10MW Solar Power Assessment & Synopsis (SPAnS) Report PDF
10MW Solar Power Assessment & Synopsis (SPAnS) Report PDF
Designed By
Checked By Amrit Mandal
Rev. No. 1.00
Dated: __/__/2015
E-Mail ID: info@indecons.co
Website: https://indecons.co
Solar PV Module Specification & Array Design Criteria Solar Inverter Design Criteria
Required Electrical Characteristics of SPV Modules Required Operating condition Details Inverter Type String Inverter (MPPT)
Quantity 53
Design criteria IEC-61853-1, IEC 61215, Maximum System Voltage 1000V INPUT (DC)
(IEC)
IEC 61646, IEC 62108 Max absolute Input Voltage 1000V
Maximum Fuse Rating 15A
MPPT input DC range 585 to 850V @ 1050KW
Watt Peak 250Wp Limiting Reverse Current 15A
Operating temp Range (-10 to 60)0C Nominal MPP voltage range 470V-900V
VOC 37.20V Max Input Current per module (Idcmax,m) 694A
Max Static Load Front 5500PA
VMPP 30.10V (Snow +Wind) Max combined DC input current 2082A (3x694A)
ISC 8.87A Max Static Load Rear (wind) 2500PA Nos. of Independent MPP inputs 15
IMPP 8.30A OUTPUT (AC)
Required Temperature Co-eff. characteristics @STC Rated Output Power @p.f=1 1170KW
Module Efficiency/module 15% Max. Apparent AC Power
0
NOCT ( C) 45 ± 2 C 0 1170KVA
area
Power Threshold 20W
Power Tolerance ±2% Module Efficiency (%/0C) -0.07 ± 0.01
Nominal AC Voltage 690V
Temp. Co-Eff. Pmax (%/0C) -0.43 ± 0.05 AC Power Frequency/ range 50Hz
Technology Si-Poly
Temp. Co-eff of Voc (%/0C) -0.34 ± 0.05 Max. output current 975A
No. of cells 60 cells in series Temp. Co-eff of Isc (%/0C) 0.065 ± 0.05 Fault Current 1554
Feed-In phases/connection phases 3-phase 3W+PE
PV Module Power Output @different Irradiation Level Efficiency
Max. Efficiency 98.7%
PV Module Behavior at different irradiance level Inverter Connection Details
Total nos. of inverter 53
PV Parameters @ 1000W/m2 @ 800 W/m2 @ 400 W/m2 Nos. of strings per inverter 4
PMPP 249.8.2W 200.6 W 100.00 Connection of strings/inverter Parallel
VOC 37.2V 36.8 V 35.8V Inter-inverter connection Parallel into Cu busbar
VMPP 30.1V 30.2 V 30.1V Inter-Inverter isolator Provided
ISC 8.87A 6.64A 3.55A
IMPP 8.31A 7.10A 3.33A
Module efficiency 15.54% 15.32% 15.27%
Temperature co-eff -0.43%/0C -0.43%/0C -0.44%/0C
Components Certifications t
Solar PV module IEC 61215, IEC 61646, Use of RFID is mandatory in all types of PV
IEC 62108 modules, regardless of their capacity, when used in
such systems.
Solar inverter Inverter should also qualify damp heat cycling/study
IEC 61683, IEC 60068 state and thermal cycling (as per the relevant
standard). It should also qualify the hammer test and
robustness of terminations and drop test.
Yearly Sunshine Duration Housing The field and array junction boxes have to
IP65 standard, comply with IP65 standard. The electronics,
IP including inverters, CPU, charge controllers, MPPTs,
and AC & DC distribution boxes, should have IP 21
standards.
Cables, Standards for cables, switches, circuit breakers,
connectors, connectors, junction boxes, and enclosures will
switches & circuit remain the same as in the administrative approval.
breakers All components of the system should conform to
standard, and the composite system should also be
certified with testing laboratories.
SPV system design IEC 62124 and A committee of PV experts/consultants will study the
& installation I standards and identify the minimum requirements,
practices and the same will be intimated.
Energy meters All PV power plants above 1 kWp have to install
IEC 62053-21 energy meters for accounting and also have to
provide energy delivery guarantee for the customers.
Designed By
Checked By Amrit Mandal
Rev. No. 1.00
Dated: __/__/2015
E-Mail ID: info@indecons.co
Website: https://indecons.co