CONTENT
WIRING CABLES
PVC-Insulated, Conduit Wiring Cables (Single Core) NCY 3-4
Low Smoke Zero Halogen (LSZH), Conduit Wiring Cables (Single Core) NCH 5-6
PVC-Insulated, PVC Sheathed Surface Wiring Cables NCYY-F & NCYY-F+E 7-8
PVC-Insulated Flexible Cords & Flat flexible Cords NCY...f, NCY-F…f 9-10
PVC-Insulated, PVC Sheathed Round Flexible Cords NCYY-R…f 11-12
INSTRUMENTATION CABLES
Technical Information
PVC, PE or XLPE insulated, overall screened, PVC or LSZH Sheathed E-Y(st)Y, E-2Y(st)Y & E-2X(st)Y 55-56
Non Armoured Cables E-2Y(st)H & E-2X(st)H
PVC, PE or XLPE insulated, Individual & overall screened, PVC or LSZH E-Y(st)(st)Y, E-2Y(st)(st)Y & E-2X(st)(st)Y 57-58
Sheathed Non Armoured Cables E-2Y(st)(st)H & E-2X(st)(st)H
PVC, PE or XLPE insulated, overall screened, PVC or LSZH Sheathed E-Y(st)YRY, E-2Y(st)YRY & E-2X(st)YRY 59-60
Armoured Cables E-2Y(st)HRH & E-2X(st)HRH
PVC, PE or XLPE insulated, Individual & overall screened, PVC or E-Y(st)(st)YRY, E-2Y(st)(st)YRY & E-2X(st)(st)YRY 61-62
LSZH Sheathed Armoured Cables E-2Y(st)(st)HRH & E-2X(st)(st)HRH
SECTION B
Guide for selection of power cables 63-66
Medium Voltage Cables 67
Core Identification 68
Flame Retardant, Halogen Free, Low Smoke and Fire Resistant cables 69
Dimensions and Weight of Wooden Drums 70
Recommendation for Handling and storage of cables and cable drums 71-72
Legend 73
Symbols 74
Kabelmetal Nigeria Plc
History
For over 50 years Kabelmetal Nigeria Plc has been admired for its cable making expertise.
Because of our drive for excellence in quality of products and passion for innovation, we have
established ourselves as the leader and pioneer in the Nigerian cable market.
The company has its manufacturing facility and head office located at Ikeja, Lagos and is the
largest manufacturer of power, control and instrumentation cables in the West African sub
region.
Benefitting from the parent company’s cable making expertise of over 100 years and local
manufacturing experience, Kabelmetal strengthens the nerves and sinews of the Nigerian
economy.
At the beginning of the 1980-s the development of cross linked polyethylene (XLPE) for low
voltage insulated cables opened the door to new market segments including the oil and gas
market. The introduction of air field lighting cables and cables with enhanced fire performance
features over the following years further fortified our product range and expanded our
customer base.
Kabelmetal Nigeria Plc is the first cable manufacturer in Nigeria, certified according to ISO
9000 in the year 2000. We are also Nigerian Industrial Standards (NIS) Diamond Award
winner. Our products are in conformance to IEC standards, Nigerian Industrial Standards and
BS standards for some specific products.
Kabelmetal as pioneer in the industry and the first to be ISO certified way back in year 2000, has
followed and adopted the revisions through the years up to the current ISO 9001:2015
standard. This yet positions Kabelmetal as the first organisation within the cable manufacturing
industry in Nigeria and one of the very few across the globe to be certified to the new ISO
9001:2015 standard.
Increased globalization has changed the way businesses are run. With increased expectations
from customers and other interested parties, and with more access to information, today’s wider
society has a stronger voice than ever before. Kabelmetal underscores these changes in order to
remain relevant and be responsive to the emerging business environment.
Kabelmetal Nigeria Plc is the most advanced manufacturer of cables in the West Africa Sub
Saharan region. With our manufacturing facility and head office located in Ikeja Industrial
Estate, Ikeja Lagos and distributor outlets across the Nigeria, we are well represented
nationwide.
Our product scope covers the whole range of low voltage power, control and instrumentation
cables. Cables for power distribution and several special cables supplement our product
portfolio.
2
Kabelmetal Nigeria Plc
Design
1 Conductor
Class 1 plain solid copper
Class 2 stranded plain copper
2 Insulation
PVC (Polyvinyl Chloride)
3
Kabelmetal Nigeria Plc
WIRING CABLES
NCY
4
Kabelmetal Nigeria Plc
NCH
WIRING CABLES IEC 60227 - 3
Single Core LSZH Insulated Copper Conduit
Wiring Cable 450/750V
Applications:
For indoor general wiring cable primarily for installation in public areas such
as shopping centers, theatres, offices, hotels, schools, libraries, data centers, j
ails, hospitals and high-rise buildings for the higher safety provided in case of fire.
The reduction in smoke and effluent gases is key to saving human lives and
facilitating the work of rescue teams during fire emergencies.
Design
1 Conductor
Class 1 plain solid copper
Class 2 stranded plain copper
2 Insulation
Haloge free low smoke thermoplastic material
5
Kabelmetal Nigeria Plc
WIRING CABLES
NCH
6
Kabelmetal Nigeria Plc
Applications:
For use in electrical installations in houses, offices,
factories to be fixed on surface.
Design
1 Conductor
Class 1 solid plain copper 1 2 3
Class 1 stranded plain copper
2 Insulation
PVC (Polyvinyl Chloride)
3 Outer sheath
PVC (Polyvinyl Chloride)
colour: grey
7
Kabelmetal Nigeria Plc
WIRING CABLES
NCYY-F and NCYY-F+E
8
Kabelmetal Nigeria Plc
Design
1 Conductor
Class 5 Flexible copper conductors
2 Insulation
Polyvinyl Chloride (PVC)
Abbreviation:
...f Flexible
-F Flat cord
9
Kabelmetal Nigeria Plc
WIRING CABLES
NCY-f and NCY-F…f
10
Kabelmetal Nigeria Plc
Design
1 Conductor
Class 5 Flexible Copper conductor
2 Insulation
PVC (Polyvinyl Chloride)
3 Outer sheath
PVC (Polyvinyl Chloride)
colour: grey
11
Kabelmetal Nigeria Plc
WIRING CABLES
NCYY-R..f
12
Kabelmetal Nigeria Plc
Applications:
For use in indoor installations, in cables ducts/trays, in industrial plants, substations
and power utility distribution schemes. Installation underground with additional protection, where
mechanical damage may be expected.
