You are on page 1of 9

Saudi Aramco 2616-ENG (03/99)

PMT OPRNS

AAN SAUDI ARABIAN OIL COMPANY

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
AHB
ENGG CERT

GJB

KHURAIS AL CRUDE INCREMENT-300MBCD


MCC

RESIDENTIAL & INDUSTRIAL COMPLEX

BI-10-01506
ISSUED FOR CONSTRUCTION
DESCRIPTION

TWO (2) IDENTICAL PRE-CAST RESIDENTIAL


BUILDINGS AT RIC - KHURAIS
JO/EWO
10-01506-

DESIGN PHILOSOPHY
0007 06/26/16
NO. DATE
REV

00

DISCIPLINE
FIRE WATER SYSTEM
ENGINEER
MARTE COMETA

06/26/16
DATE:
PROJECT
ENGINEER
GEORGE JACOB
06/26/16
DATE:

GEORGE JACOB
CERTIFIED ISSUED FOR CONSTRUCTION
06/26/16
DATE:
CONSTRUCTION
AGENCY
ALI HASSAN AL-BAGGAL

06/26/16
DATE:
JUNE 2016
OPERATIONS
AYMAN ABDULLATIF AL-NAMI

06/26/16
DATE:
CONTROL NUMBER
VERIFICATION

PREPARED BY:
EDSD

DATE:

MUSTANG-HDP
BY:

Al-Khobar, Saudi Arabia


APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
REVISION CERTIFICATE

OF THIS DRAWING IS COVERED, FOR ALL

BY DRAWING COMPLETION CERTIFICATE


00

_____________________
(DCC) NO. 10-01506-0007-001

DESIGN PHILOSOPHY – FIRE WATER SYSTEM DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO REV.NO.
TWO (2) IDENTICAL PRE-CAST RESIDENTIAL BUILDINGS AT RIC DOC 1
B44 B FI-E00001
RESIDENTIAL & INDUSTRIAL COMPLEX Of 00
KHURAIS SAUDI ARABIA JO: 10-01506-0007 9
EDSD/2616-0399.doc
Saudi Aramco 2616-ENG (03/99)
PMT OPRNS

AAN SAUDI ARABIAN OIL COMPANY

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
AHB

TABLE OF CONTENTS
ENGG CERT

GJB

1. INTRODUCTION ............................................................................................................ 3
MCC

2. CODES AND STANDARD .............................................................................................. 3


2.1 INDUSTRY CODES AND STANDARDS ................................................................................................. 3
2.2 SAUDI ARAMCO ENGINEERING STANDARDS AND SPECIFICATIONS ............................................... 4
3 DESIGN CRITERIA ........................................................................................................ 4
ISSUED FOR CONSTRUCTION

3.1 DESIGN CRITERIA ............................................................................................................................ 4


3.2 WATER SUPPLY ................................................................................................................................ 4
DESCRIPTION

3.3 WATER VELOCITY ........................................................................................................................... 4


3.4 RESIDUAL PRESSURE ....................................................................................................................... 5
3.5 HYDROSTATIC TEST REQUIREMENTS ............................................................................................. 5
3.6 WIND DIRECTION ............................................................................................................................. 5
3.7 PIPING SYSTEM ................................................................................................................................ 5
4 FIRE FIGHTING EQUIPMENT ....................................................................................... 6
4.1 FIRE HYDRANTS ............................................................................................................................... 6
JO/EWO
10-01506-
0007

4.2 SECTIONAL VALVES ......................................................................................................................... 7


4.3 ALARM CHECK VALVE ................................................................................................................... 7
06/26/16
DATE

4.4 FIRE DEPARTMENT CONNECTION ................................................................................................... 7


4.5 GATE VALVE .................................................................................................................................... 8
NO.
REV

00

DISCIPLINE
ENGINEER
4.6 SPRINKLER HEAD ............................................................................................................................ 8
MARTE COMETA
4.7 PORTABLE FIRE EXTINGUISHER ..................................................................................................... 8
06/26/16
DATE:
PROJECT
ENGINEER
5 ATTACHMENT ............................................................................................................... 9
GEORGE JACOB
06/26/16
DATE:
CERTIFIED
GEORGE JACOB

06/26/16
DATE:
CONSTRUCTION
AGENCY
ALI HASSAN AL-BAGGAL

06/26/16
DATE:
OPERATIONS
AYMAN ABDULLATIF AL-NAMI

06/26/16
DATE:
CONTROL NUMBER
VERIFICATION
EDSD

DATE:
BY:
APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
REVISION CERTIFICATE

