Professional Documents
Culture Documents
The purpose of the mechanical inspection is to evaluate if all mechanical aspects are properly installed.
The tools & measurement equipment required for the mechanical inspection are as follows
a. Measure tape
b. Degree angle meter (inclinometer)
c. IR tension meter
d. Laser alignment device
e. Marker
f. Torch light (Ex-proof)
g. Caliper
h. Camera
In order to carry out a mechanical inspection, the fans need to be shut down.
A mechanical inspection will last for approximate 1-2 hours per fan. It is
absolutely necessary FOR YOUR SAFETY to have the fan electrically
isolated. Some end users also require a confined space permit for entry
inside plenum chamber. Please also note that most instruments are NOT Ex-
proof. Therefore a hot work permit could be required
1. Identification of mechanical parts such as drives and fans. For this, it is important to carry out the following
things (please see Excel document entitled “Survey sheet complete Rev00 2016” where you can find standard
sheets of how to carry this out.
The main purpose of identifying mechanical parts is to be able to firstly verify if the installed equipment corresponds to
the design data and to be able to verify if everything is according to OEM specifications. What should be done is the
following:
Fan – fill in all data in Excel sheet entitled “Survey sheet complete Rev00 2016”
For blade condition, please find below examples of possible problems with blades
Trailing edge split (can also be leading edge) FRP blades eroded by sun (epoxy or resin is eroded by UV)
Measure driven pulley diameter (if the specification of drive is not indicated on pulley as illustrated in picture
below)
Measured diameter of driver pulley using a large caliper if V drive. If HTD drive, mark one groove and count
the number of grooves
Measure shaft diameters using caliper (motor, driven pulley and fan shaft)
Measure center line distance between motor and fan shaft
Identify belt type and if individual V belts, count number of belts
Measure how much motor can go forward and backward (for eventual new selection of drives)
Identify condition of belts and drives
By using PDF files entitled “IPL GT 14M” for HTD drives and “IPL V belts” for V belts, one can identify the type of
pulleys by comparing pulley diameter to O.D. of pulley indicated in these documents.
Belt can mostly be identified by the description on the belt as illustrated in picture below
For V belt drives, one should look in particular at position of belt in pulley (especially with driver pulley) as illustrated
below
Wrong
Poor belt condition or belt positioning in pulley will reduce belt or pulley life. Furthermore, it will reduce drive
efficiency. A poor belt positioning will mostly result in belt slipping which in turn will reduce fan RPM and therefore
airflow. Reduced airflow mostly leads to reduced cooling capacity of ACHE.
TIP
One can also check tooth mashing by using a
stroboscope while fan is running. This will indicate
how well belt is positioned in groove and will allow
to check all fans without the need to stop fan
Although this is not part of the mechanical inspection, you will need to carry out this visual inspection (on forced draft
units) as this is the only possibility to carry this out.
Check for bent fins (bottom row of fins). Try and estimate % of bent fins in relation to total number of fins. See
below examples of bent fins (bottom row)
No bent fins
Scratch with metal device (tools or caliper) slightly lower row of fins and estimate (in mm) rotten part of lower
fin. You will see that if you scratch fins, a part of the fin will deteriorate and fall down (if older bundle). Measure
the part that is “rotten”.
A small portion of the top fin (1st row)
can be deteriorated in such a way that is
simply falls of when scratched with
metal object. Measure how many mm
this is
In order to identify degree of external fouling, one must shine a torch light in the triangular path of the tubes in order to
assess the external fouling.
Please note that external fouling will always be in the bottom 2 rows of the bundle. External fouling will never be on top
of finned tube bundle (or for another reasons such as insects, birds, spills, isolation material, etc.)
We also try with our bare eyes to see the light through
the finned tube bundle. This will give a better indication of
external fouling and if the air can still pass through (as
light means passage for air). No day light means finned
tube bundle is completely clogged. Please take into
consideration direction of sun when trying to see day light
through bundle!!!!
Please find some illustration of external fouling. Please note that this is not a precise scale but just an illustration for
your assistance/guidance
2. A certain number of measurements need to be carried out during the mechanical inspection
The following instruments are required to carry out these measurements. Operation manuals can be found in
corresponding files.
a. Drive system
For the drive system, it is important to carry out the following measurements (values should be filled in in the Excel
Sheet entitled “Survey sheet complete Rev00 2016”)
i. Pulley alignment. It is important that pulleys are aligned properly from each other as indicated with
device below.
