DESIGN PHILOSOPHY
0007 06/26/16
NO. DATE
REV
00
DISCIPLINE
FIRE WATER SYSTEM
ENGINEER
MARTE COMETA
06/26/16
DATE:
PROJECT
ENGINEER
GEORGE JACOB
06/26/16
DATE:
GEORGE JACOB
CERTIFIED ISSUED FOR CONSTRUCTION
06/26/16
DATE:
CONSTRUCTION
AGENCY
ALI HASSAN AL-BAGGAL
06/26/16
DATE:
JUNE 2016
OPERATIONS
AYMAN ABDULLATIF AL-NAMI
06/26/16
DATE:
CONTROL NUMBER
VERIFICATION
PREPARED BY:
EDSD
DATE:
MUSTANG-HDP
BY:
_____________________
(DCC) NO. 10-01506-0007-001
DESIGN PHILOSOPHY – FIRE WATER SYSTEM DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO REV.NO.
TWO (2) IDENTICAL PRE-CAST RESIDENTIAL BUILDINGS AT RIC DOC 1
B44 B FI-E00001
RESIDENTIAL & INDUSTRIAL COMPLEX Of 00
KHURAIS SAUDI ARABIA JO: 10-01506-0007 9
EDSD/2616-0399.doc
Saudi Aramco 2616-ENG (03/99)
PMT OPRNS
THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
AHB
TABLE OF CONTENTS
ENGG CERT
GJB
1. INTRODUCTION ............................................................................................................ 3
MCC
00
DISCIPLINE
ENGINEER
4.6 SPRINKLER HEAD ............................................................................................................................ 8
MARTE COMETA
4.7 PORTABLE FIRE EXTINGUISHER ..................................................................................................... 8
06/26/16
DATE:
PROJECT
ENGINEER
5 ATTACHMENT ............................................................................................................... 9
GEORGE JACOB
06/26/16
DATE:
CERTIFIED
GEORGE JACOB
06/26/16
DATE:
CONSTRUCTION
AGENCY
ALI HASSAN AL-BAGGAL
06/26/16
DATE:
OPERATIONS
AYMAN ABDULLATIF AL-NAMI
06/26/16
DATE:
CONTROL NUMBER
VERIFICATION
EDSD
DATE:
BY:
APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
REVISION CERTIFICATE
_____________________
(DCC) NO. 10-01506-0007-001
DESIGN PHILOSOPHY – FIRE WATER SYSTEM DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO REV.NO.
TWO (2) IDENTICAL PRE-CAST RESIDENTIAL BUILDINGS AT RIC DOC 2
B44 B FI-E00001
RESIDENTIAL & INDUSTRIAL COMPLEX Of 00
KHURAIS SAUDI ARABIA JO: 10-01506-0007 9
EDSD/2616-0399.doc
Saudi Aramco 2616-ENG (03/99)
PMT OPRNS
THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
AHB
1. INTRODUCTION
ENGG CERT
GJB
This document represents Fire Protection Philosophy to be adopted for the project.
MCC
SAES-M-100 (IBC 2009 Edition) is adopted as a code for selection and design of fire
protection systems for the project.
ISSUED FOR CONSTRUCTION
The project shall be designed and implemented in accordance with Saudi Aramco
Engineering Standards and Specifications dated June 2014 and latest National Fire
DESCRIPTION
All the Fire Protection work in this project shall be performed in accordance with
JO/EWO
10-01506-
Code Title
06/26/16
DATE
00
Marking of Hydrants
VERIFICATION
_____________________
(DCC) NO. 10-01506-0007-001
DESIGN PHILOSOPHY – FIRE WATER SYSTEM DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO REV.NO.
TWO (2) IDENTICAL PRE-CAST RESIDENTIAL BUILDINGS AT RIC DOC 3
B44 B FI-E00001
RESIDENTIAL & INDUSTRIAL COMPLEX Of 00
KHURAIS SAUDI ARABIA JO: 10-01506-0007 9
EDSD/2616-0399.doc
Saudi Aramco 2616-ENG (03/99)
PMT OPRNS
THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
AHB
GJB
The design shall be carried out as per “June 2014” issue of the following SAUDI
MCC
Number Title
Equipment
3 DESIGN CRITERIA
SAES-M-100 (IBC 2009 Edition) is adopted as a code for selection and design of
fire protection systems for the project.
JO/EWO
10-01506-
00
DATE:
06/26/16 3.2.1 Dedicated firewater system shall be used which shall be provided thru an
PROJECT
ENGINEER
existing firewater network. Tie-in to the existing network shall be done as
GEORGE JACOB per tie-in schedule BB-090210-001.
06/26/16
DATE:
GEORGE JACOB
CERTIFIED 3.2.2 It is assumed that the existing firewater system which is also supplying
06/26/16
the firewater demand of the existing identical residential buildings is
DATE:
CONSTRUCTION
sufficient to supply the new firewater demand.
