIDTH INCH 88 88 88 88 88 88

UNIT HEIGHT INCH 96 96 96 96 96 96

SHIPPING WEIGHT LBS 16035 18623 20713 21596 22522 23080

OPERATING WEIGHT LBS 16494 19218 21479 22362 23288 23900

OPERATING CHARGE R-22 LBS 472 524 582 644 716 780

* 45°F WITH SOLENOID CONTROL AND FAN CYCLING.


1.0 INTRODUCTION

MODEL ACFX 360-6 ACFX 420-6 ACFX 450-6 ACFX 480-6 ACFX 500-6 ACFX 530-6

COMPRESSOR

MODEL (QTY) MSC 1218(2) MSC 1212(1) MSC 1215(3) MSC 1215(2) MSC 1215(1) MSC 1218(3)
MSC 1215(2) MSC 1218(1) MSC 1218(2)

RPM 3500 3500 3500 3500 3500 3500

OIL CHARGE (QTY) GAL 12.50 (2) 10.25 (1) 12.50 (3) 12.50 (3) 12.50 (3) 12.50 (3)
12.50 (2)

SUMP HEATER (QTY) kW 0.4 (2) 0.4 (3) 0.4 (3) 0.4 (3) 0.4 (3) 0.4 (3)

NOMINAL CAPACITY TR 355.4 417.2 446.9 472.5 500.1 521.7

COMPRESSOR KWI 373.9 434.7 458.0 494.1 530.0 565.1

FAN KWI 34.2 54.0 54.0 60.0 66.0 72.0

UNIT EER 10.45 10.24 10.47 10.23 10.47 9.83

MIN. % UNIT CAPACITY 12.50% 5.90% 8.33% 7.80% 7.40% 8.33%


REDUCTION

EVAPORATOR

MODEL EF20102M EF24125H EF26125H EF28125H EF28125H EF28125H


180KAG(2) 298KAJ 336KAJ 358KAJ 378KAJ 395KAJ

WATER CONNECTOR INCH 8 8 10 10 10 10

NOM. WATER FLOW (GPM)/ PD 898/ 1022/ 18.5 1089/ 17.0 1156/ 17.3 1224/ 17.3 1291/ 17.6
(FT IN WG) (5.2 X 2)

MIN/MAX WATER FLOW (GPM) 525/ 2100 299/ 1496 329/ 1643 350/ 1750 370/ 1848 387/ 1931

MIN/MAX WATER PD (FT IN WG) (1.9/ 24.2) X 2 2.0/ 37.0 1.9/ 36.0 2.0/ 36.5 2.0/ 36.5 2.0/ 36.5

CONDENSER

COIL ROWS DEEP/ TOTAL FA 4/423.5 3/192.5, 4/577.5 4/577.5 4/577.5 4/577.5
FT² 4/385.0

NO OF FAN 18 18 18 18 18 18

FAN DIA. (QTY) INCH 31.5 (18) 31.5 (6), 33.9 (18) 33.9 (18) 33.9 (18) 33.9 (18)
33.9 (12)

FLA , AMP (QTY) 3.6 (18) 4.3 (18) 4.3(18) 4.3(12), 4.3(6), 5.7(18)
5.7(6) 5.7(12)

*MIN. AMBIENT TEMPERATURE 65 65 65 65 65 65


(°F) AT MIN. LOAD

GENERAL

UNIT LENGTH INCH 444 473 473 473 473 473

UNIT WIDTH INCH 88 88 88 88 88 88

UNIT HEIGHT INCH 96 118 118 118 118 118

SHIPPING WEIGHT LBS 24595 28858 29991 32036 33179 34308

OPERATING WEIGHT LBS 25610 29767 31032 33178 34362 35527

OPERATING CHARGE R-22 LBS 846 963 1025 1089 1152 1216

* 45°F WITH SOLENOID CONTROL AND FAN CYCLING.


2.0 INSTALLATION

2.1 GENERAL 2.) Check the model number and the electrical
characteristics on the nameplate to determine
Packaged chillers are designed to cool water or
if they are correct.
other non-corrosive liquid. The liquid to be
cooled is to be circulated through the tubes of a 3.) Check for freight damage, shortages or other
refrigerant evaporator where the temperature is discrepancies and note them on the delivery
reduced to the desired level. The heat absorbed by receipt before signing.
the refrigerant in the evaporator is rejected via the In the event of any damage, a damage claim
condenser coils where it raises the temperature of
should be filed immediately by the purchaser.
cross flow air.
Care should be taken to see that the equipment is
properly installed and adjusted. An installer or
operator should first be familiar with the 2.3 RIGGING
information contained in this manual. 2.3.1 GENERAL
Each unit has been carefully tested at the
2.1.1 APPLICATION PRECAUTIONS factory where every precaution is taken to
ensure that the unit reaches you in perfect
The following instructions are intended to
condition. It is very important that the
help ensure that your water chilling
machine performs adequately. riggers and movers use the same care and
precaution in moving the equipment into
place. Make sure that chains, cables or
2.1.2 CHILLED WATER FLOW other moving equipment are placed so as
The Dunham-Bush ACFX Packaged to prevent damage to the unit or piping.
Water Chiller is designed for constant The refrigerant piping must not be used as
chilled water flow rate, even when the a ladder or a handle. Do not attach a chain
cooling load varies. The machine will hoist sling to the piping or equipment.
generally perform satisfactorily with Move the unit in an upright position and
steady flow rates deviating from design by let it down gently from trucks or rollers.
as much as ±10%. However, varying water
flow rates can cause instability in control 2.3.2 RIGGING AND MOVING
which will result in undesirable system
effects, particularly poor control of leaving Any unit mounted on skids may be moved
chilled water temperature. If two-way with a forklift, but care must be taken not
valves are used to control flow through the to damage the unit with forks. The skids
cooling coils, some means such as an should not be removed until the unit is at
automatic modulating valve should be its final location.
provided in the system to maintain steady The ACFX model is to be rigged through
flow through the cooler. the holes in the base side rails. In all cases,
spreader bars must be used between
rigging lines to prevent damage to the
coils or fan deck. The unit must be lifted
2.2 INSPECTION using All Rigging Points. Refer to
When the equipment is delivered, it is important Rigging Instructions on Figure 2.3.2.
that the following inspection be implemented in All models can be pushed or pulled (with
the presence of the forwarder’s representative.
chains) from the control box end only.
1.) Check all crates and cartons received against Truck forks must be kept level and not
the Bill of Lading/ Shipping Papers to be sure tilted back. Do not raise the unit end by
they agree. more than 2" above the floor.
2.0 INSTALLATION

FIGURE 2.3.2 TYPICAL RIGGING


2.0 INSTALLATION

2.4 SPACE REQUIREMENTS ample supply of ambient air to the


condenser, and removal of heated air
AND CLEARANCE from the condenser area. If this essential
requirement is not met, it will result in
2.4.1 GENERAL higher condensing temperatures, which
The dimensional data and clearances will cause poor operation, higher power
shown in Figure 2.4.1 are useful for consumption and possibly, eventual
determining space requirements. The unit failure of the equipment. Units must not
should be placed to make the clearance be located in the vicinity of steam, hot air
noted available for proper servicing. or fume exhausts.
Failure to allow these clearances will Another consideration which must be
result in higher costs for operation, taken into account is that the unit should
maintenance and repair. be mounted away from noise sensitive
spaces and must have adequate support to
avoid vibration and noise transmission
2.4.2 ACFX into the building. Units should be
The dimensional data are shown in Figure mounted over corridors, utility areas, rest
2.4.2 and space requirements are shown rooms or other auxiliary areas where
in Figure 2.4.1. The most important sound levels are not an important factor.
consideration which must be taken into Sound and structural consultants should
account when deciding upon location of be retained for recommendations on
air cooled equipment is provision for critical installations.

FIGURE 2.4.1 SPACE REQUIREMENTS

WALLS OR OBSTRUCTIONS

The unit should be located so that air may circulate freely and not be recirculated. For proper air flow
and access all sides of the unit must be at least six feet away from any wall or obstruction. It is
preferred that this distance be increased whenever possible. Care should be taken to see that ample
space is left for maintenance work through access doors and panels. Overhead obstructions are not
permitted. When the unit is in an area where it is enclosed by three walls the unit must be installed as
indicated for units in a pit.

72"[1829mm]
MIN.
2.0 INSTALLATION

FIGURE 2.4.1 SPACE REQUIREMENTS

Single Pit (See Note 2)

72"[1829mm] 72"[1829mm]
84"[2134mm] MAX. MIN. MIN.

Double Pit (See Note 2)

72"[1829mm] 96"[2438mm] 72"[1829mm]


84"[2134mm] MAX. MIN. MIN. MIN.

Multi Pit

72"[1829mm] MIN.
48"[1219mm]
MIN.

96"[2438mm] MIN.