Max core temperature 70 °C
Max short circuit temperature 160 °C
Design
1 Conductor
Class 1 solid plain annealed copper or
Class 2 stranded plain annealed copper
2 Insulation
PVC (Polyvinyl Chloride)
3 Outer sheath
PVC (Polyvinyl Chloride)
colour: black
13
Kabelmetal Nigeria Plc
14
Kabelmetal Nigeria Plc
15
Kabelmetal Nigeria Plc
POWER AND CONTROL CABLES
NCYY and NCYY-cc
Maximum Permissible Current
Nominal Maximum DC Rating Delivery
Approx. Standard
Cross Class of Resistance of Approx. Form on
Overall Three loaded Conductors Delivery
Sectional Conductor Conductor @ Weight Wooden
Diameter length
Area 20°C in Ground in Air Drum
@20 °C @30 °C
mm² Ω/km mm A A m kg/km
5 - Cores
5 x 1.5 1 12.1 11.3 21 16.5 1000 204 R10
5 x 1.5 2 12.1 11.8 21 16.5 1000 207 R10
5 x 2.5 2 7.41 12.3 29 22.5 1000 270 R10
5 x 2.5 2 7.41 12.9 29 22.5 1000 273 R10
5x4 1 4.61 14.5 39 30.0 1000 396 R12
5x4 2 4.61 15.6 39 30.0 1000 406 R12
5x6 1 3.08 15.9 47 38.0 1000 523 R12
5x6 2 3.08 17.2 47 38.0 1000 530 R12
5 x 10 2 1.83 19.4 63 53.0 1000 752 R12
5 x 16 2 1.15 22.1 81 71.0 1000 1076 R14
5 x 25 2 0.727 26.7 104 89.0 1000 1627 R16
5 x 35 2 0.524 29.9 126 111.0 500 2178 R14
5 x 50 2 0.387 35.3 149 135.0 500 2892 R16
5 x 70 2 0.268 41.6 183 174.0 500 4024 R16
5 x 95 2 0.193 46.9 216 212.0 500 4498 R18
Control cables with 1.5 mm² conductors
5 x 1.5 1 12.1 11.7 21 16.5 1000 205 R10
7 x 1.5 1 12.1 12.6 19 14.0 1000 251 R10
10 x 1.5 1 12.1 15.6 16 12.0 1000 340 R12
12 x 1.5 1 12.1 16.2 15 11.5 1000 388 R12
16 x 1.5 1 12.1 17.7 13 10.5 1000 494 R12
19 x 1.5 1 12.1 18.6 13 10.0 1000 559 R12
24 x 1.5 1 12.1 21.6 11 9.0 1000 691 R14
27 x 1.5 1 12.1 22.2 11 8.5 1000 760 R14
33 x 1.5 1 12.1 23.7 10 8.0 1000 891 R14
37 x 1.5 1 12.1 24.6 10 8.0 1000 978 R14
40 x 1.5 1 12.1 25.5 10 8.0 1000 1005 R14
Control cables with 2.5 mm² conductors
5 x 2.5 1 7.41 12.8 29 22.5 1000 270 R10
7 x 2.5 1 7.41 13.8 24 19.5 1000 336 R10
10 x 2.5 1 7.41 17.2 21 16.5 1000 460 R12
12 x 2.5 1 7.41 17.9 20 16.0 1000 530 R12
16 x 2.5 1 7.41 19.6 17 14.0 1000 677 R12
19 x 2.5 1 7.41 20.6 16 13.5 1000 775 R12
24 x 2.5 1 7.41 24.0 14 12.0 1000 962 R14
27 x 2.5 1 7.41 24.7 14 11.5 1000 1063 R14
33 x 2.5 1 7.41 25.9 14 11.0 1000 1269 R14
37 x 2.5 1 7.41 27.4 13 10.5 1000 1402 R14
40 x 2.5 1 7.41 28.6 13 10.5 1000 1518 R16
Control cables with 4 mm² conductors
5x4 1 4.61 15.2 39 30.0 1000 398 R12
7x4 1 4.61 16.5 33 26.0 1000 500 R12
10 x 4 1 4.61 20.8 27 22.0 1000 688 R14
12 x 4 1 4.61 21.7 26 21.0 1000 797 R14
16 x 4 1 4.61 23.8 23 19.0 1000 1015 R14
19 x 4 1 4.61 25.1 21 18.0 1000 1179 R14
24 x 4 1 4.61 29.6 19 16.0 500 1480 R14
27 x 4 1 4.61 30.5 19 15.0 500 1640 R14
Current ratings based on IEC 60364.5.52 - Multi core cables
Three loaded conductors or two loaded conductors.
Conditions for installation
1. Underground: Thermal resistivity of soil: 1 K.m/W. Burying depth: 0.7 m. Load factor: 0.7
2. In air: Load factor is 1.0
Control cable with stranded conductors - Class 2 – are available on request.
16
Kabelmetal Nigeria Plc
Applications:
For use in underground installations, indoors, in cable ducts/trays and under sunlight. In industrial
distribution schemes, substations and for power utility distribution.
Design
1 Conductor
Class 1 plain solid annealed copper or
Class 2 stranded plain annealed copper
2 Insulation
PVC (Polyvinyl Chloride)
3 Inner Sheath
PVC (Polyvinyl Chloride)
5 Outer Sheath
PVC (Polyvinyl Chloride)
Good 10 x OD
temperature 70 ºC conductor Flame retardant
Bending radius
flexibility
18
Kabelmetal Nigeria Plc
18
Kabelmetal Nigeria Plc
20
Kabelmetal Nigeria Plc
21
Kabelmetal Nigeria Plc
CONTROL CABLES
NCYRY -cc
Maximum Permissible
Maximum DC Approx. Current Rating Amp Delivery
Nominal Standard
Class of Resistance of Overall Three loaded Conductors Approx. Form on
Cross Delivery
Conductor Conductor @ Diameter Weight Wooden
Sectional length
20 °C of Cable in Ground in Air Drum
Area
@20 °C @30 °C
mm² Ω/km mm A A m kg/km
Control cables with 2.5 mm² conductors
5 x 2.5 1 7.41 16.5 29 22.5 1000 578 R12
5 x 2.5 2 7.41 18.1 29 22.5 1000 621 R12
7 x 2.5 1 7.41 17.5 24 19.5 1000 716 R12
7 x 2.5 2 7.41 18.1 24 19.5 1000 749 R12
10 x 2.5 1 7.41 20.9 21 16.5 1000 944 R14
10 x 2.5 2 7.41 19.1 21 16.5 1000 1035 R14
12 x 2.5 1 7.41 22.3 20 16.0 1000 1058 R14
12 x 2.5 2 7.41 23.1 20 16.0 1000 1144 R14
16 x 2.5 1 7.41 24.2 17 14.0 1000 1293 R14
16 x 2.5 2 7.41 24.9 17 14.0 1000 1374 R14
19 x 2.5 1 7.41 25.5 16 13.5 1000 1426 R14
19 x 2.5 2 7.41 26.0 16 13.5 1000 1496 R14
24 x 2.5 1 7.41 28.6 14 12.0 1000 1717 R16
24 x 2.5 2 7.41 30.0 14 12.0 1000 1856 R16
27 x 2.5 1 7.41 29.5 14 11.5 1000 1853 R16
27 x 2.5 2 7.41 31.3 14 11.5 1000 2192 R16
33 x 2.5 1 7.41 31.2 14 11.0 1000 2131 R16
33 x 2.5 2 7.41 33.3 14 11.0 1000 2450 R16
37 x 2.5 1 7.41 33.0 13 10.5 1000 2504 R14
37 x 2.5 2 7.41 33.9 13 10.5 1000 2670 R14
40 x 2.5 1 7.41 34.6 13 10.5 1000 2660 R14
40 x 2.5 2 7.41 36.1 13 10.5 1000 2849 R14
Control cables with 4 mm² conduct ors
5x4 1 4.61 18.6 39 30.0 1000 746 R12
5x4 2 4.61 19.7 39 30.0 1000 814 R12
7x4 1 4.61 19.9 33 26.0 1000 880 R14
7x4 2 4.61 21.8 33 26.0 1000 1077 R14
10 x 4 1 4.61 24.8 27 22.0 1000 1326 R14
10 x 4 2 4.61 26.4 27 22.0 1000 1406 R14
12 x 4 1 4.61 25.6 26 21.0 1000 1433 R14
12 x 4 2 4.61 28.7 26 21.0 1000 1611 R14
16 x 4 1 4.61 26.3 23 19.0 1000 1759 R14
16 x 4 2 4.61 29.6 23 19.0 1000 1886 R14
19 x 4 1 4.61 29.2 21 18.0 1000 1745 R16
19 x 4 2 4.61 34.8 21 18.0 1000 2451 R16
24 x 4 1 4.61 35.0 19 16.0 500 2616 R16
24 x 4 2 4.61 37.6 19 16.0 500 2873 R16
27 X 4 1 4.61 35.8 19 15.0 500 2826 R16
27 x 4 2 4.61 38.5 19 15.0 500 3098 R16
21
Kabelmetal Nigeria Plc
Applications:
For use in indoor installations, in cables ducts/trays, in industrial plants, substations
and power utility distribution schemes. Installation underground with additional protection, where
mechanical damage may be expected.
