REPUBLIC OF THE PHILIPPINES

OFFICE OF THE BUILDING OFFICIAL


CITY OF CEBU

LEGEND
1 LED LAMP RECOMMENDING APPROVAL:
11
4 5 9
PANEL BOARD _________________________________________
Head of Electrical Section Date
S2 S1 10 C.O. 2 GANG
3
S2 C.O.3 GANG
S1
ACU
S1 SINGLE SWITCH APPROVED BY:
S1
S1 S2
S3w S2 TWO GANG SWITCH
_________________________________________
S3 THREE GANG SWITCH Building Official Date

S1
CIRCUIT HOMERUN
S1 S1S3w
SINGLE PHASE LINE
2
LINE TO SWITCH
S1
CIRCUIT BREAKER
6 7 8

S1

3
ELECT DESIGN
ELECTRICAL SYMBOLS/LEGEND

ALL WORKS SHALL COMPLY WITH PROVISION OF THE LATEST


1 LIGHTING LAYOUT 2 POWER LAYOUT APPROVAL OF THE RULES AND REGULATION OF THE PHILIPPINE
ELECTRICAL CODE AND LOCAL AUTHORITIES CONCERNED IN THE
ELECT DESIGN
SCALE: 1:1 METER ELECT DESIGN
SCALE: 1:1 METER
ENFORCE OF ELECTRICAL AND ORDINANCE WITH REGULATION OF
NO. OF TOTAL THE OWNER.
CKT # DESCRIPTION OUTLET LOAD, VA VOLT AMP CKT PROTECTION CKT WIRE DESCRIPTION CONDUIT DESCRIPTION

1 L.O 7 700 220 3.18 15 AT/100AF 2-#14 AWG,COPPER,STRANDED,THWN 1


2
1. THAT A CONTINUOUS TYPE OF LOAD SHOULD BE CONSIDERED
AT 125 % OF ACTUAL LOAD IN ALL LOAD CALCULATIONS.
2 L.O 7 700 220 3.18 15 AT/100AF 2-#14 AWG,COPPER,STRANDED,THWN 1
2. PHILIPPINE ELECTRICAL CODE SPECIFICALLY LIMITS THE USE
2

3 L.O 10 1000 220 4.55 15 AT/100AF 2-#14 AWG,COPPER,STRANDED,THWN 1 OF A 3.50% OR #12 AWG COPPER WIRE AS THE MINIMUM SIZE
2
220 AC MDB(L-N) FOR ALL TYPES OF CONVENIENCE OUTLET.
4 C.O 7 1620 220 7.36 15 AT/100AF 2-#14 AWG,COPPER,STRANDED,THWN 1
2 3. ON CONVENIENCE RECEPTACLES THE "PEC" PROVIDES EACH
7.36
RECEPTACLE SHALL BE AT NO LESS THAN 180 WATT RATING.
5 C.O 7 1620 220 20 AT/100AF 2-#12 AWG,COPPER,STRANDED,THWN 1
2 4. WIRING METHOD SHOULD BE POLYVINYL CHLORIDE(PVC).
6

7
ACU 1HP

ACU 1HP
1

1
746

746
220

220
3.39

3.39
20 AT/100AF

30 AT/100AF
2-#12 AWG,COPPER,STRANDED,THWN

2-#10 AWG,COPPER,STRANDED,THWN
1
2

1
2
M 5.