Notes:
1.) All dimensions are the minimum,
Corner Wall unless otherwise noted.
2.) Pit installations are not re-
commended. Re-circulation of hot
condenser air, combined with
surface air turbulence cannot be
predicted. Hot air re-circulation will
72"[1829mm] MIN. severely affect unit efficiency ratio
(EER) and can cause high pressure
or fan motor temperature trips.
Dunham-Bush will not be
responsible for ducting fans to a
higher level to alleviate the above
mentioned conditions.
48"[1219mm] 3.) ACFX 200-6 is shown in this
MIN. drawing.
2.0 INSTALLATION

FIGURE 2.4.2 DIMENSIONAL DATA


ACFX 200-6
AIR IN AIR IN

CONTROL/POWER
PANEL

AIR IN AIR IN

6" [152] AIR OUT

96" [2438]

13 3/4" [350] 8" [203]

6 NOS OF 2 1/2"[63.5]Ø 6 NOS OF 3/4"[19.1]Ø


LIFTING HOLES ON BOTH MOUNTING HOLES FOR
SIDE OF BASE FRAME. SPRING ISOLATORS.
86" [2184]
32" [813] 220" [5588]
88" [2235]
48" [1219] 123 1/4" [3131] 123 1/4" [3131] 28" [711]

21" [533] 141 3/4" [3600] 141 3/4" [3600] 18" [457]
322 1/2" [8191]

ACFX 220-6
AIR IN AIR IN

CONTROL/POWER
PANEL

AIR IN AIR IN

6" [152] AIR OUT

96" [2438]

14 3/4" [375] 8" [203]

6 NOS OF 2 1/2"[63.5]Ø 6 NOS OF 3/4"[19.1]Ø


LIFTING HOLES ON BOTH MOUNTING HOLES FOR
SIDE OF BASE FRAME. SPRING ISOLATORS. 86" [2184]
34 1/2" [876] 220" [5588]
88" [2235]
48" [1219] 147 1/2" [3746] 147 1/2" [3746] 22" [559]

21" [533] 163" [4140] 163" [4140] 18" [457]

365" [9271]

NOTE : ALL DIMENSIONS ARE IN INCHES [MM].


2.0 INSTALLATION

ACFX 250-6, 280-6, 300-6


402" [10211]

AIR IN AIR IN

CONTROL/POWER
PANEL

88" [2235]

AIR IN AIR IN

6" [152] AIR OUT

96" [2438]

8" [203]

6 NOS OF 8 NOS OF 3/4"[19.1] Ø


2 1/2"[63.5] Ø MOUNTING HOLES FOR
LIFTING HOLES SPRING ISOLATORS. 86" [2184]
34 1/2" [876] ON BOTH SIDE OF
BASE FRAME.
88" [2235]
220" [5588]

80" [2032] 141" [3581] 141" [3581] 40" [1016]


28" [711]
118" [2997] 120" [3048] 118" [2997] 18" [457]

ACFX 330-6, 360-6

444" [11278]

AIR IN AIR IN AIR IN AIR IN

CONTROL/ POWER
PANEL

88" [2235]

AIR IN AIR IN AIR IN AIR IN

6" [152] AIR OUT

96" [2438]

8" [203]

10 NOS OF 3/4"[19.1]Ø 6 NOS OF


MOUNTING HOLES FOR 2 1/2"[63.5]Ø
SPRING ISOLATORS. 86" [2184]
LIFTING HOLES ON
BOTH SIDE OF
BASE FRAME. 88" [2235]
76 1/2" [1943] 220" [5588]

100" [2540] 100" [2540] 100" [2540] 100" [2540] 18" [457]
26" [660]

80" [2032] 162" [4115] 162" [4115] 40" [1016]

NOTE : ALL DIMENSIONS ARE IN INCHES [MM].


ACFX 420-6, 450-6, 480-6, 500-6, 530-6
MODEL A WATER
ACFX CONN.
SIZE

420-6 17 3/4 8 [203]


[451]
AIR IN AIR IN AIR IN
450-6 19 5/8 10 [254]
[499] CONTROL/ POWER
PANEL
480-6 19 3/4 10 [254]
[502]

500-6 19 3/4 10 [254]


[502]

530-6 19 3/4 10 [254]


[502]
AIR IN AIR IN AIR IN
NOTE: ALL DIMENSIONS ARE
IN INCHES [MM].
6" [152] AIR OUT

118" [2997]

A 8" [203]

6 NOS OF
2.0 INSTALLATION

INLET/ 12 NOS OF 3/4"[19.1]Ø 2 1/2"[63.5]Ø 86" [2184]


OUTLET MOUNTING HOLES LIFTING HOLES ON
ON SAME FOR SPRING BOTH SIDE OF
ISOLATORS. BASE FRAME. 88" [2235]
SIDE
80" [2032] 80" [2032] 80" [2032] 80" [2032] 80" [2032] 33" [838]
40" [1016]
80" [2032] 176 1/2" [4483] 176 1/2" [4483] 40" [1016]

473" [12014]
2.0 INSTALLATION

2.5 FOUNDATION vent points to permit complete air purging of the


chilled water circuit. Install drain valves in
Refer to index for unit dimensions and load
similar low points to facilitate complete water
points. Foundations must be level for proper
system drainage. Install temperature & pressure
operation and functioning of controls and
indicators in the water piping at the unit to
provisions must be made for supporting the
monitor water flow. Install shut-off valves to
individual load points as shown in the unit
isolate the unit from the piping system during unit
dimensions. Roof mounted units must be
servicing.
supported on adequate steel structure. If units are
located on the ground level, a concrete base is Note: Due to possible high pressures resulting
recommended. from rising temperatures, do not close shut-off
valves with cold water in the cooler.
It is important that the chilled water system be
2.6 VIBRATION ISOLATION cleaned before startup to avoid collecting debris
Under certain critical conditions. it may be in the cooler. After filling the system with water
necessary to install vibration isolators under the (or a glycol solution), start the pump, bleed off
base of the Packaged Chiller. the trapped air, and check for proper flow rate by
measuring water pressure drop across cooler.
Rubber-in-shear or spring vibration isolators are
offered as optional items. When spring isolators
are used, flexible connections must be installed in NOTE: WATER QUALITY - ACFX
the water piping system and in the refrigerant Coolers used in these packages are made
lines of split systems. Note: These flexible of steel, copper and brass and are
connectors must be suitable for the fluid and suitable for operation with well-
pressures involved. maintained water systems. However, if
All external pipings must be supported by spring the fluid used in cooler is corrosive, high
mounted hangers and any piping which goes in mineral content or entrained solids,
through the wall, ceiling or floor should be the water can cause reduced
properly sheathed to prevent transmission of performance and even failure of heat
piping vibration to the structure. exchangers. Therefore, it may be
When spring isolators are used, electrical service necessary to obtain the services of a
to the unit must also be flexibly connected by water treatment consultant and to
means of a 36" section of flexible conduit. provide and maintain water treatment.
This is particularly important with glycol
solution systems.
2.7 PIPING CONNECTIONS
Refer to the dimensional drawings for water
piping connection locations. After the unit has
2.8 ELECTRICAL WIRING
been leveled and isolators (if any) installed &
adjusted, connect cooler water piping, keeping in In connecting power wiring to the unit, the
mind that the cooler tubes may require cleaning following precautions should be taken:
or replacement at some future date, and
1.) All field wiring is to be in accordance with
removable sections of piping will be required to
the National Electric Code and must comply
permit cooler head removal.
with state and local codes. See Electrical Data
Piping must be supported to avoid excess stress for minimum circuit ampacity and fuse size.
on the cooler heads. Cut piping holes in the panel
at the end of the unit, if there is any. Install air
2.0 INSTALLATION

FIGURE 2.5 ISOLATOR LOCATION

ACFX 200-6, 220-6

ACFX 250-6, 280-6, 300-6

ACFX 330-6, 360-6

ACFX 420-6, 450-6, 480-6, 500-6, 530-6


2.0 INSTALLATION

TABLE 2.5A ISOLATOR LOCATION


Unit Model Dimensions – Inches [mm]

ACFX A Dim. B Dim. C Dim. D Dim. E Dim. F Dim. G Dim. H Dim.

200-6 86 [2184] 18 [457] 141 3/4 [3600] 141 3/4 [3600] 21 [533] - - -

220-6 86 [2184] 18 [457] 163 [4140] 163 [4140] 21 [533] - - -

250-6 86 [2184] 18 [457] 118 [2997] 120 [3048] 118 [2997] 28 [711] - -

280-6 86 [2184] 18 [457] 118 [2997] 120 [3048] 118 [2997] 28 [711] - -

300-6 86 [2184] 18 [457] 118 [2997] 120 [3048] 118 [2997] 28 [711] - -

330-6 86 [2184] 18 [457] 100 [2540] 100 [2540] 100 [2540] 100 [2540] 26 [914] -

360-6 86 [2184] 18 [457] 100 [2540] 100 [2540] 100 [2540] 100 [2540] 26 [914] -

420-6 86 [2184] 33 [838] 80 [2032] 80 [2032] 80 [2032] 80 [2032] 80 [2032] 40 [1016]

450-6 86 [2184] 33 [838] 80 [2032] 80 [2032] 80 [2032] 80 [2032] 80 [2032] 40 [1016]

480-6 86 [2184] 33 [838] 80 [2032] 80 [2032] 80 [2032] 80 [2032] 80 [2032] 40 [1016]

500-6 86 [2184] 33 [838] 80 [2032] 80 [2032] 80 [2032] 80 [2032] 80 [2032] 40 [1016]

530-6 86 [2184] 33 [838] 80 [2032] 80 [2032] 80 [2032] 80 [2032] 80 [2032] 40 [1016]

TABLE 2.5B ISOLATOR POINT LOAD DATA


Unit Total
Model Point Load – Lbs [Kg] Operating

ACFX Weight
Pos. #1 Pos. #2 Pos. #3 Pos. #4 Pos. #5 Pos. #6 Pos. #7 Pos. #8 Pos. #9 Pos. #10 Pos. #11 Pos. #12 Lbs [Kg]

200-6 3010[1365] 2801[1270] 2591[1175] 2486[1127] 2697[1223] 2907[1319] - - - - - - 16494[7480]

220-6 3428[1555] 3279[1487] 3129[1419] 2978[1351] 3129[1419] 3279[1487] - - - - - - 19218[8716]

250-6 2743[1244] 2744[1245] 2745[1245] 2746[1245] 2623[1190] 2625[1190] 2626[1191] 2628[1192] - - - - 21479[9741]

280-6 2801[1271] 2827[1282] 2853[1294] 2879[1306] 2758[1251] 2753[1249] 2749[1247] 2744[1244] - - - - 22362[10142]