Max core temperature 70 °C
Max.short circuit Temp. 160 0C
Design
1 Conductor
Class 2 stranded plain aluminium
2 Insulation
PVC (Polyvinyl Chloride)
3 Outer sheath
PVC (Polyvinyl Chloride)
colour: black
22
Kabelmetal Nigeria Plc
POWER CABLES
NAYY
Maximum Permissible
Maximum DC Approx. Current Rating Delivery
Nominal Standard
Class of Resistance of Overall Three loaded Conductors Approx. Form on
Cross Delivery
Conductor Conductor @ Diameter in Ground in Air Weight Wooden
Sectional length
20 °C @ 20 °C @ 30 °C Drum
Area
mm² Ω/km mm A A m kg/km
2 - Cores
2 x 16 2 1.91 18.0 89 73 1000 327 R12
2 x 25 2 1.20 21.4 114 89 1000 470 R14
2 x 35 2 0.868 23.8 137 111 1000 584 R14
2 x 50 2 0.641 27.2 161 135 1000 741 R16
2 x 70 2 0.443 31.2 200 173 500 850 R14
2 x 95 2 0.320 36.0 237 210 500 1318 R16
2 x 120 2 0.253 39.4 270 244 500 1572 R18
2 x 150 2 0.206 43.8 304 282 500 1930 R20
3 - Cores
3 x 16 2 1.91 19.1 74 61 1000 370 R12
3 x 25 2 1.20 22.8 94 78 1000 523 R14
3 x 35 2 0.868 25.6 114 96 1000 654 R14
3 x 50 2 0.641 28.7 134 117 1000 793 R14
3 x 70 2 0.443 32.7 167 150 500 1028 R14
3 x 95 2 0.320 30.3 197 183 500 1366 R14
3 x 120 2 0.253 32.9 224 212 500 1652 R16
3 x 150 2 0.206 36.6 254 245 500 2020 R16
3 x 185 2 0.164 40.5 286 280 500 2512 R18
3 x 240 2 0.125 45.2 329 330 400 3208 R18
3 x 300 2 0.100 50.1 371 381 250 3980 R20
3½ - Cores
3 x 35+16 2 0.868 27.3 114 96 1000 693 R14
3 x 50+25 2 0.641 32.0 134 117 1000 926 R16
3 x 70+35 2 0.443 36.4 167 150 500 1218 R14
3 x 95+50 2 0.320 42.3 197 183 500 1640 R16
3 x 120+70 2 0.253 46.4 224 212 500 2004 R18
3 x 150+70 2 0.206 51.3 254 245 500 2368 R18
3 x 185+95 2 0.164 57.3 286 280 500 2540 R20
3 x 240+120 2 0.125 64.2 329 330 400 3803 R20
3 x 300+150 2 0.100 71.7 371 381 400 4688 R22
23
Kabelmetal Nigeria Plc
POWE R CAB L ES
NAYY
Maximum Permissible
Current Rating
Nominal Maximum DC Approx. Delivery
Three loaded Conductors Standard
Cross Class of Resistance of Overall Approx. Form on
Delivery
24
Kabelmetal Nigeria Plc
POWER CABLES
NAYRY IEC 60502-1
PVC Insulated, PVC Sheathed, Armoured
Aluminium Mains Cable 600/1000 V
Applications:
For use in indoor installations, in cable ducts/trays and underground, in industrial plants,
substations and for power utility distribution
Design
1 Conductor 1
Class 2 stranded plain aluminium
2
2 Insulation
PVC (Polyvinyl Chloride)
3 Inner Sheath 3
PVC (Polyvinyl Chloride)
4 Armour
4
Steel Wire Armour (SWA)
5 Outer Sheath 5
PVC (Polyvinyl Chloride)
25
Kabelmetal Nigeria Plc
POWER CABLES
NAYRY
Maximum Permissible
Nominal Maximum DC Approx. Current Rating Delivery
Standard
Cross Class of Resistance of Overall Three loaded Conductors Approx. Form on
Delivery
Sectional Conductor Conductor @ Diameter Weight Wooden
in Ground in Air Length
Area 20°C Drum
@20 °C @30 °C
mm² Ω/km mm A A m kg/km
2 - Cores
2 x 16 2 1.91 22.6 89 73 1000 846 R14
2 x 25 2 1.20 24.8 114 89 1000 915 R14
2 x 35 2 0.868 27.2 137 111 1000 1094 R14
2 x 50 2 0.641 30.8 161 135 500 1336 R14
2 x 70 2 0.443 35.2 200 173 500 1696 R16
2 x 95 2 0.32 40.0 237 210 500 2138 R18
2 x 120 2 0.253 42.6 270 244 500 2490 R18
2 x 150 2 0.1825 48.2 304 282 500 2966 R20
3 - Cores
3 x 16 2 1.91 24.1 74 61 1000 913 R14
3 x 25 2 1.20 27.9 94 78 1000 1003 R14
3 x 35 2 0.868 30.3 114 96 1000 1226 R14
3 x 50 2 0.641 35.6 134 117 1000 1317 R14
3 x 70 2 0.443 39.5 167 150 500 1606 R14
3 x 95 2 0.32 45.9 197 183 500 2098 R16
3 x 120 2 0.253 50.0 224 212 500 2432 R16
3 x 150 2 0.1825 54.4 254 245 500 2884 R18
3 x 185 2 0.164 60.1 286 280 500 3514 R20
3 x 240 2 0.125 66.3 329 330 400 4395 R20
3 x 300 2 0.10 74.4 371 381 250 5396 R20
3½ - Cores
3 x 35+16 2 0.868 32.9 114 96 1000 1215 R16
3 x 50+25 2 0.641 38.8 134 117 500 1534 R14
3 x 70+35 2 0.443 43.2 167 150 500 1952 R14
3 x 95+50 2 0.320 50.0 197 183 500 2446 R18
3 x 120+70 2 0.253 54.4 224 212 500 2888 R18
3 x 150+70 2 0.1825 60.1 254 245 500 3396 R20
3 x 185+95 2 0.164 66.3 286 280 500 4132 R22
3 x 240+120 2 0.125 74.4 329 330 400 4680 R22
4 - Cores
4 x 16 2 1.91 25.7 74 61 1000 601 R14
4 x 25 2 1.20 30.0 94 78 1000 888 R16
4 x 35 2 0.868 32.9 114 96 1000 1285 R16
4 x 50 2 0.641 38.8 134 117 1000 1620 R16
4 x 70 2 0.443 43.2 167 150 500 2072 R16
4 x 95 2 0.320 50.6 197 183 500 2612 R18
4 x 120 2 0.253 54.8 224 212 500 3072 R18
4 x 150 2 0.1825 60.1 254 245 500 3692 R20
4 x 185 2 0.164 66.0 286 280 400 4453 R20
4 x 240 2 0.125 74.4 329 330 400 5595 R22
4 x 300 2 0.10 82.3 371 381 250 6784 R22
5 - Cores
5 x 16 2 1.91 27.8 61 55 1000 886 R14
5 x 25 2 1.20 33.6 80 67 500 1458 R14
5 x 35 2 0.868 37.2 96 83 500 1802 R16
5 x 50 2 0.641 43.4 113 101 500 2252 R18
5 x 70 2 0.443 48.8 140 130 500 2714 R20
5 x 95 2 0.32 55.4 166 158 400 3705 R20
Current ratings based on IEC 60364.5.52 - Multi core cables
Three loaded conductors or two loaded conductors. Conditions
for installation
1. Underground: Thermal resistivity of soil: 1 K.m/W. Burying depth: 0.7m. Load factor: 0.7
2. In air: Load factor is 1.0
26
Kabelmetal Nigeria Plc
Applications:
For use in indoor installations, in cable ducts/trays, in industrial plants,
Substations and power distribution schemes. Installation underground
with additional protection, where mechanical damage may be expected.
