Professional Documents
Culture Documents
MATTERS
Autumn 08 Issue 28
It’s here!
Do it right.
SECTION 559 (of BS 7671:2008) installations has been expanded, requirements where bare conductors
luminaires and lighting installations compared to Section 611 in the 16th are used, the types of transformers
is a new series of Regulations giving Edition, to cover car parks, gardens, and converters and requirements for
particular requirements for fixed parks, places open to the public, suspended systems.
outdoor lighting installations, extra- illumination of monuments and
low voltage lighting installations and floodlighting. Other lighting LUMINAIRES
lighting for display stands. arrangements specifically mentioned Protection against fire
Section 559 includes requirements include telephone kiosks, bus shelters, Regulation 559.5.1 requires that in the
from Regulations 553-03 (lampholders) advertising panels and town plans, selection and erection of a luminaire
and 553-04 (lighting points) in the 16th which it is recommended are provided the thermal effects of radiant and
Edition. This new section also with additional protection by a convected energy on the surroundings
includes requirements from Section 30mA RCD. are to be taken into account, including:
611 (Highway Power Supplies and Regulation group 559.11 is a (i) the maximum permissible power
Street Furniture) of the 16th Edition. completely new series of Regulations dissipated by the lamps
The impact of this new section is that were not included in the 16th (ii) the fire-resistance of adjacent
that additional requirements are now edition covering requirements for material at the point of installation
included in the Regulations for general extra-low voltage lighting and in the thermally affected areas
lighting including requirements for installations. The particular (iii) the minimum distance to
protection against fire, connection of requirements of these Regulations combustible materials, including
luminaires to the fixed wiring, fixing apply to extra-low voltage lighting material in the path of a spotlight
of the luminaires, requirements for installations supplied from sources beam.
through wiring in a luminaire, with a maximum rated voltage of 50 V
requirements for control gear, ac rms or 120 V dc. The Regulations Luminaires are usually installed on
e.g. ballasts and compensation include requirements for protection non-combustible surfaces, defined in
capacitors. A further new requirement against electric shock (SELV), BS EN 60598-1 as “material incapable of
is the need to give consideration to protection against the risk of fire due supporting combustion” and taken to
stroboscopic effects. to short circuit, types of wiring include metal, plaster and concrete.
The Regulations for outdoor lighting systems including special However, sometimes it may be
2
necessary to mount luminaires on writing this article are the subject of Connection of luminaires
materials that may be considered to be change; the reader is advised to consult Regulation 559.6.1.1 has requirements
flammable (e.g. wood and wood based the latest edition of BS EN 60598 for for Connection to the fixed wiring.
materials of more than 2 mm thick) current luminaire marking The Regulation states:
and in such cases a classified luminaire requirements. At each fixed lighting point one of
to BS EN 60598 marked with the the following shall be used:
following symbol should be selected: From a thermal view the (i) A ceiling rose to BS 67
temperature of illuminated objects (ii) A luminaire supporting coupler to
Luminaire suitable
for direct mounting is also important and the heat from a BS 6972 or BS 7001
on normal flammable wrongly placed luminaire can (iii) A batten lampholder or a pendant
surfaces
initiate combustion. Luminaires to set to BS EN 60598
BS EN 60598, where required to be so, (iv) A luminaire to BS EN 60598
Where luminaires are marked with can also be marked with a symbol to (v) A suitable socket-outlet to
this symbol, the excessive indicate the minimum distance from a BS 1363-2, BS 546 or BS EN 60309-2
temperatures which may arise in lighted object and a maximum lamp (vi) A plug-in lighting distribution unit
operation, or due to the failure of a wattage. to BS 5733
component, will not cause the (vii) A connection unit to BS 1363-4
mounting surface temperature to (viii) Appropriate terminals enclosed
exceed 90 °C and, thereby, cause a risk in a box complying with the relevant
of fire. Originally this mark only part of BS EN 60670 series or BS 4662
covered luminaires with integral (ix) A device for connecting a
control gear but is now applicable to The above figure shows minimum luminaire (DCL) outlet according to
all luminaires complying with the BS distance from a lighted object (m). IEC 61995-1.