300-6 3001[1361] 2981[1352] 2960[1343] 2940[1333] 2818[1278] 2841[1288] 2863[1299] 2886[1309] - - - - 23288[10562]

330-6 2514[1140] 2475[1123] 2436[1105] 2397[1087] 2358[1069] 2261[1025] 2303[1044] 2345[1063] 2386[1082] 2428[1101] - - 23900[10840]

360-6 2680[1216] 2645[1200] 2609[1183] 2574[1167] 2538[1151] 2441[1170] 2477[1124] 2514[1140] 2550[1157] 2587[1173] - - 25610[11616]

420-6 2652[1203] 2595[1177] 2539[1152] 2483[1126] 2426[1100] 2370[1075] 2257[1023] 2334[1059] 2412[1094] 2489[1129] 2567[1164] 2644 [1199] 29769[13501]

450-6 2694[1222] 2659[1206] 2623[1190] 2588[1174] 2553[1158] 2518[1142] 2407[1092] 2471[1121] 2534[1149] 2598[1178] 2662[1207] 2725[1236] 31032[14073]

480-6 2917[1323] 2863[1299] 2809[1274] 2755[1250] 2702[1225] 2648[1201] 2543[1154] 2625[1191] 2707[1228] 2789[1265] 2870[1302] 2952[1339] 33178[15047]

500-6 2993[1357] 2947[1337] 2902[1316] 2856[1295] 2811[1275] 2766[1254] 2661[1207] 2736[1241] 2811[1275] 2885[1308] 2960[1342] 3035[1376] 34362[15583]

530-6 3016[1368] 2999[1360] 2983[1353] 2967[1345] 3086[1338] 2934[1331] 2830[1283] 2877[1305] 2924[1326] 2970[1347] 3017[1368] 3064[1390] 35527[16112]
2.0 INSTALLATION

2.) Check unit wiring for damage and all terminal 2.10 REQUEST FOR START-
connections for tightness. Unit terminal
UP REPRESENTATIVE
blocks are to be connected with copper
conductors only, sized per ampacity listed on
unit data plate. After the installation has been completed and
checked, Form 9180 must be filled out and sent to
3.) Connections to unit should match the unit
the Dunham-Bush Service Department for
nameplate in volts, phase, and Hertz. Voltage
must not vary beyond ±10% of nameplate authorized start-up representative to perform the
value and voltage imbalance between phases initial start-up of the Dunham-Bush packaged
must not exceed 2% at any time during chiller. The purchaser will have competent
operation of the unit. service and operating personnel in attendance to
4.) Phase sequence to connectors L1, L2 and L3 assist in the work involved, and also to be trained
shall be in that order. Check with Amprobe in the service and maintenance of this unit.
phase sequence adapter PSA-1 or equivalent. (During the warranty period, the manufacturer is
responsible for parts only upon proof of defective
workmanship or manufacture).
2.9 CONTROLS
Following receipt of the signed Form 9180, a
2.9.1 CONNECTIONS representative will be sent to the customer. He
will inspect the installation to determine whether
Controls which are to be field installed
should be connected in accordance with it meets Dunham-Bush requirements; perform the
the appropriate wiring diagram initial start-up of the installation; determine
accompanying the unit. The following whether it is in satisfactory operating condition;
connections should be made where and instruct the specified customer personnel in
applicable: its operation and maintenance for the length of
1.) Connect a set of normally open time specified in the purchase contract.
auxiliary contacts from chilled water
pump contactor into unit controls as NOTE: Sump oil heaters should be energized for
shown on unit wiring diagram. a minimum of 24 hours and the oil sump
2.) Install a chilled water flow switch temperature must be at a minimum of
(paddle type recommended) (or 100°F (38°C) prior to arrival of start-up
differential pressure switch) in straight representative. This will ensure that the
length of chilled water piping to avoid oil is warm enough to vaporize any
turbulence. Connect in same electrical dissolved refrigerant and that the oil is
circuit as ( 1.)
within the normal operating temperature
range.
2.9.2 SETTINGS
All controls are factory set, however WARNING: The compressor(s) should be
operating control settings are not always started initially ONLY under the
applicable under all operating conditions. direct supervision of an
For recommended control settings, see Authorized Dunham-Bush Start-
wiring diagram accompanying unit. Safety Up Representative.
controls must be set to factory
recommendations.
3.0 OPERATION

3.1 GENERAL Important: Do not use chilled water pump


operation via the flow switch or Aux chilled
The unit should be started up only by a
refrigeration technician who is familiar with water pump contacts to start & stop this unit.
accepted operation practices for refrigeration These are safety controls, not operational
systems. controls.
Use small screw unit start-up report to record all
temperature, pressure, electrical readings and 3.4.1 AIR COOLED PACKAGE
control settings. A copy must be forwarded to CHILLER START-UP
Dunham-Bush, before the warranty will be
honored. The unit is ready for start-up when the
following procedures have been
completed.
3.2 UNIT PIPING
1. Water piping for the cooler is installed
Each unit has a separate refrigerant circuit for and tested.
each compressor. See Figure 3.2 for typical unit
piping schematic. 2. Electrical connections are made and
properly fused.
3. Unit has been leak tested. leaks
3.3 SYSTEM WATER FLOW corrected, and charge completed.
RATE 4. Compressor crankcase heater(s) has
The quantity of chilled water being circulated can been energized for a minimum of 24
be measured quite accurately (±5%) by hours.
determining the water pressure drop through the
5. Calibrated refrigerant gages have been
cooler and reading GPM from the cooler pressure
connected to the suction and discharge.
drop curve, Figure 3.3. Connect reliable pressure
gauges to valves installed in cooler entering and 6. Turn on the chilled water pump, check
leaving water vent connections and read pressure direction of rotation and adjust the
difference with chilled water pump in operation. water flow through the cooler to the
An alternative method of determining GPM is to specified flow rate. Bleed off all
measure pressure difference from pump inlet to entrained air.
outlet and read GPM from pump curve. 7. Manually energize the fan starters and
However due to the quality of water at the jobsite, check the fan rotation. Fans should pull
the accuracy of the curve might vary. Conditions air through the condenser coil and
such as water hardness, organic material, discharge vertically upwards.
suspended solids and water velocity may 8. Check all refrigerant valves to be sure
contribute to a greater fouling. The quality of the they are open.
water could be maintained by chemical treatment
and periodical cleaning. The curve plotted is 9. Proceed to System Start-up.
based on a clean water system. Compressor #1 will start in about 15
minutes & proceed to load up if leaving
water temperature is above setpoint.
3.4 STANDARD AMBIENT Compressor #2 will follow as the demand
UNIT OPERATION (65°F dictates.
MINIMUM AMBIENT)
INCLUDING OVERNIGHT 3.5 SYSTEM START UP
SHUT-DOWN AND 1. Before starting the compressor(s), check all
MORNING RESTART three phases of supply voltage, of all legs of
Caution: These units may be equipped with the motor. They must be within ±10% of the
manifold installed manual discharge valve that nameplate voltage. Check to be sure
must be opened before attempting to start. compressor is not running backwards.
3.0 OPERATION

FIGURE 3.2 TYPICAL PIPING SCHEMATIC


A.) 2 COMPRESSORS
3.0 OPERATION

B.) 3 COMPRESSORS
3.0 OPERATION

FIGURE 3.3 COOLER WATER PRESSURE DROP

100

ACFX 200-6 ACFX 330-6


ACFX 220-6 ACFX 360-6
ACFX 250-6
ACFX 280-6
ACFX 300-6
PRESSURE DROP - FT WG

10

ACFX 420-6
ACFX 450-6
ACFX 480-6
ACFX 500-6
ACFX 530-6

1
10 100 1000 10000

CHILLED WATER FLOW RATE - USGPM


3.0 OPERATION

2. Start compressor(s), check the gages and note all vent & drain plugs from both heads of the
if the pressures are within the prescribed cooler, and blow out tubes will compressed air
limits. to avoid serious stagnant water corrosion.
3. Stage unit down until all compressors are off 6. Finally, it is recommended that an oil sample
and check the compressor crankcase sight be taken from each compressor & submitted
glass for oil level. It should be 1/2 to 3/4 of the for lab analysis. Dunham-Bush offers this
compressor sight glass. service in its "Oil Kare" program. This
4. The electrical control settings should be analysis should be done at the end of each
checked and if necessary, reset to those operating season or every 6 months if the unit
settings indicated on the wiring diagram. is used year round, to maintain compressor
Safety controls are factory set and must be warranty.
maintained at settings indicated on the wiring The power supply to the unit may be de-
diagram. energized to conserve energy. Just remember
5. The temperatures of the chilled water both in that all heaters will now be inactive, and the
and out, should be checked to insure the unit is cooler could freeze-up if not properly drained.
operating within the desired temperatures.

