You are on page 1of 55

12TH EDITION 09 29 00/NGC

Gypsum Board
Systems

09 29 00

57
Gold Bond® BRAND Gypsum Board Products
National Gypsum Company Our concentration isn’t on Frame Wall and Ceilings, Company. Substitution of
features a wide variety of building products alone, Gypsum Board Over Foam any product or other
gypsum board products however. At the National Insulated Masonry and brands in a tested system
and accessories including Gypsum Research and Solid Laminated Partitions. is not recommended.
regular gypsum board, Fire- Testing Center, we develop Before a National Gypsum Field installation of tested sys-
Shield fire resistant board, complete construction sys- System is released to the tems must be identical to
1/4" High Flex Gypsum tems. In such systems, building industry, it is thor- laboratory installation to
Board, 1/2" High Strength products are evaluated oughly tested, and results are produce optimum perfor-
Ceiling Gypsum Board, Hi- together as complete build- correlated and charted to mance of these systems.
Impact Gypsum Board, ing assemblies–walls, parti- make it easier for the builder Performance tests are con-
Gridstone Ceiling Boards, tions, floors and ceilings. or specifier to match a sys- ducted in accordance with
Gypsum Sheathing, Fire- We have included in this sec- tem to their needs or to the accepted national stan-
Shield Shaftliner, Durasan tion details and application building codes. dards under controlled lab-
Prefinished Gypsum Board, instructions for many of oratory conditions to mini-
Exterior Soffit Board, and The drywall construction sys-
those assemblies: Steel tems referred to in this cata- mize variances and to per-
Joint Treatment products. Frame Partitions, Steel mit comparison of test
log are designed primarily
Frame Ceilings/Furring with materials manufac- results with all types of sys-
Channels or Studs, Wood tured by National Gypsum tems, similar and dissimilar.

DESCRIPTION
Description Core Thickness/Type Width/Edge Lengths

Gold Bond BRAND Gypsum Regular 1/4" (6.3 mm) 4' (1219 mm) 6' (1828 mm)
Board with tapered edge 3/8" (9.5 mm) Square thru
1/
permits smooth joint 1/2" (12.7 mm)* or 16' (4876 mm)
BRAND WALLBOARD

GOLD BOND BRAND


® 1/2
treatment; surface takes any Tapered
BO ND WALLBOARD ® 1/2" decoration. Basic
GOLD BRAND WALLBOARD
ND
® 1/2" x recommendations:
GOLD BO BRAND 1/2" board for single layer;
WALLBOARD
® 1/2" x 8
GOLD BOND BRAND 3/8" board for 2-layer; 1/4"
WALLBOARD
® 1/2" x 8
GOLD BOND BRAND board is regular gypsum
ND W
®
ALLBOARD 1/2" x 8'
GOLD BO BRAND LBOARD 1/2" x 8' T board used in remodeling and
®
W AL
GOLD BOND BRAND LB OARD for sound control in double
®
W AL
GOLD BOND layer applications. Refer to
page 65. Note: 1/2" gypsum board available in 54" widths.

Gold Bond BRAND XP Gypsum Regular 1/2" (12.7 mm) 4' (1219 mm) 8' (2438 mm)
Board is designed to provide Square 10' (3048 mm)
extra protection against mold or 12' (3657 mm)
and mildew compared to stan- Tapered
dard gypsum board products.
Tapered edge permits smooth
joint treatment. Refer to page
70.

Gold Bond BRAND Fire-Shield Type X 5/8" (15.9 mm) FSW* 4' (1219 mm) 6' (1828 mm)
Gypsum Board is manufac- Square thru
tured with a type X core to or 16' (4876 mm)
achieve fire resistance ratings Tapered
when used in recommended
systems. Refer to page 66. Type X 1/2" (12.7 mm) FSW-C 4' (1219 mm) 6' (1828 mm)
Gold Bond BRAND Fire-Shield C Square thru
Gypsum Board has a specially or 16' (4876 mm)
formulated type X core to Tapered
achieve superior performance
when used in specific fire Type X 5/8" (15.9 mm) FSW-C 4' (1219 mm) 8' (2438 mm)
rated assemblies. May be used Square thru
in designs requiring Fire-Shield or 14' (4267 mm)
Gypsum Board (type X core). Tapered
Refer to page 66.
Note: 5/8" Fire-Shield gypsum board available
in 54" widths.
* Available with Foil Backing. Refer to page 86.
Reference www.nationalgypsum.com for fire safety information.
58 NATIONAL GYPSUM BOARD PRODUCTS
09 29 00/NGC

Description Core Thickness/Type Width/Edge Lengths

Gold Bond BRAND XP Fire-Shield Type X 5/8" (15.9 mm) FSW-3 4' (1219 mm) 8' (2438 mm)
Gypsum Board is manufac- Square thru
tured with a fire resistive type X or 12' (3657 mm)
gypsum core and is designed to Tapered
provide extra protection against
mold and mildew. Refer to Type X 1/2" (12.7 mm) FSMR-C 4' (1219 mm) 8' (2438 mm)
page 70. Square thru
Gold Bond BRAND XP Fire-Shield C or 12' (3657 mm)
Gypsum Board has a specially Tapered
formulated type X gypsum core
to achieve superior fire resis- Type X 5/8" (15.9 mm) FSMR-C 4' (1219 mm 4' (1219 mm)
tance performance and is Square thru
designed to provide extra pro- or 12' (3657 mm)
tection against mold and Tapered
mildew. Refer to page 70.

Gold Bold BRAND Sta-Smooth Regular 1/2" (12.7 mm) 4' (1219 mm) 6' (1828 mm)
Gypsum Board, used with Sta-Smooth thru
1/2
ProForm BRAND Sta-Smooth Joint 16' (4876 mm)
BRAND WALLBOARD ® 1/2" Compound, forms a drywall
STA-SMOOTH BRAND ALLBOARD system offering maximum joint
W
STA-SMOOTH BRAND ALLBOARD
® 1/2" x
Type X 5/8" (1519 mm) FSW 4’ (1219 mm) 8' (2438 mm)
OO TH W ® 1/2" x strength. Two edge Sta-Smooth thru
STA-SM BRAND WALLBOARD configurations provide relief on
® 1/2" x1 16' (4876 mm)
STA-SMOOTH BRAND ALLBOARD 1/2" x12 joint deformities. The round
W ®

STA-SMOOTH BRAND ALLBOARD 1/2" x 12 edge configuration solves joint


OOTH W ®

STA- SM
BRAND WALLBOARD ® 1/2" x 12'
deformity problems caused by Type X 1/2" (12.7 mm) FSW-C 4' (1219 mm) 6' (1828 mm)
STA-SMOOTH BRAND ALLBOARD twisted framing, damaged board
W ®

edges, poor alignment and Sta-Smooth thru


STA-SMOOTH 16' (4876 mm)
extremes in humidity and
temperature. Refer to page 67.

09 29 00
Note: 1/2" regular Sta-Smooth gypsum board
available in 54" widths.

Gold Bond BRAND Kal-Kore Regular 3/8" (9.5 mm) 4' (1219 mm) 8' (2438 mm)
Plaster Base is a tapered edge 1/2" (12.7 mm) Square thru
1/2"
gypsum board plastering base or 16' (4876 mm)
BRAND PLASTER BA
SE having a blue absorptive face
KAL-KORE BRAND
® 1/2" x
Tapered
PL ASTER BASE ® 1/2" x paper surface designed to
KAL-KORE BRAND SE permit rapid trowel
PLASTER BA ® 1/2" x 8 Type X 1/2" (12.7 mm) FSK-C 4' (1219 mm) 8' (2438 mm)
KAL-KORE BRAND SE application and strong bond
KORE PLASTER BA ® 1/2" x 8 5/8" (15.9 mm) FSK Square thru
KAL- BRAND PLASTER BA
SE 1/2" x 8' T of veneer or conventional
KAL-KORE BRAND
®
or 16' (4876 mm)
PL AS TER BASE
® 1/2" x 8' T gypsum plaster. Refer to Tapered
KAL-KORE BRAND SE page 45.
PLASTER BA® 1/2" x 8' TE
KAL-KORE BRAND SE
KO RE PLASTER BA
®

KAL- Note: 1/2" regular Kal-Kore plaster base available


in 54" widths.

Gold Bond BRAND Gypsum Regular 1/2" (12.7 mm) 4' (1219 mm) 8' (2438 mm)
Sheathing is used Square 9' (2743 mm)
1/2" as an underlayment on 10' (3048 mm)
THING exterior walls. Finish
JUMBO SHEA ® BRAND
1/2"
GOLD BOND BRAND
MBO SH EA THING 1/2" x materials are applied with Type X 5/8" (15.9 mm) FSW-3 4' (1219 mm) 8' (2438 mm)
JU ®

GOLD BOND BRAND THING fasteners through sheathing Square 9' (2743 mm)
JUMBO SHEA 8
®
1/2" x
GOLD BOND BRAND BO SHEATHIN
G 1/2" x 8 into studs or furring strips. 10' (3048 mm)
JU M ®

GOLD BOND BRAND BO SHEATHIN


G 1/2" x 8' T Refer to page 28.
JU M®

GOLD BOND BRAND THING 1/2" x 8' T


JUMBO SHEA
®

GOLD BOND BRAND SH EATH ING 1/2" x 8' TE


®
JUMBO
GOLD BOND BRAND BO SHEATHIN
G
®
JU M
GOLD BOND

NATIONAL GYPSUM BOARD PRODUCTS 59


Description Core Thickness/Type Width/Edge Lengths

Gold Bond BRAND Exterior Soffit Regular 1/2" (12.7 mm) 4' (1219 mm) 8' (2438 mm)
Board is designed to provide, Sta-Smooth thru
1/2" in a fire resistive gypsum 12' (3658 mm)
BRAND SOFFIT BOAR
D® 1/2" ceiling board, the extra
GOLD BOND BRAND Type X 5/8" (15.9 mm) FSW 4' (1219 mm) 8' (2438 mm)
ND SO FFIT BOARD
® 1/2" x resistance to moisture and
GOLD BO BRAND D sagging required to meet Sta-Smooth thru
SOFFIT BOAR
® 1/2" x 8
GOLD BOND BRAND IT BOARD 1/2" x 8 protected outdoor conditions. 12' (3658 mm)
SO FF ®

GOLD BOND BRAND D Refer to page 71.


SOFFIT BOAR
® 1/2" x 8' T
GOLD BOND BRAND
ND SO® FFIT BOARD 1/2" x 8' T
GOLD BO BRAND D
®
SOFFIT BOAR 1/2" x 8' TE
GOLD BOND BRAND IT BOARD
®
SO FF
GOLD BOND

Gold Bond BRAND Fire-Shield Type X 1" (25.4 mm) FSW 2' (610 mm) Custom Cut
Shaftliner is used as a Beveled 7' (2134 mm)
component in shaftwall Edges thru
systems, in area separation 14' (4267 mm)
walls and in solid gypsum
partitions. The product has
moisture resistant green paper
on both faces. Refer to pages
73, 110, 124 and 140.

Gold Bond BRAND Fire-Shield Type X 1" (25.4 mm) FSW 2' (610 mm) Custom Cut
Shaftliner XP is used as a Beveled 7' (2134 mm)
component in shaftwall Edges thru
systems, area separation 14' (4267 mm)
walls and solid laminated
gypsum partitions. The
product has moisture/
mold/mildew resistant purple
paper on both faces. Refer to
page 74, 110, 124, and 140.

Gold Bond BRAND High Flex Regular 1/4" (6.3 mm) 4' (1219 mm) 8' (2438 mm)
Gypsum Board is specifically Eased thru
1/4 designed for radius 10' (3048 mm)
BRAND WALLBOARD ® 1/4" construction such as curved
HIGH FLEX BRAND walls, archways and
FLEX WALLBOARD ® 1/4" x
HIGH BRAND WALLBOARD
® 1/4" x 8 stairways. It can be used for
HIGH FLEX BRAND both concave and convex
WALLBOARD
® 1/4" x 8
HIGH FLEX BRAND surfaces. 1/4" High Flex is
FLEX WALLBOARD
® 1/4" x 8'
HIGH
BRAND WALLBOARD
® 1/4" x 8' E typically applied in double
HIGH FLEX BRAND layers. Refer to page 75.
®
WALLBOARD 1/4" x 8' EE
HIGH FLEX BRAND
®
W ALLBOARD
HIGH FLEX

60 NATIONAL GYPSUM BOARD PRODUCTS


09 29 00/NGC

Description Core Thickness/Type Width/Edge Lengths

Gold Bond BRAND High Strength Regular 1/2" (12.7 mm) 4' (1219 mm) 6' (1828 mm)
Ceiling Gypsum Board is Tapered thru
1/2
designed to resist sagging 16' (4876 mm)
BRAND CEILING BO
ARD 1/2" equal to 5/8" gypsum board.
TH ™
HIGH STRENG ™ BRAND CEILING BOARD 1/2" x Installed perpendicular to
TH
HIGH STRENG ™ BRAND CEILING BOARD 1/2" x 1 framing, span can be up to
ST RENG TH
HIGH BRAND CEILING BO
ARD 1/2" x 12 24" o.c. Can be decorated
TH ™
HIGH STRENG ™ BRAND CEILING BOARD 1/2" x 12 with spray textures and will
TH
HIGH STRENG ™ BRAND CEILING BOARD 1/2" x 12' support insulation. Refer to
TH
HIGH STRENG ™ BRAND CEILING BOARD 1/2" x 12' T page 77.
TH
HIGH STRENG ™ BRAND CEILING BOARD
TH
HIGH STRENG

Gold Bond BRAND Hi-Abuse XP Regular 5/8" (15.9 mm) FSW 4' (1219 mm) 8' (2438 mm)
Fire-Shield Gypsum Board is Square thru
designed for use in areas where or 12' (3657 mm)
surface durability and Tapered
indentation resistance are major
concerns. The product is
manufactured with a mold and
fire resistive Type X gypsum
core encased in heavy smooth
abrasion resistant, mold/mildew
resistant purple paper on the
face side and heavy
mold/mildew resistant liner
paper on the back side. Refer
to page 78.

09 29 00
Gold Bond BRAND Hi-Impact XP Type X 5/8" (15.9 mm) FSW-5 4' (1219 mm) 8' (2438 mm)
Fire-Shield Gypsum Board is thru
designed for use in areas Tapered 12' (3657 mm)
where impact/penetration
resistance is a major concern.
The product is manufactured
with a mold, moisture and fire
resistant Type X gypsum core
encased in heavy smooth
abrasion resistant, moisture,
mold/mildew resistant purple
paper on the face side and
heavy mold/mildew resistant
liner paper on the back side. A
fiberglass mesh is embedded in
the board to provide additional
impact/penetration resistance.
Refer to page 81.

Gold Bond BRAND Soundbreak Regular 5/8" (15.9 mm) 4' (1219 mm) 8' (2438 mm)
Gypsum Board is an Tapered thru
acoustically enhanced 12' (3658 mm)
gypsum board used in the
contruction of high rated STC
wall assemblies. This 5/8"
thick gypsum board consists
of a layer of viscoelastic
damping polymer
sandwiched between two
pieces of enhanced high
density mold resistant
gypsum board, providing
constrained layer damping.
Refer to page 84.

NATIONAL GYPSUM BOARD PRODUCTS 61


Description Core Thickness/Type Width/Edge Lengths

Gridstone BRAND Ceiling Panels Type X 1/2" (12.7 mm) FSW-G 2' (610 mm) 2' (610 mm)
have a fire resistant Fire- 2' (610 mm) 4' (1219 mm)
Shield G, type X core with a Square
2-mil textured vinyl laminate
surface suited for interior
or exterior application in
exposed grid systems.
Refer to page 86.

Gridstone BRAND CleanRoom Type X 1/2" (12.7 mm) FSW-G 2' (610 mm) 2' (610 mm)
Panels are designed for areas 2' (610 mm) 4' (1219 mm)
requiring high levels of air Square
cleanliness for airborne
particulate. Boards are sealed
on face, back and long edges
with a 2-mil rigid vinyl film
and exposed edges are factory
sealed with durable coating
providing a completely sealed
panel. Refer to page 87.

Gridstone BRAND Hi-Strength Regular 5/16" (7.9 mm) 2' (610 mm) 2' (610 mm)
Ceiling Panels have a non- 2' (610 mm) 4' (1219 mm)
combustible high strength sag Square
resistant gypsum core with a
2-mil textured vinyl laminate
surface suited for interior or
exterior application in exposed
grid systems. Refer to page 88.

62 NATIONAL GYPSUM BOARD PRODUCTS


09 29 00/NGC

METRIC CAPABILITIES GUIDELINES FOR Gypsum board that has visi- LIMITATIONS
The Federal Government has PREVENTION OF MOLD ble mold growth must not
be used. 1. Maximum stud spacing for
mandated that each federal GROWTH ON GYPSUM single layer application of
agency make a transition to BOARD Gypsum board on walls must 1/2" and 5/8" gypsum board
the use of metric units in Gypsum board does not gen- be applied with a mini- is 24" o.c. If 3/8" gypsum
all federal procurement, erate or support the mum 1/4" (6.35 mm) gap board is used, it must be
grants and business-related growth of mold when it is between the gypsum applied in two layers, with
activities. National properly transported, board and the floor. the second layer adhesively
Gypsum Company, in stored, handled, installed, Gypsum board must not be applied; 24" o.c. stud spac-
complying with this order, and maintained. However, applied over building ing may be used.
provides a full line of gyp- mold spores are present materials where condi- 2. Where long, continuous runs
sum board products in everywhere and when tions exist that are favor- of this wall system are
“hard” metric dimensions conditions are favorable, able to mold growth. employed, control joints must
with regard to width and mold can grow on practi- be provided every 30' or less.
length. Standard board cally any surface. Maintenance Following
offerings are made in the Observing these guide- Application 3. Where structural movement
width of 1200 mm and a lines will help minimize Essential elements of sound may impose direct loads on
length of 3600 mm. Job the potential for mold weather tight building these systems, isolation
size lengths are available growth on gypsum board. envelope must be properly details are required.
on a special order basis Gypsum board must be maintained, such as the 4. Partitions should not be used
requiring minimum orders kept dry to prevent the roof, sealants, windows, where frequently exposed to
and extended lead times. growth of mold. etc. excessive moisture unless all
Contact your local Transportation and Receiving Immediate and appropriate surfaces are waterproofed.
National Gypsum remediation measures 5. To prevent weakening due
Company representative for Gypsum board must be pro-
tected during transit with a must be taken as soon as to calcining, gypsum board
further information. water leaks or condensa- should not be exposed to
Thickness of gypsum board weather-tight cover in
good condition. tion sources are identified. temperatures over 125˚F
will be “soft” converted to Routine cleaning and mainte- (52˚C) for extended periods
the metric equivalent. Plastic shipping bags are of time.
intended to provided pro- nance operations must be
ENVIRONMENTAL performed so as to prevent 6. Gypsum board joints on sin-
CONDITIONS tection during transit only
and must be promptly saturation of the gypsum gle layer, or the face layer
Maintain a room temperature removed upon arrival of board. on two layer applications,
of not less than 40˚F (4˚C) the load. Failure to Additional Sources of shall not occur within 12" of

09 29 00
during application of gyp- remove the shipping bag Information the corners of door frames
sum board except when can increase the likeli- The following Web sites pro- unless control joints are
adhesive is used for the hood of developing condi- vide information and rec- installed at the corners.
attachment of gypsum tions favorable to the ommendations for treating 7. When gypsum board abuts
board. For the bonding of growth of mold. mold growth; other sites concrete floors, cut board to
adhesive, joint treatment, also provide similar sug- allow for 1/8" to 1/4" clear-
texturing, and decoration, Storage and Handling
gestions. ance between board and
the room temperature shall Gypsum board must be floor to prevent potential
be maintained at least at stored in an area that pro- California Indoor Air Quality
Program at wicking.
50˚F (10˚C) for 48 hours tects it from adverse
prior to application and weather conditions, con- http://www.cal-iaq.
continuously thereafter densation, and other forms org/iaqsheet.html
until completely dry. of moisture. Federal Emergency
Note 1: Precaution–When a Job site conditions that can Management Agency at
temporary heat source is expose gypsum board to http://www.fema.gov/
used, the temperature shall water or moisture must be pdf/hazards/fststpbr.html
not exceed 95˚F (35˚C) in avoided. New York City Department
any given room or area. Gypsum board must be of Health at
Note 2: Precaution–Maintain delivered to the job site as http://www.ci,nyc.ny.
adequate ventilation in the near to the time it will be us/html/doh/html/epi/
working area during instal- used as possible. moldrpt1.html
lation and curing period. Application U. S. Environmental
Protect gypsum board products Provisions must be made to Protection Agency at
from direct exposure to rain, keep gypsum board dry http://www.epa.gov/
snow, sunlight, or other throughout application. iedweb00/pubs/
excessive weather condi- moldresources.html
tions. GA-238, Copyright Gypsum
Association

NATIONAL GYPSUM BOARD PRODUCTS 63


GOLD BOND® BRAND GRIDMARX®
DESCRIPTION easily with no bleed-
through using standard
paint products.
Gold Bond ® BRAND Gypsum
Board comes standard with Vertical Application - In a ver-
GridMarX™ guide marks, tical application, GridMarX
printed on the paper sur- serve as a guide mark to
face. These guide marks help identify the exact
align with standard build- location of framing mem-
ing dimensions and help to bers behind the gypsum
quickly identify fastener board, eliminating the
lines for stud and joist need for field applied
framing. Using GridMarX, vertical lines.
accurate cuts can be made Horizontal Application - In a
without having to draw horizontal application,
lines. GridMarX also assist GridMarX serve as a
with quick identification of reference mark to help
nail/screw pattern. identify the location of
GridMarX guide marks run the framing members behind
machine direction of the the gypsum board. (If fram-
board at five points in 4" ing member is located 2" to
increments. Marks run the right of the GridMarX
along the edge in both at the top edge of the
tapers and at 16", 24" and board, it will be located 2"
32" in the field of the to the right down the face
board. The marks cover of the board.)

DETAILS

GRIDMARX —
VERTICAL WALL APPLICATION

GRIDMARX — HORIZONTAL WALL


Studs in AND CEILING APPLICATION
example are
24" o.c.

GridMarX
spaced
4" apart

GridMarX Represents a pipe or wiring


spaced Studs in example
4" apart are 16" o.c.