Parallel misalignment
Angular misalignment
For V belt drives, the pulley misalignment should not exceed 1/2 ° or 5 mm per 500 mm of drive centre
distance.
For HTD drives, the pulley misalignment should not exceed 1/4 ° or 2.5 mm per 500 mm of drive centre
distance.
Improper pulley alignment can cause loss in efficiency of drive system and will reduce drive lifespan. Especially on
HTD drive, the belt life can be reduce significantly and will cause the belt to rise or lower as indicated in picture below
(belt broken due to improper alignment)
Belt tension is recorded by using a IR digital tension meter. Values can then be compared to specified values by using
drive selection programs supplied by drive manufacturers such as Gates, Optibelt, Goodyear, etc.
b. Fan system
For the fan, it is important to carry out the following measurements (values should be filled in in the Excel Sheet
entitled “Survey sheet complete Rev00 2016”)
Inclinometer should
be placed here
Inclinometer should
be placed here
Fan manufacturers recommend blades should be set with a margin of +/- 0.5o between each blade. A too large pitch
angle will indicate stalling of fan (see further in report for explanation of stalling) and too much difference from one
blade to the other can cause fan imbalance and turbulent airflow. ELFLOW BV recommends even setting blades within
+/- 0.2o of each other. This can be done by using our digital inclinometer.
Tip clearance is the distance between the tip of blade and the fan ring or housing.
Tip clearances are critical to the efficiency of a fan system. Too much distance at the tip will cause
air re-circulation problems; too little distance at the tip can cause rubbing, or tipping, during high winds. Note that the
blade performs most of the work in the outer portion of the airfoil (as the radius is the largest at the tip of the blade). If
a leakage path (or tip clearance) exists, the air will seek the path of least resistance and by-pass the tip, causing a
vortex leading in a loss of performance.
API recommended tip clearances for smaller (16ft and less) diameter fans. Also included in this
figure are the nominal tip clearances for larger diameter fans.
Please note that tip clearance of a fan should be measured at 4 distinct points of the fan ring using a measuring tape.
This will then allow you to determine what the situation is (fan ring oval, shaft out of center, etc.) and how much
material is required to fix the tip clearance problem on site. This means that on a fan ring inspected, please mark 4
values per fan ring as indicated below.
T.C. 1
values
T.C. 1 (mm)
T.C. 2 (mm)
T.C. 3 (mm)
T.C. 4 (mm) T.C. 2
T.C. 4
Average (mm)
T.C. 3
Blade tracking should be done at the same time as pitch angle measurements and should be done at the same point
(same for pitch angle measurements).
Blade tracking is checking whether all blades are all within the same horizontal plane of each other. The difference
between lowest and highest blade (in horizontal plane) should not exceed more than 1”.
Blade tracking is done by putting marker on each blade and check whether
Record in mm
difference in height
between highest and
lowest plane (in
horizontal plane)
General inspection are all inspections and measurements that are included in mechanical of fan performance
measurements. There are a few aspects that need to be checked such as
The tools & measurement equipment required for the general inspection are as follows
a. Measure tape
b. IR Thermometer
c. Special non reflective paint marker
d. Torch light (Ex-proof)
e. Caliper
f. Camera
Finned tube bundle – fill in all data in Excel sheet entitled “Survey sheet complete Rev00 2016”
The tools & measurement equipment required for the performance measurement are as follows
a. Measure tape
b. Vane anemometer or hot wire anemometer
c. Differential pressure measurement device
d. Pitot tube
e. Thermometer with RH measurement
f. IR thermometer
g. Stroboscope
h. Camera
i. IR camera as an option
As you might also carry out survey in winter period, it is important to simulate summer conditions as much as possible
when all fans are running at full load. There, we recommend the following
All fans measured equipped with VSD’s or auto variable hubs should always run at 100% capacity.
Louvers should be opened during measurements
Scenarios
Airflow measurements
Air velocity measurements should be taken in a plane parallel to the fan. The inlet of the fan is divided into 2
perpendicular halves or 4 quadrants with a number of equal area bands per quadrant depending on fan size and
obstructions on the mechanical/structural elements of the air cooler. Airflow measurements is made at the centroid of
each equal area band for a total average of x measurements. At each traverse point, two (2) 16-second average air
velocity readings are measured. If the readings differ of 0.5 m/s from each other, a new reading should be made until
readings are within 0.5 m/s of each other.