3.8 SEASONAL START-UP


3.6 SHUT-DOWN (OVERNIGHT PROCEDURE
OR WEEKEND)
l. Check fan drives for wear, rust, propeller
To shut-down in the unit with compressors on or clearance, etc. and make necessary repairs &
off, turn each individual compressor switch. Do adjustments. Grease main fan shaft bearings
not close any valves. The chilled water pump may with a good grade of EP ball bearing grease.
then be turn off. If it is possible that the overnight 2. Check & clean condenser fin surface if
ambient will drop below 45ºF, it is preferable to necessary. Use a warm water soap solution,
leave the chilled water pump on. Finally, do not being careful not to bend fins. Comb out bent
open the main unit disconnect. Main power is fin areas.
required to keep the sump heaters. 3. Check all power supply connections at all
points, and all control terminal screws for
tightness.
3.7 SEASONAL SHUT-DOWN 4. Energize main power to unit & leave on for at
PROCEDURE least 24 hours in order for compressors to
thoroughly warm up.
Standard Ambient Units
5. Start chilled water pump and verify correct
1. Follow standard overnight shut-down flow-rate, glycol % if required. Bleed-off
procedure system air if necessary.
2. Turn off chilled water pump 6. Open main discharge valve in discharge
header.
3. Close manual discharge valve
7. Open liquid valve on sealpot.
4. Close liquid valve on sealpot
8. Turn control circuit power switch on, and all
5. If ambient temperature during the extended individual compressor circuit switches. Press
shut-down period will not get below freezing, computer keyboard reset key (RST).
the chilled water system may be left filled, If Compressors should start after start-up clock
the ambient temperature will be below times out and will come on in sequence to
freezing, drain all water thoroughly, removing satisfy the existing load.
3.0 OPERATION

3.9 SAFETY RELIEF VALVES which feeds it into the compressor part way
Each pressure vessel is protected by a safety relief through the compression process. Check valve
valve as required by ASME Code. Each prevents backflow at shutdown in multi-
compressor is protected by a relief valve which is compressor units.
vented to atmosphere. Never install any kind of
shut-off valve in a safety relief vent line.
3.11 FAN CYCLING
On start-up, all fan will remain off (some units
3.10 REFRIGERATION CYCLE may have base fans which run together with
-MULTIPLE COMPRESSOR compressor). As the head pressure builds up, next
ACFX fan stage will start. Subsequently fan stage will
Following is the normal sequence of operation for start if the head pressure continues to rise. Refer
a unit installed in a typical air conditioning wiring circuit diagram for number of fan stage.
system. Refer to Figure 3.2, the typical piping
schematic for multiple compressor ACFX unit.
Each vertical screw compressor discharges hot, 3.12 LIQUID INJECTION
high pressure gas through service valve or stop
valve and then flow into air cooled, condenser Each compressor is fitted with a liquid injection
where it condenses, rejecting heat to the outdoor system designed to feed refrigerant liquid into the
air drawn through the coil by fans. The liquid compressor to provide additional motor cooling
refrigerant from the condenser drains out from the as required. The liquid injection is activated by
bottom of the condenser into the economizer feed solenoid valve to hold the compressor discharge
line. gas temperature below 170ºF, the maximum
discharge operating temperature of these
The refrigerant flows through the economizer
compressors.
feed ball valve, dropping its pressure, causing it
to flash. It then flows into the flash economizer
tank which is at an intermediate pressure between
condenser and evaporator Liquid is centrifugally 3.13 HYDRAULIC CAPACITY
separated from the flash gas and the liquid drains CONTROL SYSTEM
to the bottom of the tank, exits via the economizer
Each compressor has a hydraulic control system
drain line, and passes through the economizer to supply the proper force necessary to actuate the
drain ball valve. Both economizer ball valves are
capacity control slide valve, thereby regulating
actuated by a Modutrol motor that adjusts flow to
compressor loading for maximum unit capacity. It
maintain an appropriate refrigerant level in the is composed of a normally closed valve (A), a
evaporator, determined by a liquid level float
normally open solenoid valve (B), an internal
switch.
pressure regulating valve, with valves A and B
From the drain line, liquid refrigerant flows into both energized (A open, B closed) during normal
the flooded evaporator, where it boils, cooling the compressor operation, high pressure oil is
water flowing inside evaporator tubes. Vapor directed to the slide valve. This pressure acts on
from the boiling refrigerant flows up the suction the surface of the slide valve piston creating a
pipes through a shut-off valve, suction check force which is sufficient to overcome the
valve and suction filter (inside compressor) into opposing spring force and to move the valve in
the compressor where it is compressed and starts the direction of increasing capacity. When the
the cycle again. compressor is given a "hold" command, valve A
Vapor flows from the top of flash economizer is de-energized (closed) and slide valve holds its
into the compressor at the vapor injection port, position.
3.0 OPERATION

The internal pressure regulating valve allows oil slide valve spring will now move the slide valve
to bleed from the slide valve chamber during the back toward the minimum capacity position.
hold condition. If valve B is then de-energized
Under standard conditions, the compressors will
(open), the high pressure oil acting on the slide
load in 60 seconds and unload in 55 seconds.
valve will be vented to suction, and the pressure
in the slide valve chamber will be reduced. The

SLIDE VALVE POSITION


UNLOADING LOADING HOLD
SOLENOID VALVE A CLOSED OPEN CLOSED
(NORMALLY CLOSED) (DE-ENERGIZED) (ENERGIZED) (DE-ENERGIZED)
SOLENOID VALVE B OPEN CLOSED CLOSED
(NORMALLY OPENED) (DE-ENERGIZED) (ENERGIZED) (ENERGIZED)

FIGURE 3.13 COMPRESSOR CAPACITY CONTROL DETAIL

SUCTION
CHECK
VALVE

SUCTION
SERVICE
NORMALLY VALVE
OPEN
UNLOADING
SOLENOID
'B' SCHRAEDER VALVE

NORMALLY
CLOSED
LOADING
SOLENOID
'A'

TERMINAL
BOX
4.0 ELECTRICAL

4.1 ELECTRICAL DATA


COMPRESSOR COND. FAN MTR UNIT DATA USE VOLTAGE

MODEL COMP. NO'S RLA LRA


MSC NO'S FLA FLA MCA MFS MIN MAX
1st STEP XL
1210 1 154 398 995 6 3.6
200-6 355 394 550 414 506
1210 1 158 398 995 6 3.6
1212 1 189 448 1050 8 3.6
220-6 397 445 600 414 506
1210 1 158 398 995 6 3.6
1212 1 189 448 1050 8 3.6
250-6 438 485 600 414 506
1212 1 191 448 1050 8 3.6
1215 1 223 520 1330 8 3.6
280-6 471 526 700 414 506
1212 1 190 448 1050 8 3.6
1215 1 228 520 1330 8 3.6
300-6 509 566 800 414 506
1215 1 223 520 1330 8 3.6
1218 1 279 600 1530 9 3.6
330-6 571 641 900 414 506
1215 1 227 520 1330 9 3.6
1218 1 279 600 1530 9 3.6
360-6 630 700 900 414 506
1218 1 286 600 1530 9 3.6
1212 1 188 448 1050 6 4.3
420-6 1215 1 223 520 1330 6 4.3 711 758 1000 414 506

1215 1 223 520 1330 6 4.3


1215 1 223 520 1330 6 4.3
450-6 1215 1 223 520 1330 6 4.3
746 802 1000 414 506

1215 1 223 520 1330 6 4.3


1215 1 223 520 1330 6 4.3
480-6 1215 1 223 520 1330 6 4.3
814 870 1100 414 506

1218 1 282 600 1530 6 5.7


1215 1 223 520 1330 6 4.3
500-6 1218 1 282 600 1530 6 5.7
881 937 1100 414 506

1218 1 282 600 1530 6 5.7


1218 1 282 600 1530 6 5.7
530-6 1218 1 282 600 1530 6 5.7
949 1019 1250 414 506

1218 1 282 600 1530 6 5.7

NOTES: 1. RLA IS RATED LOAD AMPS. 4. FLA IS FULL LOAD AMPS.


2. LRA IS LOCK ROTOR AMPS. 5. MCA IS MINIMUM CIRCUIT AMPACITY.
3. XL IS ACROSS THE LINE STARTING. 6. MFS IS MAXIMUM FUSE SIZE.

4.2 WIRING DIAGRAM For initial start-up, the following conditions must
Figure 4.2 are typical wiring diagrams for a 2- be met:
compressor unit. This may not be an accurate ] Power supply to unit energized.
representation of your unit. It is best to use the
] Unit circuit breakers in the "on" position.
wiring diagram mounted in the package control
panel. A copy of that diagram is furnished with ] Control power switch on for at least 15
the unit owner’s manual. minutes. Compressor switches on.
] Reset pressed on microcomputer keypad.
4.3 TYPICAL OPERATION ] Chilled water pump running and chilled water
The Dunham-Bush rotary screw air-cooled water flow switch made.
chiller depends mainly on its on-board
] Leaving chilled water temperature at least 2°F
microcomputer for control. Operation described is
above setpoint.
for a two-compressor units and is very similar for
single and three compressor units. ] All safety conditions satisfied.
4.0 ELECTRICAL