OF THIS DRAWING IS COVERED, FOR ALL

BY DRAWING COMPLETION CERTIFICATE


00

_____________________
(DCC) NO. 10-01506-0007-001

DESIGN PHILOSOPHY – FIRE WATER SYSTEM DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO REV.NO.
TWO (2) IDENTICAL PRE-CAST RESIDENTIAL BUILDINGS AT RIC DOC 2
B44 B FI-E00001
RESIDENTIAL & INDUSTRIAL COMPLEX Of 00
KHURAIS SAUDI ARABIA JO: 10-01506-0007 9
EDSD/2616-0399.doc
Saudi Aramco 2616-ENG (03/99)
PMT OPRNS

AAN SAUDI ARABIAN OIL COMPANY

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
AHB

1. INTRODUCTION
ENGG CERT

GJB

This document represents Fire Protection Philosophy to be adopted for the project.
MCC

2. CODES AND STANDARD

SAES-M-100 (IBC 2009 Edition) is adopted as a code for selection and design of fire
protection systems for the project.
ISSUED FOR CONSTRUCTION

The project shall be designed and implemented in accordance with Saudi Aramco
Engineering Standards and Specifications dated June 2014 and latest National Fire
DESCRIPTION

Protection Association (NFPA) Standard.

Where a conflict arises between industry standards and/or manufacturer’s standards


and Saudi Aramco Standards, Saudi Aramco Standard will overrule. Deviation from
Saudi Aramco Engineering Standards shall require prior approval by Saudi Aramco.

2.1 Industry Codes and Standards

All the Fire Protection work in this project shall be performed in accordance with
JO/EWO
10-01506-

the following Codes and Standards, as applicable:


0007

Code Title
06/26/16
DATE

ANSI American National Standards Institute


NO.
REV

00

ASTM American Society for Testing and Materials


DISCIPLINE
ENGINEER
API-600 Specification, Steel Gate Valves Flanged and Butt
MARTE COMETA Welding End
DATE:
06/26/16 NFPA 10 Standards for Portable Fire Extinguishers
PROJECT
ENGINEER
NFPA 13 Standard for the installation of Sprinkler Systems
GEORGE JACOB NFPA 13R Standard for Installation of Sprinkler Systems in
DATE:
06/26/16 Low-Rise Residential Occupancies
CERTIFIED NFPA 17A Standard for Wet Chemical Extinguishing Systems
GEORGE JACOB
NFPA 20 Standard for the Installation of Stationary Pumps
06/26/16
DATE: for Fire Protection
CONSTRUCTION
AGENCY NFPA 22 Standard for Water Tanks for Private Fire
ALI HASSAN AL-BAGGAL
Protection
06/26/16
DATE: NFPA 24 Standard for the Installation of Private Fire Service
OPERATIONS Mains and Their Appurtenances
AYMAN ABDULLATIF AL-NAMI
NFPA 72 Standard for National fire alarm and signaling
DATE:
06/26/16 NFPA 291 Recommended Practice for Fire Flow Testing and
CONTROL NUMBER

Marking of Hydrants
VERIFICATION

IFC International Fire Code 2009 Edition


EDSD

IBC International Building Code 2009 Edition


DATE:
BY:
APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
REVISION CERTIFICATE

OF THIS DRAWING IS COVERED, FOR ALL

BY DRAWING COMPLETION CERTIFICATE


00

_____________________
(DCC) NO. 10-01506-0007-001

DESIGN PHILOSOPHY – FIRE WATER SYSTEM DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO REV.NO.
TWO (2) IDENTICAL PRE-CAST RESIDENTIAL BUILDINGS AT RIC DOC 3
B44 B FI-E00001
RESIDENTIAL & INDUSTRIAL COMPLEX Of 00
KHURAIS SAUDI ARABIA JO: 10-01506-0007 9
EDSD/2616-0399.doc
Saudi Aramco 2616-ENG (03/99)
PMT OPRNS

AAN SAUDI ARABIAN OIL COMPANY

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
AHB

2.2 Saudi Aramco Engineering Standards and Specifications


ENGG CERT

GJB

The design shall be carried out as per “June 2014” issue of the following SAUDI
MCC

ARAMCO Standards and Specifications including, but not limited to:

Number Title

SAES-M-100 Saudi Aramco Building Code


ISSUED FOR CONSTRUCTION

SAES-S-050 Sprinkler and standpipe System in Building


SAES-U-101 Regulated Vendor List for Fire Protection
DESCRIPTION

Equipment

3 DESIGN CRITERIA

3.1 Design Criteria

SAES-M-100 (IBC 2009 Edition) is adopted as a code for selection and design of
fire protection systems for the project.
JO/EWO
10-01506-

This project comprises of 2 (two) identical residential buildings located at RIC


0007

compounds in Khurais. New Residential buildings shall be supplied with


dedicated firewater system thru an existing firewater network. Existing firewater
06/26/16
DATE

network shall be extended to cover the new residential area.