LSZH sheathed type for offshore and shipboard application.
Max conductor temperature 90 °C
Max. short circuit temperature 250 °C
Design
1 Conductor
Class 1 plain solid annealed copper or
Class 2 stranded or circular compacted
annealed copper
2 Insulation
Cross-linked Polyethylene (XLPE)
3 Sheath
Polyvinyl chloride (PVC) or
Low Smoke Zero Halogen (LSZH)
temperature @ 90º cond. Flexibilty Class 2 flame retardant /halogen free bend radius factor
10xOD
26
Kabelmetal Nigeria Plc
26
Kabelmetal Nigeria Plc
Applications:
For use in indoor installations, in cable ducts/trays and underground. In industrial plants
substations and for power utility distribution
Max core temperature 90 °C
Max. short circuit temperature 250 °C
Design
1 Conductor
Class 1 plain solid annealed copper
Class 2 stranded or circular compacted annealed copper
2 Insulation
Cross linked Polyethylene
3 Inner Sheath
Polyvinyl Chloride (PVC) or Low Smoke Zero Halogen (LSZH)
4 Armour
Aluminium Wire Armour (AWA) - Single - core
Steel Wire Armour (SWA) - Multi - core
5 Outer Sheath
Polyvinyl Chloride (PVC) or Low Smoke Zero Halogen (LSZH)
o
Temperature 90 C Cond. Flexibility Flame retardant/ Halogen free Good Bending radius 10 x OD
Kabelmetal Nigeria Plc
* Single core cables are to be amoured with aluminium wire except 1 x 16 and 1 x 25 mm²
Current ratings based on IEC 60364.5.52 - Multi core cables
Three loaded conductors or two loaded conductors.
Conditions for installation
1. Underground: Thermal resistivity of soil: 1 K.m/W. Burying depth: 0.7m. 2. In air: Load factor: 1.0
32
Kabelmetal Nigeria Plc
33
Kabelmetal Nigeria Plc
34
Kabelmetal Nigeria Plc
Applications:
For use in indoor installations, in cable ducts/trays and underground. In industrial plants,
substations and for power utility distribution.
Max core temperature 90 °C
Max. short circuit temperature 250 °C
Design
1. Conductor
Class 1 plain solid annealed copper or
Class 2 stranded or circular compacted annealed copper
1
2. Insulation 2
Cross linked Polyethylene
3. Inner Sheath 3
Polyvinyl Chloride (PVC) or Low Smoke Zero Halogen (LSZH)
4. Armour 4
Aluminium Tape Armour (ATA): Single - core
Galvanized Steel Tape Armour (GSTA): Multi - core
5. Outer Sheath 5
Polyvinyl Chloride (PVC) or Low Smoke Zero Halogen (LSZH)
35
Kabelmetal Nigeria Plc
* Single Core can also be produced with Aluminium Tape Armour (Cable Type NC2XaY)
36
Kabelmetal Nigeria Plc
37
Kabelmetal Nigeria Plc
Control cable with stranded conductors - Class 2 – in various sizes as stated on page 32
are available on request with galvanized steel tape armour
38
Kabelmetal Nigeria Plc
Design
1 Conductor
Class 2 stranded plain aluminium
2 Insulation
Cross-linked Polyethelene (XLPE)
3 Sheath
Polyvinyl chloride (PVC) or
Low Smoke Zero Halogen (LSZH)
39
Kabelmetal Nigeria Plc
POWER CABLES
NA2XY and NA2XH
Maximum Permissible
Nominal Maximum DC Approx. Current Rating Amp Delivery
Standard Approx.
