Professional Documents
Culture Documents
Vol3-9 Protection PDF
Vol3-9 Protection PDF
AND TECHNIQUES
Volume 3-9
DENVER OFFICE
DENVER, COLORADO
BUREAU OF RECLAMATION
DECEMBER 1991
CONTENTS
Section Page
1. Fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
2.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.2 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3. Overcurrent relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
4. One-line diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
5. Short-circuit study . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
7. Characteristic curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
8. Selective coordination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Bibliography . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Figures
i
PART I - PROTECTIVE DEVICES
Today, protective devices, including fuses, circuit acting element protects against short-circuit cur
breakers, and relays of various types, are quite rents similar to all ordinary standard fuse. A time-
sophisticated compared to the ones used 20 years delay element permits short duration overloads
ago. The protective device provides a form of but melts if an overload is sustained. The most
insurance for high-cost electrical equipment. important application of this type of fuses is for
Protection of electrical power systems can reduce motor or transformer protection because it does
the extent and duration of an interruption, as well not open on motor starting or transformer
as reduce equipment damage or personal injury. magnetizing inrush currents but prevents damage
if a protective device operates, it does so because from sustained overloads
it reacts to a problem in the system. It is vital then,
to investigate the cause and location of the prob Where new protective equipment is being pre
lem; to merely replace the fuse element or reset scribed such as distribution cutouts, fuse links,
the protective device does not eliminate the prob secondary fuses, power fuses, distribution
lem. If the cause of the problem cannot be found, enclosed single-pole air switches, fuse
contact D-8440 or D-8450 as to possible reasons disconnecting switches, and accessories for use
the protective device operated. under unusual conditions, D-8440 should be
requested to provide assistance during design and
1. FUSES installation of the equipment.
A fuse appears to be a simple device, but study of
the numerous types and circuit applications re Unusual or extreme operating conditions for a
veals that it is a complex equipment protection fuse could be: explosive dust or gas, excessive or
device. Various circuit applications require that abrasive dust, corrosive or conductive vapors,
fuses satisfy many requirements including steam, salt water, excessive moisture or dripping
different interrupting ratings, peak let-through cur water, excessive vibration or shock, or unusually
rent, (I2t) characteristics, and melting time-current low temperatures. Unusual conditions are some
characteristics. A fuse is a thermal tripping device times created by poor storage, transportation, or
in an electric circuit the operation of which de limited space conditions, frequencies other than
pends on thermal capacity of the fuse element, its 60 Hz, poor maintenance, and infrequency of
melting temperature (to some extent), and the operation.
current flow previous to the fault condition.
Unusual operating conditions due to ambient
The fusible element may be composed of any of temperature above 40 EC (100 EF):
the following metals: bismuth, cadmium, lead, tin,
silver, copper, aluminum, or any alloy of these Equipment designed for standard temperature
elements, to achieve thermal characteristics nec rise may be used at the normal rated
essary for best system protection. Measurement of continuous current without exceeding ultimate
capacity of a particular fuse to perform a certain standard temperature limits, provided the
job depends largely upon the accuracy with which ambient temperature does not exceed 40 EC
it was manufactured, the correctness of (100 EF) times the ambient temperature factor
application, and the quality of maintenance after (table 1) which corresponds to the altitude
installation. A fuse improperly applied or where the equipment will operate.
maintained might fail to disconnect the circuit
when required, which might result in considerable Unusual operating conditions due to altitudes
damage to costly equipment. higher than 1000 m (3300 ft) above sea level:
A dual element or time-delay fuse has current Equipment that depends on air for insulating
response elements of two different fusing charac and cooling will have a larger temperature rise.
teristics in series in a single cartridge. A fast-
NOTE: Use one correction factor from column 2 or 3, but not both, for any one application. If the derating
as determined from the table is significant, equipment of suitable higher rating should be chosen to meet
requirements after the correction factor has been applied.
current limitation
• Time delay optional, minimum 10 • Voltage rating of 250 and 600 V al
second delay at 500 percent current ternating current only.
rating.
• Interchangeable with UL classes K1, K5,
1.1.2.3. Class J current-limiting fuses, and K9, NEMA class H, and UL classes
nonrenewable.- RK1 and RK5 fuses in equipment
provided with class H fuseholders.