After all above conditions are met, the If the applied load is greater than one compressor
microcomputer will call for the lead compressor can handle, it will load fully and then the
to start. After a one-minute delay, the first microcomputer will call for a second compressor.
contactor (e.g. 1M-1) is energized followed by the After one minute, the second compressor will
second contactor (e.g. 1M-2) after one-second- start in the same manner as the first. Then both
time delay. This provides reduced inrush stepped compressors will be commanded to adjust load to
start. The compressor 15-minute anti-recycle 50%. They are gradually loaded up together until
timer is initiated at compressor start. the applied load is satisfied. In this way the two
When the compressor starts, the microcomputer compressors share the load equally.
monitors amperage by means of 1CT, voltage If the applied load decreases to the point that both
using 3T, leaving water temperature using TS, compressors are running at about 40% capacity,
and condensing pressure. These inputs are used to the computer shuts down the lag compressor and
control the loading and staging of the compressor. loads the remaining compressor to about 80%. If
The compressor's loading is controlled by pulsing applied load decreases further, the remaining
signals to the load and unload solenoids. compressor unloads proportionately. If applied
The compressor and cooling capacity is load decreases to less than the minimum capacity
controlled by pulsed signals to load and unload of one compressor, the leaving chilled water
solenoid valves on the compressor. When the temperature will decline to 2°F below setpoint, at
compressor starts, it is fully unloaded, yielding which time the lead compressor will shut down. It
about 25% of its full load capacity. As the will restart automatically if leaving chilled water
computer gives it load signals, capacity gradually temperature rises to 2°F above setpoint and both
increases. The rate of compressor loading is 15 minute anti-recycle and one minute start delay
governed by ramp control which is adjustable in timers are satisfied.
the computer. During start-up operation, the computer monitors
The computer responds to leaving chilled water the difference between discharge and suction
temperature and its rate of change which is pressures to insure that minimum of 30 psi
proportional and derivative control. If leaving differential is available for compressor
chilled water temperature is within the deadband lubrication. If the difference falls below a
(+/-0.8°F from setpoint), no load or unload minimum of 30 psi, the computer closes
commands are given. If chilled water temperature refrigerant flow control valves, starving the
is above deadband, the computer will continue evaporator, causing evaporator pressure to drop,
loading the compressor until a satisfactory rate of increasing differential pressure. This is especially
declined is observed. If leaving chilled water helpful at startup, when warm chilled water and
temperature is below the deadband, the low ambient temperature would cause a low head
compressor is commanded to unload. Thus the situation. This feature is called EPCAS:
compressor capacity is continuously modulated to Evaporator Pressure Control at Startup. It is one
match applied load and hold leaving chilled water of several proactive control features of the
temperature at setpoint. microcomputer which overcome potential
Condenser control is by fans, of which some are problems while continuing operation.
base fans that are activated upon compressor Two additional proactive features are low suction
starting. The base fans are normally the ones
and high discharge pressure override. If operating
located at the liquid line header side of each ‘V’
pressures approach trip level, compressors are
coil. The remaining fans are controlled according
unloaded as necessary to continue operation.
to discharge pressure and fan stage setpoints by
the microcomputer. Optional low ambient units To shut down the unit automatically, the customer
may have base fan variable speed control which is control contacts must be opened. To shut down
independent of the microcomputer, or coil the unit manually, simply shut off the compressor
solenoid control to disable ‘V’ coil sections and switches. This will cause a no-run alarm that must
fans under the control of the microcomputer. be reset to restart the compressor.
4.0 ELECTRICAL

FIGURE 4.2 TYPICAL WIRING SCHEMATIC


4.0 ELECTRICAL
4.0 ELECTRICAL

5ΡΕΣ

Σ4

270

Σ5

270
∼ ∼
4.0 ELECTRICAL
4.0 ELECTRICAL

TABLE 4.2 TYPICAL CONTROL DATA SHEET

4.4 MICROCOMPUTER 2. Use the up or down arrow keys to select


the type of information desired. The
CONTROLLER main menu items are:
This unit is controlled by a microcomputer DATE & TIME SET
control system. The system is composed of four CONTROL POINTS
microcomputer boards, a display board and ANALOG SENSORS
analog and digital sensors. The following sections
DIGITAL SENSORS
describe the system and how to operate it.
SETPOINTS A & B
The display board has a 20-key keypad and a 2 x ALARMS
40 LCD display. The keypad and display can be
AUTHORIZATION
used to determine the status of the compressor,
and refrigeration system. Various setpoints can 3. Press the ENTER key.
also be displayed and altered. 4. Use the up or down arrow keys to select
the desired data. For control points,
The status of the machine can also be monitored additional data such as compressor
by a computer terminal either locally or remotely
operating hours and number of starts
by a modem. The terminal must be able to handle can be viewed with the right and left
RS232 communications. For more information, arrow keys.
Please contact Dunham-Bush Industries, M & E
Service Department. NOTE: When displaying analog sensors, the
PAGE MODE key can be pressed to
display two new analog inputs after each
4.4.1 TO DISPLAY DATA FROM THE arrow key is pressed. Press PAGE
MENU MODE again to return to displaying one
1. Press the MENU key. new analog input.
4.0 ELECTRICAL

4.4.2 TO RESET ALL CONTROL ENTER. A cursor will flash over the
POINTS TO COMPUTER setpoint A value.
CONTROL
4. a.) If you want to change setpoint A,
1. Press the RESET key. The display will press in the desired new value and
show RESET ALL CPs to COM press ENTER. if the new value is
MODE? N Y within allowable limits, it will be
2. Press the right arrow key to select Y. stored in memory. The cursor will
3. Press the ENTER key. The reset will then move to setpoint B.
not be accepted if a lockout control b.) If you do not want to change
point is active. Resolve the problem and setpoint A, press ENTER.
reset again. 5. Repeat 4, for Setpoint B.

4.4.3 TO DISPLAY ALARMS


1. Press the MENU key. 4.4.6 TO CALIBRATE TEMPERATURE
AND PRESSURE SENSORS
2. Use the up or down arrow to select
ALARMS. 1. You must be authorized and in the
3. Press ENTER. PROG mode. See Section 4.4.4.

4. The day, time, and alarm code is 2. Display the analog sensor to be
displayed. Alarm 1 is the most recent calibrated on the top line of the display.
alarm. 3. Press ENTER to show ZERO
CALIBRATION value.
5. Press the down arrow to view previous
alarms. 4. Use an accurate gauge to measure the
analog value when it is stable and near
6. Determine identity of alarm from alarm
design conditions.
codes on computer instruction label.
5. Determine the revised zero calibration
required as follows: Meter Reading - AI
4.4.4 TO BECOME AUTHORIZED
Display + Zero Calibration = New Zero
1. Select AUTHORIZATION on the main Calibration. The new zero calibration
menu. Press ENTER. must be rounded to the nearest whole
2. If the current status shown is VIEW, number.
press the authorization code (64) on the 6. Press ENTER to place the cursor on the
number keys. zero calibration value.
3. Press ENTER. the current status will 7. Enter the new value from 5. Negative
change to PROG (program) if accepted. values are entered by pressing LOWER
FUNCTION +/- before the number.
4.4.5 TO ALTER SETPOINT DATA 8. Press ENTER to store the revised zero
calibration.
1. You must be authorized and in the
For example, if a suction pressure gauge shows
PROG mode. See Section 4.4.4.
58 psig and the computer displays 60.3 psig with
2. Select SETPOINTS A & B on the main a zero calibration of -1, then new calibration
menu. Press ENTER. would be 58 - 60.3 + (-1)= -3.3(-3). So the zero
3. Use the up or down arrow keys to select calibration should be changed to -3. Then the
the setpoint to be changed. Press computer will display 58.3.
4.0 ELECTRICAL

4.4.7 TO SET DATE AND TIME 6. Use ® to display the first schedule.
1. You must be authorized. See Section The standard display screen would
4.4.4. show:
2. Select DATE & TIME SET on the main CP 17 SCHEDULE GRP: 1 SCH: 1
menu. Press ENTER to display current 0000 2400 DAYS: *** ALL DAYS
date and time. ***.
3. Press ENTER key to move cursor to This indicates that control point 17
each date/time item. named SCHEDULE is controlled by
schedule group (GRP) #1. The first
4. As each item flashes, use the number schedule (SCH:1) turns on at 0000
keys to enter revised data if necessary.
hours and off at 2400 hours (military
5. Press ENTER to continue. The last time) every day of the week. Thus it is
ENTER will store the new date and on all the time.
time.
7. To change this schedule, press
WARNING: Setting the clock will cause a ENTER. The cursor will flash over the
system reset. The entire unit will shut turn-on time.
down and start over again. If the change 8. Use the number keys (0-9) to enter the
was started inadvertently, press MENU revised turn on time using military
key before completing the change. format.
9. Press ENTER. The cursor will move
4.4.8 TO DISPLAY DATA WITHOUT over to the turn-off time.
ACCESSING MENU
10. Use the number keys to enter the turn-
1. Press LOWER FUNCTION. off time in military format.
2. Press function desired (blue sub-script) 11. Press ENTER. The cursor will move
3. Press item number to be displayed. to DAYS during which this schedule
4. Press ENTER. is active.
EX: To display analog input #5, press 12. To change the days for this schedule,
LOWER FUNCTION, ANALOG INPUT, press one or more of the following
5, ENTER. number keys: 0- Clear all current days;
1- Sunday(S); 2- Monday(M); 3-
Tuesday(T); 4- Wednesday(W); 5-
4.4.9 UNIT SCHEDULE OF Thursday(R); 6- Friday(F); 7-
OPERATION Saturday(A); 8- *** ALL DAYS***.
If a seven day time schedule of unit 13. Press ENTER. The revised schedule
operation is desired, the internal real time number is now stored.
clock of the microcomputer can be used. 14. To add another schedule, press the
When the SCHEDULE control point is right arrow key and repeat steps 7-13.
ON, the compressor is allowed to operate.
The following procedure is used to modify 15. To delete a schedule, clear all of the
the operating schedule. days by pressing 0 at Step 12.
The schedule group turns on when any
1. Perform the authorization procedure of the individual schedules turns on.
(See Section 4.4.4). The turn on time does not have to be
2. Press MENU key. earlier than the turn off time.
3. Use Up and Down to select Schedules turn on by time and day, but
CONTROL POINTS. turn off by time alone. For example, a
4. Press ENTER. schedule from 1900 to 0700 Saturdays
would turn on at 7:00 PM Saturday
5. Use Up and Down to select (time and day) and turn off at 7:00
SCHEDULE control point. AM Sunday (time only).
4.0 ELECTRICAL