64 NATIONAL GYPSUM BOARD PRODUCTS


09 29 00/NGC
Gold Bond® BRAND Gypsum Board
DESCRIPTION TECHNICAL DATA RECOMMENDATIONS
Gypsum Board is the name for Fire and sound ratings for Examine and inspect materials with edges of opening unless
a family of board products building systems utilizing to which gypsum board is to control joints will be
consisting of a gypsum board are dependent be applied. Remedy all installed at these points. End
noncombustible core, on the core type and defects prior to installation of joints shall be staggered, and
primarily of gypsum, with a thickness of the gypsum drywall. Any defects in the joints on opposite sides of a
paper surfacing on the face, board, its application in finished installation due to partition shall not occur on
back and long edges.* conjunction with the misaligned framing or other the same stud.
component parts, and the cause will be the Gypsum board shall be held in
The popularity of gypsum board manner in which it is
results from a number of responsibility of the work firm contact with the framing
applied. performed under that section member while fasteners are
factors. First, it takes virtually
any decoration – from paint Tests for fire resistance and of the specification and such being driven. Fastening shall
or textures to vinyl and sound transmission, defects shall be remedied proceed from center portion
paper laminates. It also lends performed by independent under that section of the of the board toward the
itself to creative shaping of laboratories, have resulted in specification. edges and ends. Fasteners
interior surfaces, allowing specific ratings for walls/ Gypsum board shall be applied shall be set with the heads
the maximum in design partitions; floor/ceiling first to ceiling at right angles slightly below the surface of
flexibility. Gypsum board is assemblies; shaftwalls, to framing members, then to the board in a dimple
an economical alternative to stairwells and area walls. Boards of maximum formed by the hammer or
other products. Because it is separation walls; and practical length shall be used power screwdriver. Care
lightweight, it is easy to columns. For maximum fire so that an absolute minimum shall be taken to avoid
handle for speedy resistance and sound control, number of end joints occur. breaking the face paper of
installation. With its natural double layer construction is Board edges shall be brought the gypsum board.
properties, it is durable yet generally recommended into contact with each other Improperly driven nails or
easy to repair. In addition, since the additional mass but shall not be forced into screws shall be removed.
gypsum board’s fire further retards heat and noise place. See page 63, Environmental
resistance and sound control penetration. Conditions and Limitations.
Gypsum board joints at
capabilities further Gypsum board can be installed openings shall be located so
demonstrate its desirability to both metal and wood that no end joint will align
in building systems. framing using nails, screws
Ever conscious of the or adhesives in combination
environmental challenges with nails or screws. In many
we face in today’s world, instances, the application CURVED SURFACES
National Gypsum produces will dictate which fastening To apply gypsum board over a curved surface, place a stop at one end
its gypsum board with 100 method is appropriate. of the board and then gently and gradually push on the other end,

09 29 00
percent recycled paper on Control joints may be necessary forcing the center against the framing until the curve is complete.
both the face and back. to prevent cracking in the Shorter radii than shown in the table may be obtained by moisten-
Gold Bond gypsum board is gypsum board facing of ing the face and back papers of the board with water, stacking on a
available with a variety of drywall systems, especially flat surface, and allowing the water to soak into the core for at least
edge configurations. For easy in areas where structural one hour. When the board is dry it will regain its original hardness.
joint finishing, the tapered elements such as slabs, Gypsum board may be applied to curved surfaces in accordance with
edge is preferred to provide columns or exterior walls the following:
a monolithic surface. Where can bear directly on non-
joints will be exposed, load-bearing partitions. To GYPSUM BOARD BENDING RADII
square or beveled edges relieve the stresses which
occur as a result of Thickness Bending Lengthwise Bending Widthwise
should be considered.
National Gypsum also movement induced by 1/4" (6.4 mm) 5'-0" (1524 mm) 15'-0" (4572 mm)
manufactures gypsum board changes in moisture, 3/8" (9.4 mm) 7'-6" (2286 mm) 25'-0" (7620 mm)
with proprietary edge temperature or both, control 1/2" (12.7 mm) *10'-0" (3048 mm)
configurations made to joints are required in both 5/8" (15.9 mm) 15'-0" (4572 mm)
accommodate a variety of partitions and ceilings.
wall systems and finishing GYPSUM BOARD *Bending two layers of 1/4" (6.4 mm) board successively will permit a bending
techniques. INSULATING PROPERTIES radius shown for 1/4" (6.4 mm) board.
*GA-216 For purposes of calculating Note: To achieve tighter bending radii, use Gold Bond 1/4" High
Fire and sound ratings for “U” values, the “C” factor for Flex Gypsum Board. See page 75 for additional information and
building systems utilizing 1" gypsum board is 1.2; 1/4" High Flex minimum bending radii chart.
gypsum board are Resistance “R” for 3/8" board
dependent on the core type is .32; for 1/2" board .45; for SURFACE BURNING CHARACTERISTICS
and thickness of the gypsum 5/8" board .56 and for 1" (Fire Hazard Classification) Tested in accordance with ASTM E 84
board .83.
Gypsum Gypsum Durasan
WEIGHTS Board Sheathing All Standard Patterns
1/4" Regular - 1.2 lbs/SF Flame Spread Index 15 20 25 or less
3/8" Regular - 1.2 lbs/SF
1/2" Regular - 1.6 lbs/SF Smoke Developed 0 0 50 or less
SPECIFICATIONS
THE FOLLOWING PARAGRAPHS ARE FOR INSERTION INTO SECTIONS OF GENERIC SPECIFICATIONS OR GENERIC/PROPRIETARY SPECIFICATIONS COVERING GYPSUM BOARD
PRODUCTS. THE NATIONAL GYPSUM PRODUCT NAME FOLLOWS THE GENERIC DESCRIPTION IN PARENTHESES.

PART 2 PRODUCTS 2.01 MATERIALS


A. Regular Gypsum Board: A gypsum core board that is fire resistant and surfaced with paper on front/back and long edges and complies with
ASTM C 1396.
1. Thickness: 1/4", 3/8", 1/2" (Gold Bond BRAND Gypsum Board) 3. Length: 6' through 16'.
2. Width: 4'. 4. Edges: Square, Tapered, or Beveled Tapered (Sta-Smooth Edge).
PART 3 EXECUTION 3.01 INSTALLATION
A. General: In accordance with the manufacturer’s recommendations, National Gypsum Company “Gypsum Construction Guide.”

NATIONAL GYPSUM BOARD PRODUCTS 65


Gold Bond® BRAND Fire-Shield® Gypsum Board
DESCRIPTION TECHNICAL DATA WEIGHTS Gypsum board joints at
1/2" Type C - 1.9 lbs/SF openings shall be located
Gold Bond BRAND Fire-Shield
® ®
SYSTEM BURNING so that no end joint will
Gypsum Board was CHARACTERISTICS 5/8" Type X - 2.2 lbs/SF align with edges of
developed to work in opening unless control
combination with other ASTM E84 5/8" Type C - 2.2 lbs/SF
joints will be installed at
products in an assembly to Flame Spread: 15 For fire safety information, go to these points. End joints
retard heat transfer through Smoke Developed: 0 www.nationalgypsum.com. shall be staggered, and
the assembly. Fire-Shield joints on opposite sides of
gypsum boards are made a partition shall not occur
with cores formulated to According to ASTM C 1396, RECOMMENDATIONS
the standard for gypsum on the same stud.
offer greater fire resistance
than regular gypsum board. board, type X gypsum Gypsum board shall be held
Examine and inspect materials in firm contact with the
Generically, these fire board must provide at least: to which gypsum board is
resistant boards that are a one-hour fire resistance framing member while
to be applied. Remedy all fasteners are being driven.
used to delay heat transfer rating for 5/8" board, or a defects prior to installation
to structural members are 3/4-hour fire resistance Fastening shall proceed
of drywall. Any defects in from center portion of the
designated as “type X” rating for 1/2" board the finished installation due
products. applied in a single layer board toward the edges
to misaligned framing or and ends. Fasteners shall
nailed on each face of other cause will be the
The Gypsum core of Fire- load-bearing wood framing be set with the heads
Shield Gypsum Board works responsibility of the work slightly below the surface
members when tested in performed under that
as a natural “sprinkler accordance with the of the gypsum board in a
system.” Gypsum naturally section of the specification dimple formed by the
requirements of Methods of and such defects shall be
contains about 21 percent Fire Test of Building hammer or power
water. When the board is remedied under that screwdriver. Care shall be
Constructions and section of the specification.
heated, the water in the Materials (ASTM taken to avoid breaking the
core begins to evaporate designation E 119). Gypsum board shall be face paper of the gysum
and is released as steam, applied first to ceiling at board. Improperly driven
retarding heat transfer. right angles to framing nails or screws shall be
Fire-Shield gypsum board For additional fire protection,
Gold Bond Fire-Shield C members, then to walls. removed.
remains noncombustible. Boards of maximum
However, as shrinkage products are formulated See page 63, Environmental
with a mineral core practical length shall be Conditions and
occurs because of the loss used so that an absolute
of water volume, cracks additive which expands Limitations.
when subjected to heat minimum number of end
occur which permit joints occur. Board edges
passage of fire and heat. which aids in holding the
gypsum board together. shall be brought into
To lessen this process, contact with each other
Fire-Shield gypsum board Fire-Shield gypsum boards but shall not be forced
is formulated by adding also can be used as into place.
noncombustible fibers column protection,
to the gypsum to help delaying the rapid transfer SPECIFICATIONS
maintain the integrity of of heat to reduce the
the core as water volume likelihood that structural
is lost while providing THE FOLLOWING PARAGRAPHS ARE FOR INSERTION INTO SECTIONS OF
members will lose strength GENERIC SPECIFICATIONS OR GENERIC/PROPRIETARY SPECIFICATIONS
greater resistance to heat and fail to carry the COVERING GYPSUM BOARD PRODUCTS. THE NATIONAL GYPSUM
transfer. intended load. PRODUCT NAME FOLLOWS THE GENERIC DESCRIPTION IN PARENTHESES.
FIRE RESISTANCE RATINGS PART 2 PRODUCTS
Fire resistance ratings 2.01 MATERIALS
represent the results of
tests on assemblies made A. Fire-Resistant Gypsum Board: A gypsum core gypsum
up of specific materials in a board with additives to enhance fire resistance of the core
specific configuration. and surfaced with paper on front, back, and long edges
When selecting and complying with ASTM C 1396, type X.
construction designs to 1. Thickness: 1/2" (Gold Bond BRAND Fire-Shield C
meet certain fire resistance Gypsum Board), 5/8" (Gold Bond BRAND Fire-Shield
requirements, caution must Gypsum Board), or 5/8" (Gold Bond BRAND Fire-Shield
be used to insure that each C Gypsum Board)
component of the assembly 2. Width: 4'
is the one specified in the 3. Length: 6' through 16'
test. Further, precaution (1/2" Fire-Shield C Gypsum Board,
should be taken that 5/8" Fire-Shield Gypsum Board)
assembly procedures are in Length: 8' through 14'
accordance with those of
the tested assembly. (5/8" Fire-Shield C Gypsum Board)
(For copies of specific tests, 4. Edges: Square, Tapered, or Beveled Tapered
call 1-800-NATIONAL.) (Sta-Smooth Edge)
PART 3 EXECUTION
3.01 INSTALLATION
A. General: In accordance with the manufacturer’s
recommendations, National Gypsum Company “Gypsum
Construction Guide.”

66 NATIONAL GYPSUM WALLBOARD PRODUCTS


09 29 00/NGC
Gold Bond® BRAND Sta-Smooth® Gypsum Board
DESCRIPTION Alignment – Sta-Smooth
board with its unique edge
(either configuration)
Sta-Smooth is a drywall allows for easy alignment
system offering maximum of the boards in the same
joint strength and easy way as conventional
application. It can be used tapered edge board. The
in any gypsum drywall taper is scientifically
system where conventional designed to reduce
types of gypsum board are crowned joints.
recommended. This
system features Sta-Smooth Stronger Bond – The bonding
Brand gypsum board with a area of the Sta-Smooth
unique edge. The two edge Joint Compounds are
configurations relieve joint increased with the “V”
deformity problems caused edge boards. The Sta-
by twisted framing, Smooth Joint Compound
damaged gypsum board used to bond the joint tape
edges, poor alignment and and fill the joints is a
extremes in humidity and hardening-type, high
temperature. Regular Sta- density material
Smooth Boards are with low shrinkage
available in 1/2" characteristics. Easier Scheduling – Taping
thicknesses, 4' wide and in Strength – The Sta-Smooth with Sta-Smooth Com- TECHNICAL DATA
customary gypsum board joint shape and the joint pounds and applying the
lengths. The Sta-Smooth compound are developed first finishing coat, even SURFACE BURNING
System is also composed of to provide greater mass before the Sta-Smooth used CHARACTERISTICS
ProForm BRAND Sta-Smooth and integral bond for for taping has dried, allows ASTM E-84
Joint Compounds, a increased strength. Sta- easier job scheduling for Flame Spread: 15
hardening-type taping Smooth Joint Compounds the drywall contractor and
compound and regular Smoke Developed: 0
add considerable strength finisher. This is particularly
Gold Bond tape and which is unaffected by advantageous under slow
finishing compounds. the amount of moisture drying conditions. WEIGHTS
ADVANTAGES normally introduced into a 1/2" Regular - 1.6 lbs/SF
structure that could cause 5/8" Type X - 2.2 lbs/SF
Improved Durability – The ridging or beading with

09 29 00
Sta-Smooth System 5/8" Type C - 2.2 lbs/SF
conventional joint
produces a smooth, flat, compounds.
durable surface that relieves
beading, ridging and other Cost – If application DETAILS
joint deformity problems. techniques are followed as
recommended, the Sta-
Greater Speed – All flat Smooth System should cost
joints in the Sta-Smooth THE SECRET IS IN THE SHAPE OF THE JOINT AND THE
no more and can cost STRENGTH OF THE COMPOUND
System are filled and taped considerably less than
with any Sta-Smooth conventional gypsum
Compounds all in one easy board drywall joint
operation, the same as finishing. The initial
conventional gypsum board savings are immediately
application methods. Sta- demonstrated with reduced
Smooth Compounds or travel time that results from
regular compounds can be this perfected 2-trip, 3-step Standard tapered-beveled edge configuration.
used to tape inside corners, joint finishing system.
cornerbeads, and spot Future cost savings will be
fasteners. Regular ProForm realized with reduced
finishing compounds or callbacks.
Sta-Smooth compounds are
used for the remaining Better Butt Joints –
finishing coats. Recommended with the Round edge configuration.
Sta-Smooth System is an
Easier Handling – The improved technique for
improved edge designs on providing a smoother, The Sta-Smooth System produces a superior joint because the
Sta-Smooth Boards makes flatter, stronger butt joint. Sta-Smooth Compounds are a hardening-type compound that
handling easier with greater Although this technique is not affected by humidity once it has hardened and dried. It
comfort to the hands. could be used in also maintains its hard core even with moisture added by the
No Special Equipment – All conventional drywall use of the regular joint compounds for the finishing work.
conventional fasteners, work and produce better Sta-Smooth Compound firmly bonds the tape to the board
adhesives, and gypsum butt joints, it is further and the board “V” edges to each other making a strong,
board application tools (T- improved by the use of the rigidized joint.
squares, knives, etc.) can be high strength Sta-Smooth Consult your local National Gypsum sales representative for
used to apply Sta-Smooth Compound. edge configuration available in your market.
Boards. Nothing new to
buy.

NATIONAL GYPSUM BOARD PRODUCTS 67


RECOMMENDATIONS SPECIFICATIONS

Note: Sta-Smooth Gypsum Board may be used with any of the THE FOLLOWING PARAGRAPHS ARE FOR INSERTION INTO SECTIONS OF GENERIC
Gypsum Drywall Systems described in this Gypsum SPECIFICATIONS OR GENERIC/PROPRIETARY SPECIFICATIONS
Construction Guide. COVERING GYPSUM BOARD PRODUCTS. THE NATIONAL GYPSUM PRODUCT
NAME FOLLOWS THE GENERIC DESCRIPTION IN PARENTHESES.
All specifications for the application of gypsum board as
described in this literature may also serve for the application PART 2 PRODUCTS
of Sta-Smooth Boards. Any deviation from these 2.01 MATERIALS
specifications is as indicated below.
A. Gypsum Board: A gypsum core wall board surfaced with
A. BOARD APPLICATION: Position each Sta-Smooth Board so paper on front, back, and long edges and complying with
that the long edges are in light contact with the edges of the ASTM C 1396 (Gold Bond BRAND Gypsum Board).
previous boards. All boards positioned to form butt joints
should have a gap approximately 1/16" between the board 1. Thickness: 1/2"
ends. This spacing can be assured by driving 2 extra fasteners 2. Width: 4'
at the end of the board to act as temporary spacers before 3. Length: 6' through 16'
abutting the next board. When the boards are fastened in 4. Edge: Beveled Tapered (Sta-Smooth Edge)
place, drive the temporary spacers flush with surface. When B. Fire-Resistant Gypsum Board: A gypsum core wall board with
gypsum board is applied horizontally, recess all butt joints on additives to enhance fire resistance of the core and
the job by shimming the face of the studs (or joists), on both surfaced with paper on front, back, and long edges and
sides of the studs (or joists), on which the joint will fall. The complying with ASTM C 1396, type X.
shim can be pressed paper, thickness of building felt or other
suitable materials not to exceed 1/16" thickness and as wide as 1. Thickness: 1/2" (Gold Bond BRAND Fire-Shield C
the stud or joist. It should be 6" longer than the butt joint and Gypsum Board), 5/8" (Gold Bond BRAND Fire-Shield
applied to the face of the stud or joist with staples or nails Gypsum Board), or 5/8" (Gold Bond BRAND Fire-Shield C
allowing the shim to extend under the edge of the abutting Gypsum Board)
boards of gypsum board to assure that the board facings 2. Width: 4'
remain on the same plane. 3. Length: 6' through 16'
B. CORNERS AND OPENINGS: All exterior corners and all (1/2" Fire-Shield C Gypsum Board,
openings that require joint treatment should receive 5/8" Fire-Shield C Gypsum Board)
protective reinforcement of ProForm Multi-Flex Tape Bead or Length: 8' through 14'
Steel Cornerbead or Steel Casing Bead as required. (5/8" Fire-Shield C Gypsum Board)
C. TREATMENT OF JOINTS*: All flat Sta-Smooth gypsum board 4. Edge: Beveled Tapered (Sta-Smooth Edge)
joints are taped with ProForm BRAND Sta-Smooth Compounds, 5. Edge: Rounded (Sta-Smooth Edge)
making sure that a sufficient amount of compound is forced C. Exterior Gypsum Soffit Board: A gypsum core soffit board
into the “V” joint and spread under the tape to form a solid with additives to enhance the sag resistance of the core;
foundation for the finishing coats.** surfaced with water repellent paper on front, back, and
1. As soon as the Sta-Smooth Joint Compound used for taping has long edges; and complying with ASTM C 1396
hardened, the first finishing coat can be applied even when (Gold Bond BRAND Exterior Soffit Board).
the Sta-Smooth Compound is still wet. 1. Thickness: 1/2"
2. When the first finishing coat is completely dry the second 2. Width: 4'
finishing coat can be applied. Any of the ProForm Joint 3. Length: 8' through 12'
Compounds may be used for the finishing coats. 4. Edge: Beveled Tapered (Sta-Smooth Edge)
3. Sta-Smooth Joint Compounds are recommended for the first D. Fire-Resistant Exterior Gypsum Soffit Board: A gypsum core
coat on nail or screw heads. Regular finishing compounds soffit board with additives to enhance the fire-resistance
may be used for subsequent spotting of the fasteners. Sta- and the sag resistance of the core; surfaced with water
Smooth Compounds are also recommended for the first coat repellent paper on front, back, and long edges; and
on cornerbead and followed by one or more finishing coats complying with ASTM C 1396, type X
as required of regular ProForm Joint or Topping Compounds. (Gold Bond BRAND Fire-Shield Exterior Soffit Board).
4. The inside corners may be treated with any of the ProForm 1. Thickness: 5/8"
Joint Treatment Compounds recommended for taping. If a 2. Width: 4'
two-trip joint treatment operation is planned, the inside 3. Length: 8' through 12'
corners are taped with Sta-Smooth Joint Compounds. This 4. Edge: Beveled Tapered (Sta-Smooth Edge)
will permit finishing one side of the inside corners the first
day. Cornerbead is treated with Sta-Smooth Compounds if a PART 3 EXECUTION
two-trip operation is employed. 3.01 INSTALLATION
*Alternate Method: When mechanical tools are to be used for A. General: In accordance with the manufacturer’s
taping joints, Sta-Smooth Compounds are used to fill the “V” recommendations, National Gypsum Company “Gypsum
joint only. Other ProForm Joint Compounds are then used to Construction Guide.”
bed the tape and finish the joints. (See page 69.)
**Sta-Smooth, Sta-Smooth HS and Sta-Smooth Lite Joint
Compounds are recommended for pre-fill or tape/bed coat
operations in the Sta-Smooth system.
See page 63, Environmental Conditions and Limitations.

68 NATIONAL GYPSUM BOARD PRODUCTS


09 29 00/NGC
INSTALLATION
APPLICATION AND FASTENING
Sta-Smooth Boards may be nailed, screwed or adhesively applied to wood studs or
furring, or screwed or adhesively applied to steel studs or furring, using conventional
type and length of fastener. All fasteners shall be applied a minimum of 3/8"
(maximum 1/2") from the edges and ends of each board. Then treat the joints in three
simple steps.
CONVENTIONAL TAPING AND FINISHING
1. Fill Joint And Bed Tape Simultaneously
All flat gypsum board joints are to be filled and taped in one operation with ProForm
BRAND Sta-Smooth Compounds, using ProForm Paper Tape in the conventional
manner. When Sta-Smooth HS tape is used, the self-adhering fiberglass mesh tape is
firmly pressed to the gypsum board, spanning the joints. Sta-Smooth Compounds can
Application And Fastening then immediately be applied to the joints. The compound must be forced through the
tape to fill the channel formed by the “V” edges of the Sta-Smooth gypsum board. All
inside corners may be taped using regular ProForm compounds. Sta-Smooth
Compounds are used for the first coat on nail or screw heads and will decrease
problems with fastener imperfections. Inside angles, first and second finishing coats
may be done using regular ProForm joint compounds.
2. First Finishing Coat
As soon as the Sta-Smooth Compound used for taping has hardened, the first finishing
coat may be applied on the flat joints even before it is dry. Any ProFrom joint
compound may be used for this operation. A second coat may be applied at this time
to nail or screw heads, one coat on cornerbead if Sta-Smooth Compound was used for
the first coat.
3. Second Finishing Coat
1. Fill Joint And Bed Tape As soon as the compounds used for the previous steps have thoroughly dried, a second
Simultaneously finishing coat is applied to all flat joints using ProForm Joint Compound or Topping
Compound. A third coat is applied over nail or screw heads and on cornerbead as
required. The unfinished side of the inside corners is also finished at this time.
STA-SMOOTH ROUND EDGE REQUIRES PRE-FILLING PRIOR TO BED & TAPING
Application Instructions For Round Edge Sta-Smooth Gypsum Board

09 29 00
1) Mix Sta-Smooth Joint Compound, Sta-Smooth Lite Joint Compound or Sta-Smooth HS
Joint Compound as per bag instructions. Care should be taken to mix no more
compound than can be applied in the designated set time.
2) Pre-fill all joints formed by the abutting round edge Sta-Smooth Gypsum Boards with
Sta-Smooth Compound, Sta-Smooth Lite Joint Compound or Sta-Smooth HS Joint
Compounds using a conventional joint finishing knife. Fill joints, level and wipe off
excess compound to the lowest level of the taper, allowing enough room for
embedding the tape. Allow prefill material to harden prior to application of tape and
2. First Finishing Coat bed coat.
3) Finish joints in the normal manner.
TAPING AND FINISHING WITH MECHANICAL TOOLS
Taping – Taping tools such as the “banjo” and “hopper” types are recommended for
taping the flat joints with Sta-Smooth Compounds and the inside corners with ProForm
regular joint compounds or with Sta-Smooth Compounds. Automatic taping tools are
not recommended for use with hardening-type compounds. Mechanical tools can be
used for taping the inside corners when a ProForm regular joint compound is used.
When automatic taping tools are used for taping the flat joints, the “V” formed by the
edges of Sta-Smooth board on the flat joints and all spaces between the gypsum board
edges on butt joints are prefilled with Sta-Smooth Compounds and allowed to harden
(30 minutes longer than the set time designated on the bag) prior to taping with a
regular ProForm joint compound.
Finishing – Mechanical type finishing tools can be used in the normal manner for the
3. Second Finishing Coat finishing operations of the Sta-Smooth System since conventional ProForm finishing
compounds are used.
MIXING INSTRUCTIONS
ProForm BRAND Sta-Smooth Compounds are available in 20, 45, 90 and 210 minute set
times. MIX NO MORE COMPOUND THAN CAN BE APPLIED IN THE DESIGNATED
SET TIME. Contact your National Gypsum Company Representative for availability.
A plastic container is recommended because of its ease in cleaning between batches.
Do not use a wood or aluminum bucket. Add the compound gradually to clean water
while stirring. Note: Use only fresh, clean water suitable for human consumption.
Mix at the ratio of 13-14 pints of water to the 25 lb. bag. Mix the compound free of
lumps with a mechanical mixer or by hand. Mechanical mixing is recommended.
Allow to stand 5 minutes as a “wetting” period and remix to further improve the
working qualities. If a slightly thinner compound is desired, add an additional pint of
water, or less, after the compound is thoroughly mixed.

