You are on page 1of 7

Table -1

POWER POWER Fire fighting


BATTERY No of Continuous Closing Tripping Emergency
EQUIPMENT CONSUMPTION LOCATION & NO. NO. CONSUMPTION Co efficient equipment Motor REMARKS
VOLTAGE Panels Load Peak peak Lighting
(Watt) (Watt) peak

Emergency Light 20 Control room building 10 200 1 0 0 0 0 0 200

Annunciator 10 1 20 1 20 0 0 0 0 0
Indicator 2 8 32 1 32 0 0 0 0 0
Meter 5 5 50 1 50 0 0 0 0 0
Alarm 3 33KV Line feeder CRP 1 2 6 1 6 0 0 0 0 0
P143 11 1 22 1 22 0 0 0 0 0
TCS 15 2 60 1 60 0 0 0 0 0
MVAJ 150 1 300 1 0 0 0 300 0 0

Annunciator 10 1 20 1 20 0 0 0 0 0
Indicator 2 7 28 1 28 0 0 0 0 0
Auxiliary
5 6 60 1 60 0 0 0 0 0
relay
Meter 5 33KV Transformer feeder 5 50 1 50 0 0 0 0 0
2
P-141 11 CRP 1 22 1 22 0 0 0 0 0
Alarm 3 1 6 1 6 0 0 0 0 0
P642 16 1 32 1 22 0 0 0 0 0
TCS 15 2 60 1 60 0 0 0 0 0
MVAJ 150 2 600 1 0 0 0 600 0 0

Indicator 2 2 4 1 4 0 0 0 0 0
33KV Control(Common) 1
Meter 5 8 40 1 40 0 0 0 0 0

110
MVAJ 150 2 600 1 0 0 0 600 0 0
11KV Incomer(SWG) 2
miscellaneous 100 1 200 1 200 0 0 0 0 0

MVAJ 150 2 300 1 0 0 0 300 0 0


11KV Bus Coupler(SWG) 1
miscellaneous 100 1 100 1 100 0 0 0 0 0

MVAJ 150 2 900 1 0 0 0 900 0 0


11KV Outgoing 3
miscellaneous 100 1 300 1 300 0 0 0 0 0

Meter 5 1 10 1 10 0 0 0 0 0
Indicator 2 8 32 1 32 0 0 0 0 0
Alarm 3 RTCC 1 2 6 1 6 0 0 0 0 0
AVR 5 1 10 1 10 0 0 0 0 0
Annunciator 10 1 20 1 20 0 0 0 0 0

33kV line
ISOLATOR(4)+33kV
Disconnector 5 control(common) 10 50 0.5 25 0 0 0 0 0
isolator(2)+33KV TRX
feeder(4)

VCB(33KV) 8 4 32 0.5 16 0 0 0 0 0

Total power For Eleven feeders 1221 0 0 2700 0 200


Table-2
POWER
POWER Continuous Tripping Emergency
EQUIPMENT LOCATION & NO. NO. CONSUMPTION( Co efficient Closing Peak Motor REMARKS
CONSUMPTION Load peak Lighting
Watt)
Tripping
330 8 2640 1 0 2640
coil
33KV VCB(4 Nos)
closing
330 4 1320 1 0 1320
coil
Tripping
330 6 1980 1 0 1980
coil
11kV CB(outgoing) 3nos(GCB)
closing
330 3 990 1 0 990
coil
Tripping
330 4 1320 1 0 1320
coil
11kV CB(incoming) 2nos(GCB)
closing
330 2 660 1 0 660
coil
Power per Feeder 0 2970 5940 0 0
Simultaneity of feeders 1 0.09090909 1 0.09090909 1
Power for all 11 feeders 0 270 5940 0 0

Summation of table 1 & 2


Closing Tripping Emergency
Continuous Load
Peak peak Lighting
Table 1 1221 0 2700 200
Table 2 0 270 5940 0
Total Power 1221 270 8640 200
Total Current 11.10 2.45 78.55 1.82
LOAD CYCLE TABLE & GRAPH
Period (min) Duration LOAD DESCRIPTION LOAD(A)
0--1 1 min Momentary tripping load+continuous load+emergency load (78.55+11.1+1.82)= 91.47 A
1--2 1 min Momentary closing load+continuous load+emergency load (2.45+11.1+1.82) = 15.37 A
2--60 58 min continuous load+emergency load (11.1+1.82) = 12.92 A
60--298 238 min continuous load (11.1) = 11.1 A
298--299 1 min Momentary tripping load+continuous load (78.55+11.1) = 89.65 A
299--300 1 min Momentary closing load+continuous load (2.45+11.1) = 13.55 A

LOAD
180
175
170
165
160
155
150
145
140
135
130
125
120
115
110
105
100
95
90
85 LOAD
80
75
70
65
60
55
50
45
40
35
30
25
20
15
10
5
0
0
9
18
27
36
45
54
63
72
81
90
99
108
117
126
135
144
153
162
171
180
189
198
207
216
225
234
243
252
261
270
279
288
297
1.1
Nominal Temperature 30ᵒC Cell Cell Mfg: Cell Type:
Lowest 20ᵒC Voltage HBL Nickel Cadmium
Highest 45ᵒC 1.2V