Cross Class of Resistance of Overall Three loaded Conductors Form on
Delivery Weight
Sectional Conductor Conductor @ Diameter Wooden
in Grou nd Length
Area 20 °C in Air Drum
@20 °C @30 °C
mm² No. x mm Ω/km mm A A m kg/km
1 - Core
1 x 16 2 1.91 9.4 86 66 1000 111 R7
1 x 25 2 1.20 11.2 106 103 1000 155 R10
1 x 35 2 0.868 12.4 130 129 1000 195 R10
1 x 50 2 0.641 13.9 161 159 1000 244 R10
1 x 70 2 0.443 16.1 204 206 1000 325 R12
1 x 95 2 0.320 18.0 252 253 1000 419 R12
1 x 120 2 0.253 20.0 295 296 1000 530 R12
1 x 150 2 0.206 22.2 339 343 1000 650 R14
1 x 185 2 0.164 24.4 395 395 1000 795 R14
1 x 240 2 0.125 27.5 472 471 1000 1009 R16
1 x 300 2 0.100 30.3 547 547 500 619 R14
1 x 400 2 0.0778 33.9 643 663 500 799 R16
1 x 500 2 0.0605 37.9 754 770 500 973 R16
1 x 630 2 0.0469 42.3 882 899 500 1224 R18
2 - Cores
2 x 16 2 1.91 16.8 104 91 1000 267 R12
2 x 25 2 1.20 20.2 133 108 1000 378 R12
2 x 35 2 0.868 22.6 160 135 1000 477 R14
2 x 50 2 0.641 25.6 189 164 500 599 R14
2 x 70 2 0.443 29.8 233 211 500 813 R16
2 x 95 2 0.320 33.8 276 257 500 533 R14
2 x 120 2 0.253 37.8 314 300 500 663 R16
2 x 150 2 0.206 42.0 356 346 500 810 R20
3 - Cores
3 x 16 2 1.91 17.8 87 77 1000 311 R12
3 x 25 2 1.20 21.5 111 97 1000 446 R12
3 x 35 2 0.868 23.4 134 120 1000 565 R14
3 x 50 2 0.641 26.9 160 146 1000 673 R14
3 x 70 2 0.443 31.3 197 187 1000 909 R14
3 x 95 2 0.320 35.7 234 227 500 585 R16
3 x 120 2 0.253 39.8 266 263 500 728 R16
3 x 150 2 0.206 44.2 300 304 500 902 R16
3 x 185 2 0.164 49.6 337 347 500 1119 R18
3 x 240 2 0.125 55.2 389 409 500 1425 R18
3 x 300 2 0.100 61.4 440 471 500 1769 R20
40
Kabelmetal Nigeria Plc
POWER CABLES
NA2XY and NA2XH
Maximum Permissible
Nominal Approx Current Rating
Delivery
Maximum DC Standard Approx
Cross Class of Overall Three loaded conductors Form on
Delivery Weight
Sectional Conductor Resistance of Diameter Wooden
Conductor in Ground in Air Length
Area @ 20 °C @20 °C @30 °C Drum
mm² No. x mm Ω/km mm A A m kg/km
3½ - Cores
3 x 35+16 2 0.868 25.8 134 120 1000 599 R14
3 x 50+25 2 0.641 30.0 160 146 1000 790 R14
3 x 70+35 2 0.443 34.9 197 187 1000 1072 R16
3 x 95+50 2 0.320 39.6 234 227 500 699 R16
3 x 120+70 2 0.253 44.4 266 263 500 879 R16
3 x 150+70 2 0.206 49.2 300 304 500 1048 R18
3 x 185+95 2 0.164 55.1 337 347 400 1059 R18
3 x 240+120 2 0.125 61.8 389 409 400 1352 R22
3 x 300+150 2 0.100 68.7 440 471 250 1056 R22
4 - Cores
4 x 16 2 1.910 19.5 87 77 1000 385 R12
4 x 25 2 1.200 23.6 111 97 1000 556 R14
4 x 35 2 0.868 25.8 134 120 1000 663 R14
4 x 50 2 0.641 30.0 160 146 1000 863 R14
4 x 70 2 0.443 34.9 197 187 1000 1184 R16
4 x 95 2 0.320 39.6 234 227 500 774 R16
4 x 120 2 0.253 44.4 266 263 500 967 R16
4 x 150 2 0.206 49.2 300 304 500 1178 R18
4 x 185 2 0.164 55.1 337 347 400 1181 R18
4 x 240 2 0.125 61.8 389 409 400 1497 R22
4 x 300 2 0.100 68.7 440 471 250 1172 R22
5-Cores
5 x 16 2 1.910 21.4 73 68 1000 474 R12
5 x 25 2 1.200 26.0 93 81 1000 514 R14
5 x 35 2 0.868 29.4 111 101 1000 902 R16
5 x 50 2 0.641 33.6 131 123 500 577 R16
5 x 70 2 0.443 39.4 163 158 500 803 R16
5 x 95 2 0.320 45.0 193 193 500 1065 R20
41
Kabelmetal Nigeria Plc
Applications:
For use in indoor and in underground installations, in cable ducts/trays, in industrial plants
substations and for power utility distribution
Design
1 Conductor
Class 2 stranded plain Aluminium
2 Insulation
Cross linked Polyethylene (XLPE)
3 Inner Sheath
Polyvinyl Chloride (PVC) or Low Smoke Zero Halogen
4 Armour
Steel Wire Armour (SWA)
5 Outer Sheath
Polyvinyl Chloride (PVC) or Low Smoke Zero Halogen
42
Kabelmetal Nigeria Plc
POWER CABLES
NA2XRY and NA2XHRH
Maximum Permissible
Nominal Maximum DC Current Rating Delivery
Approx Standard
Cross Class of Resistance of Three loaded conductors Approx. Form on
Sectional Overall Delivery Wooden
Conductor Conductor Weight
43
Kabelmetal Nigeria Plc
POWER CABLES
NA2XRY and NA2XHRH
44
Kabelmetal Nigeria Plc
Design
1 Conductor
Class 2 stranded plain Copper
Standard
DIN 48201
temperature 70 ºC
Maximum
Nominal Maximum Delivery
Approx. Permissible Standard
Cross Class of DC Approx Form on
Overall Current Delivery
Sectional Conductor Resistance Weight Wooden
Diameter Rating in Air length
Area @20 °C @35 °C Drum
mm² Ω/km mm A m kg/km
6 2 3.08 31 55 10000 540 R7
10 2 1.83 4.1 90 2000 182 R8
16 2 1.15 5.1 125 2000 288 R10
25 2 0.727 6.3 160 2000 438 R10
35 2 0.524 7.5 220 2000 620 R10
50 2 0.387 9.0 250 2000 876 R10
50 2 0.387 9.0 250 2000 892 R10
70 2 0.268 10.5 310 2000 1194 R10
70 2 0.268 10.5 310 2000 1215 R10
95 2 0.193 12.5 380 2000 1690 R12
120 2 0.153 14.0 440 2500 2650 R14
150 2 0.124 15.8 510 2000 2672 R14
185 2 0.0991 17.5 585 2000 3298 R16
240 2 0.0754 20.3 700 1000 2207 R14
300 2 0.0601 22.5 800 1000 2724 R14
400 2 0.0470 26.0 960 1000 3640 R16
500 2 0.0366 29.1 1110 1000 4547 R18
630 2 0.0283 32.7 1277 500 2872 R16
800 2 0.0221 36.8 1456 400 2917 R18
1000 2 0.0167 41.1 1660 250 2276 R20
Current carrying capacity is based on wind speed of 0.6 m/sec and ambient temperature of 35 °C.
45
Kabelmetal Nigeria Plc
Design
1 Conductor
Class 2 stranded plain Aluminium
temperature 80 ºC
Current Delivery
Nominal Number and Approx. Calculated Form on
Code Rating at Delivery Approx. Weight
Cross Diameter Overall Breaking Wooden
Name 35°C length of Conductor
Sectional Of Wire Diameter Load Drum
mm² No x mm mm kN A m kg/km
16 - 7 x 1.70 5.1 2.9 110 14000 44 R12
22 Midge 7 x 2.06 6.2 4.0 140 6000 64 R10
25 - 7 x 2.10 6.3 4.25 145 6000 66 R10
35 - 7 x 2.50 7.5 5.85 180 3500 94 R10
50 Ant 7 x 3.10 9.3 8.3 225 6000 145 R12
50 - 19 x 1.80 9.0 8.6 225 6000 133 R12
60 Fly 7 x 3.40 10.2 9.9 260 4000 174 R12
70xx - 19 x 2.10 10.5 11.5 270 4000 181 R12
95 - 19 x 2.50 12.5 15.95 340 3000 256 R12
100xx Beetle 19 x 2.67 13.4 17.42 350 3000 293 R12
100 Wasp 7 x 4.39 13.2 16.0 350 3000 290 R12
120 - 19 x 2.80 14.0 19.1 390 2500 322 R12
150 - 37 x 2.25 15.8 25.7 455 2000 406 R12
150xx Hornet 19 x 3.25 16.3 24.7 455 2000 434 R12
185 - 37 x 2.50 17.5 31.05 520 3000 501 R16
200 Chaffer 19 x 3.78 18.9 32.4 550 2000 587 R14
240 - 61 x 2.25 20.3 40.15 625 2000 670 R16
250 Cockroach 19 x 4.22 21.1 40.4 635 2000 731 R16
300 - 61 x 2.50 22.5 48.5 710 2000 827 R16
300 Butterfly 19 x 4.65 23.3 48.75 710 2000 888 R18
400 - 61 x 2.89 26.0 61.9 855 2000 1105 R14
400 Centipede 37 x 3.78 26.5 63.1 855 1000 1145 R16
500 - 61 x 3.23 29.1 76.0 990 1000 1381 R16
630 - 61 x 3.62 32.6 96.9 1140 1000 1735 R18
800 - 61 x 4.10 36.9 120.55 1340 1000 2225 R20
1000 - 61 x 4.57 41.1 148.45 1540 1000 2764 R22
Current carrying capacity is based on wind speed of 0.6 m/sec and ambient temperature of 35 °C.