EN 60598 series of standards. Regulations 422.3.1 and 422.4.2 give
Luminaires which cannot comply the following minimum distances at NOTE: In suspended ceilings one plug-
with this criterion are required to which spotlights and projectors shall in lighting distribution unit may be
carry a warning notice or have the be installed from combustible used for a number of luminaires.
following symbol: materials:
(i) rating up to 100 W - 0.5 m Fixing of the luminaires
Luminaire suitable (ii) rating over 100 W up to 300 W - 0.8 m Regulation 559.6.1.5 requires that
for direct mounting
on non-combustible (iii) rating over 300 W up to 500 W - 1.0 m. adequate means to fix the luminaire
surfaces only shall be provided.
Table 55.2 of BS 7671 gives a full The fixing means may be by
explanation of symbols used in mechanical accessories (e.g. hooks or
NOTE: These symbols are referenced luminaires, in controlgear for screws), boxes or enclosures which are
within BS EN 60598-1:2004. However, luminaires and in the installation of able to support luminaires or supporting
some of these symbols, at the time of luminaires devices for connecting a luminaire.
Wiring Matters is produced by IET Services Limited, a subsidiary of The Institution of Engineering and Technology (IET), for the IET.
Michael Faraday House, Six Hills Way, Stevenage, Herts, SG1 2AY, United Kingdom Tel: +44 (0)1438 313311 Fax: +44 (0)1438 313465
Advertising Sales D Smith +44 (0)1438 767224 daniellesmith@theiet.org | Editor G D Cronshaw +44 (0)1438 767384
gcronshaw@theiet.org | Contributing Editors M Coles, J Elliott | Design Sable Media Solutions
IEE Wiring Matters is a quarterly publication from the Institution of Engineering and Technology (IET). The IET is not as a body responsible for
the opinions expressed.
©2008: The Institution of Engineering and Technology. All rights reserved. No part of this publication may be reproduced, stored in a retrieval
system, or transmitted in any form or by any means without the permission in writing of the publisher. Copying of articles is not permitted
except for personal and internal use. Multiple copying of the content of this publication without permission is always illegal. Web-offset
printing by Wyndeham Heron, The Bentall Complex, Colchester Road, Heybridge, Maldon, Essex, UK
Co-operating Organisations The Institution of Engineering & Technology acknowledges the contribution made by the following
organisations in the preparation of this publication: British Electrotechnical & Allied Manufacturers Association Ltd – P D Galbraith,
M H Mullins | Department for Communities and Local Government – I Drummond | Electrical Contractors Association – D Locke,
S Burchell | City & Guilds of London Institute – H R Lovegrove | Energy Networks Association – D J Start | Electrical Contractors Association
of Scotland SELECT – D Millar, N McGuiness | Health & Safety Executive – K Morton | Electrical Safety Council | ERA Technology Limited –
M Coates | British Cables Association – C Reed | Scottish Building Standards Agency | DTI – D Tee | CORGI – P Collins | GAMBICA –
M. Hadley, A. Sedhev | Lighting Association – K Kearney
ISSN 1749-978-X
FOR LESS!
TRADE PRICES MASSIVE RANGE FREE NEXT DAY DELIVERY
BOX OF 500 PACK OF 3
BOX OF 600
Lightweight £12.99
Canadian Riggers
64p
pair
20 Piece
Screwdriver Set
£9.99
Workbench
Quote: 15447-92 Quote: 17241-92 Quote: 54906-92
BRANCHES
OPEN
7 DAYS ONLY
CALL
130 BRANCHES NATIONWIDE!
CLICK VISIT £149.99
0500 41 41 41 www.screwfix.com Branches
TEXT SCREWFIX TO 84880 OR VISIT SCREWFIX.COM FOR YOUR NEAREST BRANCH 18V Drill / Driver
BUYING AT SCREWFIX • Model No: DC759KB
BRANCHES IS AS EASY AS... 1 CHOOSE FROM THE CATALOGUE 2 PAY IN-STORE 3 COLLECT & GO! • 2 x 2.6Ah Ni-MH Batteries
Quote: 92618-92
Prices valid until 22/09/08
SECTION 559
4
but with no temperature marking, heat
resistant cables are not required
(ii) for a luminaire complying
with BS EN 60598 but with temperature
marking, cables suitable for the
marked temperature shall be used
(iii) in the absence of information,
heat-resistant cables and/or insulated
conductors of type H05S-U, H05S-K,
H05SJ-K, H05SS-K (BS 6007) or
equivalent shall be used.