Short-circuit interrupting rating of
200,000 A, rms, symmetrical. • May or may not be dual element, if
labeled as "time delay" it must have a
Current rating up to 600 A. minimum 10-second delay at 500
percent current rating.
• Voltage rating of 600 V alternating
current only. 1.2. POWER FUSES.-The selection of a power
fuse, which is a fuse rated over 600 V, should be
• Not interchangeable with any other based on the following considerations. A power
fuse class. Fuses having a time delay fuse consists of an assembly of a fuse support
characteristic are available in class J and a fuseholder which may or may not include
dimensional sizes although they do the refill unit or fuse link. Power fuses provide
not meet the UL standards for current- consistent and fast protection for equipment short
limiting performance. circuits where it is not economically advisable to
use a circuit breaker. Power fuses are usually
1.1.2.4. Class L current-limiting fuses, used for primary or secondary protection of power
nonrenewable.- transformers but are also used for feeder circuits
and capacitor banks. Because power fuses are not
• Short-circuit interrupting rating of designed for automatic restoration of service but
200,000 A, rms, symmetrical. require manual replacement of the fused ele-
ment, it is not advisable to use them where • Fuses rated above 100 A shall melt
overloads may occur frequently. in 600 seconds at an rms current within
the range of 220 to 264 percent of the
1.2.1. Current-limiting fuses.-To obtain a continuous rating of the fuse element.
high-interrupting capacity starter on systems
above 600 V, these fuses were primarily Some power fuse elements comply with the
developed for use with motor-starting NEMA standard "N" rating which has the following
contactors to limit the short-circuit current to characteristic requirements:
a value within the "withstand capabilities" of
the contactors. Other typical applications of • The current rating of the fuse must be
current-limiting fuses are protection of carried continuously.
potential transformers and protection of
small loads on high-capacity circuits. Due to • The element will melt in 300 to 600
the time-current characteristics of power seconds at an rms current within 115
fuses being near vertical, it makes them to 125 percent of the continuous
difficult to coordinate with overcurrent relays rating.
on their load side.
To provide the best possible coordination, power
1.2.2. Expulsion-type fuses.-Generally fuse elements are available in three speed ratios:
used in distribution system cutouts or dis fast, medium, and low. The speed ratio of a fuse
connecting switches, this type of fuse must element is defined as the ratio of the minimum
use an arc-confining tube with deionizing melting current at 0.1 second to the minimum
fiber liner to interrupt a fault current. The arc melting current at 300 seconds for fuses rated 100
is interrupted by the rapid production of the A or less and 600 seconds for fuses rated above
pressurized gas within the fuse tube which 100 A. These values can be obtained from the
extinguishes the arc by expulsion from the manufacturer (time-current characteristic curves
open end, or ends, of the fuse. This process on the particular ampere rating and type of fuse
is comparatively noisy and, if applied with an element).
enclosure, care must be taken to vent any
ionized gases which would cause a flash 1.2.4. Power fuse ratings.-Power fuses should
over between internal live parts. be selected on the basis of the following ratings:
1.2.3. Power fuse element characteris- 1.2.4.1. Current rating.-The current rating of a
tics.-For any given element melting time, fuse element must be large enough to handle
the maximum steady-state symmetrical the following normal short-time overloads,
current shall not exceed the minimum by energizing, and switching surges under normal
more than 20 percent. operating conditions without operating.
Most power fuse elements comply with • Short-time daily overloads within the
NEMA standard "E" rating which has the limits recommended by ANSI C57.92,
following characteristic requirements: 1962.
• Switching surges normally experi • Refinish fuse tubes made of organic (class
enced on a utility system. "A") material as required and specified by
the manufacturer.
• Ambient temperature up to 40EC.