NO.
REV

00

DISCIPLINE 3.2 Water Supply


ENGINEER
MARTE COMETA

DATE:
06/26/16 3.2.1 Dedicated firewater system shall be used which shall be provided thru an
PROJECT
ENGINEER
existing firewater network. Tie-in to the existing network shall be done as
GEORGE JACOB per tie-in schedule BB-090210-001.
06/26/16
DATE:

GEORGE JACOB
CERTIFIED 3.2.2 It is assumed that the existing firewater system which is also supplying
06/26/16
the firewater demand of the existing identical residential buildings is
DATE:
CONSTRUCTION
sufficient to supply the new firewater demand.
AGENCY
ALI HASSAN AL-BAGGAL

06/26/16
3.2.3 Flow test data:
DATE:
OPERATIONS
AYMAN ABDULLATIF AL-NAMI
Actual Flow: 851 gpm @ 120 psig
06/26/16
DATE: Predicted Flow: 3107 gpm @ 20 psig
CONTROL NUMBER
VERIFICATION

For complete flow test result, please refer to Attachment-1.


EDSD

DATE:
BY:

3.3 Water Velocity


APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
REVISION CERTIFICATE

OF THIS DRAWING IS COVERED, FOR ALL

BY DRAWING COMPLETION CERTIFICATE


00

3.3.1. Water velocity for underground mains in the firewater network shall be
_____________________

considered for a maximum velocity of 4.6 m/sec [Ref: SAES-M-100, sec


(DCC) NO. 10-01506-0007-001

101.4.5.1]
DESIGN PHILOSOPHY – FIRE WATER SYSTEM DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO REV.NO.
TWO (2) IDENTICAL PRE-CAST RESIDENTIAL BUILDINGS AT RIC DOC 4
B44 B FI-E00001
RESIDENTIAL & INDUSTRIAL COMPLEX Of 00
KHURAIS SAUDI ARABIA JO: 10-01506-0007 9
EDSD/2616-0399.doc
Saudi Aramco 2616-ENG (03/99)
PMT OPRNS

AAN SAUDI ARABIAN OIL COMPANY

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
3.3.2. Minimum water velocity is 3.1 m/s as per SAES-M-100 clause 101.4.5.1.
AHB

3.3.3. Pressure-drop calculations shall be based upon Hazen-Williams


ENGG CERT

GJB

formulae. The following flow factors (C-factors) shall be used.


MCC

FBE-Lined Carbon Steel C = 120


RTR Pipe C = 135
Galvanized Carbon Steel C = 120
ISSUED FOR CONSTRUCTION

3.4 Residual Pressure


DESCRIPTION

3.4.1. The Minimum residual pressure at all points in the firewater network shall
be 20 psig. [Ref: SAES-M-100, Clause 101.4.5.1]

3.5 Hydrostatic Test Requirements

Hydrostatic testing of new construction shall meet the requirements of NFPA 24


for underground firewater mains and NFPA 13 for Sprinkler System Piping.
JO/EWO
10-01506-
0007

3.5.1. Prior to Hydrostatic test all underground piping, from the water supply to
06/26/16

the system riser, and lead-in connections to the system riser shall be
DATE

completely flushed before the connection is made to downstream fire


protection system piping. [Ref: NFPA 24, Clause 10.10.2.1.1]
NO.
REV

00

DISCIPLINE
ENGINEER 3.5.2. All underground piping and attached appurtenances subjected to system
MARTE COMETA