6.
BRANCH CIRCUIT CONDUCTORS SUPPLYING A MOTOR SHALL
BE NOT LESS THAN 125% OF FULL LOAD CURRENT.
THE CODES PROVIDES THAT WIRING FOR ELECTRICAL CIRCUIT
8 ACU 1HP 1 746 220 3.39 30 AT/100AF 2-#10 AWG,COPPER,STRANDED,THWN 1
2
SHALL BE TYPES RHW, T, THW, XHHW, IN RACEWAY OR CABLES
1
7. HEIGHT OF ALL CONVENIENCE OUTLET MUST BE 50 MM FROM
9 ACU 1HP 1 746 220 3.39 30 AT/100AF 2-#10 AWG,COPPER,STRANDED,THWN 2 100 A THE FLOOR HEIGHT OF ALL SWITCH MUST BE AT LEAST 140 MM
SPECIAL FROM THE FLOOR HEIGHT OF ALL POWER PANEL MUST BE 180
10 1 746 220 3.39 30 AT/100AF 2-#10 AWG,COPPER,STRANDED,THWN 1
2
OUTLET
SPECIAL 1
MM FROM THE POWER PANEL TO THE FLOOR.
11 1 746 220 3.39 30 AT/100AF 2-#10 AWG,COPPER,STRANDED,THWN 15 A 15 A
OUTLET 2
CKT # 1 L.O CKT # 2 L.O 8. SERVICE ENTRANCE MUST BE SEE ON ACCORDANCE OF THE
MAIN LINE 1 10116 220 45.98 50 AT/100AF 2-#8 AWG,COPPER,STRANDED,THWN 1
2
PHILIPPINE ELECTRICAL CODE.
15 A 15 A
CKT # 3 L.O CKT # 4 L.O

4
ELECT DESIGN
SCHEDULE OF LOADS
CKT # 5 C.O
20 A 20 A
CKT # 6 C.O
5
ELECT DESIGN
GENERAL NOTES AND GENERAL SPECIFICATION

CKT # 7 ACU
30 A 30 A CKT # 8 ACU THIS SITE
N

Y
CKT # 1 & 2(L.O) CKT # 6,7,8,9,10&11 (ACU) COMPUTATION OF MAIN CONDUCTOR

IT
C
CKT # 9 ACU 30 A 30 A CKT # 10 ACU

U
EB
7 X 100= 700 WATTS 1HP X 746= 746 WATTS

C
G

TO
AS
800 746 IC= 1.25 X HIGHEST RATED CURRENT +
220= 3.64 A = 3.39 A

ST
220 30 A

AT
SPARE

AY
CKT # 11 ACU
ALL OTHER LOAD X D.F.

IO
W

N
H
CKT # 3(L.O) CKT # 4 & 5 (C.O)

IG
= 1.25 (7.36) + (45.98 - 7.36 X 0.8)

H
AL
10 X 100= 1000 WATTS 2(GANG) X7X160= 1620 WATTS = 45.98 A

N
IO
2-22MM2, THWN + 1-8MM2 THW

AT
1000 1620 USE:
220 = 4.55 A = 7.36 A

N
220

E
ET
COMPUTATION OF MAIN PROTECTION ONE LINE DIAGRAM

U
AG
AL
ELECT DESIGN

D
TO
IP= 2.0 X HIGHEST RATED CURRENT +
6
ELECT DESIGN
COMPUTATION OF LOAD
=
ALL OTHER LOAD X D.F.
[2.0 (7.36 X 2) + (45.98-7.36 X 2)] X 0.8
8 VICINITY MAP
= 48.56 A
ELECT DESIGN
SCALE: 1:100 METERS
USE: 100AT/250AF,2-POLE, 220V, MCCB, BOLT-ON TYPE

RECOMMENDING APPROVAL : NOTED BY : SHEET NO: PAGE NO : CONSTRUCTION COMPANY: FROM THE OFFICE OF: SEAL: PROJECT:
1. LIGHTING LAYOUT ELECTRICAL PLAN
2. POWER LAYOUT ________________________ RESIDENTIAL WIRING INSTALLATION
3. ELECTRICAL SYMBOL/LEGEND
4. SCHEDULE OF LOADS
1 1 GIGATECH INCORPORATED PEE TITLE
JONBERT JUDE D. ESOTO ANGELIE LIBATON 5. GENERAL NOTES PRC N.:___________
PTR N.: ___________
VALIDITY:___________
DATE: ___________ NAPO SAPANGDAKU, CEBU CITY
6. COMPUTATION OF LOAD
S2
S3w

S1
S1

S1
S1S3w

S1
DESIGN ENGINEER OWNER/REPRESENTATIVE E V.RAMA AVE., CEBU
ADDRESS
TIN N.: ___________ PLACE: ___________ ADDRESS