You are on page 1of 6

CONTROL DAMPERS

PITCH 100 mm WM-10


SERIES
OVERVIEW
TECHNICAL DIAGRAMS

OVERVIEW : WM-10 Figure n° 1

WM-10 control dampers are a new series of products from the 1 Telaio
FRAME
WM series. The WM-10 series of control dampers are suitable
for the application on square and rectangular ducts. The
control of these dampers can be manual, electric or 2 BLADE
Aletta
pneumatic, according to the needs of the ventilation system.
The installation of these components allows the control of the
air flow rate variation (VAV) or the pressure variation control
on several kinds of plants. Specifically: 3 HOLDING JOINT
Incastro a tenuta
a) HVAC plants regulation
b) modulated calibration 4 Ingranaggio
INTERNAL interno
MECHANISM

c) modulated or total closing

WM-10 control damper is new in its type due to the


5
Battuta
STOPPER

innovative movement transmission system of gear-drives, the


non existent friction of the mechanism, the assembly method
of the materials used, the particular requirement of air flow
control with the wing design of the movable blades and the MANUAL COMMAND DETAIL
integrated interchangeable controls, allow for a diverse
integration and installation in ventilation systems.

ASSEMBLY DIAGRAMS : SPECIAL ASSEMBLY WITH


HINGE :
H

Q Regulation-vers_16_00.xls Q-9
CONTROL DAMPERS
PITCH 100 mm WM-10
SERIES
TECHNICAL DATA
NSTALLATION PROCEDURE

CHARACTERISTICS : Mounting
By screws through damper flange and duct flange or by self-
Damper threading screws through damper flange and air-treatment unit
Mobile closing system mounted into an air duct, designed to panel.
control and close air flow.
MOUNTING SYSTEM :
Frame, materials and construction method
The frame is manufactured in extruded aluminium and Damper mounted inside (figure n°2) or at the beginning or at
designed to withstand the lateral stress from to air pressure, the end of the air duct (figure n°3 and 4) fixed by the frame
and built with lateral frame to protect the drive gears. flange to the duct flange. The control damper can be mounted
on the floor or ceiling (figure n°5).
Flange
Manufactured with 30 mm height.

Blades, materials and construction system


The blades are manufactured from extruded aluminium with a
particular profile in order to be a better sealing surface and a
good strength to air pressure.

Transversal reinforcement
Present on all dampers with B dimension wider than 1300 mm.

Finishing
Extruded aluminium.

Gear drive, materials and construction system


Opposed rotation gears made from PBT with 30% of glass fibre.
The gear drive is closed and protected on the frame. The
materials used allow a use between a a temperature range
between - 40 °C and + 130 °C.

WM-10 Figure no. 2 WM Figure no. 3

WM-10 Figure no.4 WM-10 Figure no. 5

Q Regulation-vers_16_00.xls Q-10
CONTROL DAMPERS
PITCH 100 mm WM-10
SERIES
AIR FLOW RATE - PRESSURE DROP
BLADES REGULATION - DAMPER SECTION

CONTROL DAMPER ON FIGURE No. 1

WM-10 Figure No. 6

CORRECTION FACTOR "C" FOR DIFFERENT INSTALLATION THAN FIGURE 1


Control damper opening as function of blades inclination
Type of installation
0° 10° 20° 30° 40° 50° 60° 70°
Figure No. 3 6,1 5,4 3,1 2,0 1,5 1,2 1,1 1,0
Figure No. 4 4,0 3,6 2,3 1,8 1,4 1,3 1,2 1,1
Figure No. 5 8,9 8,2 4,5 2,8 2,0 1,7 1,6 1,2
SELECTION EXAMPLE NO. 1 : SELECTION EXAMPLE No. 2 :

a) Control damper positioned as figure No. 2 a) Control damper positioned as figure No.3

b) Air Flow rate = 2000 m3/h b) Air flow rate = 2000 m3/h

c) Pressure drop rp = 200 Pa c) Blades deflection angle on opening α = 30°

d) Blades deflection angle on opening α = 47° d) Correction factor C = 2,0

e) Damper selection m2 = 0,10 d) Pressure drop rp = 200 x 2,0 = 400 Pa

Q Regulation-vers_16_00.xls Q-11
CONTROL DAMPERS
PITCH 100 mm WM-10
SERIES
ACOUSTIC LEVEL
MANUAL CONTROL SYSTEM
ELECTRIC CONTROL SYSTEM

ACOUSTIC POWER LEVEL

The diagram shows the values of acoustic level


in dB(A) as a result of the frontal velocity and
pressure drop. The acoustic levels found on the
diagram are relative to an air section 1 m². For
other sections see correction factor K in below
table.

CALCULATION EXAMPLE:
a) values as shown in figure No.1
b) Calculate the result between velocity V(m/s)
x pressure drop rp (Pa) with result 5 x 53 = 265

CORRECTION FACTOR "K" OF ACOUSTIC LEVEL


Section in m2 0,10 0,13 0,25 0,30 0,40 0,50 0,60 0,80 1,00 1,25 1,55 2,00 3,00 4,00
K (dB) -9
9 -88 -66 -55 -4
4 -33 -22 -11 0 +11 +22 +33 +4
4 +55

Figure no. 7

Mechanism, manual control: The basic kit (figure n° 7) includes a handle for the movement and locking, a transmission lever
for the strength of the transmission shaft axle and a numbered modular plate inserted in the internal mechanism, inside the
frame.
Figure no. 8

Mechanism, servo control: The complete kit (figure no. 8) guarantees the functionality of the mechanism via means of an
electrical signal. It includes the transmission axle and adjustable plate fixed to the frame. This plate is drilled in order to fix
standard actuators available on the market.

Q Regulation-vers_16_00.xls Q-12
CONTROL DAMPERS
PITCH 100 mm WM-10
SERIES
HOW TO ORDER

WM Control damper

10 pitch 100 mm

C with manual command


P with hinge

Base

Haight

WM 10 C 800 611

standard bases standard haight


B mm H mm
200 211
300 311
400 411
500 511
600 611
700 711
H

800 811
900 911
1000 1011
1100 1211
1200 1411 B
1300 1611
1400 1811
1500 2011
1600
1700
1800
1900
2000

Q Regulation-vers_16_00.xls Q-13
CONTROL DAMPERS
PITCH 100 mm WM-10
SERIES
OPTIONALS

Image Description Code

Aluminium graduated plate for attuator support. WM 20

Fixing leaver with fixing bolt, complete with knob for


WM 21
graduated plate for motor support.

Complete manual command kit, compelte with graduated


WM 22
plate, actioning lever, fixing bolt and knob.

Q Regulation-vers_16_00.xls Q-14