06/26/16
working pressure shall be hydrostatically tested at 200 psi (13.8 bar) or
DATE:
PROJECT 50 psi (3.5 bar) in excess of the system working pressure, whichever is
ENGINEER
GEORGE JACOB greater, and shall maintain that pressure at ±5 psi (0.35 bar) for 4 hours.
DATE:
06/26/16 [Ref: SAES-B-017 Sec. 12.6]
CERTIFIED
GEORGE JACOB
3.5.3. All above ground sprinkler system piping and attached appurtenances
06/26/16
DATE: subjected to system working pressure shall be hydrostatically tested at
CONSTRUCTION
AGENCY
ALI HASSAN AL-BAGGAL
200 psi (13.8 bar) and shall maintain that pressure without loss for 2
06/26/16
hours. [Ref: NFPA 13, Clause 25.2.1.1]
DATE:
OPERATIONS
AYMAN ABDULLATIF AL-NAMI
3.6 Wind Direction
06/26/16
DATE: As per SAES-A-112, Table 1, following data is considered for Wind Directions.
CONTROL NUMBER
VERIFICATION

Area : Khurais
EDSD

Prevailing Wind Direction : N


DATE:
BY:
APPROVAL/CERTIFICATION REQUIREMENTS,

3.7 Piping System


THIS INDICATES THAT REV. NO.__________
REVISION CERTIFICATE

OF THIS DRAWING IS COVERED, FOR ALL

BY DRAWING COMPLETION CERTIFICATE


00

_____________________

3.7.1. All “NEW” underground (U/G) piping shall be Reinforced Thermosetting


(DCC) NO. 10-01506-0007-001

Raisin Pipe (RTR).


DESIGN PHILOSOPHY – FIRE WATER SYSTEM DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO REV.NO.
TWO (2) IDENTICAL PRE-CAST RESIDENTIAL BUILDINGS AT RIC DOC 5
B44 B FI-E00001
RESIDENTIAL & INDUSTRIAL COMPLEX Of 00
KHURAIS SAUDI ARABIA JO: 10-01506-0007 9
EDSD/2616-0399.doc
Saudi Aramco 2616-ENG (03/99)
PMT OPRNS

AAN SAUDI ARABIAN OIL COMPANY

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
3.7.2. All aboveground (A/G) piping inside the building shall be Galvanized
AHB

Carbon Steel. [Ref. SAES-S-050, Table 6.3.1(A)]


ENGG CERT

GJB

3.7.3. Note to Construction Contractor all metallic piping shall be painted.


MCC

3.7.4. Note to construction Contractor all firefighting equipment shall be painted


in red.

3.7.5. Minimum Water supply line serving Fire Hydrant shall be 6 Inch (152 mm)
[Ref: SAES-M-100, Sec 101.4.5]
ISSUED FOR CONSTRUCTION

3.7.6. Fire mains shall be installed underground. Depth of cover shall be


DESCRIPTION

minimum 900 mm. However, for instances that will need more depth,
refer to SAES-L-460 for additional requirements. [Ref: NFPA 24, Clause
10.4.4, SAES-L-460 Sec.16]

3.7.7. All tees, plugs, caps, bends reducers, valves, and hydrant branches shall
be restrained against the movement by using thrust blocks in accordance
with NFPA 24, Clause 10.8.2. [Ref: NFPA 24, Clause 10.8.1.1]
JO/EWO
10-01506-

3.7.8. Dead-end lines serving fire hydrants shall not be greater than 68 feet
0007

(20.7 meters). [Ref: SAES-M-100, Sec 101.4.5.1]


06/26/16
NO. DATE
REV

00

4 FIRE FIGHTING EQUIPMENT


DISCIPLINE
ENGINEER
MARTE COMETA 4.1 Fire Hydrants
06/26/16
DATE:
PROJECT
ENGINEER
4.1.1 Hydrant Spacing shall be provided as follows: (SAES-M-100, Clause
GEORGE JACOB 101.4.5)
06/26/16
DATE:
CERTIFIED Classification Spacing between Spacing between Hydrant & Fire
GEORGE JACOB
Hydrants (max.) Department Connection
06/26/16 Minimum Maximum
DATE:
CONSTRUCTION
AGENCY
Building and 90 m N.A 30.5 m
ALI HASSAN AL-BAGGAL Structures (Ref: SAES-S-050
06/26/16 Clause 8.17.2.4.1.5)
DATE:
OPERATIONS
AYMAN ABDULLATIF AL-NAMI

06/26/16 4.1.2 All new fire hydrants shall be UL Listed and or FM Approved for fire main
DATE:
service and shall also meet ANSI/AWWA C503 Standard as per
CONTROL NUMBER
VERIFICATION

9COM6000001310. [Ref: SAES-U-101, sec 6]


