Professional Documents
Culture Documents
Outline
Page 2
1
11/5/2019
Outline
• CT connections
Page 3
Introduction
Page 4
2
11/5/2019
Page 5
• The most common type of C.T. is consists of an iron toroid, which forms the core of
the transformer, and is wound with many secondary turns.
Page 6
3
11/5/2019
Page 7
Steady-State Performance of CT
• The function of transducers is to provide current and voltage signals to the relays
(and meters) that are faithful reproductions of the corresponding primary quantities.
• Thus, the performance of the relays can be assessed in the presence of
transformation errors introduced by the transducers.
• CTs are usually two types,
˗ Metering CT → performance is important during normal loading conditions
˗ Relaying CT → performance is important during fault conditions
• In spite of this difference, the performance of both measuring and relaying CT may
be calculated with the same equivalent circuit but with different values of equivalent
circuit parameters.
Page 8
4
11/5/2019
Steady-State Performance of CT
Metering CTs
Protective CTs
Page 9
Steady-State Performance of CT
• In the equivalent circuit shown in fig (a), the primary winding of the CT is connected
in series with the power network and its primary current I1’ is dictated by the network.
• Leakage impedance of the primary winding Zx1 has no effect on the performance of
the transformer, and may be omitted.
• Referring all quantities to the secondary winding, the simplified equivalent circuit of
fig (b) is obtained.
Page 10
5
11/5/2019
Steady-State Performance of CT
• Load impedance Zb is known as the burden on the CT and includes the impedance
of all the relays, meters connected to the secondary winding, as well as the leads
connecting the secondary winding terminals of the CT located in the substation yard
to the protection equipment, which is located in the control house of the substation.
secondary current at which the burden is specified, the burden would be 25Zb volt-
amperes.
Page 11
Steady-State Performance of CT
• Referring to the phasor diagram in fig, the voltage Em across the magnetizing
impedance Zm is given by,
• For small values of the burden impedance, Eb and Em are also small, and
consequently Im is small.
Page 12
6
11/5/2019
Steady-State Performance of CT
• Per unit error ϵ , is small for small values of Zb i.e. CTs work at their best when
they are connected to very low-impedance burdens. In the limiting case of zero-
burden impedance (and a small Zx2) I1 = I2, and the CT error is zero.
• CT error is also presented in terms of a ratio correction factor R instead of the per
unit error ϵ.
• The ratio correction factor (RCF) is defined as the constant by which the name
plate turns ratio n of a CT must be multiplied to obtain the effective turns ratio.
Page 13
Steady-State Performance of CT
Page 14
7
11/5/2019
Steady-State Performance of CT
Page 15
Multi-Ratio CT
• Each CT may be provided with several taps, which can be used to obtain a turns
ratio that is most convenient in a given application.
• For example, a dual-ratio consists of a center tapped secondary winding such that
the ratio obtained by the tap is usually one-half the ratio obtained by the full
secondary winding.
• A schematic example is previously shown with 200 amperes flowing in the primary, a
connection X2 – X3 will produce 5 amperes out of the secondary. As the load grows
to 400 amperes, the secondary circuit will be reconnected to X1 – X3 to still produce
5 amperes in the secondary circuit.
Page 16
8
11/5/2019
Multi-Ratio CT
Single-Ratio CT Dual-Ratio CT
Page 17
Multi-Ratio CT
Page 18
9
11/5/2019
Numerical Problem
• Evaluate the performance of the multi-ratio CT with turns ratio 100:5 for the following
(a) IB = 5 A, ZB = 0.5 Ω
(b) IB = 10 A, ZB = 0.8 Ω
(c) IB = 20 A, ZB = 1.5 Ω
Page 19
Page 20
10
11/5/2019
• For example, 10C400 CT will have an error of less than or equal to 10% at a
secondary current of 100 A for burden impedances that produce 400 V or less at its
secondary terminals.
• The letter “C” in the class designation implies that the transformer design is such that
the CT performance can be calculated, whereas the letter “T” signifies some
uncertainties in the transformer design, and the performance of the CT must be
determined by testing the CT.
Page 21
Page 22
11
11/5/2019
Page 23
• An alternative way is to label the primary winding terminals H1 and H2, and the
secondary winding terminals X1 and X2. H1 and X1 may then be assumed to have
the polarity mark on them. Both of these conventions are shown in fig.
Page 24
12
11/5/2019
• When a fault occurs on a power system, the fault current is given by,
• When the current is passed through the primary winding of a current transformer, the
response can be examined by replacing the CT with an equivalent circuit.
• Assuming an ideal CT has no losses and exciting current, all further analysis can be
carried out in terms of equivalent secondary quantities (is and Is).
Page 25
• Integrating for each component in turn, the steady state peak flux over a quarter
cycle is given by:
Page 26
13
11/5/2019
• Hence, the ratio of the transient flux to the steady state value is:
where X and R are the primary system reactance and resistance values.
• The CT core has to carry both fluxes, so that:
• The term (1+X/R) has been called the 'transient factor' (TF), the core flux being
increased by this factor during the transient asymmetric current period.