For a forced draught unit, this plane should be below the fan, as close as possible to the fan ring or inlet bell to negate
the effects of ambient wind as illustrated below.
Determine location of your airflow measurement planes. Based on air cooler mechanical & structural configuration and
obstructions, you will decide to choose 2 perpendicular halves or 4 quadrants. The choice must be based on the
choice to have the most steady measurement readings.
Step # 2
Based on the mechanical inspection (fan ring diameter, fan guard position with regard to inlet bells and seal disc or
hub diameter), you can input fan diameter, seal disc or hub diameter and number of measurement points in Excel
sheet entitled “Fan performance sheet_Template_2016_Rev05” taking into consideration the following
Fan diameter – it is important to take into consideration on Forced draft unit where you will measure airflow as the
diameter to input could differ from fan diameter as illustrated below (fan sizes are examples!!!)
Fan guard under fan ring Fan guard under inlet bells with 12 ft
with 12 ft fan so input 12ft fan so input 13ft in Excel sheet if
in Excel sheet diameter with inlet bells is 13ft
12 ft 12 ft
Position of 13 ft
anemometer during
measurements
STA 1. =
0 Measurements point
closest to tip of blade
Step # 3
Mark measurement points on special metallic rod with hooks that can directly be hooked to fan guard and start
measuring fan velocities using vane anemometer.
Vane anemometer
Mst points
Illustration of fan performance measurements on forced draft units with vane anemometer
Because the anemometer does NOT record negative values, it is important to have the anemometer go up
and down at the tip of the blade (first 2 measurements) in order to check if there is no recirculation of air of
even negative airflow at the tip of the blade. This should ALWAYS be carried out prior to measuring airflow.
Airflow measurements should always be carried out with 2 persons. One holding the anemometer and the
other taking the readings.
Air temperature & relative humidity should be recorded before the measurement of every fan performance
measurement (per fan)
Date and time of measurement should also always be recorded for each fan measured
Wind velocity should be measured & recorded at the start and end of the airflow test using a rotating vane
anemometer. This measurement should be taken at a location that is upwind and unobstructed. If wind
velocity is greater than 16 km/h, the test should not be conducted
If precipitation (very high rains) is occurring, the test should not be conducted
The static pressure (= ΔPairside) is the Sum of all the system resistances against which the fan must work,
expressed in inches of H2O. This is the useful work required from the fan. (Velocity
pressure excluded).
In order to ONLY measure static pressure(=Sp), a static tube is inserted in the four (4) lower corners of the plenum
chamber as we assume that there is no velocity pressure available there. This can be done in 2 ways. The traditional
way is to stick a standard pitot tube through a draining hole (or drilled hole) in the corners as illustrated below. If there
is no access due to the fact that scaffold is not possible), one can always use the second method which is to insert the
specially fabricated through the finned tube bundle to reach (the best we can) the corners of plenum chamber.
If possible, the static pressure readings should be taken at every corner of the plenum chamber
Pitot tube
This method is used when there is no access to the corners of the plenum chamber but there is a walkways at the
header of the ACHE. The idea is to stick a specially fabricated pitot tube through the finned tube bundle (as almost all
tube bundles have triangular pitch and therefore, it is possible to stick this pitot tube through the bundle as illustrated
below
Pitot tube
Pitot tube no yet inserted through bundle Pitot tube inserted through bundle reaching lower corner
Air velocity measurements should be taken in a plane parallel to the fan. The inlet of the fan is divided into 2
perpendicular halves or 4 quadrants with a number of equal area bands per quadrant depending on fan size and
obstructions on the mechanical/structural elements of the air cooler. Airflow measurements is made at the centroid of
each equal area band for a total average of x measurements. At each traverse point, two (2) 16-second average air
velocity readings are measured. If the readings differ of 0.5 m/s from each other, a new reading should be made until
readings are within 0.5 m/s of each other.
For an induced draught unit, this plane should be above the fan and as close to the fan as
possible to negate the effects of ambient wind. The anemometer is held parallel to the plane of the fan during the
reading. The velocity reading can be affected by the yaw of the fan. That is why it is absolutely essential to use a level
meter on your anemometer
Determine location of your airflow measurement planes. Based on air cooler mechanical & structural configuration and
obstructions, you will decide to choose 2 perpendicular halves or 4 quadrants. The choice must be based on the
choice to have the most steady measurement readings.