AGENCY
ALI HASSAN AL-BAGGAL
06/26/16
3.2.3 Flow test data:
DATE:
OPERATIONS
AYMAN ABDULLATIF AL-NAMI
Actual Flow: 851 gpm @ 120 psig
06/26/16
DATE: Predicted Flow: 3107 gpm @ 20 psig
CONTROL NUMBER
VERIFICATION
DATE:
BY:
3.3.1. Water velocity for underground mains in the firewater network shall be
_____________________
101.4.5.1]
DESIGN PHILOSOPHY – FIRE WATER SYSTEM DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO REV.NO.
TWO (2) IDENTICAL PRE-CAST RESIDENTIAL BUILDINGS AT RIC DOC 4
B44 B FI-E00001
RESIDENTIAL & INDUSTRIAL COMPLEX Of 00
KHURAIS SAUDI ARABIA JO: 10-01506-0007 9
EDSD/2616-0399.doc
Saudi Aramco 2616-ENG (03/99)
PMT OPRNS
THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
3.3.2. Minimum water velocity is 3.1 m/s as per SAES-M-100 clause 101.4.5.1.
AHB
GJB
3.4.1. The Minimum residual pressure at all points in the firewater network shall
be 20 psig. [Ref: SAES-M-100, Clause 101.4.5.1]
3.5.1. Prior to Hydrostatic test all underground piping, from the water supply to
06/26/16
the system riser, and lead-in connections to the system riser shall be
DATE
00
DISCIPLINE
ENGINEER 3.5.2. All underground piping and attached appurtenances subjected to system
MARTE COMETA
06/26/16
working pressure shall be hydrostatically tested at 200 psi (13.8 bar) or
DATE:
PROJECT 50 psi (3.5 bar) in excess of the system working pressure, whichever is
ENGINEER
GEORGE JACOB greater, and shall maintain that pressure at ±5 psi (0.35 bar) for 4 hours.
DATE:
06/26/16 [Ref: SAES-B-017 Sec. 12.6]
CERTIFIED
GEORGE JACOB
3.5.3. All above ground sprinkler system piping and attached appurtenances
06/26/16
DATE: subjected to system working pressure shall be hydrostatically tested at
CONSTRUCTION
AGENCY
ALI HASSAN AL-BAGGAL
200 psi (13.8 bar) and shall maintain that pressure without loss for 2
06/26/16
hours. [Ref: NFPA 13, Clause 25.2.1.1]
DATE:
OPERATIONS
AYMAN ABDULLATIF AL-NAMI
3.6 Wind Direction
06/26/16
DATE: As per SAES-A-112, Table 1, following data is considered for Wind Directions.
CONTROL NUMBER
VERIFICATION
Area : Khurais
EDSD
_____________________
THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
3.7.2. All aboveground (A/G) piping inside the building shall be Galvanized
AHB
GJB
3.7.5. Minimum Water supply line serving Fire Hydrant shall be 6 Inch (152 mm)
[Ref: SAES-M-100, Sec 101.4.5]
ISSUED FOR CONSTRUCTION
minimum 900 mm. However, for instances that will need more depth,
refer to SAES-L-460 for additional requirements. [Ref: NFPA 24, Clause
10.4.4, SAES-L-460 Sec.16]
3.7.7. All tees, plugs, caps, bends reducers, valves, and hydrant branches shall
be restrained against the movement by using thrust blocks in accordance
with NFPA 24, Clause 10.8.2. [Ref: NFPA 24, Clause 10.8.1.1]
JO/EWO
10-01506-
3.7.8. Dead-end lines serving fire hydrants shall not be greater than 68 feet
0007
00
06/26/16 4.1.2 All new fire hydrants shall be UL Listed and or FM Approved for fire main
DATE:
service and shall also meet ANSI/AWWA C503 Standard as per
CONTROL NUMBER
VERIFICATION
4.1.3 All hydrants shall have protection against mechanical damage by use of
DATE:
BY:
DESIGN PHILOSOPHY – FIRE WATER SYSTEM DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO REV.NO.
TWO (2) IDENTICAL PRE-CAST RESIDENTIAL BUILDINGS AT RIC DOC 6
B44 B FI-E00001
RESIDENTIAL & INDUSTRIAL COMPLEX Of 00
KHURAIS SAUDI ARABIA JO: 10-01506-0007 9
EDSD/2616-0399.doc
Saudi Aramco 2616-ENG (03/99)
PMT OPRNS
THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
4.1.5 Hydrants shall be numbered and clearly stenciled on the riser to meet
AHB
NFPA 291. The numbering system shall be coordinated with the Fire
Protection Department before entering or updating these numbers in the
ENGG CERT
GJB
drawing system.
MCC
4.1.6 Fire hydrants in residential and service areas shall be located on the
street side of houses or buildings. If such locations are not available or
feasible, the requirements shall meet SAES-M-100.