• Examine the fuse tube, renewable
1.2.4.2. Voltage rating.-The voltage rating element, and fuse unit for corrosion of
of a fuse should be selected as equal to the fuse element or connecting
or greater than the nominal system conductors, excessive erosion of the
voltage on which it is used. inside of fuse tubes, discharge (tracking)
and dirt on the outside of the fuse tube,
1.2.4.3. Interrupting current rating.-De- and improper assembly that may prevent
termine the maximum asymmetrical proper operation. Replace fuse units or
short-circuit current available on the sys tubes that show signs of deterioration.
tem at the fuse location. Select a fuse
having a current interrupting rating 1.2.6. Power fuse tests.-Refer to ANSI
greater than the available short-circuit C37.41 and figure 1 for procedure in fuse
current. tests and test procedure of fuse-mounting
equipment. Refer to ANSI C37.46 for perfor
1.2.4.4. Frequency rating.-Fifty or sixty mance characteristics of fuse units, refill
hertz. units, and fuse links for power fuses.
cuit current at the location of the circuit breaker • Check the trip coil.-An open turn or ter
on the system. The time delay characteristic is minal could cause failure to trip.
generally a thermal element composed of a
bimetal strip; however, some manufacturers use • Foreign matter may be preventing move
a magnetic sensing device with a dashpot for ment of the following breaker parts: trip
the time delay characteristic. bar, armature, latch release, trigger, bi
metal, bellows or dashpot, or spring as
2.2. MAINTENANCE.-Keep the circuit breakers semblies.
clean and dry. If a breaker is located in a dirty
or dusty atmosphere, frequently remove and The testing procedure of molded-case circuit
blow it out with clean, dry, low-pressure air. breakers (IEEE Standard 242-1975, paragraph
15.3.1.) or NEMA publication "Procedures for
Caution: DO NOT blow the dirt into the re Verifying Performance of Molded-Case Circuit
cesses of the unit. Breakers" may be used as an alternate guide for
testing molded-case circuit breakers.
Check for heating due to poor electrical con
nections, improper trip unit alignment, or im 3. OVERCURRENT RELAYS
proper mechanical connections within the circuit
breaker housing. Abnormal heating is evident Electromagnetic attraction, induction, and solid-state
by discoloration of terminals, deterioration of overcurrent relays are usually used for short-circuit
molded material, or nuisance tripping. If any of protection of low-voltage systems. When a relay
these abnormal heating symptoms exist, locate operates, it initiates a circuit breaker tripping
the cause by making the following checks: operation to isolate the fault from the rest of the
system. Overcurrent relays with voltage control can
• Check the load current.-The current distinguish between overload and fault conditions
in each of the individual poles because a short circuit on an electrical system is
should be less than the circuit always followed by a corresponding voltage dip;
breaker rating; if not, all bolted whereas, an overload causes only a moderate dip.
connections and contacts should be
examined and tightened to the There are two types of overcurrent relays:
manufacturer's specifications.
• Instantaneous overcurrent relays operate
• Check the movement of the trip without intentional time delay.
bar.-Excessive friction or binding of
the trip bar will not allow the bimetal • Time delay relays to allow transient currents
to exert sufficient pressure to move caused by sudden overloads of brief
the trip bar. The mechanism should duration. Most overcurrent relays are of this
be adjusted or lubricated. type, with time delay features to allow
current several times in excess of the
• Check the bimetal or dashpot.-A setting for a limited time without closing the
defective bimetal or dashpot could contacts. A relay with an inverse time
alter the operating characteristics. characteristic operates faster as current
increases.
• Normal and emergency switching condi Note: In the process of plotting the time-cur-
tions. rent characteristic curves, it must be remem
bered that all currents must be referred to a
• Nameplate ratings and subtransient common voltage, either primary or
reactance of all major motors and secondary, before attempting to determine
generators as well as transient coordination. On a delta-wye system, the
reactances of synchronous motors and current that the primary fuse sees due to a
generators, plus synchronous secondary fault depends on the type of fault,
reactances of generators. as well as the severity of the fault. Figure 4
shows several unbalanced faults for delta-
• Conductor sizes, types, and configura wye and wye-delta transformers and the
tions. current relationships of the windings and line
conductors.