EXAMPLE: If a unit is to operate at all 4.5.3 Anti-Recycle Timer


times except between the hours of 1:00 (Microcomputer)
AM and 6:00 AM, the following The compressor motor requires an anti-
schedules would be entered: recycle time delay which prevents restart
CP 17 SCHEDULE GRP :1 SCH: for 15 minutes after a start. The purpose
1 0000 0100 DAYS: of this feature is to avoid frequent starts
*** ALL DAYS *** which tend to elevate the motor winding
temperature and impose undue wear on
CP 17 SCHEDULE GRP:1 SCH:
contactors. The microcomputer will not
2 0600 2400 DAYS: ***ALL DAYS *** restart the compressor motor until the 15
ANOTHER EXAMPLE: A typical minutes have elapsed. COFF is displayed
building may require cooling from 6:00 when the compressor control point (1 CP
AM to 7:00 PM Monday - Friday and for compressor 1 respectively) is
from 7:00 AM- 3:00 PM on Saturdays. addressed, and when other conditions for
The schedules would be entered as compressor start are satisfied. See Section
follows: 4.3.
CP 17 SCHEDULE GRP:1 SCH:
1 0600 1900 DAYS: MTWRF
4.5.4 Load Control (Microcomputer)
CP 17 SCHEDULE GRP: 1 SCH:
2 0700 1500 DAYS: A The microcomputer controls the leaving
water temperature within a narrow
deadband by pulsing load and/ or unload
solenoids on the compressor. The load
4.5 CONTROL FUNCTIONS and unload solenoids position the slide
valve within the compressor to control its
4.5.1 Chilled Water Pump interlock capacity. The microcomputer determines
And Flow Switch (CWP And a desired level of loading and varies pulse
CWFS) duration depending on difference between
These are field installed switches, both of load target and actual load. The load
which are used to ensure chilled water target is varied based on rate of approach
flow before the unit is allowed to start. to desired temperature preventing
Failure of either one during operation will significant temperature oscillations. The
cause the compressor to shut down. current limit function (see Section 4.5.7)
A water flow alarm will be generated and overrides the temperature control.
RESET must be pressed to clear the The status of the compressor can be
alarm. observed by displaying the compressor
NOTE: The flow switch or pump interlock cannot control point (1CP). One of the following
be used for normal control of the unit. messages will be displayed:
(See Section 4.5.2). COMP # LOAD Automatic load
COMP # HOLD Automatic hold
4.5.2 Customer Control interlock COMP # UNLD Automatic unload
Control contacts from an external COMP # OFF Off on temperature or
controller can be used to enable or disable customer control
operation of the unit. The wiring diagram COMP # COFF Off on timer (C lock
specifies the terminals to which the off)
contacts must be wired. To enable the COMP # LOFF Manual off or safety
unit, the contacts must be closed. To shutdown
disable the unit, the contacts must be Where # is 1 for compressors 1
opened. respectively.
4.0 ELECTRICAL

4.5.5 Ramp Control (Microcomputer) profile: Ramp rate and start point. Ramp
Another feature of the microcomputer is rate defines the length of time the unit
ramp control, which is the ability to vary takes to load from start point to full load.
load time of the machine from start. Often Start point is the percent of full load at
when the machine is started, the water in which the ramp begins. The ramp rate A
the chilled water circuit is warm, and the setpoint can be set anywhere from 0.1 to
unit will go to full load quickly. With 0.4, smaller values producing slower
ramp control, the user can program the loading rates. The ramp start B setpoint
computer so that it loads at a can be set anywhere between 10 and
predetermined rate. This is a valuable 50%. The compressor will load quickly to
tool, since it can help reduce power this value and then follow the ramp slope
consumption and demand charges. Two from there. See Table 4.5.5 for ramp rates
variables are used to define the ramp at various settings.

TABLE 4.5.5 SAMPLE RAMP TIMES (MINUTES)


A.) TWO-COMPRESSORS UNIT
Ramp Rate 0% Start Point 50% Start Point 75% Start Point
Setpoint Setpoint Setpoint Setpoint
0.1 33.4 25.0 20.9
0.2 16.6 12.5 10.4
0.3 11.2 8.4 7.0
0.4 8.4 6.3 5.2
0.5 6.6 5.0 4.1
0.6 5.6 4.2 3.5
0.8 4.2 3.1 2.6
1.0 3.4 2.5 2.1

B.) THREE COMPRESSORS UNIT


Ramp Rate 0% Start Point 50% Start Point 75% Start Point
Setpoint Setpoint Setpoint Setpoint

0.1 100.0 83.3 75.0


0.2 50.0 41.7 37.5
0.3 33.3 27.8 25.0
0.4 25.0 20.8 18.8
0.5 20.0 16.7 15.0
0.6 16.7 13.9 12.5
0.8 12.5 10.4 9.4
1.0 10.0 8.3 7.5

C.) FOUR-COMPRESSORS UNIT


Ramp Rate 0% Start Point 50% Start Point 75% Start Point
Setpoint Setpoint Setpoint Setpoint
0.1 133.3 116.7 108.3
0.2 66.7 58.3 54.2
0.3 44.4 38.9 36.1
0.4 33.3 29.2 27.1
0.5 26.7 23.3 21.7
0.6 22.2 19.5 18.0
0.8 16.7 14.6 13.5
1.0 13.3 11.7 10.8
4.0 ELECTRICAL

4.5.6 Current Limiting (Microcomputer) ON. Press ENTER. The compressor


will start and operate on manual
A maximum desired current is specified
control.
by amp limit B setpoint for each
compressor. Above the B setpoint, the 6. Use the following keys to control the
status of the compressor:
compressor will not load. If the amps rise
above the A setpoint, the computer will 1 - Hold
give an unload command to the 2 - Load
compressor until the current drops below 3 - Unload
the A setpoint. The amp value in the A Manual control is maintained for 15
setpoint should be 10% of RLA higher minutes after the last manual entry. After
than the B setpoint. this, the compressor reverts to automatic
control. To retain manual control, enter a
4.5.7 Staging Control (Microcomputer) 1, 2, or 3 command to the compressor at
least once every 15 minutes. (See Item 5
On multiple-compressor machines, when above)
the microcomputer determines that a
In manual control, to transfer from one
compressor is fully loaded and compressor to another or to display data,
temperature is not being maintained, press MENU, then continue as above.
another compressor is added. When
CAUTION: Do not start compressor
unloading, a compressor is taken off line manually more than once every 15
when the computer determines that the minutes. Verify that chilled water flow
remaining compressors can control water switch is closed.
temperature.

4.5.10 Chilled Water Reset and


4.5.8 Manual Lead-Lag Control
Customer Control Interlock
(Microcomputer)
(Optional)
On multi-compressor machines, the lead
compressor can be chosen by storing 0.0 The chilled water temperature setpoint
or 1.0 in the lead setpoint B position. 0.0 can be raised automatically by a 0-5 VDC
is for lead on compressor #1, and 1.0 is signal provided by an external controller.
for lead on compressor #2 (if applicable). The reset signal must be between 0VDC
and 5VDC, with 0VDC being no reset
and 5VDC being max. reset. The
4.5.9 Manual Load-Unload Control maximum temperature reset (increase)
(Microcomputer) desired must be stored in CWR max. B
Loading of the compressor can be setpoint. For example, to raise the chilled
controlled manually. To place computer water setpoint from 44°F to 50°F (6.0°F)
in manual control, do the following: with a 5VDC input, a 6.0 is stored in
1. Press RESET if the compressor is CWR max. setpoint.
locked out.
Control contacts from an external
2. Obtain authorization per 4.4.4. controller can be used enable or disable
3. Select CONTROL POINTS on the operation of compressors. The wiring
main Menu. Press ENTER. diagram specifies the terminals to which
4. Use up or down arrow to select the the contacts must to be wired. To enable
compressor to be controlled manually. the compressors, the contacts must he
Press ENTER. closed. To disable the compressors, the
5. Press up or down arrow to select MAN contacts must be opened.
4.0 ELECTRICAL

4.5.11 Variable Fan Speed Control pressure setpoint and turn on the alarm
(Optional) pilot light.
When variable fan speed control has been A low pressure alarm will be recorded by
applied with the package, an output from the microcomputer. Reset by pressing the
the computer controls the Variable Speed RESET button on the microcomputer.
Drive (VFD). The VFD is turned on to Standard setpoint is 45 psig for water
maintain the set discharge pressure. Fan systems.
speed increases as discharge pressure
rises and decreases as discharge pressure 4.6.3 Evaporator Freeze Shutoff
drop. Refer VFD manual for drive (Microcomputer)
operation.
If the leaving chilled water temperature
drops below the freeze setpoint, the
4.5.12 Sump Heater Control
microcomputer will shut down the unit
Each compressor is fitted with an oil and store the freeze alarm. After solving
sump band-heater. The heater is the problem, press RESET on the
energized at all times when compressor is microcomputer to clear the alarm.
off and de-energized when the
compressor is running.
4.6.4 High Pressure Cut-off
Its purpose is to prevent refrigerant (Microcomputer)
migration into the oil during shut down.
This function protects the compressor
For this reason, it is essential that heaters
from operating at abnormally high
be energized for 24 hours before starting
discharge refrigerant pressures. The
a compressor.
microcomputer will shut down the
compressor when condenser pressure
reaches the high pressure set-point, and
4.6 SAFETY FUNCTlONS turn on the alarm indicator lamp on the
control box. The high discharge pressure
4.6.1 Control Power Loss alarm will be recorded by the micro-
(Microcomputer)
computer. Reset by pressing the RESET
The microcomputer can be set up to start button on the microcomputer. Setpoint is
automatically or manually after a power 360 psig.
failure to the microcomputer. The power
loss B setpoint is factory set to 0.0 to
4.6.5 Oil Level Sensor (LS)
allow automatic start after a control
power loss. To select manual reset, set An oil level sensor is located in each
power loss B setpoint to 1.0. In this case, compressor. If low oil indication (digital
a power loss alarm will be stored by the input is OFF) persists for 60 seconds
microcomputer and RESET must be during compressor operation, the
pressed to start. microcomputer will then shut down the
compressor. The status of the level sensor
4.6.2 Low Pressure Cut-off can be seen on the computer display or
(Microcomputer) the associated LED of the Digital I/O
Board. Failure is indicated on the alarm
This function protects the unit from
operating at abnormally low evaporator pilot light. The low oil alarm code will be
refrigerant pressure. The microcomputer recorded by the computer. Press the
will shut down the compressor when RESET key to reset the system. See
cooler pressure falls below the low Section 5.8 concerning oil level.
4.0 ELECTRICAL

4.6.6 High Oil Temperature relay (lCR) will de-energize and open the
Thermostat (12TAS) control circuit. A LED light, located on
A thermostat is located in each the PCR, indicates a good voltage supply.
compressor which will open the The power loss A setpoint is factory set to
compressor run circuit if oil temperature 0.0 to allow automatic start after UVR
exceeds 203°F. The high oil temperature failure. Compressor will not start for 15
pilot light will indicate an excessive oil minutes after failure. To select manual
temperature and a No-Run error will be reset, set power loss A setpoint to 1.0. In
recorded by the computer. Reset is this case, a power loss alarm will be
activated by pressing the RESET button stored by the microcomputer and RESET
on microcomputer. must be pressed to start.