Stroboscopic effects
Stroboscopic effects can be extremely
dangerous in particular
circumstances. In the case of lighting
for premises where machines with
moving parts are in operation,
consideration shall be given to
stroboscopic effects which can give a
misleading impression of moving
parts being stationary. Such effects
may be avoided by selecting
luminaires with suitable lamp
controlgear, such as high frequency
controlgear, or by distributing lighting
loads across all the phases of a three
phase supply.
OUTDOOR LIGHTING
Regulation group 559.10 has
requirements for outdoor lighting,
highway power supplies and street
In places where the fixing means is installed so that any expected stresses furniture. Similar to the 16th Edition,
intended to support a pendant in the conductors, terminals and the protective measures of placing out
luminaire, the fixing means shall be terminations will not impair the safety of reach and obstacles must not be
capable of carrying a mass of not less of the installation. used; Regulations 559.10.1 gives an
than 5 kg. If the mass of the luminaire exception. Also the protective measures
is greater than 5 kg, the installer shall Through wiring in a luminaire non-conducting location and earth-free
ensure that the fixing means is capable In some instances, it may be necessary local equipotential bonding must not be
of supporting the mass of the pendant to link the wiring through the used. A relaxation is permitted giving a
luminaire. luminaire on to the next luminaire. maximum disconnection time of 5 s
The installation of the fixing means This method of installation should (Regulation 559.10.3.3) for all circuits
shall be in accordance with the only be used if the luminaire is feeding fixed equipment used in
manufacturer’s instructions. designed for such practice. highway power supplies for compliance
The weight of luminaires and their A cable for through wiring shall be with Regulation 411.3.2.3 (TN system)
eventual accessories shall be selected in accordance with the or 411.3.2.4 (TT system).
compatible with the mechanical temperature information on the The Regulations now clearly state
capability of the ceiling or suspended luminaire or on the manufacturer’s in 559.10.3.4 that the earthing
ceiling or supporting structure where instruction sheet, if any, as follows: conductor of a street electrical fixture
installed. (i) unless specified in the shall have a minimum copper
Any cable or cord between the fixing manufacturer’s instructions, for a equivalent cross-sectional area not less
means and the luminaire shall be luminaire complying with BS EN 60598 than that of the supply neutral
6
by gating control or a regulating shall be insulated for that part of the Suspension devices for extra-low
process or a lamp failure) or if there is circuit between the transformer and voltage luminaires, including
a failure which causes a power the short-circuit protective device to supporting conductors, shall be
increase of more than 60 W prevent a short-circuit. capable of carrying five times the
(iv) The device shall provide automatic mass of the luminaires (including
disconnection upon connection of the Types of transformers and converters their lamps) intended to be supported
supply circuit if there is a failure Where the SELV source of a SELV but not less than 5 kg. Terminations
which causes a power increase of lighting system is a safety isolating and connections of conductors
more than 60 W transformer, it should meet the shall be made by screw terminals or
(v) The device shall be fail-safe. requirements of BS EN 61558-2-6. screwless clamping devices
Regulation 559.11.4.2 requires that the complying with BS EN 60998-2-1 or
NOTE: Account needs to be taken of transformer has a protective device on BS EN 60998-2-2.
starting currents. the primary side or it should be short- Insulation piercing connectors and
circuit proof and marked with the termination wires which rely on
Bare conductors following symbol: counterweights hung over suspended
If the nominal voltage does not exceed conductors to maintain the electrical
25 V a.c. or 60 V d.c., bare conductors connection shall not be used. The
may be used providing that the extra- suspended system shall be fixed to
low voltage lighting installation walls or ceilings by insulated distance
complies with all the following cleats and shall be continuously
requirements: Where an electronic converter, such accessible throughout the route.