NATIONAL GYPSUM BOARD PRODUCTS 69


Gold Bond® BRAND XP® Gypsum Board
DESCRIPTION call 1-800-NATIONAL. For XP Gypsum Board can be used as XP Gypsum Board that is to
fire safety information, see a tile backer board in dry areas have a wallcovering applied
Gold Bond BRAND XP
® ® www.nationalgypsum.com.) or areas with limited water to it should be prepared and
Gypsum Board panels MOLD AND MILDEW exposure such as directly primed as described for
consist of a fire-resistant, RESISTANCE behind tile in tub and shower
areas.
painting.
mold and moisture-
resistant gypsum core XP Gypsum Board was XP Gypsum Board can be
designed to provide extra installed on the interior south
SPECIFICATIONS
encased in heavy
moisture/mold/mildew protection against mold face of exterior walls.
and mildew compared to PART 2 PRODUCTS
resistant, 100% recycled XP Gypsum Board should not be THE FOLLOWING PARAGRAPHS ARE
purple paper on the face standard gypsum board used as a backer board FOR INSERTION INTO SECTIONS
and backsides. products. When tested by directly behind tile in tub and OF GENERIC SPECIFICATIONS OR
XP Gypsum Board was an independent lab per shower areas. GENERIC/PROPRIETARY
designed to provide extra ASTM D3273 (“Standard SPECIFICATIONS COVERING
XP Gypsm Board should not be GYPSUM BOARD PRODUCTS. THE
protection against mold Test Method for NATIONAL GYPSUM PRODUCT
and mildew compared to Resistance to Growth of used in areas subject to NAME FOLLOWS THE GENERIC
standard gypsum board constant and/or excessive DESCRIPTION IN PARENTHESES.
Mold on the Surface of moisture and high humidity
products. The face paper Interior Coatings in an 2.01 MATERIALS
is folded around the long such as gang showers, saunas,
Environmental Chamber”), steam rooms and swimming A. Mold-Resistant Gypsum
edges to reinforce and XP Gypsum Board
protect the core, and the pool enclosures. PermaBase Board: A gypsum core wall
achieved a score of 10, BRAND cement board is panel with additives to
ends are square-cut and the best possible score for
finished smooth. Long recommended for these areas. enhance the water resistance
edges of panels are this test. of the core; surfaced with
XP Gypsum Board must be
tapered. Tapered edges The use of XP Gypsum Board stored off the ground and moisture/mold/mildew
allow joints to be treated in in actual installations may under cover. Sufficient risers resistant paper on front,
the normal manner. For must be used to ensure back and long edges and
optimum mold and not produce the same
results as were achieved support for the entire length of complying with ASTM
mildew resistance, the gypsum board to prevent C 1396 (Gold Bond BRAND
National Gypsum in controlled, laboratory sagging.
conditions. No material XP Gypsum Board).
recommends ProForm
BRAND XP Ready Mix or can be considered “mold- XP Gypsum Board must be kept 1. Thickness: 1/2”
ProForm BRAND Sta- proof,” nor is it certain dry to minimize the potential 2. Width: 4'
Smooth/Sta-Smooth Lite that any material will for mold growth. Adequate 3. Length: 8', 10' or 12'
setting compounds. resist mold or mildew care should be taken while 4. Edges: Square or
indefinitely. When used in transporting, storing, applying Tapered
Gold Bond BRAND XP Fire- and maintaining gypsum
Shield® Gypsum Board conjunction with good 5. Mold and Mildew
design, handling and board. For additional
features a type X core to information, refer to the Resistance: Panel score
provide additional fire construction practices, XP Gypsum Association of 10 when tested in
resistance ratings when Gypsum Board can publication, “Guidelines for accordance with ASTM
used in tested systems. provide increased mold the Prevention of Mold D 3273
Gold Bond BRAND XP Fire- resistance versus standard Growth on Gypsum Board” B. Fire-Resistant Mold and
Shield C Gypsum Board gypsum board products. (GA-238-03), which is Mildew-Resistant Gypsum
Panels have a specially As with any building available at www.gypsum.org Board: A gypsum core wall
formulated type X core to material, exposure during under the “Download Free panel with additives to
achieve superior handling, storage, and Gypsum Association enhance the fire resistance
performance when used in installation, and after Publications” section. and water resistance of the
specific fire-rated installation is complete, is core; surfaced with
assemblies where the the best way to avoid the DECORATION
weight and number of moisture/mold/mildew
formation of mold or For best painting results, all resistant paper on front,
gypsum board layers are a mildew. surfaces, including joint
concern. back and long edges and
WEIGHTS compound, should be clean, complying with ASTM
TECHNICAL DATA dust-free and not glossy. To C 1396, type X.
1/2” Regular - 1.75 lbs/SF improve fastener and joint
1/2” Type C - 1.95 lbs/SF concealment, a coat of a 1. Thickness: 1/2” (Gold
SURFACE BURNING 5/8” Type X - 2.4 lbs/SF Bond BRAND XP Fire-
CHARACTERISTICS
quality drywall primer is
recommended to equalize Shield C Gypsum Board),
ASTM E 84 5/8” (Gold Bond BRAND
Flame spread: 15 RECOMMENDATIONS the porosities between the
paper and joint compound. XP Fire-Shield Gypsum
Smoke developed: 0 Exposure to excessive or Board,) 5/8” (Gold Bond
FIRE RESISTANCE RATINGS continuous moisture and The selection of a paint to give Brand XP Fire-Shield C
Fire resistance ratings represent extreme temperatures should the specified or desired Gypsum Board.)
the results of tests on be avoided. XP Gypsum Board finished characteristics is the 2. Width: 4'
assemblies made up of is not recommended where it responsibility of the architect 3. Length: 8', 10', or 12'
specific materials in a will be exposed to temperatures or contractor. 4. Edges: Square or
specific configuration. When exceeding 125˚F (52˚C) for Tapered
selecting construction extended periods of time. 5. Mold and Mildew
designs to meet certain fire MAXIMUM FRAMING SPACING - For Single Layer XP Gypsum Board Resistance: Panel score
resistance requirements, of 10 when tested in
Gypsum Board Gypsum Board Maximum
caution must be used to Thickness Orientation to Framing Framing Spacing
accordance with ASTM
insure that each component D 3273
Ceilings: 1/2" (12.7mm) Parallel 16" (406mm) o.c.
of the assembly is the one 1/2" (12.7mm) Perpendicular 24" (610mm) o.c. PART 3 EXECUTION
specified in the test. Further, 5/8" (15.9mm) Parallel 16" (406mm) o.c. 3.01 INSTALLATION
precaution should be taken 5/8" (15.9mm) Perpendicular 24" (610mm) o.c.
that assembly procedures are Walls: 1/2" (12.7mm) Perpendicular or Parallel 24” (610mm) o.c. A. General: In accordance
in accordance with those of 5/8” (15.9mm) Perpendicular or Parallel 24” (610mm) o.c. with the manufacturer’s
the tested assembly.(For recommendations, National
NOTE: On ceilings to receive hand or spray applied, water based texture material,
copies of specific tests, XP Gypsum Board products shall be applied perpendicular to framing. Gypsum Company “Gypsum
Construction Guide.”
70 NATIONAL GYPSUM BOARD PRODUCTS
09 29 00/NGC
Gold Bond® BRAND Exterior Soffit Board

DESCRIPTION

Gold Bond® BRAND Exterior Typical uses for sheltered


Soffit Board is designed to exterior ceiling and soffit
provide, in a fire-resistive areas are covered parking
gypsum board, the extra areas, walkways and
resistance to moisture and marquees in commercial
sagging required to meet construction and, in
outdoor conditions. The residential construction,
specially treated gypsum carports, breezeways and
core is covered on both open porches.
sides with water-repellent
paper formed to the Sta-
Smooth edge. Boards are
1/2" (regular) and 5/8" (Fire-
Shield) x 4' x 8' through 12'
lengths.

TECHNICAL DATA
4. METAL FRAMING AND support equal to that of the 8. VENTILATION
FURRING interrupted members. Provide at least 1 sq. ft. of
1. WEIGHTS
A suspended framework for Apply Soffit Board with 1" venting to exterior for each
1/2" Regular - 1.8 lbs/SF support of the ceiling board Type “S” Screws, 12" o.c. 150 sq. ft. of Ceiling/Soffit
5/8" Type X - 2.2 lbs/SF is composed of 1 1/2" cold- max. Board. Vent each enclosed
2. GENERAL rolled steel channels for 5. CONTROL JOINTS bay. If the space above the
main runners and either the ceiling board is not open to
Use longest practical board Furring Channel or the To compensate for the effect areas above or below
lengths to minimize the Steel Stud for cross-furring. of structural movement on habitable rooms, provide
number of butt joints. large ceiling areas, control ventilating area of not less
Position end joints at Space main runners as joints in the Ceiling/Soffit
follows: 4' o.c. max. if than 1/300 of the ceiling
supports, allowing 1/16" to Board are recommended. area. Otherwise, vent in
1/8" between butted ends. Furring Channels are to be These should be E-Z Strip accordance with HUD

09 29 00
When board is applied used, 6' o.c. max. for 2 1/2" Expansion Joints.
Steel Studs, and 8' o.c. max Minimum Property
with long edges parallel to Install E-Z Strip with 1/2" min. Standard No. 4900.1 or in
framing, framing spacing is for 3 5/8" Steel Studs. Main
runners are suspended with staples 6" o.c. Use accordance with local
16" o.c. max. When board additional staples if codes.
is applied with long edges 8 gauge (min.) galvanized
wire spaced 4' o.c. max. necessary for snug contact 9. JOINT TREATMENT
perpendicular to framing, with board. Install joints no
framing spacing may be Secure Furring Channels to more than 30' apart and, if ProForm BRAND Sta-Smooth
up to 24" o.c. max. Drive main runners with 1 1/2" possible, to coincide with Joint Compound is required
fasteners to provide Furring Channel Clips, expansion joints in the roof for filling, taping and
uniform dimples not over alternating sides at each above. Control joints may finishing. Since Sta-Smooth
1/32" deep. intersection, or saddle tie be installed to intersect is a setting material, cut any
with double strands of 16 light fixture or other high points while still wet
3. WOOD FRAMING AND gauge galvanized tie wire.
FURRING openings where stresses are and wet sand as necessary.
Secure Steel Stud furring to usually concentrated. 10. PAINTING
Apply Soffit Board with the main runners with double
long edges at right angles to Wings of “L”, “U”, and “I” The surface of the Soffit Board
strand 16 gauge tie wire shaped areas should always
framing. Use Type “W” 16" o.c. max. For added should be painted with two
1 1/4" Drywall Screws be separated. coats of exterior paint as
rigidity, nest an 8" length
spaced 12" o.c. max. of track at each tie wire 6. INTERSECTION WITH soon as joint compound is
Electric screw gun should location. OTHER BUILDING dry, about one week after
be equipped with ELEMENTS joints are completed.
adjustable depth control Main runners and furring must
have a minimum clearance Allow a minimum 1/4" space
and a #2 Phillips bit. 1 1/2" between ceiling board and
galvanized box nails or between their ends and any
abutting structural element. any intersecting structure.
1 1/2" aluminum nails Do not caulk this space.
spaced 7" o.c. max., may A main runner must be
located within 6" of parallel Install suitable trim
be used if desired. moulding to conceal the
walls. The ends of these
Wood furring 1" x 4" nom. runners must be supported gap or use J Casing Bead
may be used for screw by hangers not more than and flexible sealant.
application of board where 6" from the ends. The
support member spacing 7. BOARD EDGE
closest edge of the furring PROTECTION
does not exceed 24" o.c. member must be no more
Furring 2" x 2" nom. must Install fascia so that its drip
than 2" from the parallel line is at least 1/4" below
be used for nail application wall. At any openings for
of board or when support the Ceiling Soffit Board
vents, light fixtures, etc., molding.
member spacing exceeds that interrupt runners or
24" o.c. but is not greater furring, reinforcement must
than 48" o.c. be provided to maintain

NATIONAL GYPSUM BOARD PRODUCTS 71


DETAILS

TO ROOF VENT

VENTILATION

J CASING BEAD

FLEXIBLE SEALANT

1/4"

1/4"
CONTROL JOINT
09250B
"A" VIEW "A"
VENTILATOR Scale: 1 1/2" = 1'-0"

EXTERIOR SOFFIT BOARD VENTILATION


09250A
Scale: 1 1/2" = 1'-0"

INSTALLATION SPECIFICATIONS

THE FOLLOWING PARAGRAPHS ARE FOR INSERTION INTO SECTIONS


HANGERS 48" O.C. MAX. OF GENERIC SPECIFICATIONS OR GENERIC/PROPRIETARY
SPECIFICATIONS COVERING GYPSUM BOARD PRODUCTS. THE
1 1/2" C.R. CHANNEL
NATIONAL GYPSUM PRODUCT NAME FOLLOWS THE GENERIC
DESCRIPTION IN PARENTHESES.
PART 2 PRODUCTS
2.01 MATERIALS
A. Exterior Gypsum Soffit Board: A gypsum core soffit
board with additives to enhance the sag resistance
FURRING of the core; surfaced with water repellent paper on
CHANNEL CLIP front, back, and long edges; and complying with
ASTM C 1396 (Gold Bond BRAND Exterior Soffit
Board).
1. Thickness: 1/2"
2. Width: 4'
FURRING
3. Length: 8' through 12'
CHANNEL
4. Edges: Beveled Tapered (Sta-Smooth Edge)
CEILING/SOFFIT BOARD
B. Fire-Resistant Exterior Gypsum Soffit Board: A
gypsum core soffit board with additives to enhance
the fire resistance of the core; surfaced with water
RECOMMENDATIONS repellent paper on front, back, and long edges; and
complying with ASTM C 1396, type X (Gold Bond
Installation of Gold Bond Exterior Soffit Board should be in BRAND Fire-Shield Exterior Soffit Board).
accordance with page 70 of the National Gypsum Company 1. Thickness: 5/8"
“Gypsum Construction Guide.” 2. Width: 4'
A qualified structural engineer should evaluate design, including 3. Length: 8' through 12'
uplift bracing. 4. Edges: Beveled Tapered (Sta-Smooth Edge)
See page 63, Environmental Conditions and Limitations.
PART 3 EXECUTION
3.01 INSTALLATION
A. General: In accordance with the manufacturer’s
recommendations, National Gypsum Company
“Gypsum Construction Guide.”

72 NATIONAL GYPSUM BOARD PRODUCTS


09 29 00/NGC
Gold Bond® BRAND 1" Fire-Shield® Shaftliner

DESCRIPTION RECOMMENDATIONS SPECIFICATIONS


Gold Bond® BRAND 1" Fire- Installation of 1" Fire-Shield THE FOLLOWING PARAGRAPHS ARE
Shield Shaftliner panels Shaftliner should be FOR INSERTION INTO SECTIONS
consist of a fire-resistant consistent with methods OF GENERIC SPECIFICATIONS OR
type X gypsum core described in specific GENERIC/PROPRIETARY
encased in a heavy application details for Cavity SPECIFICATIONS COVERING
moisture-resistant green, Shaftwall Systems or H-Stud GYPSUM BOARD PRODUCTS.
100% recycled paper on Area Separation Wall THE NATIONAL GYPSUM
the face and back sides. Systems or other fire-rated PRODUCT NAME FOLLOWS THE
The face paper is folded designs shown in National GENERIC DESCRIPTION IN
around the long edges to Gypsum Company “Gypsum PARENTHESES.
reinforce and protect the Construction Guide.”
core, and the ends are
square-cut and finished Exposure to excessive or PART 2 PRODUCTS
smooth. Long edges of continuous moisture or
standing water and extreme 2.01 MATERIALS
panels are beveled for ease
of installation. temperatures should be A. Fire-Resistant Gypsum
avoided. Shaftliner Board: A
1" Shaftliner panels are gypsum core shaftwall
designed to be used to board with additives to
construct lightweight fire To prevent weakening due to enhance fire resistance of
barriers for cavity shafts calcining, 1" Fire-Shield the core and surfaced with
and area separation walls Shaftliner panels, like any water resistant paper on
in multifamily housing. The gypsum board, should not front, back and long
panels are key components be exposed to temperatures edges; and complying with
in the Cavity Shaftwall over 125˚F (52˚C) for ASTM C 1396, type X
Systems and the I-Stud (Gold Bond BRAND Fire-
and H-Stud Area extended periods of time.
Shield Shaftliner).
Separation Wall Systems.
Not to be used in an unlined 1. Thickness: 1"
2. Width: 2'
air supply duct. 3. Length: 7' through 14'
TECHNICAL DATA 4. Edges: Beveled
Always store Shaftliner Gypsum
SURFACE BURNING Panels flat on a level surface

09 29 00
CHARACTERISTICS and support with properly
ASTM E84 placed risers. Care should be PART 3 EXECUTION
Flame Spread: 15 taken to avoid impact,
unwarranted flexing and 3.01 INSTALLATION
Smoke Developed: 0 subsequent damage to board A. General: In accordance
edges, ends and corners. with the manufacturer’s
WEIGHTS recommendations,
1" Shaftliner - 3.75 lbs/SF National Gypsum
Company “Gypsum
FIRE RESISTANCE RATINGS Construction Guide.”
Fire resistance ratings repre-
sent the results of tests on
assemblies made up of
materials authorized by
National Gypsum in specific
configurations. When
selecting construction
designs to meet certain fire
requirements, caution must
be used to ensure that each
component of the assembly
is the one specified in the
test.
Further, precaution should be
taken that assembly
procedures are in accor-
dance with those of the
tested assembly. (For copies
of specific tests, call 1-800-
NATIONAL.)

NATIONAL GYPSUM BOARD PRODUCTS 73


Gold Bond® BRAND 1" Fire-Shield® Shaftliner XP®
DESCRIPTION
Shaftliner XP™ Gypsum Panels When tested by an Care should be taken to
consist of a mold and fire- independent lab per ASTM avoid impact, unwarranted
resistant type X gypsum D3273 (Standard Test flexing and subsequent
core encased in a heavy Method for Resistance to damage to board edges,
moisture/mold/mildew- Growth of Mold on the ends and corners.
resistant, 100% recycled Surface of Interior Coatings Shaftliner XP may be
purple paper on the face in an Environmental substituted for National
and back sides. Shaftliner Chamber), Shaftliner XP Gypsum’s Gold Bold
XP was designed to achieved a score of 10, the BRAND Fire-Shield Shaftliner
provide extra protection best possible score for this in Cavity Shaftwall, Area
against mold and mildew. test. Separation Wall Systems
The face paper is folded The use of Shaftliner XP in and solid laminated
around the long edges to actual installations may not partitions.
reinforce and protect the produce the same results as
core, and the ends are were achieved in
square-cut and finished controlled, laboratory SPECIFICATIONS
smooth. Long edges of conditions. No material can
panels are beveled for be considered “mold proof,”
ease of installation. THE FOLLOWING PARAGRAPHS ARE
nor is it certain that any FOR INSERTION INTO SECTIONS
1" Shaftliner XP Panels are material will resist mold OF GENERIC SPECIFICATIONS OR
designed to be used to indefinitely. When used in GENERIC/PROPRIETARY
construct lightweight fire conjunction with good SPECIFICATIONS COVERING
barriers for cavity shaft design, handling and
walls and area separation GYPSUM BOARD PRODUCTS.
construction practices, THE NATIONAL GYPSUM
walls in multifamily Shaftliner XP can provide PRODUCT NAME FOLLOWS THE
housing. The panels are increased mold resistance GENERIC DESCRIPTION IN
key components in Cavity versus standard shaftliner PARENTHESES.
Shaftwall Systems and products. As with any
H-Stud Area Separation building material, avoiding
Wall Systems. water exposure during PART 2 PRODUCTS
handling, storage and
TECHNICAL DATA installation, and after 2.01 MATERIALS
installation is complete, is A. Fire and Mold-Resistant
SURFACE BURNING the best way to avoid the Gypsum Shaftliner Board:
CHARACTERISTICS formation of mold or A gypsum core shaftwall
mildew. board with additives to
ASTM E84 enhance fire resistance of
Flame Spread: 15 RECOMMENDATIONS the core and surfaced with
Smoke Developed: 0 a moisture/mold/mildew
Installation of 1" Shaftliner XP resistant paper on front,
WEIGHT Gypsum Panels should be back and long edges; and
1" XP - 3.75 lbs/SF consistent with methods complying with ASTM
described in specific C1396, Type X (Gold
FIRE RESISTANCE RATINGS application details for Bond BRAND Fire-Shield
Fire resistance ratings repre- Cavity Shaftwall Systems, or Shaftliner XP).
sent the results of tests on H-Stud Area Separation Wall 1. Thickness: 1"
assemblies made up of Systems, or other fire-rated 2. Width: 2'
materials authorized by designs shown in National 3. Length: 7' through 14'
National Gypsum in Gypsum Company “Gypsum 4. Edges: Beveled
specific configurations. Construction Guide.” 5. Mold and Mildew
When selecting contruc-
tion designs to meet certain Exposure to excessive or Resistance: Panel score
fire requirements, caution continuous moisture or of 10 when tested in
must be used to ensure that standing water and accordance with
each component of the extreme temperatures should ASTM D3273.
assembly is the one be avoided.
specified in the test.
Further, precaution should To prevent weakening due
be taken that assembly to calcining, 1" Fire-Shield PART 3 EXECUTION
procedures are in Shaftliner panels, like any 3.01 INSTALLATION
accordance with those of gypsum board, should not
the tested assembly. be exposed to temperatures A. General: In accordance
(For copies of specific tests, over 125˚F (52˚C) for with the manufacturer’s
call 1-800-NATIONAL) extended periods of time. recommendations,
National Gypsum
Not to be used in an unlined Company “Gypsum
MOLD AND MILDEW air supply duct.
RESISTANCE Construction Guide.”
Always store Shaftliner XP
Shaftliner XP was designed to Gypsum Panels flat on a
provide extra protection level surface, and support
against mold and mildew. with properly placed risers.
to Growth of Mold on the
Surface of Interior Coatings.

74 NATIONAL GYPSUM BOARD PRODUCTS


09 29 00/NGC
Gold Bond® BRAND High Flex® Gypsum Board
DESCRIPTION “Recommended spaced closer together than For convex surfaces, one end
Specifications for the required for typical flat wall of the gypsum board shall
Gold Bond BRAND High Flex Application of Gypsum and ceiling surfaces (see be attached to the framing
Gypsum Board consists of Board,” ASTM C 840, Table 1). 1/4" High Flex with nails or screws. The
a fire-resistive gypsum core “Standard Specifications for Gypsum Board should be gypsum board shall be
encased in heavy natural- Application and Finishing of held in firm contact with progressively pushed into
finish paper on the face Gypsum Board,” and the framing member while contact with the framing
side and strong liner paper GA214, “Recommended fasteners are being driven. members, working from
on the back side. The face Levels of Gypsum Board the fixed end to the free
paper is folded around the For concave surfaces, a stop
Finish.” shall be applied to one end end. The gypsum board
long edges to reinforce shall be held tightly against
and protect the core and Exposure to extreme of the curve to restrain one
temperatures should be end or edge of the board each framing member
the ends are square-cut while fasteners are being
and finished smooth. Long avoided. 1/4" High Flex during installation. Pressure
Gypsum Board is not shall be applied to the driven.
edges of boards are slightly
tapered, allowing joints to recommended where it will unrestrained end or edge of Fasteners should be set with
be reinforced and be exposed to temperatures the gypsum board forcing the heads slightly below
concealed with ProForm exceeding 125˚F. the field of the gypsum the surface of the gypsum
Joint Tape and Joint Installing 1/4" High Flex board into firm contact board in a dimple formed
Treatment Compounds. Gypsum Board over an with the framing. Gypsum by the hammer or power
insulating blanket, installed board shall be fastened by screwdriver. Care should
1/4" High Flex Gypsum Board working from the be taken to avoid breaking
is specifically designed for continuously across the face
of the framing members, is “stopped” end or edge. The the face paper of the
radius construction such as gypsum board shall be held gypsum board. Improperly
curved walls, archways not recommended. Blankets
should be recessed and tightly against the framing driven nails or screws
and stairways. It can be while fasteners are being should be removed.
used for both concave and flanges attached to the sides
of the studs or joists. driven.
convex surfaces. 1/4" High
Flex is typically applied in For best painting results, all Table 1
double layers. surfaces, including joint MINIMUM BENDING RADII FOR 1/4" HIGH FLEX GYPSUM BOARD
1/4" High Flex Gypsum Board compound, should be
is a lightweight, cost- clean, dust-free and not Lengthwise Widthwise
efficient material that glossy. To improve fastener Bend Max. Stud Bend Max. Stud
readily accepts a wide and joint concealment, a Application Radii Spacing Radii Spacing
range of decorative coat of a quality latex
finishes. primer is recommended to Inside (Concave) Dry 32" 9" o.c. 20" 9" o.c.

09 29 00
equalize the absorption
1/4" High Flex Gypsum Board between surface paper and Outside (Convex) Dry 30" 9" o.c. 15" 8" o.c.
is easily cut for quick joint compound. Inside (Concave) Wet 20" 9" o.c. 10" 6" o.c.
installation, permitting
painting or other 1/4" High Flex Gypsum Board Outside (Convex) Wet 14" 6" o.c. 7" 5" o.c.
decoration and the should be applied first to
installation of metal or ceiling at right angles to Lengthwise denotes long edges perpendicular to the framing
wood trim almost framing members, then to members. Widthwise denotes long edges parallel to the framing
immediately. walls. Boards of maximum members. The values listed in Table 1 were achieved at 65° F and
practical length should be 45% relative humidity. Lower temperatures and lower humidity
The gypsum core is non- used so that an absolute will decrease the flexibility.
combustible. minimum number of end Wetting the board is only required on extremely tight radii, or when
With joints reinforced by joints occur. Board edges temperature and humidity conditions are lower than 65° F and
ProForm BRAND Joint should be brought into 45% relative humidity. When wetting the board, apply 10-15
Compounds, Gold Bond contact with each other but ounces of clean water per side with a paint roller or sprayer.
Gypsum Board forms walls should not be forced into Allow to soak 10-15 minutes before bending.
and ceilings exceptionally place.
resistant to cracks caused 1/4" High Flex Gypsum Board
by structural and thermal is significantly more flexible
changes. in the vertical direction
Expansion and contraction (long edges parallel to the
under normal atmospheric framing) than in the
changes is negligible. horizontal direction. (See
Table 1.)
TECHNICAL DATA Gypsum board joints at
SURFACE BURNING openings should be located
CHARACTERISTICS so that no end joint will
align with edges of openings
ASTM E 84 unless control joints will be
Flame spread: 15 installed at these points. End
Smoke developed: 0
joints should be staggered,
WEIGHT and joints on opposite sides
1/4" High Flex - .95 lbs/SF of a partition should not
occur on the same stud.
RECOMMENDATIONS 1/4" High Flex Gypsum Board
is typically installed in
Installation of Gold Bond BRAND double layer construction.
gypsum board should be To prevent flat spots,
consistent with methods framing members should be
described in GA216
NATIONAL GYPSUM BOARD PRODUCTS 75
SPECIFICATIONS
THE FOLLOWING PARAGRAPHS ARE
FOR INSERTION INTO SECTIONS
OF GENERIC SPECIFICATIONS OR
GENERIC/PROPRIETARY
SPECIFICATIONS COVERING
GYPSUM BOARD PRODUCTS.
THE NATIONAL GYPSUM
PRODUCT NAME FOLLOWS THE
GENERIC DESCRIPTION IN
PARENTHESES.
PART 2 PRODUCTS
2.01 MATERIALS
A. Flexible Gypsum Board:
A gypsum core wall
board with additives to
enhance flexibility
surfaced with paper on
front, back and long
edges and complying
with ASTM C 1396.
(High Flex BRAND
Gypsum Board).
1. Thickness: 1/4"
2. Width: 4'
3. Length: 8' through 12'
4. Edges: Slightly tapered

PART 3 EXECUTION
3.01 INSTALLATION
A. General: In accordance
with the manufacturer’s
recommendations,
National Gypsum
Company “Gypsum
Construction Guide.”

