GENERAL NOTES:

A B C D E F G H I J K L M N O P
28135
3000 1525 1650 1550 450 1725 2150 3575 1050 1725 1685 615 2475 2135 2825
ME
CC
A

NOR
28660

T
NO ACCESS FROM THIS SIDE

H
N 2770857.369 PLOT LIMIT PLOT LIMIT N 2770884.871
E 507747.025 E 507755.088

1
900mm HEIGHT FROM
S.S.L OF ROOF TOP
(WALL PARAPET)

4750
GENERAL NOTES:
LEGENDS
1. THE COMPLETE INSTALLATION OF FIRE ALARM SYSTEMS SHALL CONFIRM TO THE APPLICABLE SECTION
BREAK GLASS POINT OF NFPA-72 & OTHER NATIONAL COMPLYING ELECTRICAL CODES.
2. THE SYSTEM SHALL HAVE PROVISIONS FOR DISABLING AND ENABLING ALL CIRCUITS INDIVIDUALLY FOR
SMOKE DETECTOR MAINTENANCE -OR-TESTING PURPOSES.
3. EM IN PLANT ROOMS AND PARKING MUST BE IP-54.
SMOKE DETECTOR WITH BUILT IN SOUNDER 4. EXIT IN CAR PARKING AND PLANT ROOMS MUST BE IP-54.
5. ELECTRICAL OPERATED DOORS MUST BE INTERLOCKED WITH FIRE ALARM SYSTEM AND MUST BE KEPT
900mm HEIGHT FROM HEAT DETECTOR OPEN INCASE OF FIRE.
S.S.L OF ROOF TOP 6. THE CONTRACTOR SHALL BE RESPONSIBLE FORTHE COORDINATION OF ALL SERVICES.
(WALL PARAPET) 7. THE FAHU's SHALL BE INTERLOCKED WITH FIRE ALARM SYSTEM & SHALL AUTOMATICALLY SWITCH-OFF
1x5W LED SELF-CONTAINED NON-MAINTAINED TYPE WITH 3
2 HOURS BACK-UP BATTERY IP-54 RECESSED MOUNTED 8.
WHENEVERA SIGNAL IS INITIATED IN THE PANEL.
SHORT CIRCUIT PROTECTION FOR EVERY15 DETECTORS TO BE PROVIDED IN GENERAL AREAS AND IN
CHANGE OF FLOORS /FIRE ZONES.
1x5W LED SELF-CONTAINED NON MAINTAINED TYPE 9. ALL EXIT DOORS MUST BE PROVIDED WITH EXIT LIGHTS.
EMERGENCY LIGHT WITH MONITORING MODULE & 3-HOUR 10. ALL EQUIPMENT SHALL BE TO THE APPROVAL OF CIVIL DEFENCE DEPARTMENT.

1850
DURATION, IP-54 SURFACE MOUNTED, WITH 11. ALL GAPS & OPENINGS FOR THE CABLES TO BE FILLED WITH SMOKE /FLAME PROOF FIRE BARRIER.
RECHARGEABLE BATTERY & CHARGING MODULE 12. LIFTS TO BE INTERLOCKED WITH FIRE ALARM SYSTEM.
13. ANY DISCREPANCIES ARE TO BE BROUGHT TO THE ATTENTION OF ENGINEER AND RESOLVED BEFORE
1x5W LED SELF-CONTAINED NON-MAINTAINED WALL COMMENCEMENT OF ANY WORK.
MOUNTED TYPE EXIT LIGHT WITH 3-HOUR DURATION, IP-54 14. FIRE ALARM SYSTEM SHALL BE CONVENTIONAL TYPE.
15. MAIN FIRE PANEL MUST BE LINKED TO THE CIVIL DEFENCE CENTRAL MONITORING STATION THROUGH
WITH DIRECTIONS WITH ARROW , DCD APPROVED.
3 SHO.
SPEAKER 16.
A CIVIL DEFENCE APPROVED COMMUNICATION DEVICE WITH MODEM, DEDICATED TELEPHONE LINE
AND UNFUSED SPUR OUTLET.
ALL EXPOSED CONDUITS MUST BE GI.
17. ALL EMERGENCY LIGHTS MUST BE SELF CONTAINED & NON MAINTAINED TYPE.
SOUNDER WITH FLASHER
SHO. 18.
19.
ALL EXIT LIGHTS MUST BE NON-MAINTAINED.
FIRE PROOF CABLE TO BE USED FOR SPEAKER WIRING.
SOUNDER WITH FLASHER, W/P
W.I.C. 20.
21.
FOR TYPE OF EMERGENCY / EXIT LUMINARIES REFER SPECIFICATIONS.
PULL BOX TO BE PROVIDED IN EVERY 15m RUN OF CONDUIT AND CHANGE IN DIRECTIONS AND SHALL
BATH MASTER
ALARM GONG BE INSTALLED NOT LESS THAN 42 INSH (1067mm) NOT MORE THAN 48 INSH (1219mm) ABOVE THE FINUSH
FLOOR.
1st - FIRE ALARM REPEATER PANEL 22. EXIT STICKERS MUST BE PROVIDED IN FIRE ESCAPE AND MUST BE PROVIDED IN FIRE ESCAPE DOORS,
BEDROOM 01 BATH BEDROOM 02 IF EXIT LUMINAIRE IS NOT INSTALLED ABOVE THE DOOR.