(i) the lighting installation shall be as a switch-mode power supply, is used
designed, and installed or enclosed in to supply an extra-low voltage lighting CONCLUSION
such a way that the risk of a short- installation, it should comply with BS Under the 17th Edition, designers and
circuit is reduced to a minimum, and EN 61347-2-2 bearing the following persons involved in general lighting,
(ii) the conductors used shall have a symbol: fixed outdoor lighting installations
cross-sectional area of at least 4 mm, and extra-low voltage lighting
for mechanical reasons, and installations now have detailed
(iii) the conductors shall not be not requirements to follow. For further
placed directly on combustible information consult BS 7671:2008.
material. Also, help is at hand, in the form of
Suspended systems a new edition of IEE Guidance Note 1
For suspended bare conductors, at Regulation 559.11.6 has requirements (Selection & Erection edited by Mark
least one conductor and its terminals for Suspended systems. Coles) available soon. I
Guidance Notes
The IET published a series of Guidance Notes, each of Hager has created the Consumer Unit Guide to
which enlarges upon and amplifies a particular
the 17th Editon to guide you through these
requirement of the IEE Wiring Regulations. All these are
in the course of being updated and will be published over changes. Order your copy online from
the coming months. www.hager.co.uk
Exam Success
The IET, in collaboration with City & Guilds, has now
published four books to help students prepare for their exams.
Each title is an exam practice guide to help candidates feel
confident ahead of their exams. Sample papers are provided
together with hints and tips from examiners. I
www.theiet.org/publishing
APPENDIX 4
M&E is the premier event for building services professionals relating to the complete spectrum of
mechanical and electrical services. Whether you are an installer, contractor, mechanical engineer or
anything in between you can’t afford to miss out.
M&E will feature over 120 of the industry’s leading companies including:
• Applied Energy Products • Clearvision Lighting • Marshall-Tufflex Ltd
• Brother UK Ltd • Lapp Group Limited • MK Electric
• CBS Group • Leica Geosystems Ltd • Power Electrics – FG Wilson
Commercial Partners
incorporates
APPENDIX 4
10
Reference Example of installation method Relevant table from Image
method BS 7671:2008
Non-sheathed cables in conduit in a The wall consists of an outer weatherproof skin, Installation Method 1 of Table 4A2
thermally insulated wall thermal insulation and an inner skin of wood or
wood-like material having a thermal conductance
of at least 10 W/m.K. The conduit is fixed such that
it is close to, but not necessarily touching, the inner
A skin. Heat from the cables is assumed to escape
through the inner skin only. The conduit can be
Multicore cables in conduit in a metal or plastic. Installation Method 2 of Table 4A2
thermally insulated wall
Non-sheathed cables in conduit The conduit is mounted on a wooden wall such Installation Method 4 of Table 4A2
mounted on a wooden or that the gap between the conduit and the surface is
masonry wall less than 0.3 times the conduit diameter. The
conduit can be metal or plastic. Where the conduit
is fixed to a masonry wall the current-carrying
B capacity of the non-sheathed or sheathed cable
Multicore cables in conduit may be higher. Installation Method 5 of Table 4A2
mounted on a wooden or
masonry wall
Single-core or multicore cable on a Non-sheathed cables in conduit mounted on a Installation Method 20 of Table 4A2
C wooden or masonry wall wooden or masonry wall
(clipped direct)
Multicore unarmoured cable in Non-sheathed cables in conduit mounted on a Installation Method 70 of Table 4A2
conduit or in cable ducting in the wooden or masonry wallThe cable is drawn into a
ground 100 mm diameter plastic, earthenware or metallic
duct laid in direct contact with soil having a thermal
resistivity of 2.5 K.m/W and at a depth of 0.8 m.
The values given for this method are those stated in
this appendix and are based on conservative
installation parameters. If the specific installation
D parameters are known (thermal resistance of the
ground, ground ambient temperature, cable depth),
reference can be made to the cable manufacturer
or the ERA 69-30 series of publications, which may
result in a smaller cable size being selected.
NOTE: The current-carrying capacity for cables laid
in direct contact with soil having a thermal resistivity
of 2.5 K.m/W and at a depth of 0.7 m is
approximately 10 % higher than the values
tabulated for Reference Method D
Single-core or multicore cable in The cable is supported such that the total heat Installation Method 70 of Table 4A2
free air dissipation is not impeded. Heating due to solar
radiation and other sources is to be taken into
account. Care is to be taken that natural air
convection is not impeded. In practice, a clearance
between a cable and any adjacent surface of at
E, F and G least 0.3 times the cable external diameter for
multicore cables or 1.0 times the cable diameter for
single-core cables is sufficient to permit the use of
current-carrying capacities appropriate to free air
conditions.
