You are on page 1of 4

TM

Control Damper Revent Air tech


1

MODEL : M-VCD
Manual Operated Volume Control Damper

INTRODUCTION
Two damper arrangements are used for air-handling system flow control:
parallel-blade and opposed-blade.Parallel-blade dampers are adequate for two position control
and can be used for modulating control when they are the primary source of pressure drop and
directional air flow is not a problem. Opposed-blade damper are preferable, because they normally
provided better control.
Revent standard manual volume control dampers are come with opposed blade 3'V’ style
arrangement with concealed linkage and brass bush/bearing press fit into galvanized steel frame.
However parallel blade 3'V’ style arrangement also available as alternative.

STANDARD CONSTRUCTION
Frame : 18 G (1.2 mm) galvanized steel C channel
reinforced Corners 6 in. x 1 in.

Blade : 18 G (1.2 mm) galvanized steel 3 ‘V’ groove


6" wide opposed action

Bearing/Bush : GI plated collar type 16.5 mm dia.

Axles : 9.5 mm square GI plated.

Linkage : Concealed heavy duty type 12 G galvanized


steel

Handle : Lockable handle quadrant with scaled


indicator plate and open/close handle
indicator galvanized steel.

Finish : Mill Galvanized.

DAMPER RATING
Max. Operating temperature : 240°F

Operating pressure in excess of 2.5 inches w.g.

Operating velocity in excess of 2000 fpm Opposed blade action


3 ‘V’ groove
SIZE LIMITATION arrangement
Minimum size : 200 X 200 mm

Maximum size : 1000 X 1000 mm


For unlimited size damper will be multiple section assembly.

Note:-In a multiple section.

www.reventairtech.com Tel: +91 - 124 -4237502/09


TM

Control Damper Revent Air tech


2

DIMENSIONAL DETAILS

W+F D
Stopper 150 mm

A
W

H+F
H

50 mm

A SECTION A-A
Air Flow
Frame
AVAILABLE OPTIONS

Blade F-Flange-25,30,40 & 50

D-Depth-150 & 200


Handle
Wing Nut Material-GI,SS304 & SS316

Blade action-Opposed & parallel

Linkage Cover Frame Gauge-14G,16G,18G & 20G

Blade Gauge-16G,18G & 20G

Qty SIZE FLANGE DEPTH MATERIAL BLADE ACTION

W H

For Order

Note:-Required all dimensions are in mm

www.reventairtech.com Tel: +91 - 124 -4237502/09


TM

Control Damper Revent Air tech


3

PRESSURE DROP DATA

PRESSURE DROP DATA


Pressure drop testing was conducted in accordance with AMCA Standard 500-D using Figure 5.3.
All data has been corrected to represent standard air at a density of 0.075 Ib/ft 3 (1.201kg/m3)
Actual pressure drop found in any HVAC system is a combination of many factors.This pressure drop
information along with an analysis of other system influences should be used to estimate actual
pressure losses for a damper installed in a given HVAC system
AMCA FIGURES

Figure 5.3 illustrates a fully ducted damper. This configuration has the lowest pressure drop of the
three test configurations because entrance and exit losses are minimized by straight duct runs
upstream and downstream of the damper.

Figure 5.2 illustrates a ducted damper exhausting air into an open area. This configuration has a
lower pressure drop than Figure 5.5because entrance losses are minimized by a straight duct run
upstream of the damper.

Figure 5.5 illustrates a plenum mounted damper. This configuration has the highest pressure
drop because of extremely high entrance and exit losses due to the sudden changes of area in
the system.

www.reventairtech.com Tel: +91 - 124 -4237502/09


TM

Control Damper Revent Air tech


4

PRESSURE DROP DATA

SIZE(mm) 203 X 203 406 X 406 610 X 610 813 X 813 1220 X 915
Velocity(fpm) Pressure Drop(in.w.g)
500 0.09 0.03 0.02 0.01 0.005
1000 0.37 0.11 0.06 0.03 0.02
1500 0.83 0.24 0.14 0.06 0.04
2000 1.48 0.44 0.26 0.12 0.08

Size(mm)
Pressure drop(in.w.g)

Pressure Drop For Only (610 X 610 mm)

0.7

0.5

The pressure drop data in the tables above is for fully ducted 0.3

dampers as represented by Figure 5.3 on page 1. For dampers not 0.2


fully ducted, represented by Figure 5.2 and Figure 5.5 on page
Pressure Drop in.w.g

For example, the pressure drop across a 610 x 610 mm 0.1

damper in an air system with a velocity of 1,000 FPM is .03 inches .07
w.g. If the application more closely resembles Figure 5.2, the actual
pressure drop is closer to .09 inches w.g. (.03 x 3). .05

.03

.02

.01
200 300 500 700 1000 2000 3000
Velocity (fpm)