ISSUED FOR CONSTRUCTION
DESCRIPTION
4.2.2 All Post indicator valve shall be as UL/FM approved and shall be as per
9COM6000001380. [Ref: SAES-U-101, sec 6]
sectional valves does not exceed six (06). [Ref: NFPA 24, Clause 6.6.1]
0007
4.2.4 All below grade sectional valves in mains or branch service shall be a
06/26/16
DATE
listed post indicator type valve with position indicators above grade. [Ref:
NFPA 24, Clause 6.1.3]
NO.
REV
00
DISCIPLINE
ENGINEER
MARTE COMETA
DATE:
06/26/16 4.3 Alarm Check Valve
PROJECT
ENGINEER
GEORGE JACOB 4.3.1 Alarm Check Valve shall be UL/FM approved and shall be as per
DATE:
06/26/16 9COM6000001325. [Ref: SAES-U-101, sec 6]
CERTIFIED
GEORGE JACOB
4.3.2 Alarm Check Valve to be interfaced with Fire Alarm System.
06/26/16
DATE:
CONSTRUCTION
AGENCY
ALI HASSAN AL-BAGGAL
DATE:
06/26/16 4.4 Fire Department Connection
OPERATIONS
AYMAN ABDULLATIF AL-NAMI
4.4.1 Fire Department Connection shall be UL/FM approved and shall be as
DATE:
06/26/16 per 9COM6000001325. [Ref: SAES-U-101, sec 6]
CONTROL NUMBER
VERIFICATION
_____________________
(DCC) NO. 10-01506-0007-001
DESIGN PHILOSOPHY – FIRE WATER SYSTEM DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO REV.NO.
TWO (2) IDENTICAL PRE-CAST RESIDENTIAL BUILDINGS AT RIC DOC 7
B44 B FI-E00001
RESIDENTIAL & INDUSTRIAL COMPLEX Of 00
KHURAIS SAUDI ARABIA JO: 10-01506-0007 9
EDSD/2616-0399.doc
Saudi Aramco 2616-ENG (03/99)
PMT OPRNS
THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
4.5 Gate Valve
AHB
4.5.1 All Gate Valve shall be as UL/FM approved and shall be as per
ENGG CERT
GJB
4.5.2 All manual block valves in fire protection service shall be car-sealed in
their normal operating position or shall be otherwise supervised per
NFPA 13.
ISSUED FOR CONSTRUCTION
4.6.3 Quick Response Sprinkler of K-Factor 5.6 shall be used for Light Hazard
Occupancy and for Ordinary Hazard Occupancy.
JO/EWO
10-01506-
0007 06/26/16
4.7.1 Portable Fire Extinguisher shall be UL/FM approved and shall be as per
NO.
REV
00
4.7.6 Portable Fire Extinguisher shall be consistent with the intent of NFPA 10.
DATE:
BY:
APPROVAL/CERTIFICATION REQUIREMENTS,
THIS INDICATES THAT REV. NO.__________
REVISION CERTIFICATE
_____________________
(DCC) NO. 10-01506-0007-001
DESIGN PHILOSOPHY – FIRE WATER SYSTEM DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO REV.NO.
TWO (2) IDENTICAL PRE-CAST RESIDENTIAL BUILDINGS AT RIC DOC 8
B44 B FI-E00001
RESIDENTIAL & INDUSTRIAL COMPLEX Of 00
KHURAIS SAUDI ARABIA JO: 10-01506-0007 9
EDSD/2616-0399.doc
EDSD REV
REVISION CERTIFICATE VERIFICATION NO. DATE JO/EWO DESCRIPTION ENGG CERT PMT OPRNS
DATE:
DATE:
DATE:
DATE:
DATE:
THIS INDICATES THAT REV. NO.__________
00
00 10-01506-
OF THIS DRAWING IS COVERED, FOR ALL 06/26/16 0007 ISSUED FOR CONSTRUCTION MCC GJB AHB AAN
CONTROL NUMBER
APPROVAL/CERTIFICATION REQUIREMENTS,
AGENCY
BY:
PROJECT
BY DRAWING COMPLETION CERTIFICATE
ENGINEER
06/26/16
ENGINEER
MARTE COMETA
06/26/16
DISCIPLINE
06/26/16
06/26/16
06/26/16
CERTIFIED
GEORGE JACOB
GEORGE JACOB
OPERATIONS
CONSTRUCTION
KHURAIS
Saudi Aramco 2616-ENG (03/99)
5 ATTACHMENT
SAUDI ARABIA
JO:
B44
B
DWG.TYPE PLANT NO. INDEX
SAUDI ARABIAN OIL COMPANY
10-01506-0007
DRAWING NO.
FI-E00001
9
9
Of
SHT.NO
00
EDSD/2616-0399.doc
REV.NO.
THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.