Other methods of installation Edition now references cables buried installations, where investigations
Other methods of installation are in the ground (installation methods 70 establish more accurate values of soil
recognised but are, essentially, to 73). The current-carrying capacities thermal resistivity appropriate for the
variations of other methods and are tabulated for cables in the ground are load to be carried, the values of
therefore allocated appropriate based upon a soil thermal resistivity of current-carrying capacity may be
reference methods, shown in table 2 2.5 K.m/W and are intended to be derived by the methods of calculation
overleaf. applied to cables laid in and around given in BS 7769 (BS IEC 60287) or
It is worth noting that the 17th buildings, i.e. disturbed soil. For other obtained from the cable manufacturer.
Part P.
just ridiculously easy and that once
registered we keep your paperwork
down to an absolute minimum.
Or the fact that our assessors are all
time-served electricians who offer
a fair and objective service.
orted.
Whatever the reasons are, be a
bright spark and ease the process of
Part P with ELECSA.
www.elecsa.co.uk
The Institution of
Engineering and Technology
Call now on 01438 765678 and quote WM08 to join and receive your discount
immediately. Alternatively you can visit our website www.theiet.org/join
*Discount received on the first copy of each title only.
APPENDIX 4
12
2.5 K.m/W are given in Table 4B3. Cable ladder This is a construction which offers a minimum of impedance to the air flow around the cables, i.e.
system supporting metalwork under the cables occupies less than 10% of the plan area. The current-carrying
Flat, twin and earth cables installed capacity for cables on ladder systems should be taken as Reference Methods E or F.
in thermal insulation are also
Cable cleats, cable Cable supports hold the cable at intervals along its length and permit substantially complete free air flow
recognised by installation methods 100 ties and cable around the cable. The current-carrying capacity for cable cleats, cable ties and cable hangers should be
hangers taken as Reference Methods E or F.
to 103.
Cable installed in a This is similar to Reference Method A. It may be necessary to apply the rating factors due to higher
ceiling ambient temperatures that may arise in junction boxes and similar mounted in the ceiling.
Sizing of cables
NOTE: Where a junction box in the ceiling is used for the supply to a luminaire, the heat dissipation from
Relationship of current-carrying the luminaire may provide higher ambient temperatures than permitted in Tables 4D1A to 4J4A (see
capacity to other circuit parameters also Regulation 522.2.1). The temperature may be between 40 °C and 50 °C, and a rating factor
according to Table 4B1 must be applied.
The relevant symbols used in the
Regulations are shown in Table 3: Table 2: Other recognised methods of installation
Iz It Ib
The current-carrying capacity The value of current tabulated in The design current of the circuit, i.e.
of a cable for continuous this appendix for the type of the current intended to be carried
service, under the particular cable and installation method by the circuit in normal service. In
installation conditions concerned, for a single circuit in the rated current or current setting
concerned. the ambient temperature stated of the protective device.
in the current-carrying capacity
tables.
In I2 C
The rated current or current The operating current (i.e. the A rating factor to be applied where
setting of the protective fusing current or tripping current the installation conditions differ
device. for the conventional operating from those for which values of
time) of the device protecting the current-carrying capacity are
circuit against overload. tabulated in this appendix.
Ca Cg Ci
Ct Cc
For operating temperature of For the type of protective device
conductor. or installation condition.
Fig. 1: Coordination of load, device and cable characteristics Fig. 2: Coordination for overload protection
Where the overcurrent device is By referring to fig. 1, the current- so that In is greater than or equal to
intended to afford protection against carrying capacity of the cable, Iz, must the design current, Ib, of the circuit.
overload, I2 must not exceed 1.45 Iz and equal or exceed the circuit overcurrent
In must not exceed Iz, see fig. 2. device rated current, In. In ≥ Ib
Where the overcurrent device is
intended to afford fault current Iz ≥ In So, in the example of the 6 kW shower
protection only, In can be greater than In must be ≥ 26;
Iz and I2 can be greater than 1.45 Iz. and, hence, by combining the two
The protective device must be selected equations above, we get: select say a 32 A circuit-breaker, that is
for compliance with Regulation 434.5.2.
