Calculation and
Specification of Fire
Main System
Attachment of Doc.No. 05 - 42 19 AB023 - FI
Doc. No. 05 - 42 19 AB023 - FI
Calculation and
Specification of Fire Rev. No. 00
Main System Page 1 of 7
I. INTRODUCTION
Fire main system is one of safety system in ship. Fire fighting
system is a system that is used to treat, prevent and stop the
fire that occurred in the ship, either as a whole or by part. Fire
became one important consideration and can not be ignored,
because it involves the safety of crew, cargo and ship continuity
itself. Although the fire in the ship can not be predicted when it
happened, but all of the components and specifications have
been set up well in the classification and design standards &
there must be on the ship.
II. OBJECTIVES
The objectives of Fire Main System are:
a) Calculate the piping of fire main system
b) Calculate the pump of fire main system
III. REFERENCES
a) American Bureau of Shipping (ABS), Part 4, Chapter 6, Section 4
b) SOLAS Chapter II-2 Part C Regulation 10
c) Pompa dan Kompresor, Sularso-Haruo, 2000, Chapter 2
d) Marine Engineering, Roy L. Harrington, 1971, Chapter XVIII - Piping System
V. SYSTEM DESCRIPTION
This system is a safety system on board. Fire fighting system is
a system that is used to treat, prevent and stop the fire that
occurred on the ship, either as a whole or by part. Fire became
one important consideration and can not be ignored, because it
involves the safety of crew, cargo and ship continuity itself.
Although the fire in the ship can not be predicted when it
happened, but all of the components and specifications have
been set up well in the classification and design standards and
there must be onboard the ship. Fire is an event the flame as a
result of the reaction between the material, the source of heat
and oxygen. In general, compounds and elements are expressed
as the fire triangle shape. The only way to prevent fires is to
eliminate or separating any of the three elements. This can be
done by:
1. Lowering the temperature below the combustion temperature removes hea
2. Lower levels of oxygen eliminate oxygen.
3. Tearing combustible materials removes material (if possible).
Key
No. Equipme Reference Parameter Design
nt There are to be at least 2
independently driven fire pumps.
ABS Part 4, For vessels less than 500 gross
Chapter 7,
tonnage, only one of the required
Section 3, 1.5.1
Number of fire pumps need independently
Pumps driven. The fire pumps are to be
Arrangem certified in accordance with 4-6-
ent of Fire 1/7.3.1.
Sanitary, ballast, bilge or general
2. Pumps
and Fire service pumps may be accepted as
Main ABS Part 4, fire pumps, provided that they are
Chapter 7, not normally used for pumping oil
Section 3, 1.5.2 and that if they are subject to
Acceptable occasional duty for the transfer or
Pumps pumping of oil fuel, suitable
changeover arrangements are
fitted.
The capacity of the pump is not to
be less than 40% of the total
capacity of the fire pumps required
ABS Part 4, by 4-7-3/1.3.1 and in any case not
Chapter 7, less than the following:
Section 3, 1.5.3, • for cargo vessels of 2000 gross
i) tonnage and upwards: 25 m3/h,
and
• for cargo vessels less than 2000
gross tonnage: 15 m3/h.
The total suction head and net
Emergenc positive suction head of the pump
3. y Fire are to be such that the
Pump requirements of 4-7-3/1.5.3i), 4-7-
3/1.5.3ii) and 4-7-3/1.7.2 are
obtained under all conditions of
ABS Part 4,
list, trim, roll and pitch likely to be
Chapter 7,
encountered in service. In
Section 3, 1.5.3,
v) selecting the emergency fire
pump, the minimum available net
positive suction head is to provide
a safety margin of at least the 1
meter (3.3 feet) or 30% of required
net positive suction head of the
The total suction head and net
Emergenc positive suction head of the pump
3. y Fire are to be such that the
Pump requirements of 4-7-3/1.5.3i), 4-7-
3/1.5.3ii) and 4-7-3/1.7.2 are
Doc. No. 05 - 42 19 AB023 - FI
Calculation
ABS Part 4,
andobtained under all conditions of
list, trim, Rev.
Specification
Chapter 7, of Fire roll andNo. pitch
00 likely to be
encountered in service. In
Main3,System
Section 1.5.3,
selecting the
Page emergency
3 of 7 fire
v)
pump, the minimum available net
positive suction head is to provide
a safety margin of at least the 1
meter (3.3 feet) or 30% of required
net positive suction head of the
pump, whichever is less.
Key
No. Equipme Reference Parameter Design
nt
The diameter of the fire main and
water service pipes is to be
sufficient for the effective
distribution of the maximum
required discharge from two fire
ABS Part 4, pumps operating simultaneously or
Chapter 7,
maximum specific vessel design
Section 3, 1.7.1
Fire Main flow through the system,
Diameter whichever is the greater.. However,
unless otherwise specified by the
Naval Administration, the diameter
need only be sufficient for the
Diameter discharge of 140 m3/hour (616
and gpm).