4.6.7 Motor Temperature Protector 4.6.10 Sensor Alarm (Microcomputer)


(1 TAS) - Optional If the computer measures an analog value
Three thermistor sensors are embedded in (temperature, pressure, volts.) that is far
the windings of each compressor motor. beyond normal operating values, the
They are monitored by a solid state motor associated compressors are shutdown.
temperature protector. If any exceed safe The computer then stores the alarm code
temperature, the protector opens the corresponding to the sensor alarm. A
compressor run circuit and lights the sensor alarm indicates a problem in the
appropriate "high motor temperature" analog measurement system.
(HMT) pilot light. The microcomputer
then stores a No-Run error. To reset the 4.6.11 No-Stop Alarm (Microcomputer)
motor temperature protector, press the
appropriate "HMT RESET" button on the If the microcomputer turns off a
control panel. Hold reset button for 5 compressor, but the compressor digital
seconds . Then press RESET button on input does not turn off, a No-Stop alarm
the microcomputer. is generated. The computer will turn off
the control power relay which disables all
compressor control circuits and will turn
4.6.8 Overload Protector (OL) on the alarm light. This alarm indicates a
A solid state overload protects each wiring or hardware error.
compressor by three phase current
monitoring to prevent high current draw. 4.6.12 Low Differential Pressure
The trip setting is factory set and is reset
Alarm (Microcomputer)
by pressing button on overload after
correcting problem. The RESET button For proper lubrication, a compressor
on micro-computer must also be pressed requires a 30 psi differential pressure
to clear the alarm. A no-run error is between condenser and evaporator
stored in the microcomputer. pressures. If the differential pressure is
less than 30 psi for 3 minutes while a
compressor is operating, all compressors
4.6.9 Under Voltage Relay (UVR) will be shut down. The microcomputer
The UVR protects the unit from the will store the low differential pressure
following electric supply malfunctions: alarm code and turn on the alarm light.
Phase Control Relay, phase reversal and The RESET key must be pressed to clear
single phasing. If the UVR trips, a control the alarm.
5.0 MAINTENANCE

5.1 GENERAL 5.4.2 WATER SIDE CLEANING OF


COOLER
As with all mechanical equipment, a program of
regular inspection, cleaning and preventive The effects of fouling of the cooler
maintenance by trained personnel will contribute heattransfer surfaces can be detected by
greatly to the long satisfactory service life of this recording full load performance data on
product. the log sheet. The best measure of
performance of cooler is approach, which
is the difference between leaving water
temperature and saturated refrigerant
5.2 PERIODIC INSPECTION temperature at the pressure in the vessel.
Read essential temperatures and pressures At full load, read cooler pressure and
periodically to see that they indicate normal leaving chilled water temperature on the
operation. It is a good idea to record these computer. Then use Table 5.4.2 to find
readings on a log sheet. If any abnormal operation saturated temp. in cooler. Then calculate
is observed, try to remedy it. See Trouble approaches as follows:
Shooting Guide Section. Cooler Approach = T lvg chilled water -
T sat cooler
If the approach increases by more than
5.3 MONTHLY INSPECTION 2°F above the approach recorded at clean
Remote dirt and debris from condenser coil. Shut conditions, the tubes should be cleaned. It
unit down, open main disconnect, inspect control is generally advisable to clean the water
panel, checking for loose wires, burned contacts, side surfaces at least annually and more
signs of overheated wires, etc. Restart unit and often if severely foul water is used. In
check performance of controls. Check sight chemical cleaning, a caustic solution is
glasses for proper refrigerant charge, see pumped through the heat exchanger,
charging. which attacks dirt, slime and mineral
deposits and flushes then away.
Chemicals can be recommended by water
5.4 VESSEL MAINTENANCE treatment specialists, but it is important to
rinse the system thoroughly after cleaning
5.4.1 GENERAL to remove the chemicals before they
The efficient performance of the cooler attack the metal surfaces.
and condenser heat transfer surfaces is
essential for efficient performance of
your packaged water cooling machine. If
these surfaces accumulate a film of dirt, 5.5 AIR COOLED
scale or slime, their performance CONDENSER CLEANING
efficiency will degrade substantially. The
The face of the condenser should be cleaned at
refrigerant side of heat transfer surfaces
least once a month during operation. If conditions
does not foul since refrigerant is a good
are bad and condensers pick up dirt very quickly,
solvent and it is in a closed, filtered cycle.
it is suggested that they can be cleaned more
Water side surfaces can foul from the
frequently. If the condenser is allowed to get too
water system. A program of water
dirty, the unit will run at high head pressure and
treatment can slow the rate of fouling on
heat transfer surfaces, but not eliminate it. will not give satisfactory performance.
5.0 MAINTENANCE

TABLE 5.4.2 R-22 PRESSURE / TEMPERATURE PROPERTIES


Pressure Temperature Pressure Temperature Pressure Temperature
o o o o o o
psig kPa F C psig kPa F C psig kPa F C

0 101.4 -41.4 -40.8 104 818.6 61.3 16.3 208 1535.9 104.1 40.1
2 115.2 -36.4 -38.0 106 832.4 62.4 16.9 210 1549.7 104.8 40.4
4 129.0 -31.8 -35.4 108 846.2 63.4 17.4 212 1563.5 105.4 40.8
6 142.8 -27.7 -33.2 110 860.0 64.4 18.0 214 1577.3 106.1 41.2
8 156.6 -23.8 -31.0 112 873.8 65.4 18.6 216 1591.0 106.7 41.5
10 170.3 -20.2 -29.0 114 887.6 66.4 19.1 218 1604.8 107.4 41.9
12 184.1 -16.9 -27.2 116 901.4 67.4 19.7 220 1618.6 108.0 42.2
14 197.9 -13.7 -25.4 118 915.2 68.3 20.2 222 1632.4 108.6 42.6
16 211.7 -10.7 -23.7 120 929.0 69.3 20.7 224 1646.2 109.3 42.9
18 225.5 -7.8 -22.1 122 942.8 70.2 21.2 226 1660.0 109.9 43.3
20 239.3 -5.1 -20.6 124 956.6 71.2 21.8 228 1673.8 110.5 43.6
22 253.1 -2.5 -19.2 126 970.4 72.1 22.3 230 1687.6 111.2 44.0
24 266.9 0.0 -17.8 128 984.1 73.0 22.8 232 1701.4 111.8 44.3
26 280.7 2.4 -16.4 130 997.9 74.0 23.3 234 1715.2 112.4 44.7
28 294.5 4.8 -15.1 132 1011.7 74.9 23.8 236 1729.0 113.0 45.0
30 308.3 7.0 -13.9 134 1025.5 75.8 24.3 238 1742.8 113.6 45.3
32 322.1 9.2 -12.7 136 1039.3 76.6 24.8 240 1756.6 114.2 45.7
34 335.9 11.3 -11.5 138 1053.1 77.5 25.3 242 1770.4 114.8 46.0
36 349.7 13.3 -10.4 140 1066.9 78.4 25.8 244 1784.2 115.4 46.3
38 363.5 15.3 -9.3 142 1080.7 79.3 26.3 246 1797.9 116.0 46.7
40 377.2 17.2 -8.2 144 1094.5 80.1 26.7 248 1811.7 116.6 47.0
42 391.0 19.1 -7.2 146 1108.3 81.0 27.2 250 1825.5 117.2 47.3
44 404.8 20.9 -6.2 148 1122.1 81.8 27.7 254 1853.1 118.3 47.9
46 418.6 22.6 -5.2 150 1135.9 82.6 28.1 258 1880.7 119.5 48.6
48 432.4 24.4 -4.2 152 1149.7 83.4 28.6 262 1908.3 120.6 49.2
50 446.2 26.1 -3.3 154 1163.5 84.3 29.1 266 1935.9 121.8 49.9
52 460.0 27.7 -2.4 156 1177.2 85.1 29.5 270 1963.5 122.9 50.5
54 473.8 29.3 -1.5 158 1191.0 85.9 29.9 274 1991.0 124.0 51.1
56 487.6 30.9 -0.6 160 1204.8 86.7 30.4 278 2018.6 125.1 51.7
58 501.4 32.4 0.2 162 1218.6 87.5 30.8 282 2046.2 126.1 52.3
60 515.2 33.9 1.1 164 1232.4 88.3 31.3 286 2073.8 127.2 52.9
62 529.0 35.4 1.9 166 1246.2 89.0 31.7 290 2101.4 128.3 53.5
64 542.8 36.9 2.7 168 1260.0 89.8 32.1 294 2129.0 129.3 54.1
66 556.6 38.3 3.5 170 1273.8 90.6 32.6 298 2156.6 130.3 54.6
68 570.3 39.7 4.3 172 1287.6 91.3 32.9 302 2184.2 131.4 55.2
70 584.1 41.0 5.0 174 1301.4 92.1 33.4 306 2211.7 132.4 55.8
72 597.9 42.4 5.8 176 1315.2 92.8 33.8 310 2239.3 133.4 56.3
74 611.7 43.7 6.5 178 1329.0 93.6 34.2 314 2266.9 134.4 56.9
76 625.5 45.0 7.2 180 1342.8 94.3 34.6 318 2294.5 135.4 57.4
78 639.3 46.3 7.9 182 1356.6 95.0 35.0 322 2322.1 136.4 58.0
80 653.1 47.5 8.6 184 1370.4 95.8 35.4 326 2349.7 137.3 58.5
82 666.9 48.7 9.3 186 1384.1 96.5 35.8 330 2377.3 138.3 59.1
84 680.7 50.0 10.0 188 1397.9 97.2 36.2 334 2404.8 139.2 59.6
86 694.5 51.2 10.7 190 1411.7 97.9 36.6 338 2432.4 140.2 60.1
88 708.3 52.3 11.3 192 1425.5 98.6 37.0 342 2460.0 141.1 60.6
90 722.1 53.5 11.9 194 1439.3 99.3 37.4 346 2487.6 142.1 61.2
92 735.9 54.6 12.6 196 1453.1 100.0 37.8 350 2515.2 143.0 61.7
94 749.7 55.8 13.2 198 1466.9 100.7 38.2 354 2542.8 143.9 62.2
96 763.5 56.9 13.8 200 1480.7 101.4 38.6 358 2570.4 144.8 62.7
98 777.2 58.0 14.4 202 1494.5 102.1 38.9 362 2597.9 145.7 63.2
100 791.0 59.1 15.1 204 1508.3 102.8 39.3 366 2625.5 146.6 63.7
102 804.8 60.3 15.7 206 1522.1 103.4 39.7 370 2653.1 147.5 64.2
5.0 MAINTENANCE