76 NATIONAL GYPSUM BOARD PRODUCTS


09 29 00/NGC
Gold Bond® BRAND High Strength Ceiling Board
DESCRIPTION RECOMMENDATIONS
Gold Bond BRAND High Installation of Gold Bond BRAND
Strength Ceiling Board is a Gypsum Board should be
specialty gypsum board with consistent with methods
increased uniformity and described in, GA216,
integrity of its gypsum core, “Recommended
making its sag resistance Specifications for the
equivalent to 5/8" type X Application of Gypsum
gypsum board. Board,” ASTM C 840,
1/2" High Strength Ceiling “Standard Specification for
Board is specifically Application and Finishing of
designed for ceilings where Gypsum Board.”
framing members are spaced Not recommended in areas of
up to 24" o.c. and a water- continuous high humidity
based texture will be used. such as saunas, steam
1/2" High Strength Ceiling rooms, gang shower rooms,
Board is available and indoor pool enclosures.
nationwide as a stocked Prime with sealing latex
item at all National Gypsum primer and allow to dry
plants. thoroughly. Apply insulation
and polyethylene vapor
Excellent working character- barrier (if used) before
istics, improved score and installing ceiling board.
snap properties reduce the Insulation not to exceed 2.2
need for rasping. lbs./square foot (10.7 kg/m2).
Excellent sag resistance. Adequate ventilation
Witnessed test results show required.
overall sag on tested 1/2" High Strength Ceiling
assembly to be equivalent to Board must be stored off the
5/8" type X gypsum board. ground and under cover.
Test report available upon Sufficient risers must be
request. used to ensure support for
Eliminates need for two board the entire length of the

09 29 00
sizes on the job. Scrap from gypsum board to prevent
ceiling is reduced since this sagging.
material also can be used on Not to be exposed to Gypsum Association GA-214, SS-L-30D type III,
the walls. temperatures exceeding Recommended Specification Grade R, Class 1. (Gold
125˚F (52˚C) for extended for Levels of Gypsum Board Bond BRAND High Strength
TECHNICAL DATA periods of time. Finish, should be referred to Ceiling Board).
Installing gypsum board over in order to determine the 1. Thickness: 1/2"
In independent tests, High an insulating blanket, level of finishing needed to
ensure a surface properly 2. Width: 4'
Strength Ceiling Board installed continuously across
exhibited an average sag of the face of the framing prepared to accept the 3. Length: 6' through 16'
only .033 (approx. 1/32") members, is not desired decoration. 4. Edge: Tapered
on joists spaced 24" on recommended. Blankets
center with a spray texture should be recessed and SPECIFICATIONS PART 3 EXECUTION
applied. This test was flanges attached to the sides
conducted over one month of the studs or joists. 3.01 INSTALLATION
THE FOLLOWING PARAGRAPHS ARE
at temperatures between DECORATION FOR INSERTION INTO SECTIONS A. General: In accordance
66˚-79˚F (19˚C-26˚C) and OF GENERIC SPECIFICATIONS OR with the manufacturer’s
relative humidities between For best painting results, all recommendations,
surfaces, including joint GENERIC/PROPRIETARY
30%-60%. (Reference: PSI SPECIFICATIONS COVERING National Gypsum
report #722600-R71 March compound, should be clean, Company “Gypsum
dust-free and not glossy. To GYPSUM BOARD PRODUCTS.
25, 1991) THE NATIONAL GYPSUM Construction Guide.”
improve fastener and joint
Under the strict ASTM C-473 concealment, a coat of a PRODUCT NAME FOLLOWS THE
Physical Testing for quality primer is GENERIC DESCRIPTION IN
Humidified Deflection, recommended to equalize PARENTHESES.
Gold Bond BRAND 1/2" the porosities between
High Strength Ceiling surface paper and joint PART 2 PRODUCTS
Board exhibited sag- compound. Drywall primer
resistant properties equal to 2.01 MATERIALS
is a product specially
5/8" type X gypsum board. formulated for this purpose. A. Gypsum Ceiling Board:
A gypsum core ceiling
The selection of a paint to give board with additives to
SURFACE BURNING the specified or desired
CHARACTERISTICS enhance the sag
finished characteristics is the resistance of the core
ASTM E 84 responsibility of the and surfaced with paper
Flame spread index: 15 architect or contractor. on front, back, and long
Smoke developed: 0 Gypsum board that is to have a edges, complying with
wallcovering applied to it ASTM C 1396 and
WEIGHT should be prepared and Federal specification
1/2" Hi Strength - 1.8 lbs/SF primed as described for
painting.
NATIONAL GYPSUM BOARD PRODUCTS 77
Gold Bond® BRAND Hi-Abuse XP® Gypsum Board
DESCRIPTION

Gold Bond® BRAND Hi-Abuse XP® Gypsum Board panels consist


of a mold and fire resistant type x gypsum core encased in
heavy mooth abrasion resistant, moisture, mold/mildew-
resistant, 100% recycled purple paper on the face side and
heavy mold/mildew-resistant liner paper on the back side. Hi-
Abuse XP Gypsum Board is designed to provide extra
protection against mold and mildew compared to standard
gypsum board products. The panels feature a specifically
formulated core to provide greater resistance to surface
indentation and impact than fiber-reinforced gypsum panels.
Long edges of the panels are tapered. Tapered edges allow
joints to be treated in the normal manner. For optimum mold
and mildew resistance, National Gypsum recommends
ProForm BRAND XP Ready Mix, or Sta-Smooth/Sta-Smooth Lite
setting compounds.

TECHNICAL DATA

Surface Abrasion Test


ASTM – D 4977 (Modified)
5/8" 5/8" Gypsum Board
Hi-Abuse XP Type X
Mean Depth Abrasion 0.009 in. 0.576 in. Walls and ceilings in school corridors and cafeterias are ideal
Performance Classification Level 3 Does Not Qualify applications for Gold Bond® BRAND Hi-Abuse XP® Gypsum Board.
Procedure Summary – A sample is laid flat and subjected to 50 abrasion cycles of a wire brush
with additional 25 lbs. weight. The depth of abrasion in three consecutive samples is measured and
reported as a mean depth of abrasion in inches. This test measures the ability of a panel to withstand
surface scuffs and abrasions.

Surface Abrasion Test


ASTM-D 4977 (Modified)
Depth of Abrastion (in.)

5/8" Hi-Abuse XP 5/8" Gypsum Board, Type X

Surface Indentation Resistance


Single Drop Soft Body Impact Test Modified ASTM – D 5420 (Gardner Impact)
Modified ASTM – E 695 (Modified)
5/8" 5/8" Gypsum Board
5/8" 5/8" Gypsum Board
Hi-Abuse XP Type X Hi-Abuse XP Type X
Mean Depth of indentation 0.132 in. 0.230 in.
Ft.-Lbs. required to penetrate 210 120
Performance Classification Level 1 Does Not Qualify
Performance Classification Level 2 Level 1
Procedure Summary – A sample is laid flat and impacted by a 5/8" hemispherical rod raised to
Procedure Summary – This test is conducted with a leather bag loaded with steel pellets to a height that provides 72 in.-lbs. of impact energy. The depth of the indentation is measured from
weight of 60 lbs. The bag is suspended by a rope and dropped at an angular distance until three board samples and reported as a mean depth of indentation in inches. This test measures the
specimen is impacted. ability for a panel to resist dents.

Single Drop Soft Body Test Surface Indentation Test


ASTM -E 695 (Modified) ASTM-D 5420
300 0.400
Depth of Indentation (in.)

0.350
250
Impact Force in ft.lbs.

0.300
210
200 0.230
0.250

150 0.200
120
0.150 0.132
100
0.100
50
0.050

0 0.000
5/8" Hi-Abuse XP 5/8" Gypsum Board, Type X 5/8" Hi-Abuse XP 5/8" Gypsum Board, Type X

78 NATIONAL GYPSUM BOARD PRODUCTS


SURFACE BURNING RECOMMENDATIONS 09 29 00/NGC
CHARACTERISTICS
ASTM E 84 Installation of Hi-Abuse XP
Flame spread (Face): 15 Gypsum Board should be
Smoke developed: 0 consistent with methods Minimum bending radii for
described in the standards 5/8" Hi-Abuse XP Gypsum
WEIGHT references noted. For best Board is 20'-0" applied
1/2" Hi-Abuse XP - 2.4 lbs/SF performance, use vertical lengthwise perpendicular to
5/8" Type X Hi-Abuse - 2.8 lbs/SF application. framing spaced not greater
than 12" on center.
GridMarX®
FIRE RESISTANCE RATINGS Lightweight, cost-efficient
Hi-Abuse® BRAND XP Gypsum
Fire resistance ratings represent Board comes standard with material that readily accepts
the results of tests on assem- GridMarX® guide marks a wide range of decorative
blies made up of specific printed on the paper surface. finishes.
materials in a specific con- These guide marks align with The gypsum core will not
figuration. When selecting standard building dimen- support combustion or
construction designs to meet sions and help to quickly transmit temperatures great-
certain fire resistance re- identify fastener lines for stud
quirements, caution must be ly in excess of 212˚F (100˚C)
and joist framing. Using until completely calcined, a
used to ensure that each GridMarX, accurate cuts can
component of the assembly be made without having to slow process.
is the one specified in the draw lines. The use of Expansion and contraction
test. Further, precaution GridMarX also provides under normal atmospheric
should be taken that assem- quick identification and changes are negligible.
bly procedures are in accor- uniform nail/screw patterns.
dance with those of the Hi-Abuse XP 5/8" Fire-Shield
tested assembly. (For copies GridMarX guide marks run the panels may be used where
of specific tests, call machine direction of the Type X gypsum panels are
1-800-NATIONAL.) board at five points in 4" specified in fire-rated wall
increments. Marks run along and floor-ceiling assemblies
the edge in both tapers and (i.e. UL, U300, U400, V400
MOLD AND MILDEW and at 16", 24" and 32" in
RESISTANCE the field of the board. The and L500 series.)
Hi-Abuse® BRAND XP Gypsum marks cover easily with no Exposure to excessive or
Board has been designed to bleed-through using stand- continuous moisture and
provide extra protection ard products. extreme temperatures should
against mold and mildew Vertical Application - In a be avoided. Hi-Abuse XP
compared to standard vertical application, Gypsum Board is not recom-
gypsum board products. mended where it will be
When tested by an GridMarX serves as a

09 29 00
independent lab per ASTM guide mark to help identify exposed to temperatures
D3273 (“Standard Test the exact location of framing exceeding 125˚F (52˚C) for
Method for Resistance to members behind the gypsum extended periods of time.
Growth of Mold On the board, eliminating the need
Surface of Interior Coatings in for field-applied vertical Hi-Abuse XP Gypsum Board
an Environmental Chamber”), lines. shall not be used where
Hi-Abuse XP Gypsum Board there will be direct exposure
achieved a score of 10, the Horizontal Application - In a to water or continuous high
best possible score for this horizontal application, humidity conditions, such as
test. GridMarX serves as a found in tub and shower
reference mark to help enclosures, saunas, steam
The use of Hi-Abuse XP identify the location of
Gypsum Board in actual framing members behind the rooms and gang showers. If
installations may not the area is to be exposed to
produce the same results as gypsum board. (If framing
member is located 2" to the water or continuous high
were achieved in controlled, humidity, National
laboratory conditions. No right of the GridMarX at the
material can be considered top edge of the board, it will Gypsum’s PermaBase®
“mold proof,” nor is it be located 2" to the right BRAND Cement Board should
certain any material will down the face of the board.) be used.
resist mold or mildew Provides greater resistance Hi-Abuse XP Gypsum Board
indefinitely. When used in to surface abuse, indentation must be stored off the
conjunction with good
design, handling and and impact than fiber-rein- ground and under cover.
construction practices, Hi- forced gypsum panels. Sufficient risers must
Abuse XP Gypsum Board Hi-Abuse XP smooth face be used to ensure support
can provide increased mold paper is highly resistant to for the entire length of the
resistance versus standard scuffing when sanding gypsum board to prevent
gypsum board products. As gypsum board joints and sagging.
with any building material, fasteners providing a
avoiding water exposure superior surface for deco-
during handling, storage and
installation, and after ration.
installation is complete, is Hi-Abuse XP Gypsum Board is
the best way to avoid the easily scored and snapped
formation of mold or for quick installation. Open-
mildew. ings and outlet boxes are
cut out in same manner as
regular gypsum board.

NATIONAL GYPSUM BOARD PRODUCTS 79


Hi-Abuse XP Gypsum Board SPECIFICATIONS
must be kept dry to mini-
mize the potential for mold THE FOLLOWING PARAGRAPHS ARE
growth. Adequate care FOR INSERTIONS INTO SECTIONS
should be taken while trans- OF GENERIC SPECIFICATIONS OR
porting, storing, applying GENERIC/PROPRIETARY SPECIFI-
and maintaining gypsum CATIONS COVERING GYPSUM
board. For additional BOARD PRODUCTS. THE
information, refer to the NATIONAL GYPSUM PRODUCT
Gypsum Association pub- NAME FOLLOWS THE GENERIC
lication, “Guidelines for DESCRIPTION IN PARENTHESES.
the Prevention of Mold
Growth on Gypsum Board”
(GA-238-03), which PART 2 PRODUCTS
is available at www. 2.01 MATERIALS
gypsum.org under the A.Fire, Abuse and Mold
“Download Free Gypsum Resistant Gypsum Board: A
Association Publications” gypsum core wall panel
section. with additives to enhance
fire resistance, surface
DECORATION indentation resistance and
For best painting results, all sur- impact resistance of the
faces, including joint com- core and surfaced with abra-
pound, should be clean, sion, moisture/mold/mildew
dust-free and not glossy. To resistant paper on front,
improve fastener and joint back and long edges; and
concealment, a coat of a complying with ASTM
quality drywall primer is re- C 1396 Type X (Hi-Abuse
BRAND XP Fire-Shield
commended to equalize the
porosities between surface Gypsum Board).
and joint compound. 1. Thickness: 5/8"
2. Width: 4'
The selection of a paint to give 3. Length: 8' through 12'
the specified or desired 4. Edges: Tapered
finished characteristics is the 5. Surface Abrasion Resis-
responsibility of the architect tance: Not greater than
or contractor. 0.009 depth when tested
Hi-Abuse XP Gypsum Board at 50 cycles in accord-
that is to have a wall ance with ASTM D 4977,
covering applied to it should modified.
be prepared and primed as 6. Indentation Resistance:
described for painting. Not greater than 0.132"
depth when tested at an
Gypsum Association GA-214, impact load of 72 in.-lbs.
“Recommended Specifica- In accordance with ASTM
tions for Levels of Gypsum D 5420.
Board Finish,” should be re- 7. Impact/Penetration Resist-
ferred to in order to deter- ance: Not less than 210
mine the level of finishing ft.-lbs. required to penetrate
needed to ensure a surface when tested in accordance
properly prepared to accept with ASTM E 695,
the desired decoration. modified.
8. Mold/Mildew Resistance:
Panel score of 10 when
tested in accordance with
ASTM D 3273.

PART 3 EXECUTION
3.01 INSTALLATION
A. General: In accordance
with the manufacturer’s
recommendations,
National Gypsum Company
“Gypsum Construction
Guide.”

80 NATIONAL GYPSUM BOARD PRODUCTS


Gold Bond® BRAND Hi-Impact XP® Gypsum Board 09 29 00/NGC

DESCRIPTION
Gold Bond® BRAND Hi-Impact XP® Gypsum Board panels consist
of a mold, moisture and fire resistant type X gypsum core
encased in heavy, smooth, abrasion-resistant, mold/mildew-
resistant, 100% recycled purple paper on the face side and
heavy mold/mildew resistant liner paper on the back side. A
fiberglass mesh is embedded in the core, close to the back of
the board to provide additional impact/penetration resistance.
Hi-Impact XP Gypsum Board features a specially formulated
core to provide fire resistance ratings when used in tested
systems in addition to providing extra protection against mold
and mildew compared to standard gypsum board products.
Long edges of panels are tapered. Tapered edges allow joints
to be treated in the normal manner. For optimum mold and
mildew resistance, National Gypsum recommends ProForm
BRAND XP Ready Mix, or Sta-Smooth/Sta-Smooth Lite
compounds.

TECHNICAL DATA
Surface Abrasion
ASTM – D 4977 (Modified)
5/8" Hi-Impact XP 5/8" Gypsum Board
with Fiberglass Scrim Type X
Mean Depth Abrasion 0.009 in. 0.576 in.
Performance Classification Level 3 Does Not Qualify Prison walls have to be strong. And, with GOLD BOND® BRAND
Procedure Summary – A sample is laid flat and subjected to 50 abrasion cycles of a wire brush
Hi-Impact XP® Gypsum Board, strong walls can be installed as
with additional 25 lbs. weight. The depth of abrasion in three consecutive samples is measured and easily as regular gypsum board.
reported as a mean depth of abrasion in inches. This test measures the ability of a panel to withstand
surface scuffs and abrasions.

Surface Abrasion
ASTM – D 4977(Modified)
Depth of Abrasion (in.)

09 29 00
5/8" Hi-Impact XP 5/8" Gypsum Board, Type X
with Fiberglass Scrim

Surface Indentation Test


Single Drop Soft Body Impact Test ASTM – D 5420 (Gardner Impact)
ASTM – E 695 (Modified)
5/8" Hi-Impact XP 5/8" Gypsum Board
5/8" Hi-Impact 5/8" Gypsum Board with Fiberglass Scrim Type X
with Fiberglass Scrim Type X
Mean Depth of indentation 0.114 in. 0.230 in.
Ft.-Lbs. required to penetrate >540* 120
Performance Classification Level 1 Does Not Qualify
Performance Classification Level 3 Level 1
Procedure Summary – A sample is laid flat and impacted by a 5/8" hemispherical rod raised to
Procedure Summary – This test is conducted with a leather bag loaded with steel pellets to a height that provides 72 in.-lbs. of impact energy. The depth of the indentation is measured from three
weight of 120 lbs. The bag is suspended by a rope and dropped at an angular distance until specimen
is impacted.* In the test the framing collapsed without failure to the Hi-Impact panels. board samples and reported as a mean depth of indentation in inches. This test measures the ability
for a panel to resist dents.

Single Drop Soft Body Test Surface Indentation Test


ASTM-E 695 (Modified) ASTM – D 5420
600 0.400
> 540 *
Depth of Indentation (in.)
Impact Force in ft.-lbs.

500 0.350
0.300
400
0.250 0.230
300 0.200

200 0.150
0.114
120
0.100
100
0.050
0 0.000
5/8" Hi-Impact XP 5/8" Gypsum Board, Type X 5/8" Hi-Impact XP 5/8" Gypsum Board, Type X
with Fiberglass Scrim with Fiberglass Scrim

NATIONAL GYPSUM BOARD PRODUCTS 81


Hard Body Impact - ASTM C 1629 specified in the test. Further at 16", 24" and 32" in the
precaution should be field of the board. The marks
5/8" Hi-Impact XP 5/8" Gypsum Board taken specified in the test. cover easily with no bleed-
with Fiberglass Scrim Type X Further precaution should be through using standard
Ft.-lbs. to penetrate into cavity >160 35 taken that assembly products.
Performance Classification Level 3 Does Not Qualify procedures are in accordance
with those of the tested Vertical Application - In a
Procedure Summary – A 2' x 2' board sample is mounted to a 3-5/8", 20 gauge steel frame and
assembly. (For copies of vertical application,
runners using drywall screws. The sample is impacted with a ram mounted on a pendulum which is GridMarX serves as a guide
faced with a 2-3/4" steel cylinder dropped from a fixed height. Weights are added to increase the specific tests, call 1-800-
impacting energy. The maximum impact force that the sample can withstand without penetration NATIONAL.) mark to help identify the
through the sample and into the stud cavity is reported in foot-pounds. This test measures the ability exact location of framing
to withstand the impact of a hard object such as a hammer or heel of a boot. FIRE ENDURANCE members behind the gypsum
1-Hour Rating: Hi-Impact XP board, eliminating the need
Hard Body Impact for field-applied vertical
180 Gypsum Board screw
>160 attached vertically to both lines.
Impact Force in ft.-lbs.