In In = 32 A
Determination of the size of cable It ≥
CaCgCiCc
to be used A cable must now be selected so that its
When overcurrent protection is to be rating, Iz, in the particular installation
provided, the current-carrying This equation can be read as, when conditions exceeds the design current
capacity of the cable, Iz, is determined overcurrent protection is to be of the load, Ib.
by applying correction factors to the provided, the tabulated cable ratings
tabulated cable ratings, It, from from Appendix 4 of BS 7671 must equal Iz ≥ Ib
Appendix 4 of BS 7671. or exceed the circuit overcurrent
device rating corrected for ambient In the example of the 6 kW shower
Iz = It Ca Cg Ci Cc temperature, grouping, thermal load, Ib = 26, so Iz ≥ 26.
insulation and the use of a rewirable
where: fuse if applicable. Where overload protection of the cable
is to be provided, as is usual, the cable
Ca is rating factor for ambient Example 1 is also selected so that its rating in its
temperature, see Table 4B1 of BS 7671 A circuit supplying a shower with a installed conditions Iz exceeds the
Cg is rating factor for grouping see, loading of 6 kW would have a design current rating of the circuit protective
Table 4C1 of BS 7671 current Ib given by: device.
Ci is rating factor for conductors
surrounded by thermal insulation 6 x 1000 W Iz ≥ In
Cc is a rating factor applied when Ib = = 26 A
230 V
overload protection is being provided In the example of the 6 kW shower
by an overcurrent device with a fusing circuit with overload protection,
factor greater than 1.45, e.g. Cc = 0.725 The nominal current rating in amps, Iz ≥ 32. It may be argued that no
for semi-enclosed fuses to BS 3036, and In, of the protective device (fuse or overload need be provided for a shower
when the cable is laid in the ground. circuit-breaker) for a circuit is selected as the load is fixed.
14
Therefore, Iz ≥ In ≥ Ib
Iz = It Ca Cg Ci Cc
Consultancy
High voltage accredited courses & competence
assessment, including:
ADIPS is the fairground and amusement park
industry’s self regulated safety inspection • HV safety training: land based & marine/offshore
scheme which registers competent ride power systems
inspectors and the rides they inspect. • HV ‘authorised person’ training courses
• Electrical protection & switchgear maintenance
Qualified and competent groups or individuals can
• 17th Edition Wiring Regulations
register with the scheme to be able to inspect
• HV safety rules auditing and developing
amusement devices in various engineering
disciplines, for pre-use inspection and in-service • Electrical Testing
annual inspection, on behalf of the members of the • Basic Electrical Safety
industry trade associations. • Electrical Equipment in Hazardous Area
• Electrical for Non-electrical Personnel
ADIPS offers an unique electrical inspection
course which gives additional information, examples Training centres in the UK & Cyprus
and assessment related specifically to the travelling
fairground and static amusement/theme park industry to
enable registration under the ADIPS scheme. Those
wishing to take the course must be qualified to C. & G. The Faraday Centre
2391 and/or 2392 (or equivalent). When successfully Tel: 01642 467236
registered, individuals and organisations may provide their
services to the fairground and amusement device industry. www.faradaycentre.co.uk
NEW
from Publishing The IEE is a registered trademark of
The Institution of Engineering and Technology
Guidance Note 3:
16
AVAILA AVAILA
BLE BLE
NOW! NOW!
REQUIREMENTS
FOR ELECTRICAL ELECTRICIAN’S
INSTALLATIONS GUIDE TO THE
BS 7671: 2008
ON-SITE GUIDE BUILDING
(IEE Wiring Regulations, (BS 7671: 2008 17th REGULATIONS
17th Edition) Edition) (PART P, 2nd EDITION)
The Wiring Regulations are the national The On-Site Guide is intended to enable the The law requires you from 1 January 2005
standard to which all domestic competent electrician to deal with small to meet the requirements of the
and industrial wiring must conform. installations (up to 100 A, 3-phase). It Building Regulations. This guide has been
Substantial changes have been provides essential information in a updated to align with the 17th edition of the
incorporated in BS 7671: 2008 to align convenient, easy to use form, avoiding the IEE Wiring Regulations. It also includes a new
with European documents. Essential for all need for detailed calculations. chapter on requirements for Scotland.
electricians, electrical contractors and their
• Paperback 183pp • Paperback 210pp
managers, installation designers, and
• 2008 • 2008
students in further education and
• ISBN 978-0-86341-854-9 • ISBN 978-0-86341-862-4
professional training.