SHAFT
FIRE ALARM CONTROL PANEL 23. THE SOUND LEVEL AT BED HEAD MUST BE 75 dB. SPECIALIST VENDORS TO PEOVIDE ADDITIONAL
1st SOUNDERS IF REQUIRED TO ACHIEVE THE REQUIREMENT.

4987
24. ALL EQUIPMENT SHALL BE UL/FM LISTED AS PER THE CIVIL DEFENSE AND EHS REQUIREMENTS.
EMERGENCY LIGHT MONITORING PANEL
25. ACTUAL LOCATION FOR FIRE ALARM POINT TO BE COORDINATED WITH FALSE CEILING DRAWING.
26. MAXIMUM 20 NOS. FITTING PER CIRCUIT.
27. ALL FITTINGS ARE CONSIDER 8W.
28. ALL EQUIPMENT SHALL BE UL/FM LISTED AS PER THE CIVIL DEFENSE AND E.H.S.REQUIREMENT
29. DO NOT SCALE FROM THIS DRAWING.
30. ALL DIMENSIONS ARE IN MM UNLESS NOTED OTHERWISE.

4 SHAFT

AC
2360

SHAFT
W.I.C.
PANTRY

AC
5 SHAFT

OPEN
BELOW
7000

FAMILY
HALL
PROPERTY OF ADJACENT PLOT

PROPERTY OF ADJACENT PLOT


PROJECT:
RESIDENTIAL VILLA
41560

41560
41210

G + 2 FLR. RESIDENTIAL
6

SHAFT
PLOT No.913-1403, UMM NAHAD 3RD, DUBAI, U.A.E.
2713

BATH CLIENT/OWNER:
SHO.
1st -
W.I.C.
ELEC. Ms. Alia Jamil Ahmad
CAB.

7 CLIENT REPRESENTATIVE:
2225

UP

MAIN CONSULTANT:
8 MASTER BEDROOM 02
BEDROOM 02
BATH
KAIZEN
ARCHITECTS & ENGINEERS
UP
4325

Architectural & Engineering Consultants


P.O. Box 445607 Dubai, United Arab Emirates

SHAFT
Tel:+971 4 3339079 Fax:+971 4 3339078
SHO. Info@kae.ae www.kae.ae

DECK M.E.P. CONSULTANT:

9
475

VOID

10 INTERIOR DESIGNER:
1575

INTENDED FOR
LIGHT STRIP

11
LANDSCAPE CONSULTANT:
4550

LIGHTING CONSULTANT:

KITCHEN & LAUNDRY CONSULTANT:


12

SPA CONSULTANT:
4400

2770845.676 N
N 2770873.179 F&B CONSULTANT:
507786.906 E
E 507794.969
13
CONTRACTOR :

PLOT LIMIT PLOT LIMIT

28660
DRAWING TITLE:

18.29 METERS WIDE ROAD


FIRST FLOOR PLAN
FIRE ALARM LAYOUT

FA-102 1:100