160
sides of 20 gauge 3-5/8" studs Horizontal Application - In a
140
spaced16" o.c. with 1-1/4" horizontal application,
120 long, type S screws spaced 8" GridMarX serves as a
100 o.c. along edges and 12" o.c. reference mark to help
80 in the field of the board. identify the location of
60 Gypsum board joints framing members behind the
40
staggered. UL U465 gypsum board. (If framing
35
2-Hour Rating: Constructed member is located 2" to the
20
with a base layer of right of the GridMarX at the
0 top edge of the board, it will
5/8" Hi-Impact XP 5/8" Gypsum Board, Type X Hi-Impact XP Gypsum Board
with Fiberglass Scrim with an additional layer be located 2" to the right
of 5/8" Fire-Shield Gypsum down the face of the board.)
Water Absorption Board Type X screw attach- Hi-Impact XP Gypsum Board can
ASTM C 473 ed vertically to both sides of be used as a tile backer board
5/8" High-Impact XP 5/8" Gypsum Board 20 gauge 3-5/8" studs in dry areas and areas with
with Fiberglass Scrim Type X spaced 16" o.c. with joints limited water exposures such
Percentage of Weight Gained 4% 47% staggered between face and as toilet/sink areas and areas
Procedure Summary – Three dry board samples were cut and weighed. Each sample was then base layer. Base layer above tile in tubs and showers
submerged in a 3-inch water bath for two hours. The samples were removed, wiped and weighed attached with 1-1/4" long
again. The weight gained is calculated and reported as a percentage. The higher the percentage the type S screws spaced 8" Hi-Impact XP Gypsum Board
more water the panel absorbed.
o.c. along edges and 12" should not be used as a backer
o.c. in the field of the board. board directly behind tile in
Water Absorption tub and shower areas.
ASTM C 473 Outer layer attached with
50%
Less is Better 2-1/2" long type S screws Hi-Impact XP should not be used
45% 47%
spaced 8" o.c. in the field in areas subject to constant
and along vertical edges and and/or excessive moisture and
% of Weight Gain

40%
to the floor and ceiling high humidity such as gang
35%
runners. UL U411 showers, saunas, steam rooms
30%
For additional UL Design and swimming pool enclo-
25%
Listings, please reference sures. PermaBase BRAND
20% cement board is recommended
the UL Directory.
15% for these areas.
10%
5% 4% RECOMMENDATIONS Hi-Impact XP Gypsum Board can
0
be used on the interior side
5/8" Hi-Impact XP 5/8" Gypsum Board, Type X Installation of 5/8" Hi-Impact of exterior walls in hot, hu-
with Fiberglass Scrim XP Fire-Shield Type X mid climates such as the
Gypsum Board should be Southern Atlantic and Gulf
consistent with methods Coast areas.
SURFACE BURNING laboratory conditions. No described in Applicable
CHARACTERISTICS material can be considered Standards with one Hi-Impact XP Gypsum Board
“mold proof,” nor is it certain exception - for best results, features a type X core to
ASTM E 84 provide additional fire
(Face) any material will resist mold cutting and scoring of
Flame spread: 15 or mildew indefinitely. When Hi-Impact XP should be from resistance when used in
Smoke developed: 0 used in conjunction with tested systems.
good design, handling and the back side of the board.
WEIGHT construction practices, Hi- Hi-Impact XP Gypsum Board is
GridMarX® easily cut for quick installa-
5/8" Hi-Impact XP - 2.8 lbs/SF Impact XP Gypsum Board tion, permitting painting or
can provide increased mold Hi-Impact XP Gypsum Board
resistance versus standard comes standard with other decoration and the
MOLD AND MILDEW installation of most metal
RESISTANCE gypsum board products. As GridMarX® guide marks
with any building material, printed on the paper surface. or wood trim almost
Hi-Impact® XP Gypsum Board has avoiding water exposure These guide marks align with immediately.
been designed to provide extra during handling, storage and standard building dimensions Minimum bending radii for 5/8"
protection against mold and installation, and after and help to quickly identify Hi-Impact XP Gypsum Board is
mildew compared to standard installation is complete, is the fastener lines for stud and 20'-0" applied lengthwise
gypsum board products. When best way to avoid the joist framing. Using GridMarX, perpendicular to framing
tested by an independent lab formation of mold or mildew. spaced not greater than 12"
per ASTM D3273 (“Standard accurate cuts can be made
FIRE RESISTANCE RATINGS without having to draw lines. on center.
Test Method for Resistance to
Growth of Mold On the Fire resistance ratings represent The use of GridMarX also The gypsum core will not
Surface of Interior Coatings in the results of tests on assem- provides quick identification support combustion or trans-
an Environmental Chamber”), blies made up of specific and uniform nail/screw mit temperatures greatly in
Hi-Impact XP Gypsum Board configuration. When patterns. excess of 212˚F (100˚C)
achieved a score of 10, the best selecting construction GridMarX guide marks run the until completely calcined,
possible score for this test. designs to meet certain fire machine direction of the a slow process.
The use of Hi-Impact XP resistance requirements, board at five points in 4"
Gypsum Board in actual caution must be used to increments. Marks run along
installations may not ensure that each component the edge in both tapers and
produce the same results as of the assembly is the one at 16", 24" and 32" in the
were achieved in controlled, field of the board. The marks
82 NATIONAL GYPSUM BOARD PRODUCTS
Exposure to excessive or The selection of a paint to give 09 29 00/NGC
continuous moisture and the specified or desired
extreme temperatures should finished characteristics is the
be avoided. responsibility of the architect 5. Surface Abrasion Resis-
Listed impact/penetration or contractor. tance: Not greater than
ratings apply to walls con- Hi-Impact XP Gypsum Board 0.009" depth when
structed with Hi-Impact XP that is to have a wall tested at 50 cycles in
Gypsum Board applied with covering applied to it should accordance with ASTM
long edges parallel to and be prepared and primed as D 4977, Modified.
centered over minimum 20 described for painting. 6. Indentation Resistance:
gauge framing members Not greater than 0.114"
spaced a maximum of 16" Gypsum Association GA-214, depth when tested at
o.c. “Recommended Specifica- an impact load of 72
tion for Levels of Gypsum in.-lbs. in accordance
Hi-Impact XP Gypsum Board Board Finish,” should be
must be stored off the with ASTM D 5420.
referred to in order to deter- 7. Impact/Penetration
ground and under cover. mine the level of finishing
Sufficient risers must be Resistance: Not less than
needed to ensure a surface 720 ft.-lbs. required to
used to ensure support for properly prepared to accept
the entire length of the penetrate when tested in
the desired decoration. accordance with ASTM
gypsum board to prevent
sagging. E 695, Modified.
SPECIFICATIONS 8. Mold/Mildew
Hi-Impact XP Gypsum Board Resistance: Panel score
must be kept dry to mini- THE FOLLOWING PARAGRAPHS ARE of 10 when tested in
mize the potential for mold FOR INSERTION INTO SECTIONS accordance with ASTM
growth. Adequate care OF GENERIC SPECIFICATIONS FOR D 3273.
should be taken while trans- GENERIC/PROPRIETARY SPECIFI-
porting, storing, applying CATIONS COVERING GYPSUM
and maintaining gypsum PART 3 EXECUTION
BOARD PRODUCTS. THE
board. For additional NATIONAL GYPSUM PRODUCT 3.01 INSTALLATION
information, refer to the NAME FOLLOWS THE GENERIC
Gypsum Association pub- A. General: In accordance
DESCRIPTION IN PARENTHESES. with the manufacturer’s
lication, “Guidelines for
the Prevention of Mold recommendations,
Growth on Gypsum Board” PART 2 PRODUCTS National Gypsum
(GA-238-03), which Company “Gypsum
2.01 MATERIALS Construction Guide.”
is available at www.
gypsum.org under the A. Fire, Impact/Penetration
and Mold-Resistant Gypsum

09 29 00
“Download Free Gypsum
Association Publications” Board: A gypsum core wall
section. panel with additives to
enhance the fire and
DECORATION resistance, and mold/mildew
resistance of the core; surfaced
For best painting results, all with abrasion/moisture/mold/
surfaces, including joint mildew resistant paper on the
compound, should be clean, front, back and long edges
dust-free and not glossy. To with a fiberglass mesh
improve fastener and joint embedded in the board to
concealment, a coat of high enhance impact/penetration
quality latex primer is resistance and complying with
recommended to equalize ASTM C 1396, Type X.
the absorption between sur- (Gold Bond BRAND Hi-Impact
face paper and joint com- XP Fire-Shield Gypsum Board).
pound. Drywall primer is
specially formulated for this 1. Thickness: 5/8"
purpose. 2. Width: 4'
3. Length: 8' through 12'
4. Edges: Tapered

NATIONAL GYPSUM BOARD PRODUCTS 83


GOLD BOND® BRAND SoundBreak™ Gypsum Board

DESCRIPTION SoundBreak Gypsum Board


can be cut by scoring
Gold Bond® BRAND deeply from both sides of
SoundBreak™ Gypsum the board before snapping,
Board is an acoustically or with the use of a hand
enhanced gypsum board or reciprocating saw.
used in the construction of
high rated STC wall TECHNICAL DATA
assemblies. This 5/8" thick
gypsum board consists of a
layer of viscoelastic SURFACE BURNING
damping polymer CHARACTERISTICS
sandwiched between two ASTM E 84
pieces of enhanced high Flame spread: 15
density mold resistant Smoke developed: 0
gypsum board, providing
constrained layer damping. WEIGHT
For speed of installations, SoundBreak - 2.7 lbs/SF
GridMarX® guide marks are
printed on the paper FIRE RESISTANCE RATINGS
surface. As an option, SoundBreak
Long edges of the panels are Gypsum Board may be
tapered. Tapered edges used as an additional layer
allow joints to be on one or both sides of fire-
reinforced with ProForm® rated wall assemblies (i.e.,
BRAND Joint Tape and U300, W300, U400, W400
concealed with ProForm® and V400 series designs).
BRAND Ready Mix, Easy SoundBreak Gypsum Board
Finish® BRAND Ready Mix or cannot be used as a
ProForm® BRAND Sta- substitute for 5/8" Type X
Smooth® Joint Compounds. gypsum board in a fire-
For optimum mold and related assembly. Mold and Moisture
mildew performance, Resistant Face
SoundBreak Gypsum Board Paper
National Gypsum shall be attached in
recommends ProForm® accordance with
BRAND XP® Ready Mix. manufacturer’s
Use of SoundBreak Gypsum recommendations. When Viscoelastic
Polymer
Board results in wall SoundBreak Gypsum Board
partitions with high rated is installed between the
STC values that are thinner framing and the UL/ULC
than traditionally built high Classified gypsum board,
rated STC wall partitions, the UL/ULC Classified
providing increased usable gypsum board layer(s)
floor space. required for the design
Mold and
Superior sound damping, cost- is/are to be installed as Moisture Resistant
efficient material that is indicated in the design as Enhanced Back Paper
easily finished and to fastener type and High Density
spacing, except that the Mold Resistant Core
decorated in the same
manner as regular gypsum required fastener length
board. shall be increased by a
minimum of 5/8" (16 mm). For additional information go to
All SoundBreak Gypsum
Board designs were tested For U300, W300, U400, www.SoundBreak.info.
by an independent third- W400 and V400 series
party acoustical laboratory designs, outer layer treated
using the full scale ASTM with joint compound and
E90 test procedure. paper tape as specified in **MOLD AND MILDEW When tested by an
the design. RESISTANCE independent lab per ASTM
SoundBreak Gypsum Board is D3273 (“Standard Test
installed like traditional For additional information go SoundBreak Gypsum Board
to UL/ULC Online Method for Resistance to
gypsum board offering a was designed to provide Growth of Mold on the
more reliable and less Certifications Directories, extra protection against Surface of Interior Coatings
complicated solution than Product Category Code mold and mildew in an Environmental
alternative methods CLBV.R25426 – Wall and compared to standard Chamber”), SoundBreak
Partition Facings and gypsum board products. Gypsum Board achieved a
requiring clips and/or
channels. Accessories. score of 10, the best
possible score for this test.

84 NATIONAL GYPSUM BOARD PRODUCTS


09 29 00/NGC
RECOMMENDATIONS

Installation of SoundBreak SoundBreak Gypsum Board


Gypsum Board should be must be stored off the ground SPECIFICATIONS
consistent with methods and under cover. Sufficient
described in the standards risers must be used to ensure
support for the entire length PART 2 PRODUCTS
and references noted.
of the gypsum board to THE FOLLOWING PARAGRAPHS ARE
Stagger SoundBreak Gypsum
Board joints from one side of prevent sagging. FOR INSERTION INTO SECTIONS OF
GENERIC SPECIFICATIONS OR
the wall to another. SoundBreak Gypsum Board
GENERIC/PROPRIETARY
Allow a 1/4" gap along all must be kept dry to minimize
SPECIFICATIONS COVERING
perimeter edges and the potential for mold
GYPSUM BOARD PRODUCTS. THE
completely seal 1/4" gap with growth. Adequate care
should be taken while NATIONAL GYPSUM PRODUCT
acoustical sealant or caulk. NAME FOLLOWS THE GENERIC
transporting, storing, applying
Refrain from wall penetrations DESCRIPTION IN PARENTHESES.
and maintaining SoundBreak
when possible. Gypsum Board. For 2.01 MATERIALS
Limit necessary wall additional information, refer A. Acoustically Enhanced Mold
penetrations to one per stud to the Gypsum Association and Mildew Resistant
cavity. publication, “Guidelines for Gypsum Board: A gypsum
Seal all penetrations with the Prevention of Mold core wall panel with a
acoustical sealant and/or Growth on Gypsum Board” constrained viscoelastic
putty pads. (GA-238-03), which is polymer center layer; surfaced
available at with moisture/mold/mildew
The use of SoundBreak Gypsum www.gypsum.org under the
Board in actual installations resistant paper on front, back
“Download Free Gypsum and long edges and
may not produce the same Association Publications”
results as were achieved in complying with ASTM C
section. 1396 (Gold Bond® BRAND
controlled, laboratory
conditions. SoundBreak Gypsum Board)
Use an acoustical sealant that is DECORATION 1. Thickness: 5/8"
applied per ASTM C919, For best painting results, all 2. Width: 4'
such as Grabber Acoustical surfaces, including joint 3. Length: 8' , 9' , 10' or 12'
Sealant GSC, STI SpecSeal compound, should be clean,
Smoke N Sound Caulk, BOSS 4. Edges: Tapered
dust-free and not glossy. To
824 Acoustical Sound Sealant improve fastener and joint 5. Mold and Mildew
or equivalent. concealment, a coat of Resistance: Panel Score

09 29 00
Use a putty pad that has been quality drywall primer is of 10 when tested in
tested per ASTM E90, such as recommended to equalize
the porosities between Accordance with ASTM
STI SpecSeal SSP Putty Pads
or BOSS 818 Fire-Rated Putty surface paper and joint D 3273
Pads or equivalent. compound. PART 3 EXECUTION
Exposure to excessive or The selection of a paint to give 3.01 INSTALLATION
continuous moisture and the specified or desired
finished characteristics is the A. General: In accordance
extreme temperatures should with the manufacturer’s
be avoided. SoundBreak responsibility of the architect
or contractor. recommendations,
Gypsum Board is not National Gypsum
recommended where it will SoundBreak Gypsum Board that Company “Gypsum
be exposed to temperatures is to have a wall covering Construction Guide.”
exceeding 125˚ (52˚C) for applied should be prepared
extended periods of time. and primed as described for
SoundBreak Gypsum Board is painting.
for use in wall assemblies. Gypsum Association GA-214,
Installing SoundBreak Gypsum Recommended Specification
Board panels over an for Levels of Gypsum Board
insulating blanket, installed Finish, should be referred to
continuously across the face in order to determine the
of the framing members, is level of finishing required to
not recommended. Blankets ensure a properly prepared
should be recessed and surface that accepts the
flanges attached to the sides desired decoration.
of the studs.

NATIONAL GYPSUM WALLBOARD PRODUCTS 85


Gridstone® BRAND Ceiling Panels
RECOMMENDATIONS
DESCRIPTION TECHNICAL DATA
Gridstone ceiling panels are
Gridstone® BRAND prefinished A. Specification Compliance designed to be mounted in
ceiling panels have a non- standard 15/16" exposed
Gridstone panels conform to ASTM C 1396 Type X Class I. tee grid systems or
combustible, Fire-Shield G
gypsum core. The 2-mil B. Light Reflectance environmental type grids
white, stipple-textured for severe conditions, with
LRI (75% or greater) grids either 2' x 2' or 2' x
vinyl laminate combines
high light reflectance with C. Sound Attenuation 4'. Grid installation should
easy cleanability. (Per ASTM E1414) be conducted according to
manufacturer's specifi-
Gridstone panels can be used cation.
for interior and exterior Type Thickness Construction CAC NGC Report #
ceiling applications. Each panel must be supported
Gridstone 1/2" FSW-G Continuous 46dB 6098001 on all four (4) edges.
Gridstone Ceiling Panels (12.7 mm)
install easily in standard 2' Cross ventilation must be
x 2' and 2' x 4' exposed D. Abrasion provided in unheated or
grid systems. Ceiling panels enclosed space above
Wet: (Gardner Scrub Tester) 2000 oscillations with no film ceiling panels.
have a rigid gypsum core break-through and only minor erosions.
which provides extra General: Install panels in lay-
resistance to sagging and Dry: (Taber Abrasion Test with CS-17 Wheel) 500 cycles with no in suspension systems with
warping. break-through to the substrate. edges concealed by flanges
A noncombustible gypsum E. Surface Burning Characteristics of suspension members.
core ensures fire safety with (Per ASTM E 84) Cut boards to fit tightly at
1 1/2- and 2-hour fire borders and penetrations so
rating achievable Flame Smoke that cut edges are
depending on installation. Type Spread Developed Class Test concealed by trim pieces
and escutcheons.
The sturdy white vinyl Gridstone 5 0 A WHI 694-0700.7
laminate eliminates Cleaning: Common dirt and
additional finishing. F. Weight stains on the vinyl surface
can be removed with mild
As little as 1" of material can 1/2" FSW-G - 2.18 lbs/SF soap or detergent in
be cut from Gridstone G. Fire Rating lukewarm water. Use a
panels with practically light, scrubbing action with
none of the crumbling (Per ASTM E 119)
a cloth, sponge or soft
common with mineral fiber brush.
panels. Nominal
Type Thickness Size Design* Rating If the suitability of any
For exterior application, cleaning agent is unknown,
protect grid panels from Gridstone 1/2" FSW-G 2' x 2' UL G222 2 hr.
check its effect on the
direct exposure to weather, (12.7 mm) (610 mm x 610 mm) FM FC-299 Gridstone panel surface in
water and continuous high a hidden area or on a scrap
humidity. Under no 1/2" FSW-G 2' x 4' UL G259 1 1/2 hr. piece before attempting to
circumstances should remove a field stain.
water be in contact with (12.7 mm) (610 mm x 1219 mm) FM FC-300
the back of the panels. Gridstone Ceiling Panels are
*See Quick Selector, page 25, for fire rated assembly details. not recommended for use
Overlaid insulation may cause in areas exposed to
excessive panel deflection extreme or continuous
and is not recommended moisture such as found in
where high humidity is saunas, steam rooms, gang
likely to occur. shower rooms or indoor
Extreme lighting conditions pool enclosures, per ASTM
may distort texture C840 17.3.1.1.
appearance. DECORATION
The use of strong organic Gridstone Brand Ceiling
solvents (such as ketones), Panels are factory-finished
harsh abrasive cleansers or decorative products which
steel wool are not do not require painting.
recommended. These However, if desired,
materials may cause Gridstone can be painted
dulling, discoloration, with the following two
softening and other products:
permanent damage to the
vinyl surface. 1. Two coats of an alkyd or
latex enamel.
USDA Acceptance: Gridstone
panels are accepted by the 2. Oil primer with finish
USDA for use in food coat of oil or latex paint.
service and food 3. Two coats of latex paint.
processing areas. Vinyl laminate on face
of 2' x 2' Gridstone
panel is directional.
Install with all factory
edges parallel (same
direction).
86 NATIONAL GYPSUM BOARD PRODUCTS
GRIDSTONE® BRAND CLEANROOM CEILING PANELS
DESCRIPTION TECHNICAL DATA SPECIFICATIONS
Reference Gridstone technical THE FOLLOWING PARAGRAPHS
Gridstone BRAND CleanRoom data on page 86. ARE FOR INSERTION INTO SECTIONS
Ceiling Panels are
OF GENERIC SPECIFICATIONS OR
sealed on the face, back
GENERIC/PROPRIETARY
and long edges with a 2 RECOMMENDATIONS SPECIFICATIONS COVERING GYPSUM
mil rigid vinyl film. The
exposed edges are factory BOARD PRODUCTS. THE NATIONAL
Gridstone CleanRoom Ceiling GYPSUM PRODUCTS NAME
sealed with a durable Panels are designed to be FOLLOWS THE GENERIC
PACKAGING coating providing a used in a gasket seal DESCRIPTION IN PARENTHESES.
2' x 2' – 4 pcs./bundle, 16 sq. completely sealed panel. suspended grid system
ft., 80 bundles/Unit Gridstone CleanRoom panels using hold down clips.
Catalog Code – GB5044 are for use in systems Recommended use of Gordon PART 2
2' x 4' – 4 pcs./bundle, 32 sq. designed for areas requiring DS-20 gasket Seal System 2.02 MATERIALS
ft., 40 bundles/Unit high levels of air cleanliness or equivalent gasket sealed A. Fire-Resistant Sealed
Catalog Code – GB5045 for airborne particulate grid systems designed for Vinyl Laminated Gypsum
All bundles are double- levels such as clean rooms clean room applications. Grid Board: A gypsum
wrapped with long corner and clean zones. Grid installation should be core lay-in ceiling panel
protectors. Designed for clean room conducted according to with additives to enhance
use. Approved for use in manufacturer's sag and fire resistance of
systems, Class 100,000, specification. the core. Panels are
SPECIFICATIONS Class 10,000, Class Each panel must be supported sealed on face, back and
1,000, Class 100 per on all four (4) edges. long edges with a 2-mil
THE FOLLOWING PARAGRAPHS ARE Federal Standard 209E Cross ventilation must be rigid vinyl film and
FOR INSERTION INTO SECTIONS OF “Airborne Particulate provided in unheated or exposed edges are factory
GENERIC SPECIFICATIONS OR Cleanliness Classes in enclosed space above sealed with a durable
GENERIC/PROPRIETARY Clean Rooms and Clean coating providing a
ceiling panels.
SPECIFICATIONS COVERING Zones.” completely sealed panel;
GYPSUM BOARD PRODUCTS. THE General: Install panels in and complying with
Fire-resistant. A non- lay-in suspension systems
NATIONAL GYPSUM PRODUCT combustible gypsum ASTM C 1396, type X;
NAME FOLLOWS THE GENERIC with edges concealed by Class 1; E 1264, type XX,
core ensures fire safety flanges of suspension
DESCRIPTION IN PARENTHESES. with 1 1/2 and 2-hour Patterns E, G.
members. Cut panels to fit
PART 2 fire rating achievable tightly at borders and Federal Standard 209E

09 29 00
2.02 MATERIALS depending on installation. penetrations so that cut “Airborne Particulate
A. Fire Resistant Vinyl Sag-resistant. Gridstone edges are concealed by trim Cleanliness Classes in
Laminated Gypsum Grid CleanRoom panels’ rigid pieces and escutcheons. Clean Rooms and Clean
Board: A gypsum core gypsum core prevents Zones.” (Gridstone BRAND
If panel cuts are required, CleanRoom Ceiling
lay-in ceiling board with sagging and warping exposed core should be
additives to enhance problems and is backed Panels).
sealed to maintain
sag and fire resistance of by a 15-year limited performance of the system. 1. Thickness: 1/2"
the core; surfaced with warranty. 2. Width and length:
paper on the front and Cleaning: Common dirt and
Do not install panels in stains on the vinyl surface 2' x 2'
back and finished on areas exposed to
the front with a 2 mil, can be removed with mild 2' x 4'
continuous high humidity soap or detergent in
white, stipple textured such as saunas, steam
vinyl laminate; and lukewarm water. Use a light
rooms, gang showers, and scrubbing action with a PART 3
complying with ASTM indoor pools per ASTM
C 1396, type X; Class 1; cloth, sponge or soft brush. 3.03 INSTALLATION
C840, 17.3.1.1.
E 1264, type XX, If the suitability of any A. Install panels in lay-in
patterns E, G. (Gridstone Overlaid insulation may cleaning agent is unknown,
cause excessive panels suspension systems with
Brand Ceiling Panel). check its effect on the edges concealed by
deflection and is not Gridstone CleanRoom
1. Thickness: 1/2" recommended where flanges of suspension
panel surface in a hidden members. Cut panels to
2. Width and Length: high humidity is likely to area or on a scrap piece
2' x 2' occur. fit tightly at borders and
before attempting to remove penetrations so that cut
2' x 4' Extreme lighting a field stain. edges are concealed by
conditions may distort Vinyl laminate on face of 2' x trim pieces and
PART 3 texture appearance. 2' Gridstone CleanRoom escutcheons.
3.03 INSTALLATION The use of strong organic panel is directional. Install
A. Install boards in lay-in solvents (such as ketones), with all factory edges
suspension systems with harsh abrasive cleansers or parallel (same direction).
edges concealed by steel wool are not
flanges of suspension recommended. PACKAGING
members. Cut panels These materials may 2' x 2' – 4 pcs./bundle, 16 sq.
to fit tightly at borders cause dulling, discoloration, ft., 80 bundles/Unit
and penetrations so that softening and other Catalog Code – GB5040
cut edges are concealed permanent damage to the 2' x 4' – 4 pcs./bundle, 32 sq.
by trim pieces and vinyl surface. ft., 40 bundles/Unit
escutcheons. Gridstone CleanRoom Catalog Code – GB5030
panels are USDA accepted All bundles are double-
for use in food service and wrapped with long corner
food processing areas. protectors.

NATIONAL GYPSUM BOARD PRODUCTS 87


Gridstone® BRAND Hi-Strength Ceiling Panels
DESCRIPTION TECHNICAL DATA DECORATION
Gridstone Hi-Strength Ceiling
Gridstone® BRAND Hi-Strength panels are factory-finished
SURFACE BURNING decorative products which
prefinished ceiling panels CHARACTERISTICS
have a non-combustible do not require painting.
ASTM E 84 However, if desired,
high strength gypsum core
formulated with increased Flame Spread: 5 Gridstone can be painted
uniformity and integrity Smoke Developed: 0 with the following products:
which increases its sag WEIGHT 1. Two coats of alkyd or latex
resistance. enamel.
5/16" Hi-Strength - 1.24 lbs/SF
Gridstone Hi-Strength panels 2. Oil primer with finish coat
can be used for interior and SOUND ATTENUATION of oil or latex paint.
exterior ceiling applications ASTM E 1414 Test Method
in protected, well-ventilated 3. Two coats of latex paint.
spaces that receive Ceiling Attenuation Class
PACKAGING
intermittent exposure to (CAC)-41 dB 2' x 2' – 6 pcs./bundle, 24 sq.
moisture. LIGHT REFLECTANCE ft., 80 bundles/Unit
Lightweight. Gridstone LR 1 (75% or greater) Catalog Code – GB5020
Hi-Strength 5/16" panels 2' x 4' – 6 pcs./bundle, 48 sq.
are 40% lighter in weight RECOMMENDATIONS ft., 40 bundles/Unit
than standard gypsum Catalog Code – GB5010
ceiling panels. All bundles are double-
Quick, dry installation. Gridstone Hi-Strength ceiling wrapped with long corner
Gridstone Hi-Strength panels are designed to be protectors.
Ceiling panels score and mounted in standard 15/16"
snap clean and install exposed tee grid systems
or environmental type SPECIFICATIONS
easily in standard
exposed grid systems. grids for severe conditions,
with grids either 2' x 2' THE FOLLOWING PARAGRAPHS ARE
Pre-decorated. The sturdy or 2' x 4'. Grid installation FOR INSERTION INTO SECTIONS OF
white vinyl laminate should be conducted GENERIC SPECIFICATIONS OR
eliminates additional according to manufacturer's GENERIC/PROPRIETARY SPECIFICATIONS
finishing. specification. COVERING GYPSUM BOARD
Do not install panels in PRODUCTS. THE NATIONAL GYPSUM
Each panel must be supported PRODUCT NAME FOLLOWS THE GENERIC
areas exposed to on all four (4) edges.
continuous high humidity DESCRIPTION IN PARENTHESES.
such as saunas, steam Cross ventilation must be
rooms, gang showers, and provided in unheated or PART 2
indoor pools per ASTM enclosed space above
ceiling panels. 2.02 MATERIALS
C840, 17.3.1.1.
General: Install panels in lay- A. Vinyl laminated Gypsum
For exterior application, Grid board: A gypsum
protect grid panels from in suspension systems with
edges concealed by flanges core lay-in ceiling panel
direct exposure to with additives to enhance
weather, water and of suspension members. Cut
panels to fit tightly at sag resistance of the
continuous high core; surfaced with paper
humidity. Under no borders and penetrations so
that cut edges are on the front and back and
circumstances should finished on the front with
water be in contact with concealed by trim pieces
and escutcheons. a 2 mil, white, stipple
the back of the panels. textured vinyl laminate;
Overlaid insulation may Cleaning: Common dirt and and complying with
cause excessive panel stains on the vinyl surface ASTM C 1396, Class 1,
deflection and is not can be removed with mild E 1264 Type XX, Patterns
recommended. These soap or detergent in E, G (Gridstone BRAND Hi-
materials may cause lukewarm water. Use a light Strength Ceiling Panels)
dulling, discoloration, scrubbing action with a
cloth, sponge or soft brush. 1. Thickness: 5/16"
softening and other
permanent damage to the If the suitability of any 2. Width and length:
vinyl surface. cleaning agent is unknown, 2' x 2'
Gridstone Hi-Strength check its effect on the 2' x 4'
panels are not listed in Gridstone Hi-Strength panel
fire-rated assemblies. surface in a hidden area PART 3
before attempting to remove 3.03 INSTALLATION
USDA Acceptance: Gridstone a field stain.
Hi-Strength panels are A. Install panels in lay-in
accepted by the USDA for NOTE: Vinyl laminate on suspension systems with
use in food service and food face of 2' x 2' Gridstone edges concealed by
processing areas. Hi-Strength panel is flanges of suspension
directional. Install with all members. Cut panels to
factory edges parallel (same fit tightly at borders and
direction). penetrations so that cut
edges are concealed by
trim pieces and escutcheons.