Dirty coils can be cleaned using a soft brush or by circuits, each circuit should be considered
flushing with cool water or commercially separately for charging.
available coil cleaners. DO NOT USE HOT
In order to check proper refrigerant charge, look
WATER OR STEAM. To do so will cause
in each liquid line sight glass with the aid of a
excessive pressure in the system. The face of the
flashlight during system operation. At all
condenser should be cleaned at the beginning of
operating conditions, the sight glass should be
the season and periodically thereafter if
clear. If bubbles are visible at any operating
conditions require.
condition, the circuit is short of charge.
Be careful not to overcharge the machine.
overcharging will result in considerable liquid
5.6 ELECTRICAL logging in the condenser, and excessive
MALFUNCTION condensing pressure.
The unit has four devices designed to protect To add refrigerant, connect a refrigerant vessel to
compressor motors and manual motor controllers the 1/4" back seating port of the suction valve.
from electrical malfunctions: Circuit breakers. Purge the air from the tube with refrigerant gas
starter overload relays, under voltage relay, and before connecting. With the unit running, open
motor over temperature protectors (optional). the refrigerant vessel vapor connection slightly. If
If the under voltage relay trips, it is a sign of the refrigerant vessel is warmer than the cooler,
trouble in incoming power. If it trips again after refrigerant will more readily flow from the vessel
resetting, call your electric utility to investigate into the unit.
the problem. If circuit breaker or motor overload
relay or motor over temperature protectors trip,
this is a sign of possible motor trouble. DO NOT
5.8 OIL CHARGE
reset and try to run compressor again. Call
authorized service representative to check for The proper oil charge is in the unit as supplied
motor trouble. Resetting these safety devices and from the factory. Any operating compressor
repeated starting could turn a minor motor should show oil return and oil overflow at all
problem into a costly major motor burnout. time. If for some reason, a compressor runs low
on oil, a low oil level switch in the compressor
will shut it down before any damage is done. In
the event of a low oil shutdown, call a D/B
5.7 REFRIGERANT CHARGE authorized service agent to correct the problem.
All packaged chiller units are given a complete DO NOT ADD OIL TO THE SYSTEM.
charge of refrigerant at the factory. The type and Note: Only Suniso 4GS oil may be used in this
amount of refrigerant required is in Physical package. Use of other oil is not approved
Specifications. The total refrigerant shown is for by Dunham-Bush, and will result in poor
the entire system. Since these units have separate performance of the package.
5.0 MAINTENANCE

5.9 TROUBLESHOOTING
SYMPTOM POSSIBLE CAUSE REMEDY
1. Unit will not a.) Power off. a.) Check main disconnect switch and main line fuses.
start. b.) No control power. b.) Check control transformer fusing.
c.) Compressor circuit c.) Close circuit breakers. If trip, check compressor.
breakers open.
d.) Phase control relay open. d.) Check for power supply problems (low voltage, phase
imbalance). When corrected, press reset button.
e.) Flow Switch open. e.) Start pumps, check flow switch.
f.) Compressor switch open. f.) Turn switch on. Check alarm status. Correct problem.
g.) Microcomputer shutdown g.) Press reset button.
not reset.
2. Compressor a.) Compressor drawing high a.) Check motor megohms. Reset overloads , run compressor
overload. amps. an check amps. Do not exceed RL x 1.25. Call D/B
serviceman.
3. Compressor a.) Low voltage. a.) Check at main entrance and at unit. Consult power
hums but company if voltage is low and increase wire size to the unit
does not if voltage is normal at main and low at unit. Voltage must
start. be within 10% of motor nameplate rating.
b.) No power on one phase of b.) Check fuses and wiring.
3 phase unit.
c.) Faulty starter or contactor. c.) Check the contacts and time delay on part wind start.
4. Compressor a.) Cooling not required. a.) Apply load.
will not start b.) Computer's time delay b.) Wait 15 minutes max.
when reset active.
button is c.) Undervoltage relay open. c.) See 1.( d.) above.
pushed. d.) Flow switch open. d.) See 1.( e.) above.
e.) Compressor switch open. e.) See 1.( f.) above.
Check light: f.) Burned out signal light. f.) Check signal light bulbs.
None i.) Wiring problem i.) Check wiring against drawing.
5. High oil a.) Motor windings failing. a.) Check megohms.
temperature b.) Insufficient motor cooling. b.) Open liquid injection valve slightly.
6. High motor a.) Motor windings failing. a.) Check megohms. Reset by turning compressor switch off
temperature and then on.
7. Low suction a.) Inadequate feed to cooler. a.) Check to see that main expansion valve superheat.
b.) Inadequate refrigerant b.) See information on charging in Section 5.7.
charge.
c.) Fouling of water side of c.) At high load, check cooler approach (See Section 5.4). If
cooler. approach is more than 2°F above clean valve, fouling is
probably the trouble. Clean tube.
d.) Inadequate chilled water d.) Measure pressure drop across vessel and determine gpm
flow. from Figure 3.3. If gpm is low, check chilled water pump,
valves and strainers.
e.) Too much oil in system. e.) If all oil level sight glasses are full at all times, remove oil
until oil level shows at top of glass on a compressor.
8. High a.) Inadequate air flow across a.) Check condenser fan operation and condenser coil for
discharge condenser clogging.
pressure.
9. Oil low in a.) Low oil level in a.) Low oil level in compressor sight glass is acceptable.
sump. compressor.
10. Low oil a.) Low oil in compressor. a.) See Section 5.8.
shutdown.
11. Freeze a.) Operating setpoint too a.) Check leaving water setpoint on microcomputer.
warning. low.
b.) Load changing too rapidly. b.) Load on package must drop at reasonable rate for
automatic control to work properly.
12. Improper a.) Ramp rate incorrect. a.) See Section 4.5.5.
capacity
control.
5.0 MAINTENANCE

5.10 SAMPLE LOG SHEET SHEET NO. ..............................

DUNHAM-BUSH SCREW COMPRESSOR PACKAGED CHILLER


NAMEPLATE DATA:

UNIT MODEL NO. ....................................................... UNIT NO..................................... VOLTS:............................ Hz...................

UNIT SERIAL NO. ....................................................... COMPRESSOR MODEL NOS.....................................................................

START UP : DATE.......................................... TIME...................................................

DATE

TIME

ELAPSED TIME METERS


COMPRESSOR
NO.
1.
SUCTION PRESSURE 2.
3.
1.

DISCHARGE PRESSURE 2.
3.
1.
DISCHARGE PRESSURE 2.
3.

DISCHARGE SUPERHEAT 1.

(DISC. TEMP.- SAT. DISCH.)* 2.


3.
1.
LIQUID LINE TEMPERATURE 2.
3.
1.
SUBCOOLING 2.
3.

COOLER WATER TEMPERATURE-IN

COOLER WATER TEMPERATURE-OUT

COOLER PRESSURE DROP PSI/IN


WATER

COOLER WATER FLOW (GPM)

CONDENSER AIR TEMPERATURE-IN


(AMBIENT) AC ONLY
ACTUAL VOLTAGE 1.

COMPRESSOR AMPS 2.
3.

FAN AMPS

VOLTS

*USE TABLE 5.4.2 FOR OBTAINING SATURATED TEMPERATURE


THIS LOG SHEET IS PROVIDED AS A RECOMMENDATION OF THE READINGS THAT SHOULD BE TAKEN ON A PERIODIC BASIS. THE
ACTUAL READINGS TAKEN AND THE FREQUENCY WILL DEPEND UPON THE UNITS APPLICATION, HOURS OF USE, ETC. THIS TYPE OF
INFORMATION CAN PROVE VERY USEFUL IN PREVENTING AND/ OR SOLVING PROBLEMS THAT MIGHT OCCUR DURING THE LIFE OF
THE UNIT.

You might also like