4. Pressure in
the Fire With the two pumps
Main simultaneously delivering through
nozzles specified in 4-7-3/1.15 the
quantity of water specified in 4-7-
ABS Part 4, 3/1.7.1, through any adjacent
Chapter 7, hydrants, the following minimum
Section 3, 1.7.2 pressures are to be maintained at
Fire Main all hydrants:
Pressure i) Vessels of 6,000 gross tonnage
and upwards: 0.27 N/mm2 (2.8
kgf/cm2, 40 psi),
ii) Vessels less than 6,000 gross
tonnage: 0.25 N/mm2 (2.6 kgf/cm2,
37 psi).
The connection is to be of steel or
other suitable material and is to be
Internation ABS Part 4, designed for 1.0 N/mm2 (10.5
al Shore Chapter 7, kgf/cm2, 150 psi) services. The
5. Connectio Section 3, 1.19.4 flange is to have a flat face on one
n Design side, and on the other site, it is to
be permanently attached to a
Doc. No. 05 - 42 19 AB023 - FI
Calculation and
Specification of Fire Rev. No. 00
Main SystemThe connection is to be of steel or
Page 3 of and
other suitable material 7 is to be
Internation ABS Part 4, designed for 1.0 N/mm2 (10.5
al Shore Chapter 7, kgf/cm2, 150 psi) services. The
5. Connectio Section 3, 1.19.4 flange is to have a flat face on one
n Design side, and on the other site, it is to
be permanently attached to a
coupling that will fit the vessel's
hydrant and hose.
19 AB023 - FI
19 AB023 - FI
19 AB023 - FI
19 AB023 - FI
Doc. No. 05 - 42 19 AB023 - FI
Calculation and
Specification of Fire Rev. No. 00
Main System Page 1 of 9
CALCULATION DETAILS
Q = A x V = (π d2 / 4) v d = (( 4 x Q ) / ( π x v ))0.5
d = (( 4 x Q ) / ( π x v ))0,5 = (( 4 x 0.033) / (3.14 x 2))0.5
V = Flow Velocity = 0.1442 m
= 2.0 m/s = 144.213 mm
Hp = (Pdiscd - Psuct ) / ρg
= (270000 - 0) / (1025 x 9,81)
= 26.85 m
c. Head velocity
Difference speed between the suction side discharge. To
head velocity in the fluid velocity is assumed to discharge to
the suction side of the same: and there is no velocity
difference between the sides.
Hv = ( V2disch - V2suct ) / 2g
= 0 m
Re = ( dH x v ) / υ
Then: Rn = (dH x V) / υ
= (149,3 x 2) / 0,000000801
= 372784.02 if Re <2300,"laminer"
= turbulen if Re >2300,"turbulen"
Where: λ = 0,02+0,0005/D
= 0.02+0.0005/149,3
= 0.0233
L = 15 m
v = 2.0 m/s
D = 149.3 mm
- Minor losses (head because of the accessories that exist on the pipe)
No. Accesories n k nxk
1 Elbow 90o 2 1 2
2 Butterfly valve 3 0.86 2.58
3 T joint 2 1.8 3.6
4 Gate Valve 1 1.15 1.15
5 Filter or strainer 2 2.5 5
Σ 14.33
Re = ( dH x v ) / υ
Doc. No. 05 - 42 19 AB023 - FI
Calculation and
Specification of Fire Rev. No. 00
Main System Page 1 of 9
Then: Rn = (dH x V) / υ
= 372784.02 if Re <2300,"laminer"
= turbulen if Re >2300,"turbulen"
Where: λ = 0,02+0,0005/D
= 0.02+0.0005/200.025
= 0.0233
L = 80 m
v = 2.0 m/s
D = 149.3 mm
- Minor losses (head because of the accessories that exist on the pipe)
No. Accesories n k nxk
1 Non-Returned Valve 1 2 2
2 T-joint 10 0.75 7.5
3 Elbow 90o 2 1 2
4 Hydrant (Butterfly Valv 12 0.86 10.32
5 Flexible Coupling 8 0.46 3.68
Σ 25.5
Q = 117.547 m3 / h
H = 71.60 m
Pump's material :
Impeller and sea = Copper (ZCuZn16Si4)
Material shaft = Stainless steel
Pump casing = Copper (ZCuZn16Si4)
PUMP SPECIFICATION
Doc. No. 05 - 42 19 AB023 - FI
Calculation and
Specification of Fire Rev. No. 00
Main System Page 1 of 9
the navigation deck
turbulen"
4. Pump Specification
Brand = Shanghai SILI Pump Manufacture Co., Ltd
Type of Pump = vertical self-priming centrifugal pump
Doc. No. 05 - 42 19 AB023 - FI
Calculation and
Specification of Fire Rev. No. 00
Main System Page 6 of 7
Model = 125CLZ-8
Pump's material :
Impeller and sea = Copper (ZCuZn16Si4)
Material shaft = Stainless steel
Pump casing = Copper (ZCuZn16Si4)