88 NATIONAL GYPSUM BOARD PRODUCTS


09 29 00/NGC
Gold Bond® BRAND Foil Back Gypsum Board
DESCRIPTION LIMITATIONS TECHNICAL DATA Boards of maximum
1. Not recommended for practical length should be
Gold Bond® Foil Back Gypsum use where exposure to SURFACE BURNING used so that an absolute
Board consist of a fire- moisture and high outside CHARACTERISTICS minimum number of end
resistive gypsum core temperature is extreme and joints occur. Board edges
(ASTM E 84) should be brought into
encased in heavy natural- continuous. Under these
finish paper on the face side conditions, a qualified Flame spread: 15 contact with each other but
and strong liner paper on the mechanical engineer Smoke developed: 0 should not be forced into
backside to which aluminum should determine location place.
WEIGHT
foil is laminated. The ends of the vapor retarder. Gypsum board joints at
are square cut and finished 1/2" Regular - 1.6 lbs/SF openings should be located
2. Not to be used as a base for
smooth. ceramic or other tile or as a 5/8" Type X - 2.2 lbs/SF so that no end joint will
BASIC USES base layer for prefinished align with edges of openings
vinyl wall boards in double- unless control joints will be
Foil Back Gypsum Board can be FIRE RESISTANCE RATINGS installed at these points.
used for exterior walls and layer assemblies. Also, not
to be used as a base for Foil Back Gypsum Board has End joints should be
ceilings in new construction not been used in fire staggered, and joints on
and remodeling. The adhesively applied vinyl or
other highly water-vapor- resistance tests. Fire opposite sides of a partition
aluminum foil, laminated to resistance ratings represent should not occur on the
the back surface, is a vapor resistant wall coverings.
the results of tests on same stud.
retarder to keep interior 3. To prevent objectionable
sag in ceilings, weight of assemblies made up of Gypsum board should be
moisture within the building specific materials in a
at a suitable comfort level. For overlaid unsupported held in firm contact with
insulation should not exceed: specific configuration. the framing member while
use with furred masonry, When selecting
wood or steel framing, Gold 1.3 lb./sq. ft. for 1/2" thick fasteners are being driven.
boards with frame spacing construction designs to Fastening should proceed
Bond Foil Back Gypsum meet certain fire resistance
Board is effective for single- 24" o.c.; 2.2 lb./sq. ft. for from center portion of the
boards with frame spacing requirements, caution must gypsum board toward the
layer applications and as a be used to ensure that each
base layer in double-layer 16" o.c. Boards 3/8" thick edges and ends. Fasteners
must not be overlaid with component of the assembly should be set with the heads
applications where a vapor is the one specified in the
retarder of 1.0 perm or less is unsupported insulation. slightly below the surface
Unheated attic spaces should test. Further, precaution of the gypsum board in a
required. should be taken that
be properly ventilated. dimple formed by the
ADVANTAGES assembly procedures are in hammer or power
1. In tests conducted according 4. Foil Back Gypsum Board is accordance with that of the screwdriver. Care should

09 29 00
to ASTM Test Procedure E 96 not recommended for use tested assembly. (For be taken to avoid breaking
(desiccant method), 1/2" Foil in hot, humid, climates such copies of specific tests, the face paper of the
Back Gypsum Board showed as the Southern Atlantic and call 1-800-NATIONAL or gypsum board. Improperly
a performance of 0.06 perm Gulf Coast areas. 1-800-628-4662.) driven nails or screws shall
compared to 34 perm for MATERIALS be removed.
1/2" regular gypsum board RECOMMENDATIONS For best painting results, all
and 28 perm for 1/2" gypsum Manufactured boards with interior surfaces, including
board with two coats of flat gypsum core, paper-encased
with aluminum foil Examine and inspect materials joint compound, should be
latex paint. to which gypsum board is clean, dust-free and not
laminated backing.
2. In-place cost of Foil Back to be applied. Remedy all glossy. To improve fastener
Gypsum Board installation is SIZES AND TYPES defects prior to installation and joint concealment, a
lower per thousand sq. ft. Thickness Width Length of gypsum board. Any prime coat of drywall
than a similar installation for 1/2" 4' 6' to 16' defects in the finished primer is recommended to
regular gypsum board and 5/8" 4' 6' to 16' installation due to equalize the porosities
polyethylene-film retarder Edges: Square, tapered or misaligned framing or between surface paper and
installed separately. Sta-Smooth. other cause will be the joint compound.
3. Easy-to-handle Foil Back responsibility of the work See page 63, Environmental
Gypsum Board is adaptable to APPLICABLE STANDARDS performed under that Conditions and Limitations.
virtually all exterior wall and ASTM C 1396 section of the specification
ceiling construction: wood and such defects shall be
frame, furred masonry. remedied under that
secton of the specification
Gypsum board should be
applied first to ceiling at
right angles to framing
members, then to walls.

NATIONAL GYPSUM BOARD PRODUCTS 89


GYPSUM SYSTEMS
Nonload-Bearing Steel Frame Partitions
DESCRIPTION
Steel framed drywall partitions and the steel studs acting as are waterproofed.
are comprised of steel floor a composite section to 5. To prevent weakening
and ceiling tracks, steel provide a maximum due to calcining, gypsum
studs and Gold Bond deflection of L/120, L/240, board should not be
Gypsum Board which is L/360 exposed to temperatures
attached with self-drilling (L = partition height in over 125˚F for extended
drywall screws. Metal inches) with a horizontal periods of time.
products are to meet or load of 5 psf, 7.5 psf, and
exceed all applicable 10 psf of partition surface. 6. Gypsum board joints on
ASTM standards. single layer, or the face
Increased rigidity may be layer on two layer
Gypsum board may be obtained by placing applications, shall not
applied horizontally or stiffener channels through occur within 12" of the
vertically in single or the steel stud cut-outs, by corners of door frames
double layers. In double using two layer application unless control joints are
layer construction, the face, of gypsum board or by installed at the corners.
or finish layer, may be decreasing stud spacing.
Durasan panels adhesively 7. For limitations regarding
Standard 25 and 20 gauge selection of doors and
applied to the base layer. studs, recommended for
For specific fire and sound doorframes, refer to table
interior partitions, have on page 92.
ratings for this system, see height limits as shown in
test data on pages 11 Tables 1 and 2. Gypsum 8. Where reference is made
through 26. board must be attached to to nominal gauges, 25
full height on both sides of gauge relates to a
ADVANTAGES minimum base steel of
studs with Type S Bugle
1. Openings provided Head Drywall Screws .0179", and 20 gauge to
throughout the length of (Type S-12 for 20 gauge .0329".
the steel studs permit the studs) spaced not more
easy horizontal routing of than 12" o.c. on all studs
water, gas and electrical when framing is 24" o.c.
conduit. These openings and 16" o.c. if framing is
may also be used to install 16" o.c. or less. Screw
C.R. Channel stiffeners lengths must be not less
where increased rigidity is than 3/8" greater than the
required. Interruption of the total thickness of the
floor or ceiling track allows gypsum board being
the vertical installation of fastened.
larger utilities.
Light steel 20 gauge studs are
2. Fire resistance: 1-, 2-, 3- designed for exterior,
and 4-hour fire ratings have nonload-bearing curtain
been assigned to these wall systems, but are also
systems (see pages 11-26). used for interior partitions
3. Sound resistance: where to provide more ridigity or
a superior Sound greater heights than can be
Transmission Class is obtained with Standard 25
required, it can be gauge studs.
achieved through the use
of several variations with LIMITATIONS
this system. 1. Maximum stud spacing for
single layer application of
TECHNICAL DATA 1/2" and 5/8" gypsum
board is 24" o.c. If 3/8"
PARTITION HEIGHTS gypsum board is used, it
must be applied in two
Light Gauge Steel Studs are layers, with the second
designed to frame nonload- layer adhesively applied;
bearing partitions which 24" o.c. stud spacing may
are limited in height by be used.
deflection resulting from
extraneous horizontal 2. Where long, continuous
forces. For any given runs of this wall system are
horizontal load, the amount employed, control joints
of deflection increases as must be provided every 30'
the height of the partition or less.
increases. 3. Where structural movement
Tables 1 and 2 on the next may impose direct loads on
page show maximum these systems, isolation
partition heights based on details are required.
specific design criteria. The 4. Partitions should not be
height limits shown are used where frequently
based on the gypsum board exposed to excessive
moisture unless all surfaces

90 NATIONAL GYPSUM BOARD PRODUCTS


09 29 00/NGC

Table 1 Table 2

25 GAUGE STUDS/PARTITION LIMITING HEIGHTS 20 GAUGE STUDS/PARTITION LIMITING HEIGHTS


Stud Stud Deflection Lateral Pressure Stud Stud Deflection Lateral Pressure
5 psf 7.5 psf 10 psf 5 psf 7.5 psf 10 psf
Depth Spacing Limit (240 Pa) (360 Pa) (480 Pa) Depth Spacing Limit (240 Pa) (360 Pa) (480 Pa)
1-5/8 in. 12 in. L/120 11-2 (3400) 9-9 (2970) 8-10 (2690) 1-5/8 in. 12 in. L/120 13-0 (3960) 11-4 (3450) 10-4 (3150)
(41.3mm) (305mm) L/240 8-10 (2690) (41.3mm) (305mm) L/240 10-4 (3150) 9-0 (2740)
L/360 L/360 9-0 (2740)
16 in. L/120 10-7 (3230) 8-10 (2690) 8-4 (2540) 16 in. L/120 12-1 (3680) 10-7 (3230) 9-8 (2950)
(406mm) L/240 8-4 (2540) (406mm) L/240 9-8 (2950) 8-5 (2570)
L/360 L/360 8-5 (2570)
24 in. L/120 9-9 (2970) 8-0 (2440) 24 in. L/120 11-0 (3350) 9-7 (2920) 8-9 (2670)
(610mm) L/240 7-11 (2410) (610mm) L/240 8-9 (2670) 7-8 (2340)
L/360 L/360 7-8 (2340)
2-1/2 in. 12 in. L/120 15-1 (4600) 12-4 (3760) 10-9 (3280) 2-1/2 in. 12 in. L/120 17-9 (5410) 15-6 (4720) 13-11 (4240)
(63.5mm) (305mm) L/240 11-11 (3630) 10-5 (3180) 9-6 (2900) (63.5mm) (305mm) L/240 13-11 (4240) 12-1 (3680) 10-11 (3300)
L/360 10-5 (3180) 9-1 (2770) L/360 12-1 (3680) 10-6(3200) 9-5 (2870)

16 in. L/120 13-3 (4040) 10-10 (3300) 9-5 (2570) 16 in. L/120 16-5 (5000) 14-4 (4370) 12-10 (3910)
(406mm) L/240 11-3 (3430) 9-10 (3000) 8-11 (2720) (406mm) L/240 12-10 (3910) 11-2 (3400) 10-0 (3050)
L/360 9-10 (3000) 8-7 (2620) L/360 11-2 (3400) 9-8 (2950) 8-8 (2640)

24 in. L/120 11-10 (3610) 9-8 (2950) 8-5 (2570) 24 in. L/120 14-10 (4520) 13-0 (3960) 11-7 (3530)
(610mm) L/240 10-7 (3230) 9-3 (2820) 8-5 (2570) (610mm) L/240 11-7 (3530) 10-0 (3050) 8-11 (2720)
L/360 9-3 (2820) 8-1 (2460) L/360 10-0 (3050) 8-7 (2620) 7-8 (2340)

3-1/2 in. 12 in. L/120 17-8 (5380) 14-3 (4340) 12-5 (3780) 3-1/2 in. 12 in. L/120 22-6 (6860) 19-8 (5990) 17-10 (5440)
(88.9mm) (305mm) L/240 15-4 (4670) 13-3 (4040) 12-0 (3660) (88.9mm) (305mm) L/240 17-10 (5440) 15-6 (4720) 14-1 (4290)
L/360 13-3 (4040) 11-7 (3530) 10-5 (3180) L/360 15-6 (4720) 13-7 (4140) 12-4 (3760)

09 29 00
l6 in. L/120 15-4 (4670) 12-5 (3780) 10-9 (3280) 16 in. L/120 20-8 (6300) 18-1 (5510) 16-5 (5000)
* (406mm) L/240 14-4 (4370) 12-5 (3780) 10-9 (3280) * (406mm) L/240 16-5 (5000) 14-3 (4340) 12-11 (3940)
L/360 12-4 (3760) 10-10 (3300) 9-9 (2970) L/360 14-3 (4340) 12-6 (3810) 11-4 (3450)

24 in. L/120 13-9 (4190) 11-0 (3350) 9-5 (2870) 24 in. L/120 18-6 (5640) 16-2 (5840) 14-9 (4500)
(610mm) L/240 13-5 (4090) 11-0 (3350) 9-5 (2870) (610mm) L/240 14-9 (4500) 12-9 (3890) 11-7 (3530)
L/360 11-7 (3530) 10-1 (3070) 9-1 (2770) L/360 12-9 (3890) 11-2 (3400) 10-1 (3070)

4 in. 12 in. L/120 19-6 (5940) 15-9 (4800) 13-8 (4170) 4 in. 12 in. L/120 25-1 (7650) 21-11 (6680) 19-11(6070)
(101.6mm) (305mm) L/240 16-5 (5000) 14-4 (4370) 13-0 (3960) (101.6mm) (305mm) L/240 19-11 (6070) 17-4 (5280) 15-8 (4780)
L/360 14-4 (4370) 12-6 (3810) 11-4 (3450) L/360 17-4 (5280) 15-0 (4570) 13-7 (4140)

16 in. L/120 17-2 (5230) 13-10 (4220) 11-11(3630) 16 in. L/120 23-1 (7040) 20-2 (6150) 18-4 (5590)
(406mm) L/240 15-4 (4670) 13-4 (4060) 11-11(3630) (406mm) L/240 18-4 (5590) 15-11 (4850) 14-5 (4390)
L/360 13-4 (4060) 11-8 (3560) 10-6 (3200) L/360 15-11 (4850) 13-9 (4190) 12-6 (3810)

24 in. L/120 15-1 (4600) 12-1 (3680) 10-5 (3180) 24 in. L/120 20-9 (6320) 18-1 (5510) 16-5 (5000)
(610mm) L/240 14-2 (4320) 12-1 (3680) 10-5 (3180) (610mm) L/240 16-5 (5000) 14-3 (4340) 12-10 (3910)
L/360 12-4 (3760) 10-9 (3280) 9-9 (2970) L/360 14-3 (4340) 12-4 (3760) 11-2 (3400)

6 in. 12 in. L/120 22-10 (6960) 18-7 (5660) 16-2 (4930) 6 in. 12 in. L/120 33-9 (10290) 29-6 (8990) 26-9 (8150)
(152.4mm) (305mm) L/240 22-1 (6730) 18-7 (5660) 16-2 (4930) (152.4mm) (305mm) L/240 26-9 (8150) 23-5 (7140) 21-3 (6480)
L/360 19-4 (5890) 16-9 (5110) 15-0 (4570) L/360 23-5 (7140) 20-6 (6250) 18-7 (5660)

16 in. L/120 19-9 (6020) 16-2 (4930) 14-0 (4270) 16 in. L/120 30-10 (9400) 27-0 (8230) 24-6 (7470)
(406mm) L/240 19-9 (6020) 16-2 (4930) 14-0 (4270) (406mm) L/240 24-6 (7470) 21-4 (6500) 19-5 (5920)
L/360 17-11 (5460) 15-7 (4750) 3-10 (4220) L/360 21-4 (6500) 18-9 (5720) 17-0 (5180)

24 in. L/120 16-9 (5110) 13-5 (4090) 11-5 (3480) 24 in. L/120 27-2 (8280) 23-10 (7260) 19-1 (5820)
(610mm) L/240 16-9 (5110) 13-5 (4090) 11-5 (3480) (610mm) L/240 21-7 (6580) 18-10 (5740) 17-3 (5260)
L/360 16-9 (5110) 13-5 (4090) 11-5 (3480) L/360 18-10 (5740) 16-7 (5050) 15-0 (4570)

Note: Limiting height tables adapted with permission from ASTM C 754. Copyright ASTM.
Tables based on tests conducted with gypsum board attached with screws
12" o.c. to framing.

*Applicable for 3 5/8" stud depth.

NATIONAL GYPSUM BOARD PRODUCTS 91


SINGLE LAYER CONSTRUCTION
STEEL TRACK
FASTEN JAMB STUDS TO TRACK
TOP AND BOTTOM CHASE WALL

TRACK - CUT AND


BENT DOWN

1/2" GYPSUM
BOARD OR
STUD TRACK
12" 2 SCREWS
PER STUD
(ALTERNATE)

16' MAX. HEIGHT


C.R. CHANNEL
STIFFENERS
FRICTION FIT 3 DRYWALL
(OPTIONAL) SCREWS
PER STUD
48"
MAX.
TAPE AND JOINT
COMPOUND

STEEL DOOR FACE GYPSUM BOARD (APPLIED


FRAME IN NORMAL MANNER)
JAMB
ANCHORS
20" MAX. WIDTH
PER ASTM C754

FRAMING REQUIREMENTS AT DOORS


(Type of Door Frame) (Special Details) Partition Height Limits*
Jamb Steel Studs Knock Knock Bracing Requires Stud Size
Door Min. Down Down Fixed Over Mechanical 1 5/8" 2 1/2" 3 5/8" 4" 6"
Weight Base Steel, In. Alum. Steel Steel Headers Closure (41.3mm) (63.5mm) (92.1mm) (102mm) (152mm)
Up to 0.0179 x x x NA** 10'(3048mm) 14'(4267mm) 15'(4572mm) 14'(4267mm)
50 lbs. 0.0179 x x x x 10'(3048mm) 12'(3657mm) 16'(4876mm) 17'(5181mm) 16'(4876mm)
(23 kg) 0.0329 x x x x – 16'(4876mm) 21'(6400mm) 22'(6705mm) 22'(6705mm)
0.0179 x x x – 10'(3048mm) 14'(4267mm) 15'(4572mm) 14'(4267mm)
0.0179 x x x 10'(3048mm) 12'(3657mm) 14'(4267mm) 15'(4572mm) 14'(4267mm)
0.0179 x x x 12'(3657mm) 14'(4267mm) 16'(4876mm) 17'(5181mm) 16'(4876mm)
50 lbs.
(23 kg) to 0.0329 x 10'(3048mm) 14'(4267mm) 15'(4572mm) 15'(4572mm)
80 lbs. 0.0329 x x x 12'(3657mm) 16'(4876mm) 17'(5181mm) 17'(5181mm)
(36 kg) 0.0329 x x x 12'(3657mm) 16'(4876mm) 17'(5181mm) 17'(5181mm)
0.0329 dbl. web to web x 16'(4876mm) 21'(6400mm) 22'(6705mm) 22'(6705mm)
0.0329 dbl. web to web x x 16'(4876mm) 21'(6400mm) 22'(6705mm) 22'(6705mm)
80 lbs. 0.0179 x x x 12'(3657mm) 14'(4267mm) 15'(4572mm) 14'(4267mm)
(36 kg) to
120 lbs. 0.0329 x x x x 12'(3657mm) 16'(4876mm) 17'(5181mm) 17'(5181mm)
(54 kg) 0.0329 dbl. web to web x x 16'(4876mm) 21'(6400mm) 22'(6705mm) 22'(6705mm)
* For a specific partition having a door opening compare above partition height limits with height tables on page 88. The lower height table governs.
** NA – Not Allowed.

92 NATIONAL GYPSUM BOARD PRODUCTS


09 29 00/NGC
Drywall Metal Framing*

25 & 20 GAUGE STUDS FURRING CHANNEL


”C” shaped metal studs fabricated Used as cross furring members
from galvanized steel. 20 gauge for attachment of gypsum board
studs are for curtainwall con- or lath on ceiling or furred
struction or more rigid partitions. masonry walls.

25 & 20 GAUGE TRACK RESILIENT FURRING CHANNEL


Fastened at floor and ceiling to Used as cross furring members
support the steel studs. Track for attachment of gypsum board
is channel-shaped and fab- and improves sound isolation on
ricated from galvanized steel. ceilings and partitions.

09 29 00
Z FURRING CHANNEL FLOOR & CEILING RUNNER
Generally used on the inside of 2" x 2" 20 GAUGE
exterior masonry walls to support Used as a utility floor and ceiling
rigid foam insulation and to runner. Also used in vertical
provide a fastening surface for shaftwall inside corner
gypsum board. application.

COLD ROLLED CHANNEL L RUNNER


Used in suspended ceilings and Perforated – Ceiling or floor
as stiffeners in stud partitions. support for 2" solid lath and
plaster partition.
Plain – Ceiling support for 2"
solid gypsum board partition
using 1" shaftliner.

*Metal products are not manufactured by National Gypsum Company

NATIONAL GYPSUM BOARD PRODUCTS 93


Accessories*
GYPSUM BOARD ARCH CORNERBEAD
CORNERBEAD Can be used straight for exterior
Used to reinforce exterior corners or flanges, or may be
gypsum board corners. For use snipped and bent to form arches.
with all gypsum board
thicknesses, single or double
layer application.

J GYPSUM BOARD CASING E-Z STRIP® EXPANSION JOINT


Provides a finished edge at door Designed for drywall or veneer
and window jambs by slipping plaster systems. A vinyl
over edge. Is face nailed and extrusion used as an expansion
exposed surface finished with or control joint for ceilings or
joint treatment. partitions.

J GYPSUM BOARD CASING .093 ZINC CONTROL JOINT


(Reveal Trim) Designed as an expansion or
Used at door, window, inside control joint for ceiling and
corners when facing must be partition areas for both drywall
isolated from abutting elements. or veneer plaster systems.
Requires no joint treatment finish.

L GYPSUM BOARD CASING


Used as a finished edge at door
and window jambs. Is face nailed
and exposed surface finished
with joint treatment.