46
Kabelmetal Nigeria Plc
Applications:
Aluminium Conductor Steel reinforeced is composed of one or more concentric layers of
Aluminium and steel wires, whereby the central layer consist of steel wires and the peripheral
layer of Aluminium wires.
Max conductor temperature under service condition 80 °C
1 2
Design
Conductor
1 Steel wire
2 Aluminium wires
temperature 80 ºC
Current carrying capacity is based on wind speed of 0.6 m/sec and ambient temperature of 35 °C.
47
Kabelmetal Nigeria Plc
Design
1 Conductor
Class 1 plain solid aluminium
Class 2 stranded plain aluminium
2 Insulation
PVC (Polyvinyl chloride)
temperature 70 ºC
48
Kabelmetal Nigeria Plc
Applications:
For use in low voltage distribution system intended for urban and rural electrification
schemes, for consumer connection derived from the distribution system
1 2
Design
1 Conductor
Class 2 stranded plain aluminium
2 Insulation
XLPE
temperature 90 ºC 10 x OD
Bending radius
49
Kabelmetal Nigeria Plc
Applications:
Used for Airfield Lighting purposes, such as illumination of runways,
other illuminations, approach system and the like.
Max core temperature 90 °C
Max. short circuit Temperature 250 °C
Design
1 Conductor
Class 2 stranded plain annealed copper
2 Conductor screen:
semi conducting tape (for 5kV Cable)
3 Insulation
Polyethylene (PE) or Cross-linked Polyethylene (XLPE ).
4 Screen
Aluminium or Brass Tape
5 Outer Sheath
Polyvinyl chloride (PVC)
colour: black
Maximum
Delivery
DC Approx.
Nominal Cross Class of Standard Form on
Nominal Resistance of Overall
Sectional Area Conductor Delivery Weight Wooden
Conductor Diameter
Voltage length Drum
@ 200C
(mm²) Ω/km (mm) (m) (kg/km)
1 - Core
3 kV 6 2 3.08 12.3 1000 194 R10
5 kV 6 2 3.08 12.5 1000 201 R10
50
Kabelmetal Nigeria Plc
Applications:
Installation indoors and in cable ducts in industrial plants, in power utilities and substations.
Installation underground with additional protection, where mechanical damage
may be expected.
Max core temperature 90 °C
Max. short circuit temperature 250 °C
Design
1 Conductor
Class 2 stranded plain copper
2 Conductor screen
3 Insulation
XLPE - Cross linked Polyethylene
4 Insulation Screen
5 Metallic screen
7 Outer Sheath
Polyvinyl Chloride (PVC)
colour: red or black
(other colour on request)
51
Kabelmetal Nigeria Plc
52
Kabelmetal Nigeria Plc
Applications:
Installation in ground, outdoors, indoors and in cable ducts in industrial plants,
power utilities and substations.
Design
1 Conductor 1
Class 2 stranded plain copper
2
2 Conductor Screen
Semi-Conductor screen 3
3 Insulation
4
XLPE - Cross linked Polyethylene
5
4 Insulation Screen
6
5 Metallic screen
Copper Tape 7
6 Inner Sheath
PVC (Polyvinyl Chloride)
7 Armour
Aluminium Wire/Tape Aluminium Armour = Single core 8
Galvanized Steel Wire/Tape Armour = Multi-core
8 Outersheath
PVC (Polyvinyl Chloride)
53
Kabelmetal Nigeria Plc
Maximum Maximum
Nominal class of DC Outer Diameter of Permissible
Cross conductor Resistance of the Cable Current rating
Sectional Conductor Approx.
In Ground In Air
Area @20 °C Min. Max. Weight
@20 °C @30 °C
mm² Ω/km mm mm A A kg/km
1 - Core
1 x 25 2 0.727 33.8 36.7 140 163 610
1 x 35 2 0.524 34.2 37.8 166 198 935
1 x 50 2 0.387 35.3 38.9 196 238 1090
1 x 70 2 0.268 36.9 40.7 239 296 1350
1 x 95 2 0.193 38.4 42.4 285 361 1640
1 x 120 2 0.153 30.1 39.9 323 417 2010
1 x 150 2 0.124 41.1 45.4 361 473 2300
1 x 185 2 0.0991 42.8 47.2 406 543 2720
1 x 240 2 0.0754 45 49.6 469 641 3330
1 x 300 2 0.0601 47.3 52.2 526 735 4010
1 x 400 2 0.047 50.3 55.5 590 845 6267
1 x 500 2 0.0366 55.7 61.4 688 1000 7791
1 x 630 2 0.0283 60.4 66.7 774 1150 9464
3 - Cores
3 x 25 2 0.727 48.6 54.1 129 143 2760
3 x 35 2 0.524 51.1 56.8 154 172 3880
3 x 50 2 0.387 53.9 60.0 181 205 4510
3 x 70 2 0.268 57.7 64.2 220 253 5400
3 x 95 2 0.193 62.1 69.1 263 307 6450
3 x 120 2 0.153 65.7 73.0 298 352 7500
3 x 150 2 0.124 68.9 76.6 332 397 8500
3 x 185 2 0.0991 73.5 81.8 374 453 9900
3 x 240 2 0.0754 81.8 91.0 431 529 12900
3 x 300 2 0.0601 87.0 96.8 482 599 15250
Current Carrying Capacities are based on IEC 60502-2, Single-core cables arranged in trefoil formation.
Conditions for underground installation: average thermal resistivity of soil 1.5 k.m/W. Burying depth = 0.80m.
54
Kabelmetal Nigeria Plc
Applications:
For above ground installation, used mainly by the Oil & Gas Industry.
Used in process control for analog and digital signal transmission.