EDSD

4.1.3 All hydrants shall have protection against mechanical damage by use of
DATE:
BY:

bollards or guard. [Ref: NFPA 24, Clause 7.3.5]


APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
REVISION CERTIFICATE

OF THIS DRAWING IS COVERED, FOR ALL

BY DRAWING COMPLETION CERTIFICATE


00

4.1.4 Hydrants should have adequate access for pumper trucks.


_____________________
(DCC) NO. 10-01506-0007-001

DESIGN PHILOSOPHY – FIRE WATER SYSTEM DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO REV.NO.
TWO (2) IDENTICAL PRE-CAST RESIDENTIAL BUILDINGS AT RIC DOC 6
B44 B FI-E00001
RESIDENTIAL & INDUSTRIAL COMPLEX Of 00
KHURAIS SAUDI ARABIA JO: 10-01506-0007 9
EDSD/2616-0399.doc
Saudi Aramco 2616-ENG (03/99)
PMT OPRNS

AAN SAUDI ARABIAN OIL COMPANY

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
4.1.5 Hydrants shall be numbered and clearly stenciled on the riser to meet
AHB

NFPA 291. The numbering system shall be coordinated with the Fire
Protection Department before entering or updating these numbers in the
ENGG CERT

GJB

drawing system.
MCC

4.1.6 Fire hydrants in residential and service areas shall be located on the
street side of houses or buildings. If such locations are not available or
feasible, the requirements shall meet SAES-M-100.
ISSUED FOR CONSTRUCTION
DESCRIPTION

4.2 Sectional Valves

4.2.1 Sectional valves shall be directly buried, post indicator type.

4.2.2 All Post indicator valve shall be as UL/FM approved and shall be as per
9COM6000001380. [Ref: SAES-U-101, sec 6]

4.2.3 Sectional Valves shall be provided at appropriate points within piping


sections such that the number of fire protection connections between
JO/EWO
10-01506-

sectional valves does not exceed six (06). [Ref: NFPA 24, Clause 6.6.1]
0007

4.2.4 All below grade sectional valves in mains or branch service shall be a
06/26/16
DATE

listed post indicator type valve with position indicators above grade. [Ref:
NFPA 24, Clause 6.1.3]
NO.
REV

00

DISCIPLINE
ENGINEER
MARTE COMETA

DATE:
06/26/16 4.3 Alarm Check Valve
PROJECT
ENGINEER
GEORGE JACOB 4.3.1 Alarm Check Valve shall be UL/FM approved and shall be as per
DATE:
06/26/16 9COM6000001325. [Ref: SAES-U-101, sec 6]
CERTIFIED
GEORGE JACOB
4.3.2 Alarm Check Valve to be interfaced with Fire Alarm System.
06/26/16
DATE:
CONSTRUCTION
AGENCY
ALI HASSAN AL-BAGGAL

DATE:
06/26/16 4.4 Fire Department Connection
OPERATIONS
AYMAN ABDULLATIF AL-NAMI
4.4.1 Fire Department Connection shall be UL/FM approved and shall be as
DATE:
06/26/16 per 9COM6000001325. [Ref: SAES-U-101, sec 6]
CONTROL NUMBER
VERIFICATION

4.4.2 2 way FDC connections shall be used.


EDSD

4.4.3 Fire Department Connection shall be road facing.


DATE:
BY:
APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
REVISION CERTIFICATE

OF THIS DRAWING IS COVERED, FOR ALL

BY DRAWING COMPLETION CERTIFICATE


00

_____________________
(DCC) NO. 10-01506-0007-001

DESIGN PHILOSOPHY – FIRE WATER SYSTEM DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO REV.NO.
TWO (2) IDENTICAL PRE-CAST RESIDENTIAL BUILDINGS AT RIC DOC 7
B44 B FI-E00001
RESIDENTIAL & INDUSTRIAL COMPLEX Of 00
KHURAIS SAUDI ARABIA JO: 10-01506-0007 9
EDSD/2616-0399.doc
Saudi Aramco 2616-ENG (03/99)
PMT OPRNS

AAN SAUDI ARABIAN OIL COMPANY

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
4.5 Gate Valve
AHB

4.5.1 All Gate Valve shall be as UL/FM approved and shall be as per
ENGG CERT

GJB

9COM6000001380. [Ref: SAES-U-101, sec 6]


MCC

4.5.2 All manual block valves in fire protection service shall be car-sealed in
their normal operating position or shall be otherwise supervised per
NFPA 13.
ISSUED FOR CONSTRUCTION