*Accessories are not manufactured by National Gypsum Company

94 NATIONAL GYPSUM BOARD PRODUCTS


09 29 00/NGC

DETAILS

3 5/8" STEEL STUD


LOCATE AT ABUTTING WALL
AND ATTACH THRU GYPSUM
STUD SPLICE BOARD TO STUD IN
ABUTTING WALL

16" LENGTH OF
TRACK
STUDS BUTTED

4 PAN HEAD
SCREWS EACH
SIDE

CORNERBEAD – TYPICAL 5/8" GYPSUM BOARD – NUMBER OF


LAYERS DETERMINED BY PARTITION TYPE

CORNER DETAIL
09250E
Scale 3" = 1'-0"

STEEL STUD

STEEL STUD

09 29 00
TAPE AND JOINT TAPE AND JOINT
COMPOUND COMPOUND

GYPSUM
BOARD
ALTERNATE PARTITION
PARTITION INTERSECTION INTERSECTION
09250F 09250G
Scale: 3" = 1'-0" Scale: 3" = 1'-0"

E-Z STRIP VINYL


EXPANSION JOINT

VENEER PLASTER OR
JOINT COMPOUND ADHESIVE

KAL-KORE OR
GYPSUM BOARD

STEEL
STUD

CASING

CAULKING MASONRY WALLS


OR COLUMN

JOINT WHERE WALL FRAMING CHANGES


09250CC
Scale: 3" = 1'-0"

NATIONAL GYPSUM BOARD PRODUCTS 95


FURRING CHANNEL CLIP
CEILING TRACK FURRING CHANNEL
DRYWALL
CASING
CAULK
1 1/2" C.R.
CHANNEL

TOGGLE BOLT
OR MOLLY DRYWALL
CASING

STEEL STUD
FURRING TYPE S
TAPE AND CHANNEL DRYWALL
JOINT SCREW
COMPOUND
STEEL STUD TRACK
ATTACHMENT TO CONCRETE SLAB
09250H STEEL STUD ATTACHMENT TO
Scale: 3" = 1'-0" FURRED CEILING
09250J
Scale: 3" = 1'-0"
ATTACHMENT TO
SUSPENDED CEILING E-Z STRIP
CONTROL JOINT
09250I
STEEL STUD
Scale: 3" = 1'-0"

JAMB STUD
TRACK
SEALANT

WOOD TRIM

DOOR HEAD DETAIL - WOOD WALL CONTROL JOINT


09250K 09250M
Scale: 3" = 1'-0" Scale: 3" = 1'-0"

DOOR JAMB DETAIL - WOOD


09250N
1/2" E-Z STRIP VINYL
Scale: 3" = 1'-0" 5/8" FIRE-SHIELD GAP EXPANSION JOINT
STEEL STUD

JAMB ANCHOR CLIP


5/8" GAP 1 5/8" DRYWALL
STEEL STUD SCREWS
24" O.C.

METAL FRAME

TRACK
2 1/2" STEEL STUDS 5/8" FIRE-SHIELD STRIPS

DOOR HEAD DETAIL - METAL ONE HOUR FIRE RATED CONTROL JOINT DETAIL
09250L Based on Warnock Hersey Report No. WHI-651-0318.1
Scale: 3" = 1'-0" and Factory Mutual Design No. W 1B-1 hr.
DOOR JAMB DETAIL - METAL 09250P
09250O Scale: 3" = 1'-0"
Scale: 3" = 1'-0"
STEEL
STUD TAPE AND JOINT
COMPOUND
GYPSUM DRYWALL CORNERBEAD
BOARD

STEEL
STUD
WOOD BASE

RESILIENT
COVE BASE

FLOOR TRACK
BASE DETAIL PARTITION END DETAIL BUTT JOINT DETAIL
09250Q
09250R 09250S
Scale: 3" = 1'-0"
Scale: 3" = 1'-0" Scale: 3" = 1'-0"

96 NATIONAL GYPSUM BOARD PRODUCTS


09 29 00/NGC

RECOMMENDATIONS SPECIFICATIONS

1. FRAMING THE FOLLOWING PARAGRAPHS ARE FOR INSERTION INTO SECTIONS OF


Align floor and ceiling tracks to ensure plumb partition. GENERIC SPECIFICATIONS COVERING METAL FRAMING PRODUCTS.
Secure track with suitable fasteners at a maximum of 24" VERIFY DESCRIPTIONS OF METAL FRAMING PRODUCTS WITH
o.c. Position studs in track on 16" or 24" centers by MANUFACTURER.
rotating into place for a friction fit. Steel studs shall be PART 2 PRODUCTS
installed with all flanges pointed in the same direction.
Secure studs located adjacent to door and window frames, 2.02 MATERIALS
partition intersections and corners with 3/8" Pan Head A. METAL FRAMING
Type S Screws driven through both flanges of studs and 1. Studs: 1 5/8", 1 1/2", 3 5/8", 4" and 6" C shaped studs,
tracks or by using a stud clincher. weighing 312 lbs., 370 lbs., 448 lbs., 472 lbs., and 607
2. SINGLE LAYER OR FIRST PLY lbs. per 1000 lin. ft. with min. base steel of 0.0179",
Cut gypsum board to allow for a 1/8" to 1/4" gap between galvanized, and complying with ASTM C 645.
gypsum board and floor to prevent potential wicking. 2. Track: 1 5/8", 2 1/2", 3 5/8", 4" and 6" U shaped track
Apply gypsum board with the length parallel or at right angles with 1" legs, weighing 244 lbs., 303 lbs., 378 lbs., 404
to the studs. Center abutting ends or edges over the stud lbs. and 539 lbs. per 1000 lin. ft. with min. base metal of
flanges. 0.0179", galvanized and complying with ASTM C 645.
For metal framing, screws shall be Type S, of a length to 3. 1 5/8", 2 1/2", 3 5/8", 4" and 6" U shaped track with 1
provide not less than 3/8" penetration into framing and 1/4" legs, weighing 278 lbs., 337 lbs., 412 lbs., 438 lbs.
shall be spaced 24" o.c. max. If no adhesive is used, and 572 lbs. per 1000 lin. ft. with min. base metal of
standard fastener spacings shall prevail. 0.0179", galvanized and complying with ASTM C 645.
For non-fire-rated construction, locate all attaching screws 4. Studs: 2 1/2", 3 5/8", 4" and 6" C shaped studs. Studs
12" o.c. when framing is 24" o.c. and 16" o.c. when weighing 679 lbs., 817 lbs., 867 lbs. and 1105 lbs. per
framing is 16" o.c. or less. For fire-rated construction, 1000 lin. ft. with min. base metal of 0.0329", galvanized
vertical application, space screws 12" o.c. in the field and and complying with ASTM C 645.
8" o.c. along the vertical abutting edges unless otherwise 5. Track: 2 1/2", 3 5/8", 4" and 6" U shaped track with
specified. Attach the gypsum board to Steel Studs with 1.177" legs, weighing 604 lbs., 740 lbs., 785 lbs. and
Type S Drywall Screws using an electric, drywall 1027 lbs. per 1000 lin. ft. with min. base metal of
screwdriver with a #2 Phillips bit. For vertical gypsum 0.0329", galvanized and complying with ASTM C 645.
board application with studs 24" o.c., erect the gypsum 6. Z Furring Channels: 1", 1 1/2" and 2" Z shaped channels,

09 29 00
board on one side of the partition, screw attaching to open weighing 201 lbs., 236 lbs. and 268 lbs. per 1000 lin. ft.
end of stud flange first at vertical gypsum board joints. with min. base steel of 0.0179", galvanized and
Complete the gypsum board application to the entire side complying with ASTM C 645.
of the partition in this manner. For the opposite side, cut
the first gypsum board 2' wide so that joints will be 7. Floor & Ceiling Runner: L shaped runner weighing 545
staggered. Fasten this and succeeding gypsum boards to all lbs. per 1000 lin. ft. with min. base steel of 0.0329",
studs on this side. When partition face is complete, return galvanized.
to the first side and complete screw attachment of gypsum PART 3 EXECUTION
board to all intermediate studs. 3.01 INSTALLATION
Make door and window framing openings of such size that A. General: In accordance with ASTM C 754, the
when the gypsum board is secured to the studs, it will fit manufacturer’s recommendations and National Gypsum
snugly into the steel frames. Company “Gypsum Construction Guide.”
3. FACE LAYER
Mechanical attachment of face layer for fire or sound rated
constructions shall be made in accordance with the
specifications for the system selected. When the face ply is
attached with mechanical fasteners and with no adhesive
between plies, the maximum spacing and minimum
penetration recommended for screws should be the same
as for single ply application.

NATIONAL GYPSUM BOARD PRODUCTS 97


INSTALLATION

SHELF BRACKET SHELF BRACKET


BETWEEN STUDS 1" X 3" X 12" WOOD BLOCKS LAMINATE OR
SCREW ATTACHED TO BACK OF GYPSUM
GYPSUM BOARD BOARD BETWEEN STUDS

GYPSUM BOARD
SHELF
BRACKET
STEEL STUD SHELF
STEEL
STUD BRACKET
2 1/2" #14 4" MIN. BEARING
WOOD SCREWS 6" MIN. (1" MIN.
SEE CHART BELOW BRACKET
MIN. 12" LONG FOR SHELF BRACKET WIDTH)
WOOD FILLER ALLOWABLE LOADS
BLOCK CUT FOR
SNUG FIT INSIDE
STUD SHELF BRACKET BEARING 1 1/2" #10 WOOD SCREWS
(1" MIN. BRACKET WIDTH)

EXTRA HEAVY LOADS 3 5/8" STEEL STUDS. 24" O.C.


SHELF BRACKET BETWEEN STUDS
Allowable Load With Wood Blocks 16 GAUGE STEEL STUD OR U S-12 SCREWS. 16" O.C.
CHANNEL TO FLOOR
Wood Block with 1/2" (12.7 mm) gypsum board 40 ft. lbs. per bracket (54 N-M)
Wood Block with 5/8" (15.9 mm) gypsum board 70 ft. lbs. per bracket (95 N-M)
Allowable Load With Sheet Metal (.0239)
0.12 L MIN.
.0239 sheet metal substituted 40 ft. lbs. per bracket (54 N-M)
for wood with 1/2" (12.7 mm) gypsum board
.0239 sheet metal substituted 50 ft. lbs. per bracket (68 N-M)
L
for wood with 5/8" (15.9 mm) gypsum board
(PARTITION
HEIGHTS) 6" MIN. 0.12 L MIN.

SHELF BRACKET
Allowable Load 1/4" DIA. BOLT NUT
Wood Block 80 ft. lbs. per bracket (108 N-M) – 2' o.c. (610 mm) & WASHER
40 ft. lbs. per bracket (54 N-M) – 4' o.c. (1219 mm)
2 LAYERS 5/8" GYPSUM BOARD BOTH
Without filler blocks using 50 ft. lbs. per bracket (68 N-M) – 2' o.c. (610 mm) SIDES (SCREWS 12" O.C. BOTH SIDES)
min. #10 sheet metal screws 25 ft. lbs. per bracket (34 N-M) – 4' o.c. (1219 mm)
into screw stud ALLOWABLE LOAD 700 ft. lbs. per bracket.

GYPSUM BOARD FASTENERS


Allowable Load
FLUSH-TO-WALL ATTACHMENTS Type 1/2" (12.7 mm) 5/8" (15.9 mm)
Fastener Size Gypsum Board Gypsum Board
Hollow 1/8" (3.2 mm) dia. SHORT 50 lbs.(23 kg) —
STEEL ANGLE Wall 3/16" (4.8 mm) dia. SHORT 65 lbs.(29 kg) —
OUTSTANDING LEG Screw 1/4" (6.4 mm), 5/16" (7.9 mm) 65 lbs.(29 kg) —
1" WIDE MAX. Anchors 3/8" (9.4 mm) dia. SHORT — 90 lbs.(41 kg)
3/16" (4.8 mm) dia. LONG — 95 lbs.(43 kg)
1/4" (6.4 mm), 5/16" (7.9 mm),
3/8" (9.4 mm) dia. LONG
Common 1/8" (3.2 mm) dia. 30 lbs.(14 kg) 90 lbs.(41 kg)
Toggle 3/16" (4.76 mm) dia. 60 lbs.(27 kg) 120 lbs.(54 kg)
Bolts 1/4" (6.4 mm), 5/16" (7.9 mm), 80 lbs.(36 kg) 120 lbs.(54 kg)
3/8" (9.4 mm) dia.

GYPSUM BOARD FASTENERS HOLLOW WALL COMMON


SCREW ANCHOR TOGGLE BOLT

98 NATIONAL GYPSUM BOARD PRODUCTS


09 29 00/NGC
Steel Frame Ceilings/Furring Channels or Studs
DESCRIPTION RECOMMENDATIONS DETAILS

There are three types of steel DIRECT ATTACHMENT SPLICE JOINT FOR STUDS
furring members for the 1. Space and position furring
screw attachment of channels in accordance
gypsum board ceilings. with manufacturer
1. Furring Channels recommendation. Wire tie 4 PAN HEAD SCREWS
Resilient Furring Channels, EACH SIDE
2. Resilient Furring Channels
Steel Studs or Furring
3. Steel Studs Channels as shown on
All three are suitable for page 100.
fastening to the lower 2. Apply gypsum board with
chord of steel joists or to its long dimension at right
carrying channels in angles to the channels.
suspended ceiling 16" LENGTH
Locate gypsum board butt OF TRACK
constructions. Furring joints over the center of the
Channels are secured with furring channels. Attach
clips or tie wires. Resilient gypsum board with 1" self-
Furring Channels shall be drilling drywall screws 12" FURRING CHANNEL SPLICE JOINT
secured with wire ties. Steel o.c. located not less than
Studs shall be attached 3/8" nor more than 1/2"
with tie wires as shown on from edges.
page 99. Gold Bond
Gypsum Board shall be SUSPENDED 6" MIN.
applied using gypsum 1. Install 1 1/2" channels 4'
drywall screws spaced not o.c. with No. 8 ga. hanger
greater than 12" o.c. wire spaced a maximum of
RECOMMENDATIONS 4' o.c. along carrying
channels. Attach Furring
These furring systems, when Channels spaced not more
employed with normal than 24" o.c. perpendicular
steel joist construction and TIE WIRES
to 1 1/2" C.R. Channels
gypsum board, constitute with double strand of
non-combustible saddle tied No. 16 ga.

09 29 00
construction and, in galvanized tie wire, or 1
addition, fire resistance 1/2" Furring Channel Clips.
ratings are achieved as SPECIFICATIONS
indicated on page 25. 2. Apply gypsum board with
its long dimension at right See CSI Metal Framing
LIMITATIONS angles to the Furring Specifications on page 97.
Lighting and other fixtures Channels. Locate gypsum
shall be supported by board butt joints over the
framing; do not use gypsum center of Furring Channels.
board to support them. Attach gypsum board with
For large expanses of these 1" self-drilling drywall
ceiling systems with screws 12" o.c. in the field
perimeter relief, control of the board 8" or 12" o.c.
joints must be located a at butt joints, located not
maximum of 50' o.c. in less than 3/8" or more than
either direction; without 1/2" from edges.
perimeter relief, 30' o.c.
maximum in either
direction.

NATIONAL GYPSUM BOARD PRODUCTS 99


INSTALLATION

BAR JOIST
SADDLE TIE WITH DOUBLE STRAND
FURRING NO. 16 GA. GALV. TIE WIRE
CHANNEL

RESILIENT FURRING STEEL STUD SHORT LENGTH


CHANNEL OF TRACK

TIE WIRE
GYPSUM BOARD
(FASTEN WITH TYPE S
DRYWALL SCREWS 12" O.C. MAX.)

FURRING CHANNELS STEEL STUDS IN CEILING SYSTEM

HANGER SPACING
1 1/2" CHANNELS FURRING
4'0" C-TO-C MAX
4'0" C-TO-C MAX CHANNEL

FURRING
CHANNEL

MAX FURRING CHANNEL


GYPSUM BOARD SPACING 24" C-TO-C
MAIN RUNNER

FURRING CHANNEL DETAILS SADDLE TIE

HANGER WIRE,
1 1/2" CHANNEL PEICE 16" 1 1/2" CHANNEL
FURRING CHANNEL CLIP,
LONG-NESTED (TWO WIRE
OR WIRE TIE
TIES EACH SIDE)

FURRING CHANNEL

KAL-KORE OR GYPSUM VENEER PLASTER OR JOINT


3" MAX VINYL “E-Z STRIP” JOINT COMPOUND
BOARD
CONTROL JOINT PARALLEL TO FURRING CHANNELS

FURRING CHANNEL CLIP


HANGER WIRE SHORT PIECE OF
OR WIRE TIE
FURRING CHANNEL
LOOSE WIRE TIES
INVERTED FOR SPLICE
1 1/2" CHANNEL

FURRING
CHANNEL

KAL-KORE OR GYPSUM VENEER PLASTER OR JOINT


BOARD VINYL
“E-Z STRIP” COMPOUND
JOINT
CONTROL JOINT PERPENDICULAR TO FURRING CHANNELS

100 NATIONAL GYPSUM BOARD PRODUCTS


09 29 00/NGC
Wood Frame Walls and Ceilings/Single Layer Construction

DESCRIPTION FLOATING ANGLE 5/8" gypsum board or 1/2" spacing limitations as


METHOD High Strength Ceiling above. With screws,
Floating angle method of Board on ceilings will nominal 1" x 2" furring may
gypsum board application minimize sagging. During be used. Spacing of the
eliminates the use of the cold weather the use of framing members to
perimeter nails at interior polyethylene film as a receive furring must not
corners and where ceilings ceiling vapor retarder is exceed 24" o.c.
STANDARD APPLICATION and walls meet. This not recommended unless 4. In single ply installation, all
Standard application (single method reduces the stress ceiling insulation is ends and edges of gypsum
nailing) Regular Gold Bond and strain on the board if installed prior to board should occur over
Gypsum Board is usually framing settles. application of gypsum framing members or other
applied directly to wood Reference ASTM C 840, board. solid backing except where
framing members. Ceilings Section 9. LIMITATIONS treated joints occur at right
are applied first, then ADHESIVE NAIL-ON 1. 1/4" Gold Bond Gypsum angles to framing or furring
sidewalls. Boards should be METHOD Board should be applied members.
accurately cut and joints only to existing surfaces 5. Hold the gypsum board
abutted but not forced Apply drywall adhesive to
face of studs or joists in and should not be applied firmly against the framing
together. Horizontal directly to framing while fastening with nails
application, long edges at continuous beads.
Reference ASTM C 840 members, except when or screws. Start at the
right angles to nailing used with other thicknesses center and work toward
members, is preferred for it Section 10.
in double layer systems each end and edge,
minimizes joints and FIRE RESISTANCE RATINGS tested for specific purposes. spacing the fasteners as
strengthens the wall or Where fire ratings are Existing walls and ceilings recommended for each
ceiling. Nails shall be required, refer to pages should be sound, flat, level type of application.
spaced not to exceed 7" on 12, 13, 22, and 23. For and without void spaces.
ceilings, or 8" on sidewalls, 6. Lighting and other fixtures
complete construction 1/4" thick gypsum board shall be supported by
a minimum of 3/8" and a details consult the specific should be applied with a
maximum of 1/2" from framing; do not use gypsum
test report. combination of mechanical board to support them.
edges and ends of gypsum fasteners, nails or screws,
board. Gypsum board nails 7. Gypsum board ceilings to
and adhesive that will bond be decorated with water-
or annular ring nails, such to the substrate surface
as the GWB-54 illustrated thinned spray texture shall
covering. Nails or screws be 1/2" or 5/8" thick and
above, are recommended. should penetrate framing
For a description of the SCREW APPLICATION applied perpendicular to
Screw application is often spaced not over 24" o.c.

09 29 00
various types of Gold Bond the framing. Framing shall
preferred as the screw Adhesive should be applied not exceed 16" o.c. for 1/2"
Gypsum Boards, refer to between framing members
pages 58 through 89. holds the gypsum board regular gypsum board and
tight against the framing to bond the gypsum board 24" o.c. for 1/2" High
DOUBLE NAILING when applied as to the substrate. Strength Ceiling Board and
Double nailing is an alternate recommended. Type W 2. 3/8" Gold Bond Gypsum 5/8" gypsum board.
method of attachment 1 1/4" Drywall Screws are Board should not be used 8. Gypsum board ceilings to
devised to minimize nail- driven with an electric on nailing members over receive a spray texture
pops. This system requires screw gun equipped with 16" o.c. When applied to finish must be primed with
doubling up on the field adjustable screw depth ceilings, the gypsum board a sealing latex primer and
nails. The total quantity of control and a #2 Phillips must be applied with the allowed to dry before
nails used does not double, bit. If framing is spaced up paper bound edges at right spraying. This is to
however, since maximum to 16" o.c., screws are angles to the nailing mem- minimize sagging of the
nail spacing is increased to spaced 12" o.c. max on bers and shall not be used gypsum board and
12" o.c. and conventional ceilings and 16" o.c. max to support insulation. 1/2" discoloration problems.
nailing is used on the on walls. If framing is or 5/8" Gypsum Board
perimeter. Application is spaced 24" o.c., screw should not be used on The use of water-based spray
accomplished by first single spacing must not exceed nailing members over 24" textures may cause un-
nailing the field of the 12" o.c. Minimum screw o.c. When applied to primed gypsum board to
board, starting at the center penetration shall be 5/8" for ceilings with the nailing sag when any one or more
and working toward ends wood studs. members exceeding 16" of the following conditions
and edges. Another nail is o.c., the gypsum board exist:
then driven in close RECOMMENDATIONS must be applied with the 1. Unventilated buildings.
proximity (2" to 2 1/2") to Cut gypsum board to allow for paper bound edges at right
a 1/8" to 1/4" gap between 2. Use of vapor retarders
each of the first nails. The angles to the nailing under certain conditions.
first series of nails are then gypsum board and floor to members.
struck again to ensure the prevent potential wicking. 3. Periods of prolonged high
3. If gypsum board ceiling humidity due to either
board is drawn tightly to 1/2" or 5/8" gypsum board boards are nailed to cross
the nailing member. single layer application is weather conditions or
furring, these members closed building units (poor
recommended for interior shall have a minimum
finishing of all buildings drying conditions).
cross section of 2" x 2"
with wood frame (nominal) with same 4. Inadequate framing support
construction. The use of (can occur where framing
changes direction).
5. Improper type or thickness
of gypsum board.

NATIONAL GYPSUM BOARD PRODUCTS 101


RECOMMENDATIONS

SINGLE LAYER GYPSUM Type W spaced not to with 7/16" wide crown 5. ADHESIVE APPLICATION
BOARD APPLICATION (also exceed 12" o.c. on ceilings, with legs having divergent TO FRAMING
Base Layer of Double Layer) 16" o.c. on sidewalls where points. Legs shall be not A. Apply gypsum board
1. NAILS studs are 16" o.c. and 12" less than 1" long for 3/8" adhesive to the wood
o.c. on sidewalls where base board, 1 1/8" long for framing with a caulking
Nails shall be GWB-54 or studs are spaced 24" o.c. 1/2" base board or 1 1/4"
cooler type located 3/8" gun.
Screws for attaching long for 5/8" base board.
min. to 1/2" max. from gypsum board to gypsum
edges and ends of board. 4. CORNERBEADS
board shall be Type G
Nails shall be a max. of 7" spaced as required. Cornerbead shall be nailed
o.c. on ceilings and a max. with gypsum board nails
of 8" o.c. on walls, except 3. STAPLES spaced no greater than 9"
for “Double Nailing” Base layer gypsum board may apart on each flange of the
Procedure. be applied with power- bead with the nails
2. SCREWS driven staples spaced 7" opposite. In lieu of nailing,
o.c. on ceilings; 8" o.c. on cornerbead may be crimp
Drywall screws for attaching sidewalls. Staples shall be applied 6" o.c. with a
gypsum board to wood U.S. Standard 16 gauge special tool.
framing shall be 1 1/4", galvanized wire staples

INSTALLATION

FLOATING INTERIOR was improperly driven,


ANGLES remove it. If properly
To minimize fastener popping driven, reseat just below
in areas adjacent to wall the board face. Remove
and ceiling intersections, any loose material over
the floating angle method reseated nail before treat-
should be used for either ing nail heads with joint
single or double layer compound and
application of gypsum redecorating.
board to wood framing. ADHESIVE NAIL-ON
This method is applicable APPLICATION
where single nailing, The adhesive nail-on system
double nailing or screw for application of gypsum
attachment is used. board to wood framing
Gypsum board should be members strengthens the
applied to ceiling first. wall and minimizes the
FLOATING ANGLES SCREW APPLICATION REPAIRING NAIL-POPS possibility of nail-popping.
No nails in shaded area. Fast, positive, fewer Nail-pops are caused by It reduces the number of
heads to treat. lumber shrinkage after nails in the field, provides
board application; loose for intimate contact and a
gypsum board; improperly continuous bond between
aligned, twisted or bowed the gypsum board and
framing; or improper wood framing. All surfaces
nailing. that come in contact with
the adhesive should be dry,
Pops appearing before/during free of dirt, grease, oil or
decoration should be other foreign materials.
repaired immediately.
Those which occur after SCREW APPLICATION
one or more month’s Drywall screws attach gypsum
heating are usually caused board to wood or steel
by lumber shrinkage and framing or to other gypsum
should not be repaired until boards. They pull the board
after heating season. To tightly to the supports,
repair, renail about 1 1/2" minimizing surface defects
from the popped nail along due to loose boards. When
the framing while applying properly driven, they make
sufficient pressure adjacent a uniform depression free
DOUBLE NAILING ADHESIVE/NAIL-ON to the nail to bring board in of ragged edges and fuzz.
Minimizes nail-pop. Ideal for prefinished boards. firm contact with the
framing. If the popped nail

102 NATIONAL GYPSUM BOARD PRODUCTS


09 29 00/NGC

TECHNICAL DATA

FASTENER SELECTOR FOR WOOD FRAMING


Nail Type Length Gypsum Board Type Thickness
GWB-54 [Annular Ring 1/4" 1 1/4" (31.8 mm) Regular or Foil-back 3/8" (9.4 mm),
(6.4 mm) head, 098 Dia. shank] 1 3/8" (34.9 mm) gypsum board. 1/2" (12.7 mm)
Gypsum Board Nail (Coated Nail length should Regular, Foil-back or Fire-Shield 1/4" (6.4), 3/8" (9.4 mm)
cooler, flat head, diamond point) be sufficient (type X) gypsum board. 1/2" (12.7 mm),
for 7/8" (22.2 mm) penetration 5/8" (15.9 mm),
into the framing member. 1" (25.4 mm)

Where a certain degree of fire resistance is required for gypsum board assemblies and construction, nails of same
or larger length, shank diameter, and head bearing area as those described in the fire test report must be used.
Screws Type W 1 1/4" (31.8 mm) Regular or Foil-back. 3/8" (9.4 mm), 1/2" (12.7 mm),
5/8" (15.9 mm)
Staples US Std. 16 gauge 1" long (25.4 mm) Only in first 3/8" (9.4 mm)
7/16" (11.1) crown with 1 1/8" (28.6 mm) layer of multi- 1/2" (12.7 mm)
divergent points 1 1/4" (31.8 mm) layer application. 5/8" (15.9 mm)

DETAILS

Maximum Framing Spacing CEILING DETAIL JOIST


OUTSIDE CORNER PLATE
For Single-Layer Gypsum Board
PLATE CORNERBEAD
Gypsum Board Gypsum Board Maximum
Thickness Orientation Framing Spacing
to Framing

09 29 00
Ceilings:
3/8" (9.5 mm)A PerpendicularB 16" (406 mm) o.c.
1/2" (12.7 mm) ParallelB 16" (406 mm) o.c.
1/2" (12.7 mm) PerpendicularB 24" (610 mm) o.c.
5/8" (15.9 mm) Parallel 16" (406 mm) o.c.
5/8" (15.9 mm) Perpendicular 24" (610 mm) o.c.