Design
1. Conductor
Class 1 - solid annealed copper
Class 2 - round stranded annealed copper
2. Insulation
- PE
- XLPE
- PVC
3. Screen
- PT Foil
- Drain wire
- Metalised Plastic Screen
4. Outer Sheath
PVC or LSZH
55
Kabelmetal Nigeria Plc
INSTRUMENTATION CABLES
E-2Y(st)Y or E-2Y(st)H
E-2X(st)Y or E-2X(st)H
E-Y(st)Y
Electrical
Nominal Max. Mutual Max. Mutual Delivery
Loop Nominal Standard
No of Cross Class of Capacitance Capacitance Approx. Form on
Resistance Overall Delivery
Pairs Sectional Conductor [PE & XLPE [PVC Weight Wooden
@20 °C Diameter Length
Area Insulation] insulation] Drum
Max.
mm² Ω/km nF/km nF/km mm m kg/km
0.5 class 1 73.4 115 250 6.9 1000 56 R7
1.0 class 1 36.9 115 250 7.6 1000 79 R7
1 1.5 class 2 24.6 120 250 8.5 1000 100 R7
2.5 class 2 15.1 140 250 9.3 1000 135 R7
0.5 class 1 73.4 115 250 6.9 1000 95 R7
1.0 class 1 36.9 115 250 11.1 1000 130 R7
2 1.5 class 2 24.6 120 250 12.1 1000 160 R7
2.5 class 2 15.1 140 250 13.5 1000 215 R7
56
Kabelmetal Nigeria Plc
Applications:
For above ground installation, used mainly by the Oil & Gas Industry.
Used in process control for analog and digital signal transmission.
Design
1 Conductor
Class 1 - solid annealed copper
Class 2 - round stranded annealed copper
2 Insulation
- PE
- XLPE
- PVC
3 Screen
- PT Foil
- Drain wire
- Metalised Plastic Screen
4 Inner Sheath
- PT Foil
- Drain wire
- Metalised Plastic Screen
5 Outer Sheath
'PVC or LSZH
Flame retardant
57
Kabelmetal Nigeria Plc
INSTRUMENT CABLES
Individual and Collective Screen
E-2Y(st)(st)Y or E-2Y(st)(st)H
E-2X(st)(st)Y or E- 2X(st)(st)H
E-Y(st)(st)Y
Also available:
- Cables with Triads and Quads
58
Kabelmetal Nigeria Plc
Applications:
For above ground installation, used mainly by the Petroleum Industries.
Used in process control for analog and digital signal transmission.
Design
1 Conductor
Class 1 - solid annealed copper
Class 2 - round stranded annealed copper
2 Insulation 2
- PE
- XLPE
- PVC
3 Screen
- PT Foil
- Drain wire
- Metalised Plastic Screen
4 Inner Sheath
PVC or LSZH
5 Armour Galvanized
Steel Wire
6 Outer Sheath
PVC or LSZH
Flame retardant
59
Kabelmetal Nigeria Plc
INSTRUMENTATION CABLES
Collective Screen
1. E-2Y(st)YRY or E-2Y(st)HRH
2. E-2X(st)YRY or E-2X(st)HRH
3. E-Y(st)YRY
Electrical
Nominal Max. Mutual Max. Mutual Delivery
Loop Nominal Standard
Number Cross Class of Capacitance Capacitance Approx. Form on
Resistance Overall Delivery
of Pairs Sectional Conductor [PE & XLPE [PVC Weight Wooden
Diameter Length
Area at 20°C Insulation] Insulation] Drum
Max.
mm² Ω/km nF/km nF/km mm m Kg/Km
0.5 1 73.4 115 250 6.9 1000 240 R7
1.0 1 36.9 115 250 7.6 1000 275 R7
1
1.5 2 24.6 120 250 8.5 1000 320 R7
2.5 2 15.1 140 250 9.3 1000 350 R7
0.5 1 73.4 115 250 6.9 1000 330 R7
1.0 1 36.9 115 250 11.1 1000 425 R7
2
1.5 2 24.6 120 250 12.1 1000 550 R7
2.5 2 15.1 140 250 13.5 1000 650 R7
Also available:
- Cables with Triads and Quads
60
Kabelmetal Nigeria Plc
Applications:
For above ground installation, used mainly by the Petroleum Industries.
Used in process control for analog and digital signal transmission.
Design
1 Conductor
Class 1 - solid annealed copper
Class 2 - round stranded annealed copper
2 Insulation
- PE
- XLPE
- PVC
3 Screen
- PT Foil
- Drain wire
- Metalised Plastic Screen
4 Collective Screen
- PT Foil
- Drain wire
- Metalised Plastic Screen
5 Inner Sheath
Galvanized Steel Wire
6 Armour Galvanized
Steel Wire
7 Outer Sheath
PVC or LSZH
Flame retardant
61
Kabelmetal Nigeria Plc
INSTRUMENTATION CABLES
Individual & Collective Screen
1. E-2Y(st)(st)YRY or E-2Y(st)(st)HRH
2. E-2X(st)(st)YRY or E-2X(st)(st)HRH
3. E-Y(st)(st)YRY
Electrical
Nominal Max. Mutual Max. Mutual Delivery
Loop Nominal Standard
Number Cross Class of Capacitance Capacitance Approx. Form on
Resistance Overall Delivery
of Pairs Sectional Conductor [PE & XLPE [PVC Weight Wooden
Diameter Length
Area at 20°C Insulation] Insulation] Drum
Max.
mm² Ω/km nF/km nF/km mm m Kg/Km
0.5 1 73.4 115 250 6.9 1000 240 R7
1.0 1 36.9 115 250 7.6 1000 275 R7
2
1.5 2 24.6 120 250 8.5 1000 320 R7
2.5 2 15.1 140 250 9.3 1000 350 R7
0.5 1 73.4 115 250 6.9 1000 330 R7
1.0 1 36.9 115 250 11.1 1000 425 R7
5
1.5 2 24.6 120 250 12.1 1000 550 R7
2.5 2 15.1 140 250 13.5 1000 650 R7
Also available:
- Cables with Triads and Quads
62
Kabelmetal Nigeria Plc
Technical guide
For Low Voltage cable Selection criteria are as follows: Class 5 for flexible conductors, used for
installation subject to low mechanical stresses,
e.g. light fixture, home appliances.
1. Operating Voltage Class 6 for extra-flexible conductors used for
2. Nature of Conductors installation subject to heavy mechanical stresses e.g.
3. Current Ratings workshop, agriculture tools and heavy-duty mobile
4. Conditions of Installation equipment.
5. Correction Factors
6. Core Identification IEC 60228 further defines the maximum allowed
linear ohmic resistance for each cross sectional
area (CSA) of conductor depending on the conductor
material. Most common conductor materials are
1. Operating Voltage Copper and Aluminium.
Basically, for equal current rating: Aluminium CSA
The rated voltage of a cable is the voltage that cable = 1.28 copper CSA.
is designed to operate and according to which the for equal ohmic resistance: Aluminium CSA
insulation thickness of the cable core is determined. = 1.65 copper CSA.
It is also the voltage relative to which the cable is tested.
3. Current Ratings
The standard rated voltage of cables is designated
Uo /U (Um). The current carrying capacity of a cable is determined
Uo is the effective value of the voltage between the by the maximum admissible conductor temperature
cable core and the reference potential. and the ambient condition of installation, which
In three phase system, Uo is the voltage between phase influence the dissipation of heat occurring in the
and neutral and U is the voltage between phases. conductor.
The maximum permissible continuous operating voltage
The cross-section of the cable for a specified load
for which the cable may be used is Um.
current that the cable is required to carry must be
The standard value of these voltages defined in IEC standard chosen to satisfy the criteria that the working
are as follows temperature of the conductor will not exceed the
Rated voltage Maximum Permissible Operating maximum permissible working temperature for the
Uo/U Continuous Voltage Um material of insulation.