4.6 Sprinkler Head


DESCRIPTION

4.6.1 Sprinkler Head shall be UL/FM approved and shall be as per


9COM6000001325. [Ref: SAES-U-101, sec 6]

4.6.2 Quick Response Sprinkler shall be used in all residential buildings.

4.6.3 Quick Response Sprinkler of K-Factor 5.6 shall be used for Light Hazard
Occupancy and for Ordinary Hazard Occupancy.
JO/EWO
10-01506-
0007 06/26/16

4.7 Portable Fire Extinguisher


DATE

4.7.1 Portable Fire Extinguisher shall be UL/FM approved and shall be as per
NO.
REV

00

9COM6000001302. [Ref: SAES-U-101, sec 6]


DISCIPLINE
ENGINEER
MARTE COMETA
4.7.2 Portable Fire Extinguisher shall be provided and spaced in accordance
06/26/16
DATE:
PROJECT
with SAES-M-100, Clause 906.
ENGINEER
GEORGE JACOB
4.7.3 For light and ordinary hazard, a 22.9 meter (75-foot) travel distance
06/26/16
DATE:
CERTIFIED
results in a placement of extinguishers that are 32.3 meters (106 feet)
GEORGE JACOB apart as measured by a straight line.
06/26/16
DATE:
CONSTRUCTION 4.7.4 For extra hazard, a 15.25 meter (50-foot) travel distance results in a
AGENCY
ALI HASSAN AL-BAGGAL
placement of extinguishers that are 21.5 meters (70 feet) apart as
DATE:
06/26/16 measured by a straight line.
OPERATIONS
AYMAN ABDULLATIF AL-NAMI
4.7.5 Portable Fire Extinguishers shall be located in strategic places, which are
DATE:
06/26/16 easily accessible. For Example close to access doors or rooms, on
CONTROL NUMBER

access stairways and on the escape ways.


VERIFICATION
EDSD

4.7.6 Portable Fire Extinguisher shall be consistent with the intent of NFPA 10.
DATE:
BY:
APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
REVISION CERTIFICATE

OF THIS DRAWING IS COVERED, FOR ALL

BY DRAWING COMPLETION CERTIFICATE


00

_____________________
(DCC) NO. 10-01506-0007-001

DESIGN PHILOSOPHY – FIRE WATER SYSTEM DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO REV.NO.
TWO (2) IDENTICAL PRE-CAST RESIDENTIAL BUILDINGS AT RIC DOC 8
B44 B FI-E00001
RESIDENTIAL & INDUSTRIAL COMPLEX Of 00
KHURAIS SAUDI ARABIA JO: 10-01506-0007 9
EDSD/2616-0399.doc
EDSD REV
REVISION CERTIFICATE VERIFICATION NO. DATE JO/EWO DESCRIPTION ENGG CERT PMT OPRNS

DATE:
DATE:
DATE:
DATE:
DATE:
THIS INDICATES THAT REV. NO.__________
00
00 10-01506-
OF THIS DRAWING IS COVERED, FOR ALL 06/26/16 0007 ISSUED FOR CONSTRUCTION MCC GJB AHB AAN
CONTROL NUMBER
APPROVAL/CERTIFICATION REQUIREMENTS,

AGENCY
BY:

PROJECT
BY DRAWING COMPLETION CERTIFICATE

ENGINEER

06/26/16
ENGINEER
MARTE COMETA

06/26/16
DISCIPLINE

06/26/16
06/26/16

06/26/16
CERTIFIED
GEORGE JACOB

GEORGE JACOB

ALI HASSAN AL-BAGGAL

OPERATIONS
CONSTRUCTION

AYMAN ABDULLATIF AL-NAMI


(DCC) NO. 10-01506-0007-001
_____________________ DATE:

KHURAIS
Saudi Aramco 2616-ENG (03/99)

5 ATTACHMENT

Flow Test Result

RESIDENTIAL & INDUSTRIAL COMPLEX


DESIGN PHILOSOPHY – FIRE WATER SYSTEM
TWO (2) IDENTICAL PRE-CAST RESIDENTIAL BUILDINGS AT RIC
DOC

SAUDI ARABIA
JO:
B44
B
DWG.TYPE PLANT NO. INDEX
SAUDI ARABIAN OIL COMPANY

10-01506-0007
DRAWING NO.

FI-E00001

9
9
Of
SHT.NO

00
EDSD/2616-0399.doc
REV.NO.
THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.