Professional Documents
Culture Documents
WLSA -INDIA
WLSA-INDIA/GKT/2006
Instrument Transformers
Gkt/RELRPT/0605
Instrument Transformers
CURRENT TRANSFORMERS
Gkt/RELRPT/0605
Current Transformers
Gkt/RELRPT/0605
Current Transformers
Gkt/RELRPT/0605
Current Transformers
Gkt/RELRPT/0605
Current Transformers
Gkt/RELRPT/0605
Current Transformers
Important terms
► Current transformer (CT) is an instrument transformer
in which the secondary current , in normal condition of
use , is substantially proportional to the primary current
and differs in phase from it by an angle app. Zero for an
appropriate direction of the connection.
Gkt/RELRPT/0605
Current Transformers
Important terms
►Transformation ratio Kn is ideally….
Gkt/RELRPT/0605
Current Transformers
Important terms
► Phase angle error: The difference in phase between the
primary and secondary current vectors, the direction of
the vectors chosen such that the angle is zero for a
perfect transformer
Gkt/RELRPT/0605
Current Transformers
Important terms
Gkt/RELRPT/0605
Current Transformers
Important terms
► Burden= The impedance of the secondary circuit in Ohms
& power factor
► Burden is usually expressed as the apparent power (S) in
Volt-amperes absorbed at a specified power factor at the
rated secondary current Secondary winding impedance
(Internal burden)- ZS
Burden : = ZS+ ZO
Gkt/RELRPT/0605
Current Transformers
Important terms
• The induced voltage at this accuracy limit current is called the accuracy-
limit voltage, more popularly known as knee-point voltage.-ALV or KPV
Gkt/RELRPT/0605
Current Transformers
Important terms
Gkt/RELRPT/0605
Current Transformers
Effect of saturation
► If the CT core is saturated with flux during every half cycle then there
is a “Table-top” in every half cycle, and the dΦ/dt during the table top
is zero and hence the CT secondary output collapses & the CT
produces an output of pulses instead of reproducing faithfully the
wave shape of the primary current on the secondary side.
CT e.m.f output
Saturation region
Flat part
(dØ/dt=0)
Flux wave
Ø curve
Gkt/RELRPT/0605
Current Transformers
Important terms
► Accuracy class: A designation assigned to a current transformer the
error of which ( Current error, Phase displacement & Composite error)
remain with specified limits under prescribed conditions of use.
• For measuring current transformers the accuracy class is designated
by the highest permissible percentage Current error at the rated
current prescribed for the accuracy class .
• Standard accuracy classes for measuring current transformers are
0.1, 0.2, 0.5, 1, 3 , 5
• The name plate details shall be marked as,
15 VA Class 0.5 FS 10
15 VA –Burden, Class 0.5 accuracy class , FS 10 Instrument safety
factor, which is defined as the ratio of rated instrument limit
primary current to the rated primary current
• Current transformers with extended current rating, shall have this
rating indicated immediately following the class designation-
e.g. 15 VA Class 0.5 ext.150%
Gkt/RELRPT/0605
Current Transformers
Important terms- Accuracy class…
• For protective current transformers the accuracy class is designated
by the highest permissible percentage Composite error at the rated
accuracy limit primary current prescribed for the accuracy class
concerned, followed by the letter “P”( meaning protection).
5P ±1 ± 60 5
10P ±3 --- 10
15P ±5 --- 15
Gkt/RELRPT/0605
Current Transformers
CT-Standard Symbols
► One output at the secondary—two alterntate symbols
Gkt/RELRPT/0605
Current Transformers
CT-Terminal Marking
Gkt/RELRPT/0605
Current Transformers
Summation CTs
• Ratio test: -To find out the correct ratio when the same is not clearly
visible in NPD
- To distinguish between multiple secondary outputs
such as 1Amp terminals & 5 Amps terminals
Gkt/RELRPT/0605
Current Transformers
Ratio Test- Procedure
The primary of the CT under test is connected to an a.c. current
source such as a Relay test kit or the output of the welding
transformer with suitable arrangement to measure the primary
current supplied.