63
Kabelmetal Nigeria Plc
U…Voltage [V]
Either a) Voltage between 2 power supply conductors 5.1 Ambient Temperature
for a DC circuit or for a single
Phase AC circuit or
Table for correction factors for different
b) Voltage between 2 phase conductors for a
temperatures in air / ground
3 phase AC system.
cos φ...Power factor. (0.8 to be applied if not stated)
Low Voltage cables
In this brochure, the permissible current carrying capacities Insulation
of different cross sections and types of cables are given in
tables describing the different cable types. The permissible
current ratings stated in the tables are in accordance with Ambient Correction
IEC 60364-5-52 Temperature Correction factors
factors PVC XLPE or
4. Conditions of installation EPR
Underground cables
4.1 Cables buried in ground
10°C 1.1 1.07
Current rating stated for cables buried in ground are based on 15°C 1.05 1.4
standard service conditions as follows: 20°C 1 1
25°C 0.95 0.96
Thermal resistivity of soil 1 K m/W 30°C 0.89 0.93
Ground temperature 20 C
35°C 0.84 0.89
Depth of laying 70 cm
Cables in free air
No. of cables /system 1
Load factor 0.7 10°C 1.22 1.15
Spacing between cables Twice overall diameter of cable 15°C 1.17 1.12
20°C 1.12 1.08
Conditions of installation different from those described
above can considerably influence the current carrying 25°C 1.06 1.04
capacity and appropriate correction factors (see point 5.) 30°C 1 1
must be considered.
35°C 0.94 0.96
4.2 Cables installed in air 40°C 0.87 0.91
45°C 0.79 0.87
Current rating stated for cables are for installation in air 50°C 0.71 0.82
on perforated cable trays shielded from direct rays of
the sun without restricting air circulation significantly. 55°C 0.61 0.76
The installation conditions illustrated here represent 60°C 0.5 0.71
service condition most often encountered in plants. 65°C - 0.65
70°C - 0.58
o
Ambient temperature 30 C
20°C is the temperature used for underground
No. of cables /system 1 installations of cables while 30°C for installations
Load factor 1 in air.
Spacing between cables Twice overall diameter of cable For other temperatures reference current rating
shall be multiplied by the correction factor K
64
Kabelmetal Nigeria Plc
[in seconds]
H Insulation Initial Final 0.5 1 2
cable tray...
COPPER CONDUCTORS
L
cable tray...
PVC 70 160 163 115 81
XLPE/EPR
90 250 203 143 101
5.4. Installation in ground
No. of cables Correction Duration of overload
or systems factor Temperature [ C]
O
[in seconds]
Insulation Initial Final 0.5 1 2
1 0.95
ALUMINIUM CONDUCTORS
2 0.90
PVC 70 160 107 76 54
3 0.88
6 0.85 XLPE/EPR 90 250 133 94 66
9 0.84
65
Kabelmetal Nigeria Plc
66
Kabelmetal Nigeria Plc
Core Identification
2 Cores
Brown - Blue
3 Cores
OR
Blue - Brown -
Green/Yellow Brown - Black - Grey
OR
4 Cores Grey - Blue - Brown -
Black
Brown - Black - Grey
Green/Yellow
5 Cores
Blue - Brown - Black -
Grey - Green/Yellow
This Harmonization Document (HD 308 S2) was This HD 308 S2 has been integrated into national
approved by CENELEC ON 2001-05-01. CENELEC standards and applies to the low voltage cables of
members are bound to comply with CEN/CENELEC this catalogue.
(European Committee for Electrotechnical
Standardization) Internal Regulations which stipulate
the conditions for implementation of this
Harmonization Document on a national level.
68
Flame Retardant, Low Smoke Halogen Free
and Fire Resistant Cables
Practice has shown that a single PVC insulated and sheathed cable, even when laid in horizontal
position, does not propagate fire, i.e. it is flame retardant. But this is not guaranteed when several
cables are laid parallel or even bunched together and fire strikes. For that reason, test procedures
have been developed to determine and categorize fire behavior depending on the way cables are
bunched together, how much combustible material is contained and easily contributing to the fire as
well as the method of laying cables and the intensity of fire.
Beside flame propagation, developing fumes and smoke have been examined and test procedures
were developed – and are still developed and fine tuned – to minimize danger for life and property
from cables engulfed in fire.
For offices, hospitals, airports etc. where large number of people are concentrated, fire performance
of electric cables must match other security- and health safety measures.
In line with this, the following important parameters for cables have been established:
Flame propagation of bunched and/or parallel laid up cables are exposed to burners for a period of
time. After the burners are removed, affected portion of cables burnt shall not exceed a specified
length.
Insulation materials contain Halogens; for example: PVC contains Chloride. Other Polymers contain
Bromine and Fluor, which increase ignition temperature and under influence of water or humid
surroundings in fire situations, these corrosive gases change into acid (HCL) which are dangerous to
life.
Therefore HALOGEN FREE materials and materials with LOW CONTENT of HALOGENES
were developed.
Smoke not only hinders extinction of fire because it limits vision at the burning site but also
complicates evacuation of people from affected structures. Materials of LOW SMOKE DENSITY are
used for cables.
(D) Continued functionality of electric conductivity of the cable in case of fire. This parameter actually
characterizes FIRE RESISTANT cables. Fire resistant cable guaranty continuous functionality over a
period of time under burning condition.
69
Wooden Drums
mm mm mm m m3 m3 kg
R7 700 367 410 520 0.050 0.11 75
R8 800 417 420 520 0.063 0.15 76
R 10 1000 512 555 655 0.100 0.32 129
R 12 1200 600 725 820 0.159 0.61 164
R 14 1400 726 850 950 0.219 0.96 173
R 16 1600 792 960 1100 0.329 1.46 286
R 18 1800 1020 1000 1150 0.489 1.73 503
R 20 2000 1280 1000 1160 0.606 1.85 637
R 22 2200 1370 1138 1300 0.734 2.65 716
R 25 2500 1400 1144 1345 1.232 3.85 769
R 27 2700 1600 1330 1530 1.478 5.35
L1
70
Storage Handling And Transportation Of Drum
The correct handing, storage and transportation of cable - drums will help to save a lot of money
Therefore, each drum should be treated with the utmost care in order to avoid cable - damages.
NO YES
71
Instructions for laying cables
Bending radius:
During the unreeling, the bending radius shall be at least, ‘’twice the static bending radius
(as specified in our technical data sheets)’’.
Pulling strength:
The pulling strengths applied directly to the copper or aluminum cores of the cables should
not exceed:
2
·5 daN/mm of cross section for copper conductors
2
·3 daN/mm of cross section for aluminium conductors
The pulling must be regular without shocking and continuously checked by a dynamometer
(especially when using a winch).
Cables unreeling:
The drum shall be settled on jacks by using a spindle through the central hole of the drum.
The unreeling speed shall be monitored at any moment
72
Legend
a = Aluminium Tape
mm2 = Square Millimeter
cc = control cable
kg = Kilogram
DC = Direct Current
km = Kilometer
…f = Flexible Conductor
nF = Nano Farad
PA = Polyamide
(Medium Voltage)
2Y = Polyethylene (PE)
73
Symbols
Rodent resistant
Flexibility
Halogen free
Termite Resistant
Smoke-Corrosivity-Toxicity
Smoke density, gases corrosivity and toxicity
74