Step # 2
Based on the mechanical inspection (fan ring diameter, fan guard position with regard to inlet bells and seal disc or
hub diameter), you can input fan diameter, seal disc or hub diameter and number of measurement points in Excel
sheet entitled “Fan performance sheet_Template_2016_Rev05” taking into consideration the following
The Excel program entitled “Fan performance sheet_Template_2016_Rev05” will then indicate measurement points
as illustrated below.
STA 1. =
0 Measurements point
closest to tip of blade
Mark measurement points on anemometer rod using electrical tape. Start measuring fan velocities using vane
anemometer.
Measurement points
Anemometer with
level
Anemometer rod
The alternative method is carried out when access at height of fan is prohibited (for HSE or economic reasons that have
to do with scaffolds). With the alternative method, one will measure face velocities under the finned tube bundle
as illustrated below. Please note that using a hot wire anemometer for this method is more preferred then using a vane
anemometer due to the fact that hot wire anemometers are more precise at mower air velocities (ranging from 0-3
m/s). It is also recommendable to make a cylinder (10x diameter of anemometer to create laminar flow inside cylinder)
as illustrated in picture on next page. The cylinder (shield) is also necessary to minimize error due to wind effect. The
position of cylinder of anemometer should be located at least five prime tube diameters from extremities of the fins to
prevent error due to restriction effect of the tubes.
The measurement plane chosen shall be divided into imaginary rectangular areas (at least 20 or one per m 2,
whichever is greater)
Illustration of alternative method with hot wire anemometer and self-made cylinder under finned tube bundle
The airflow is then calculated by multiplying measured face velocity (m/s) by surface of bundles (-/- covered surface
which can mostly be assumed between 85 & 95% due to structural obstructions such as beams, motor support, etc.)
Airflow measurements should always be carried out with 2 persons. One holding the anemometer
and the other taking the readings.
Air temperature & relative humidity should be recorded before the measurement of every fan
performance measurement (per fan)
Date and time of measurement should also always be recorded for each fan measured
Wind velocity should be measured & recorded at the start and end of the airflow test using a
rotating vane
anemometer. This measurement should be taken at a location that is upwind and unobstructed. If
wind velocity is greater than 12 km/h, the test should not be conducted
If precipitation (very high rains) is occurring, the test should not be conducted
Just like forced draft units, there are 2 ways to measure static pressure on an induced draft unit. The traditional way is
to stick a standard pitot tube through a draining hole (or drilled hole) in the corners as illustrated below. If there is no
access due to the fact that scaffold is not possible), one can always use the second method which is to insert the
specially fabricated through the finned tube bundle to reach (the best we can) the corners of plenum chamber.
Pitot tube
traditional way
Pitot tube
alternative way
Drilling of 8 mm hole
The second way is to stick the pitot (specially fabricated for this purpose) through the finned tube bundle. This will
however be carried in the reverse way as with Forced draft units due to the fact that plenum chamber is on top of tube
bundle and not under. See page 31 for explanation.
C 801
92.8
V 802
13
V 803
ALL fans should be running during the process temperature readings. If a fan is NOT running, one
should note this
Date & time of measurement is essential
Air temperature & relative humidity should be recorded
All fans should be running at 100%
If precipitation (very high rains) is occurring, the test should not be postponed
Cover plate headers are mostly installed for fouling services (internally). Therefore, it is very probable
that you can detect internal fouling (difference in outlet temperature between 1 bundle to the other)
b y measuring different process outlet temperatures
Bent/warped tubes will mostly be a cause of internal fouling as the internally fouled tubes will have
less product running through the not fouled tubes. This will create a difference in temperature
between tubes and therefore different thermal expansion between tubes which will create some
tubes to bend
Pure condensers can be isothermal so no difference in outlet temperature can be measured. Also
partial condensers will also therefore indicate less difference in outlet temperatures compared to
coolers when bundle is working better than the other
Lower process temperatures on 1 bundle compared to the other (on a cooler) will indicate that that
particular bundle is fouling internally (airflow being equal for all bays). This is because there is less
product flowing through the bundle and therefore the medium gets cooled more
Always check on condensers if the inlet piping is symmetrical. If not, there could be an imbalance
between each bundle due to difference in process ΔP
If internal fouling is suspected, a IR scan using IR thermal camera could be a good idea
1. Site Requirements
2. Special remarks