• From this it can be seen that the ratio of reactance to resistance of the power system
is an important feature in the study of the behaviour of protection relays.
Page 27
• Alternatively, L/R is the primary system time constant T, so that the transient factor
can be written:
• Again, fT is the time constant expressed in cycles of the a.c. quantity T’, so that:
Page 28
14
11/5/2019
Page 29
Saturation of CTs
Page 30
15
11/5/2019
Saturation of CTs
• However, because of the nonlinear nature of the B-H curve for the CT, as the knee of
the excitation characteristics is passed, any further increase in flux demand causes a
disproportionately large increase in the magnetizing current requirement of the CT.
• It may also be noted that I0 is no longer sinusoidal and its waveform has a prominent
peak.
Page 31
Saturation of CTs
Page 32
16
11/5/2019
Saturation of CTs
• Thus, as the primary current ↑, a stage comes when the magnetizing current
requirement is so large that almost all the transformed current is taken up by the CT
for the sole purpose of magnetization, and that there is hardly any current available
for the burden.
• When this occurs, we say that the CT is completely saturated.
• The secondary induced voltage and burden current waveforms of a CT, operating in
saturation, are highly distorted.
• Thus, the secondary current of a CT may not represent the primary current faithfully
if the CT goes into saturation, and hence relays which depend upon the secondary
current are likely to mis-operate during this period.
Page 33
Auxiliary CTs
Page 34
17
11/5/2019
Wye Connection
Page 35
Delta Connection
Page 36
18
11/5/2019
Page 37
• The neutral of the main CT secondaries is not connected to the burden neutral.
Instead, a set of auxiliary CTs have their primaries connected in wye and their
secondaries in delta.
• The neutral of the auxiliary CTs is connected to the neutral of the main secondaries
through the neutral burden Zn.
• The secondary windings of the auxiliary CTs provide a circulating path for the zero-
sequence current, and it no longer flows in the phase impedance burdens Zf.
Page 38
19
11/5/2019
Flux-Summing CT
• It is possible to obtain the zero-sequence current using a single CT, rather than by
connecting the secondaries of three CTs as in figure.
• If three-phase conductors are passed through the window of a toroidal CT, the
secondary current is proportional to (Ia + Ib + Ic) = 3 I0.
• Since this arrangement effectively sums the flux produced by the three-phase
currents, the CT secondary contains the true zero-sequence current.
Page 39
Voltage Transformers
• VTs (also known as potential transformers) are normal transformers with the primary
winding connected directly to the high-voltage apparatus, and with one or more
secondary windings rated at the standard voltage of 120 V (for phase-to-phase
voltage) or, equivalently, 69.3 V (for phase-to-neutral voltage).
• Their performance, equivalent circuit, and phasor diagrams are similar to those of a
power transformer.
• At operating voltages higher than 345 kV, VTs are rather expensive and
consequently, they are usually found on low, medium, and high-voltage systems.
• At extra high voltages, capacitive VTs, are the more usual sources for relaying and
metering.
Page 40
20
11/5/2019
Voltage Transformers
Page 41
Voltage Transformers
Page 42
21
11/5/2019
• One of the most common voltage sources for relaying (particularly at higher
voltages) is the CCVT.
• A string of capacitors is used as a potential divider between the high-voltage
apparatus and ground, and a tap provides a reduced voltage of about 1 – 4 kV.
• The tap point is connected to a transformer through an inductance, as shown in fig.
• The turns ratio of the transformer is such that the secondary voltage is the standard
voltage (120 V or 69.3 V) required for relaying.
• The burden impedance is Zb, and Zf is a specially designed damping circuit for
suppressing ferroresonance that may occur under certain conditions.
Page 43
Page 44
22
11/5/2019
• Under normal steady-state operating conditions, the load current drawn by the
• As the transformer supplies the load current, there may be a phase shift between
• Consider the Thevenin equivalent circuit of the capacitive divider. The Thevenin
voltage is given by Eth = EpriC1/(C1 + C2), and the Thevenin source impedance is a
• If the primary and secondary currents in the transformer are I1 and I2, respectively,
then,
Page 45
• Clearly, the secondary voltage will have a phase angle error, unless the inductance L
is in resonance with (C1 + C2) at the power system frequency ω.
• To avoid a phase angle error, an inductance of an appropriate size is introduced to
satisfy the resonance condition:
Page 46
23
11/5/2019
Page 47
• The VT windings are also marked to indicate their polarity. Terminals of like polarity
may be identified by dots, or by terminal labels H1, H2 and X1, X2.
Page 48
24
11/5/2019
Page 49
• When a fault occurs on a power system, the voltages at different points on it may fall
suddenly and then they may suddenly increase when the fault is cleared.
Voltage divider
Electromagnetic VT
CVT
Page 50
25
11/5/2019
• These results clearly indicate that the response of the electromagnetic transformer is
close to the ideal, whereas the capacitor voltage transformer generates undesirable
damped oscillations when the sudden changes of system voltage occur.
• These oscillations, which arise because of the tuned nature of the transformer circuit,
together with sustained oscillations which can arise because of ferroresonance, can
affect the behaviour of protective equipment.
Page 51
26