(1) (2) (3) (4) (5) (6) (8)


Period Load(Amperes) Change in Load Duration of Period Time to End of Capacity Rating Required Section
(Amperes) (Minutes) section(Minutes) Factor (kt) Size(3)×(6)
=Rated Amp Hrs
Section 1-First 1 Period(s) Only-if A2 is greater than A1. Go to section 2
1 A1 A1-A0 M1 t=M1
91.47 91.47 1.00 1.00 0.505 46.19
Total 46.19

(1) (2) (3) (4) (5) (6) (8)


Period Load(Amperes) Change in Load Duration of Period Time to End of Capacity Rating Required Section
(Amperes) (Minutes) section(Minutes) Factor (kt) Size(3)×(6)
=Rated Amp Hrs

Section 2-First 2 Period(s) Only-if A3 is greater than A2. Go to section 3


1 A1 A1-A0 M1 t=M1+M2
91.47 91.47 1.00 2.00 0.55 50.31
2 A2 A2-A1 M2 t=M2
15.37 -76.10 1.00 1.00 0.505 -38.43
Total 11.88

(1) (2) (3) (4) (5) (6) (8)


Period Load(Amperes) Change in Load Duration of Period Time to End of Capacity Rating Required Section
(Amperes) (Minutes) section(Minutes) Factor (kt) Size(3)×(6)
=Rated Amp Hrs

Section 3-First 3 Period(s) Only-if A4 is greater than A3. Go to section 4


1 A1 A1-A0 M1 t=M1+M2+M3
91.47 91.47 1.00 60.00 1.325 121.20
2 A2 A2-A1 M2 t=M2+M3
15.37 -76.10 1.00 59.00 1.31 -99.69
3 A3 A3-A2 M3 t=M3
12.92 -2.45 58.00 58.00 1.3 -3.19
Total 18.32
(1) (2) (3) (4) (5) (6) (8)
Period Load(Amperes) Change in Duration of Time to End of Capacity Rating Factor Required Section
Load Period section(Minutes) (kt) Size(3)×(6)
(Amperes) (Minutes) =Rated Amp Hrs

Section 4-First 4 Period(s) Only-if A5 is greater than A4. Go to section 5


1 A1 A1-A0 M1 t=M1+M2+M3+M4
91.47 91.47 1.00 298.00 4.98 455.52
2 A2 A2-A1 M2 t=M2+M3+M4
15.37 -76.10 1.00 297.00 4.97 -378.22
3 A3 A3-A2 M3 t=M3+M4
12.92 -2.45 58.00 296.00 4.96 -12.15
4 A4 A4-A3 M4 t=M4
11.10 -1.82 238.00 238.00 3.98 -7.2436
Total 57.91

(1) (2) (3) (4) (5) (6) (8)


Period Load(Amperes) Change in Duration of Time to End of Capacity Rating Factor Required Section
Load Period section(Minutes) (kt) Size(3)×(6)
(Amperes) (Minutes) =Rated Amp Hrs
Section 5-First 5 Period(s) Only-if A6 is greater than A5. Go to section 6
1 A1 A1-A0 M1 t=M1+M2+M3+M4+M5
91.47 91.47 1.00 299.00 4.99 456.44
2 A2 A2-A1 M2 t=M2+M3+M4+M5
15.37 -76.10 1.00 298.00 4.98 -378.98
3 A3 A3-A2 M3 t=M3+M4+M5
12.92 -2.45 58.00 297.00 4.97 -12.18
4 A4 A4-A3 M4 t=M4+M5
11.10 -1.82 238.00 239.00 3.99 -7.2618
5 A5 A5-A4 M5 t=M5
89.65 78.55 1.00 1.00 0.505 39.66775
Total 97.69

(1) (2) (3) (4) (5) (6) (8)


Period Load(Amperes) Change in Duration of Time to End of Capacity Rating Factor Required Section
Load Period section(Minutes) (kt) Size(3)×(6)
(Amperes) (Minutes) =Rated Amp Hrs
Section 6-First 6 Period(s) Only-if A7 is greater than A6. Go to section 7
1 A1 A1-A0 M1 t=M1+M2+M3+M4+M5+M6
91.47 91.47 1.00 300.00 5 457.35
2 A2 A2-A1 M2 t=M2+M3+M4+M5+M6
15.37 -76.10 1.00 299.00 4.99 -379.74
3 A3 A3-A2 M3 t=M3+M4+M5+M6
12.92 -2.45 58.00 298.00 4.98 -12.20
4 A4 A4-A3 M4 t=M4+M5+M6
11.10 -1.82 238.00 240.00 4 -7.28
5 A5 A5-A4 M5 t=M5+M6
89.65 78.55 1.00 2.00 0.55 43.2025
6 A6 A6-A5 M6 t=M6
13.55 -76.10 1.00 1.00 0.505 -38.43
Total 62.90
Maximum Section Size(8) 97.69 + Random Section Size(9) 0 = Uncorrected Size(US)(10) 97.69
US(11) 97.69 × Design Margin(12) 1.1 × Aging Factor(13) 1.15 = 123.5737 Ah