Walls:
STUD PLATE INSIDE CORNER
3/8" (9.5 mm) Perpendicular 16" (406 mm) o.c.
or Parallel
1/2" (12.7 mm) Perpendicular 24" (610 mm) o.c. SPECIFICATIONS
or Parallel
5/8" (15.9 mm) Perpendicular 24" (610 mm) o.c.
or Parallel See CSI 3-Part format Generic/Proprietary Specifications on page
120.
A
Shall not support thermal insulation
B
On ceilings to receive hand or spray-applied water-based
texture material either 1/2" (12.7 mm) gypsum ceiling
board (ASTM C 1396/C 1396M) shall be applied
perpendicular to framing; other gypsum board products
shall be applied perpendicular to framing and board
thickness shall be increased from 3/8" (9.5 mm) to
1/2" (12.7 mm) for 16" (406 mm) o.c. framing and from
1/2" (12.7 mm) to 5/8" (15.9 mm) for 24" (610 mm) o.c.
framing.

NATIONAL GYPSUM BOARD PRODUCTS 103


Wood Frame Walls and Ceilings/Double Layer Construction

DESCRIPTION INSTALLATION
The Gold Bond double layer
system consists of a face 4. Adhesive Application, Cut gypsum board to allow for
layer of gypsum board job- Prefinished Gypsum Board a 1/8" to 1/4" gap between
laminated to a base layer of a. Pre-bow board by storing gypsum board and floor to
gypsum board, or gypsum overnight in such a position prevent potential wicking.
sound deadening board that the ends of each board In double layer construction
applied with power driven curve away from the base use any of the following
screws or staples, or nailed layer when put in vertical appropriate laminating
to the framing in the mounting position. adhesives: (1) Sta-Smooth
conventional manner. b. Apply ready-mix or Sta- Compound or Sta-Smooth
Smooth joint compound in Lite for fast hardening;
nominal 5" ribbons of four (2) All-Purpose Joint
DETAILS 1/4" x 1/4" beads located Compound for spreading
around the perimeter and on the back surface of the
OUTSIDE CORNER center of the boards finish layer boards: (3)
CEILING DETAIL JOIST drywall adhesive meeting
(approximate coverage for
PLATE CORNERBEAD PLATE ASTM C 557.
ready-mix is 9-10 gal./1000
sq.ft and Sta-Smooth is 50- Base layer is applied on
60 lbs./1000 sq.ft.). An ceilings, then sidewalls,
alternative is 2" diameter secured with 1 1/4" Type
daubs 1/2" thick, 16" o.c. W Screws 12" o.c. on
(approximate coverage for ceilings, 16" o.c. on walls;
ready-mix is 5 1/2"-6 nails located 7" o.c. on
gal./1000 sq.ft. and Sta- ceilings; 8" o.c. on
Smooth is 30 - 35 lbs./1000 sidewalls; staples 5" o.c. on
sq.ft.). ceilings and 6" o.c. on
c. Temporarily brace, as sidewalls.
required, to ensure proper Finish layer is temporarily
contact and edge alignment nailed or braced until
of boards. adhesive dries. On walls,
5. Mechanical Application of prefinished boards, applied
STUD PLATE INSIDE CORNER Face Layer vertically, can be pre-
bowed, nailed just top and
Mechanical attachment of bottom.
RECOMMENDATIONS face layer for fire or sound
rated constructions shall be RECOMMENDATIONS
made in accordance with 1. Double layer gypsum board
DOUBLE LAYER 3. Adhesive Application, the specifications for the application over wood
GYPSUM BOARD Regular Gypsum Board system selected. framing is recommended
1. Base layer The finish layer shall be For non-rated construction, for the ultimate in wall
The first layer may be positioned on the wall or nails used in wood framing surfacing and in areas
specified the same as single ceiling within 10 minutes to supplement adhesive where increased fire
layer application except (unless otherwise specified shall be type GWB, of a protection and better sound
that fasteners shall be above) and held in place length to provide 7/8" insulation are desired
driven flush with the board with sufficient temporary minimum penetration into between rooms. (For test
surface and joints will not (nails) (Type G Drywall framing and shall be results see pages 13-14 of
be treated. Base layer must Screws) (bracing) to ensure spaced 16" o.c. max. this guide.) Custom built
not be secured to framing adequate contact and Screws used in wood homes, commercial
with clips. alignment of the gypsum framing shall be Type W, of buildings and party walls
boards. When the bond a length to provide between apartments would
2. Adhesive Application of has developed (usually minimum 5/8" penetration be considered appropriate
Face Layer, General 24 hours) the temporary into the framing and shall areas for double layer
a. All joints shall fall at least (fasteners) (bracing) shall be be spaced 24" o.c. max. application.
10" from parallel joints in removed. Resulting holes If no adhesive is used,
the base layer. Adhesive shall be filled flush to the standard fastener spacings
shall be: (select one) surface with Joint shall prevail.
b. ProForm all-purpose ready Compound and the joints
mix joint compound or shall be finished.
Sta-Smooth setting type Cornerbead shall be
compound applied with a applied at all exterior SPECIFICATIONS
notched spreader to the angles.
back side of the finish See CSI 3-Part format
layer. Generic/Proprietary
c. Adhesive is applied with a Specifications on
caulking gun. Align board page 120.
edges. Reference ASTM
C 840, section 9.

104 NATIONAL GYPSUM BOARD PRODUCTS


09 29 00/NGC

2. Laminating is an excellent
way to apply Durasan, the FINISH LAYER TAPERED EDGE
CEILING JOISTS
vinyl-surfaced gypsum GYPSUM BOARD
board. This method
eliminates any
visible attachment.
3. Sta-Smooth Compound
or Sta-Smooth Lite is
recommended for
laminating as well as for
joint treatment where fast
hardening is required.
LIMITATIONS
BASE LAYER
1. Joints of succeeding layers GYPSUM BOARD
must not fall at the same
location. For greatest
strength, it is recom-
mended that the boards of LAMINATING
each layer be staggered so ADHESIVE
that joints of each layer are
at least 10" apart.
2. During cold weather,
maintain a room
temperature of not less 2 X 4 WOOD
than 40˚F during FRAMING
mechanical attachment of WOOD
gypsum board, and
between 50˚F and 70˚F
for 48 hours before
lamination, joint treatment, PROFORM JOINT TREATMENT
BASE
texturing and decoration, (ALL JOINTS AND CORNERS)
and continuously thereafter
until completely dry.

09 29 00
SOUND TRANSMISSION CLASS 45 SOUND TRANSMISSION CLASS 58
FIRE RESISTANCE RATING 1 HR. FIRE RESISTANCE RATING 2 HRS.

1/2" FIRE-SHIELD C GYPSUM BOARD 2 LAYERS 5/8" FIRE-SHIELD GYPSUM BOARD

1/4" GYPSUM BOARD


3 1/2" MINERAL WOOL
OR GLASS FIBER
2 X 4, 16" O.C.

4D NAILS 12" O.C.


2 X 4 PLATE

JOINT COMPOUND CAULKING

CAULKING

NATIONAL GYPSUM BOARD PRODUCTS 105


Resilient Furring Channel Construction

DESCRIPTION RECOMMENDATIONS

Resilient Furring Channels are 3. The point of intersection INSTALLATION (RESILIENT Where channel ends overlap
fabricated of galvanized between the wall and floor FURRING CHANNELS ON between joists, wood
steel with expanded metal shall be caulked prior to ONE SIDE OF PARTITION) blocking may be used to
legs that provide resiliency application of baseboard to Wood framing shall be take Type W Drywall
to reduce sound obtain the best sound erected in accordance with Screws driven through both
transmission through wood isolation. conventional procedure, channels through both
framed wall and ceiling 4. On wood studs fasten studs (16" o.c.) (24" o.c.). A flanges, or Type S Pan
assemblies. channel through alternate 1/2" x 3" shim strip of Head Screws may be used
STANDARD APPLICATION flanges at each stud using gypsum board shall be to fasten channel ends
1 1/4" GWB-54 Nails or nailed to the base plate together.
Resilient Channels have
punched holes spaced 1" Type W Drywall Screws. continuously on the APPLICATION OF GYPSUM
o.c. in the leg flanges to Fasten both flanges at resilient side of the BOARD
facilitate fastening to channel ends. partition. An additional
strip of gypsum board or a Attach gypsum board to
framing members spaced 5. Resilient Furring Channels Resilient Furring Channels
either 16" or 24" o.c. The should be fastened to wood Resilient Furring Channel
should be used at the with 1" Type S Drywall
12' long channels are joists with one Type W Screws 12" o.c. and to
applied perpendicular to Drywall Screw at each joist ceiling line. Resilient
Furring Channels shall be framing through filler strips
the framing members and in alternate flanges. with drywall screws 12"
spaced not more than 24" Channel ends may fall on located horizontally, 24"
o.c. max., and be secured o.c. that penetrate framing
o.c. Gypsum board is then or between joists but must 5/8" minimum.
attached to the Resilient be fastened to prevent any through alternating flanges
sliding movement which at each stud with 1 1/4" Note: Screws used to attach
Channels with power gypsum board to resilient
driven, Type S Drywall could create squeaking GWB-54 Nails or Type W
noises. When channel ends Drywall Screws. Abutting furring channels shall not
Screws spaced contact wood framing.
12" o.c. fall between joists, overlap channel ends shall be
approximately 1 1/2" and located over studs, shall be
RECOMMENDATIONS screw-attach through both gapped and shall be
1. Construction, as shown in the legs into a wood block held fastened through both
detail below, is recommend- above the channels, or flanges.
ed to achieve sound and fire- overlap approximately 6" INSTALLATION (RESILIENT
rating as shown on pages and fasten both channels FURRING CHANNELS ON
11-26. near ends with 3/8" Type S CEILINGS)
2. A 3" wide strip of 1/2" thick Pan Head Screws.
Wood framing shall be
gypsum board should be LIMITATIONS erected in accordance with
used at the floor line to conventional procedure,
assure a solid base for 1. Spacing of Resilient Furring
Channels should not joists (16" o.c.) (24" o.c.)
attaching the gypsum board Resilient Furring Channels
and the base. An additional exceed 24" o.c. nor span
more than 24". shall be installed
strip of gypsum board or a perpendicular to joists,
Resilient Furring Channel 2. Use only 1/2" or 5/8" spaced 24" o.c. and a
should be used at the gypsum board with this maximum of 6" from the
ceiling line. system. ceiling-wall line with Type
W Screws through alternate
flanges at each joist.
Where channel ends overlap
DETAIL at a joist, Type W Drywall
Screws must be driven
through both channels
5/8" FIRE-SHIELD
through both flanges into
GYPSUM BOARD
joist.

2 X 4 STUD
SPECIFICATIONS
3 1/2" MINERAL WOOL OR
GLASS FIBER FOR STC 50
See CSI 3-Part format Generic/Proprietary Specifications on
page 120.
1/2" RESILIENT
FURRING CHANNEL
5/8" FIRE-SHIELD
GYPSUM BOARD

TYPICAL SECTION

106 NATIONAL GYPSUM BOARD PRODUCTS


09 29 00/NGC

INSTALLATION

1" DRYWALL SCREWS DRYWALL SCREWS

2 x 4 PLATE

2 x 4 STUDS

3 1/2" MINERAL
WOOL OR
GLASS FIBER

RESILIENT
SPLICE ON JOIST FURRING
1 1/4" Type W Screws CHANNEL
24" O.C.

2 x 4 PLATE
TAPE JOINT
TREATMENT
3" x 1/2" THICK STRIP
GYPSUM BOARD FILLER
6"

09 29 00
SPLICE BETWEEN JOISTS
3/8" Type S Pan Head Screws

NOM. 1 X 4 BLOCK

SPLICE BETWEEN JOISTS, ALT.


1 1/4" Type W Screws

NATIONAL GYPSUM BOARD PRODUCTS 107


Gypsum Board Over Masonry
DESCRIPTION

A. Z FURRING CHANNEL application, install wood 2. Power driven fasteners 5. Since the use of foam
1. Application of Foam. furring strips (nominal 2" should be used to secure plastic insulation is
Z Furring Channel is used wide x 1/32" greater than furring to monolithic regulated by many building
to secure rigid insulation the foam thickness) concrete. Regular concrete codes, consultation with
and gypsum board to horizontally along the wall- nails can be used for local building authorities is
masonry walls. Insulation ceiling and wall-floor fastening to unit masonry. If recommended before
thickness (1", 1 1/2", 2") angles, where horizontal block is old, test nailing installation.
determines depth of Z gypsum board joints will should be done in advance Since unprotected foam
furring web. The channel is fall, and around door and to determine optimum size insulation may represent a
applied vertically and window openings. For and type of nail. fire hazard, it should be
fastened to the masonry vertical gypsum board 3. During cold weather, room covered promptly and
wall through the short (3/4") application, furring strips temperature between 50˚F completely with gypsum
flange with suitable are required at the and 70˚F must be board.
masonry fasteners 24" o.c. horizontal wall-ceiling and maintained uniformly
maximum. Application is wall-floor lines and around during application and
progressive. After fastening door and window until adhesive is thoroughly
each Z Furring Channel, a openings. dry or premises are
24" wide floor-to-ceiling- Masonry surface must be dry, occupied. Provide
high insulation board is fit clean and free of dust, dirt, adequate ventilation.
between the wall and the form release agents, oil, 4. Gypsum board is not
wide (1 1/4") flange. grease or water soluble recommended in areas
2. Application of Gypsum materials. Treat painted where it will be exposed to
Board. Erect Gold Bond masonry as recommended excessive moisture or
Gypsum Board either for laminating to painted continued high humidity.
vertically or horizontally to surfaces. Apply adhesive to
the Z Furring Channels. the foam insulation in 3/8"
Gypsum board edges or dia. beads continuously
ends that run parallel to the around the perimeter and
channels shall be centered through the field in the long DETAILS
and abutted over channels. direction with the beads
Fasten gypsum board with spaced 16" o.c. Contact
1" Type S Drywall Screws adhesive manufacturer for
spaced 12" o.c. When compatibility with foam. 1 1/4 "
gypsum board erection is Apply the foam boards
complete, finish all joints horizontally to the wall
and screw heads in with a sliding motion and
accordance with ProForm hand press entire board to
Joint Finishing System. ensure full contact of
Prefinished gypsum board adhesive and wall surface.
may be laminated vertically 2. Application of Gypsum
to the channels with screws 1", 11/2", 2"
Board. ProForm All-
at top and bottom. Purpose Joint Compounds
Limitations may be used. (Do not use
Power driven fasteners should water base compounds for
be used to secure furring laminating prefinished
only when wall is boards to foam.)
monolithic concrete. Permanent nails or screws 3/ "
4
Regular concrete nails can 12" o.c. are required to
be used for fastening to unit fasten gypsum board to
masonry. If block is old, wood furring. Gypsum Z FURRING
test nailing should be done board must be installed a
in advance to determine minimum of 1/8" from the
optimum size and type floor. Use temporary nails
of nail. or bracing as necessary to
hold gypsum board boards SPECIFICATIONS
B. LAMINATION in firm contact to the foam
1. Application of Foam. until adhesive has dried or
Insulation may be urethane set. See CSI 3-Part format Generic/Proprietary Specifications on
foam or extruded page 120.
polystyrene. Expanded Limitations
bead polystyrene is not 1. Nails or screws used for
recommended. For attachment of gypsum
horizontal gypsum board board to furring strips must
not penetrate through the
furring.

108 NATIONAL GYPSUM BOARD PRODUCTS


09 29 00/NGC

RECOMMENDATIONS

Z FURRING 4. Continue in this manner, LAMINATION 4. Cut gypsum board to allow


1. Begin application of with Z furring 24" o.c. to 1. Masonry or monolithic for 1/8" to 1/4" clearance
Z furring members by end of wall. Locate last Z concrete shall be above between board and floor to
positioning first piece so that web is located a grade, dry, free of dust, prevent potential wicking.
vertically at a corner. distance equal to insulation loose particles, oil, grease 5. Install gypsum board by
Locate the piece on the thickness from adjoining or other foreign material. hand pressing each board
wall adjacent to the wall wall. Cut last insulation tight to the wall making
board to fit remaining 2. Joint compound used as
being insulated first. adhesive shall be mixed to certain that all daubs are in
space. positive contact with the
2. Insulation thickness a consistency thick enough
determines distance of 5. At exterior corner, attach to allow a 2" daub to stick board.
Z furring web from wall the Z through its wide to the underside of a broad 6. Support boards at each
being insulated. At the flange, with narrow flange knife held parallel to the corner to keep them from
appropriate distance, and extending beyond the floor. slipping to the floor by use
with wide flange pointing corner. Begin with a of a concrete nail driven
narrow strip of floor-to- 3. Apply 2" to 2 1/2" diameter
toward applicator, secure daubs of adhesive 1/2" through a small block of
Z furring with appropriate ceiling insulation, wider nominal 1" lumber.
than insulation thickness thick, 16" o.c. in both
fasteners through short directions to the masonry 7. Butt boards to each
flange. (Note to Specifier: but not exceeding 3".
Continue application of wall. The adhesive layout previously positioned
Power driven fasteners are must provide for a row of board to ensure flush joints.
not recommended for use furring and insulation
progressively as described daubs located a maximum 8. If necessary to hold boards
with masonry block.) of 2" from board ends, and
above. straight, plumb and in
3. Install 24" wide floor-to- care must be exercised to proper alignment, drive
ceiling insulation board, 6. At windows, doors and trim center daubs on vertical
areas, use wood nailers masonry nails through
pressed snugly against web joints. No more adhesive small wood blocks and into
of first Z. Install next Z with (nom. 2" wide x insulation shall be applied to the wall
thickness plus 1/32"). Use masonry at high points
wide flange overlapping than will be covered with only. After adhesive is dry
edge of first insulation the nailers also at wall-floor board in 15 minutes.
angles to support trim and (24 - 48 hours) remove
board. Fasten to wall Approximate coverage for temporary nails.
through narrow flange. provide backing for base. joint compound (powder)
7. Apply gypsum board with used as an adhesive is 30- 9. Fill all holes and treat joints
1" Type S Screws through 35 lbs./1000 sq. ft. with tape and joint

09 29 00
flanges of Z furring, 12" o.c. compound.

INSTALLATION

Z FURRING CHANNEL HORIZONTAL INSTALLATION DAUB METHOD USING


WITH DRYWALL ADHESIVE JOINT COMPOUND

NATIONAL GYPSUM BOARD PRODUCTS 109


Solid Laminated Partitions
DESCRIPTION DETAILS

Laminated Partitions have C. Economical. The laminated


been developed for use partition offers a substantial GYPSUM BOARD CORNERBEAD
where sturdy, nonload- saving in installation time
bearing walls are desired. and subsequently in labor 12d NAIL/12" O.C.
The total thickness is costs over other types of
1" FIRE-SHIELD SHAFTLINER
nominal 2". 1" Fire-Shield solid partitions. The 1"
Shaftliner is used between gypsum core is quickly and
face layers of gypsum easily installed and the
board. large sheets of gypsum
PHYSICAL PROPERTIES board provide a dry finish
surface in minimum time.
A. Fire Resistance. Fire
endurance ratings have LIMITATIONS
been established by the The laminated partition is TAPE AND JOINT
COMPOUND
following tests: adapted to any type of
FM WP 671 - 1 HOUR: building for nonload-
1" FIRE-SHIELD SHAFTLINER
1/2" Regular Gypsum face bearing partitions not
boards and ProForm Brand exceeding 12' in height. GYPSUM BOARD

Sta-Smooth joint Further limitations to height


compound* as laminating are based on the partition CORNER WALL DETAIL
compound. length in the table below. 09250U

UL U505 - 2 HOUR: *Required for fire rating. Scale: 3" = 1'-0"

5/8" Type X Fire-Shield


face boards and ProForm
Brand Sta-Smooth joint
compound* as laminating
compound. 1" FIRE-SHIELD
SHAFTLINER
UL U525 - 2 HOUR:
1/2" Fire-Shield Type C
GYPSUM BOARD
face board and ProForm
Brand Sta-Smooth JOINT
COMPOUND
compound* as laminating ADHESIVE
compound.
UL U529 - 2 HOUR: BASE
1/2" Fire-Shield Type C FLOOR LINE L FLOOR
face boards and ProForm RUNNER
Brand Sta-Smooth joint
compound* as laminating
compound. VERTICAL SECTION USING
METAL FLOOR RUNNER
B. Sound Isolation. An STC 09250T
rating of 34 has been Scale: 3" = 1'-0"
achieved in tests con-
ducted in accordance
with ASTM E 90.

CAULKING
1/4"

1" FIRE-SHIELD SHAFTLINER

TECHNICAL DATA

Maximum Partition Length


Ceiling Height Between Restraints
L RUNNER
12' (3658 mm) 14' (4267 mm)
11' (3353 mm) 20' (6096 mm) CASING BEAD
10' (3048 mm) Over 20' (6096 mm)
ANCHORAGE TO CONCRETE
CEILINGS, WALLS OR COLUMNS
09250V
Scale: 3" = 1'-0"

110 NATIONAL GYPSUM BOARD PRODUCTS


09 29 00/NGC

RECOMMENDATIONS

1. Secure floor runner to floor board joints 12" from the


STEEL JAMB STRAP AND ANCHOR
CLIP ASSEMBLY with approved fasteners 24" Shaftliner joints and 24"
o.c. Ceiling runner shall be from joints on each side of
secured in an appropriate the wall.
manner to the ceiling Face boards are then screwed,
construction. The L runner 12" o.c. to the top and
shall be used as both floor bottom runners with 1 7/8"
and ceiling runners in Fire- Type S screws and are
Rated construction. secured to the Shaftliner
2. The 1" Fire-Shield with 1 5/8" Type S Drywall
GYPSUM BOARD
Shaftliner, cut 1/4" shorter Screws spaced 24" o.c.
than wall height, shall be horizontally and vertically
CLIPS NAILED TO SHAFTLINER installed vertically and shall to include screws along
(4d nails bent over)
be fastened to the floor and the vertical edges of each
JAMB DETAIL ceiling runners with two board.
09250X 1 5/8" Type S Drywall Gypsum board joints shall be
Scale: 3" = 1'-0" Screws, each located 2" reinforced with paper tape
from each edge of the and finished with joint
Shaftliner boards. compound.
3. Sta-Smooth Compound 4. Door frames shall be
1" FIRE-SHIELD SHAFTLINER shall be applied evenly vertical, plumb and true,
with a notched spreader and shall be securely
WOOD CASING
(with 1/4" x 1/4" notches, anchored to floor and
1 1/2" o.c.) to the back side ceilings as shown on
GYPSUM BOARD
STOP of the 4' wide, ceiling the plans.
height gypsum board face
boards. Install the boards 5. Completed partition shall
vertically to both sides of be straight and plumb.
the Shaftliner. Stagger

09 29 00
DOOR SPECIFICATIONS
JOINT COMPOUND ADHESIVE
See CSI 3-Part format Generic/Proprietary Specifications on
page 120.
WOOD JAMB DETAIL
09250W
Scale: 3" = 1'-0"

NATIONAL GYPSUM BOARD PRODUCTS 111