An a.c ammeter about 0-10 Amps. range is connected directly across
the secondary – If there are multiple secondaries, then all the unused
secondary SHOULD be kept open
Gkt/RELRPT/0605
Current Transformers
Polarity Test- Procedure
Please refer the fig below
Gkt/RELRPT/0605
Current Transformers
Polarity Test- Procedure
A DC battery of 12V, a DC analogue Voltmeter or Ammeter
& connecting leads are needed
Connect the positive of the voltmeter or ammeter to the H1 (P1 )-
(marked) terminal of the HV side of the CT and the negative lead to
theH2 (P2 ) terminal
If a window type CT is under test, run a wire through the CT &
connect the meter across the wire. Make note of the wire and meter
polarity
Connect the negative terminal of the battery to the X2 (S2) terminal of
the secondary of the CT.
Momentarily touch or connect the positive terminal of the battery to
the X1 (S1) terminal of the secondary of the CT, keeping a close watch
on the direction of the meter deflection
If the meter kicks in the +ve direction, the polarity marks are correct
If it kicks in the negative direction the polarity marks are incorrect.
Gkt/RELRPT/0605
Current Transformers
Most important precautions…..
Gkt/RELRPT/0605
Instrument Transformers
VOLTAGE TRANSFORMERS
OR
POTENTIAL TRANSFORMERS
Gkt/RELRPT/0605
Voltage Transformers
Gkt/RELRPT/0605
Voltage Transformers
Comparison…..
Electromagnetic type….
> Economical & reliable up to 66Kv
> Performance is better than CVTS
> Preferred for high speed distance protection
Capcitive type….
> Economical for voltages above 66Kv
> Carrier current equipments can be directly
connected without the need for coupling
capacitor
> Performance is affected by supply frequency ,
switching transients, magnitude of connected
burden etc.
> Generally a reactor is connected in series with
with burden requires “Tuning”
Gkt/RELRPT/0605
Voltage Transformers
Capacitive type VT
C1
Reactor
Vp
C2 Burden
Intermediate
Potential
Transformer
Gkt/RELRPT/0605
Voltage Transformers
Important terms
Gkt/RELRPT/0605
Voltage Transformers
Important terms
► Ratio error: Percentage ratio error also known as percentage voltage
error is given by
%RE = 100( KnVs- Vs)/ Vp
Where Kn = Normal ratio
Vs = Secondary voltage
Vp = Primary voltage
► Alternate method to describe the ratio error is to specify the voltage
ratio factor (V.R.F)
VRF=Kv/Kn
Where Kn = Normal ratio= Vp/Vs, Kv= Voltage ratio Vp/Vs( actual)
VRF= 1- (%RE/100)
► Burden=The load specified in Voltamperes at a rated
secondary voltage at a particular power factor, the secondary voltage
Vs, burden P, and impedence of the burden Zb, are connected by
Zb = V²s/ P Ohms
If Cos θ is the burden pf, then Rb= Zb Cos θ & Xb= Zb Sin θ
Total burden on VT should always be less than rated burden
Gkt/RELRPT/0605
Voltage Transformers
Accuracy class & limits, & Phase angle errors for voltage transformers
0.2 0.2 10
0.5 0.5 20
1.0 1.0 40
3.0 3.0 120 Protection
Gkt/RELRPT/0605
Voltage Transformers
Application of VTs depending upon Accuracy class
ACCU.CLASS APPLICATION
► Note: 1. Class 3.0 & 5.0 VTs are recommended for protection
2. Class 5.0 & 10.0 are recommended only in residual VTs
Gkt/RELRPT/0605
Voltage Transformers
Θ Two single phase VTs or one two limbed three phase VTs
are used
Θ Both primary and secondary are connected in V
Gkt/RELRPT/0605
Voltage Transformers
S1 S1 S1
P1 P1 P1
S2 S2 S2
P2 P2 P2
Voltage Coil
of Relays
Gkt/RELRPT/0605
Voltage Transformers
S1 S1 S1
P1 P1 P1
S2 S2 S2
P2 P2 P2
Primary
Secondaries connected to
Relay coil
Gkt/RELRPT/0605
Voltage Transformers
Gkt/RELRPT/0605
Voltage Transformers
Gkt/RELRPT/0605
Tech.Support & Service Projects
Questions ??
Gkt/RELRPT/0605
Service Projects
THANK YOU
Gkt/RELRPT/0605