• Plot the total symmetrical and asymmet The time intervals shown below must be main
rical short-circuit current available to the tained between the curves of various protection
power system at the fault point (plot both devices to allow for mechanical overtravel, time
three-phase and line ground fault-current delays in circuit opening, manufacturer's
magnitudes). tolerance, and calibration error:
• Also plot the full-load current and heating 8.1 RELAYS require a protection margin (with
curve of every transformer (from tile 0.3 to 0.4 second allowed between device curves
transformer manufacturer). to ensure noncascading) between device curves
of:
• Plot the short-circuit capability (trans
former damage curve) curve. If this • Circuit breaker opening time 0.08
BIBLIOGRAPHY
[1] "Recommended Practice for Protection and Switches, Power Fuses, Fuse Disconnecting
Coordination of Industrial and Commercial Power Switches and Accessories." ANSI C37.41, Boston,
Systems," IEEE (Institute of Electrical and Elec Mass., 1969.
tronics Engineers, Inc.), Std. No. 242-1975, par.
7.5.2, New York, N.Y., 1975. [11] "American National Standard Guide for Ap-
plication, Operation, and Maintenance of
[2] "Recommended Practice for Electric Power Distribution Cutouts and Fuse Links, Secondary
Distribution for Industrial Plants," IEEE, Std. No. Fuses, Distribution Enclosed Single-Pole Air
141-1976, 5th ed., New York, N.Y., 1976. Switches, Power Fuses, Fuse Disconnecting
Switches, and Accessories," ANSI C37.48, Boston,
[3] "Standard Dictionary of Electrical and Electronic Mass., 1969.
Terms," IEEE, Std. No. 100-1978, 2nd ed., Wiley
lnterscience (Division of John Wiley and Sons, Inc.), [12] "American National Standard Specifications
New York, N.Y., 1978. [4] Distribution System for Distribution Fuse Disconnecting Switches,
Protection Manual, McGraw-Edison Power System Fuse Supports, and Current-Limiting Fuses," ANSI
Division, McGraw-Edison Company, Pittsburgh, Pa. C37.47, Boston, Mass., 1981.
[5] National Electrical Code (ANSI (American [13] "American National Standard Specifications
National Standards Institute)) NFPA (National Fire for Power Fuses and Fuse Disconnecting
Protection Association), Switches," ANSI C37.46, Boston, Mass., 1981.
NFPA 70-1978, Boston, Mass.
[14] Olive, W. W., Jr., "Fuses Keep Pace with
[6] Fink, D. G. and J. M. Carrol, Standard Hand System Growth," Electrical World, vol. April 1974,
book for Electrical Engineers, 11th ed., McGraw- pp. 44-46, McGraw-Hill, Inc., New York., 1974.
Hill, Inc., New York, N.Y., 1978.
[15] Reichenstein, H.W., "A Controversial Engi
[7] Freund, A., "Overcurrent Protection Selection neering Concept: Virtual Time and Prospective
and Application," Electrical Construction and Current for Current-Limiting Fuses." Electrical
Maintenance, vol. December 1980, pp. 56-60, Construction and Maintenance, vol. August 1977,
McGraw-Hill, Inc., New York, N.Y., 1980. pp. 71-75, McGraw-Hill, Inc., New York, N.Y., 1977.
[8] "Guide for Loading Oil-Immersed Distribution [16] --- ---E.C.M. vol. September 1977, pp. 89-92,
and Power Transformers," ANSI C57.92, Boston, 1977.
Mass., 1962.
[17] --- ---E.C.M. vol. February 1978, pp. 76-80,
[9] "American National Standard Service Conditions 1978.
and Definitions for Distribution Cutouts and Fuse
Links, Secondary Fuses, Distribution Enclosed [18] --- --- "Understanding 12t Let-Through Energy
Single-Pole Air Switches, Power Fuses, Fuse of Current-Limiting Fuses," E.C.M. vol. January
Disconnecting Switches, and Accessories." ANSI 1977, pp. 74-76, 1977.
C37.40, Boston, Mass., 1969.
[19] --- --- E.C.M. vol. February 1977, pp. 72-76,
[10] "American National Standard Design Tests for 1977.
Distribution Cutouts and Fuse Links, Secondary
Fuses, Distribution Enclosed Single-Pole Air [20] --- ---E.C. M. vol. April 1977, pp. 79-84,
1977.
COMPUTATION SHEET