• Order book PWGO170B • Order book PWGP170B
Contents: Scope, Object and Fundamental £20 £20
Principles. Definitions. Assessment of • 2nd Edition 2008
General Characteristics. Protection for Safety.
Selection and Erection of Equipment.
Special Installations or Locations. Inspection
and Testing.
• Paperback 389pp
• 2008
NEW
• ISBN 978-0-86341-844-0
• Order book PWR1700B
£65 EXAM EXAM
SUCCESS: SUCCESS:
CODE OF IEE Code of Practice The IEE Wiring
PRACTICE FOR 2377 Regulations 2382-20
IN-SERVICE • Paperback 116pp • Paperback 68pp
INSPECTION • 2007 • 2008
• ISBN 978-0-86341-805-1 • ISBN 978-0-86341-886-0
AND TESTING OF • Order book PWR05070 • Order book PWR05090
ELECTRICAL £12 £12
EQUIPMENT
3rd Edition 2007
This Code of Practice has been revised to
reflect current best practice. It gives
guidance to those responsible for the NEW NEW
inspection, testing and maintenance of
electrical appliances. The text specifies the
frequency and scope of inspections and
testing in different environments. The new
EXAM EXAM
revision is printed in colour and includes SUCCESS: SUCCESS:
many drawings aimed at helping to identify Inspection and The IEE Wiring
common problems. Testing 2391-10 Regulations 2382-10
• Paperback 152pp • Paperback 84pp • Paperback 136pp
• 2007 • 2008 • 2008
• ISBN 978-0-86341-833-4 • ISBN 978-0-86341-899-0 • ISBN 978-0-86341-885-3
• Order book PWR08630 • Order book PWR05110 • Order book PWR05080
£35 £15 £12
The Institution issues a series of Guidance Notes, each of which enlarges upon the particular requirements of a part of the 17th Edition of the
Wiring Regulations. Each of these guides is extensively cross-referenced to the Regulations, thus providing convenient and ready access. Some
Guidance Notes contain information not included in the 17th Edition; this information is either from earlier editions of the IEE Wiring Regulations or
is included as guidance as a method of meeting the requirements of the Regulations. The scope generally follows that of the Regulations and the
principal section numbers are shown on the left. The relevant Regulations and appendices are noted in the right-hand margin. All of the Guidance
Notes contain references to other relevant sources of information, e.g. British Standards, HSE publications, etc.
All Guidance Notes are updated to reflect changes to IEE Wiring Regulations BS 7671: 2008
AVAILA
BLE
GUIDANCE NOTE 3: NOW! GUIDANCE NOTE 6:
Inspection and Testing, 5th Edition Protection Against Overcurrent, 5th
• Paperback 126pp • 2008 Edition
• ISBN 978-0-86341-857-0 • Paperback 113pp • 2008
• Order book PWG3170B £25 • ISBN 978-0-86341-860-0
• Order book PWG6170B £25
www.theiet.org
6 5 4 3
Electrical Installation Design Guide, On-Site Guide, A5, wire spiral bound, Electrician’s Guide to the Building
A5, wire spiral bound, Paperback, paperback, Regulations (Part P, 2nd Edition)
Order code PWR05030 74C1
Order 4 PWG0170B
code 503bound, paperback
A5, wire4spiral
Price £20 Price £20 1 Order code PWGP170B 14
2 GS5 13 Price U
O £20T 6 12
1 OUT5
This book provides step-by-step
GS4Guide1 Updated
Updated to the 17th Edition IEE
U7ARegulations, the On-Site 4 the 17th 6
10
guidance on the design of electrical Wiring 9 OUTto Edition IEE
installations, from domestic installation is intended to enable the competent 7 Wiring Regulations,
T3 the Electrician’s
J 1 6 U G S3 OUwill 4
1 4066 2
final circuit design to fault level electrician to deal with small
G S 2
Guide
5 not only
O U T 2
ensure domestic
2
installers
calculations for LV/large LV systems.18 installations (up to 100 A, 3-phase). comply with Part P, but also
13 GS1
Including simple circuit calculations, 3 with OU T
other 1
Building Regulations; U13
K Apprentices and A trainees will find it
U 1 J16L it provides essentialEinformation
N4 in a including Fire Safety, Ventilation and
very helpful in carrying out the
calculations necessary for a basic 2 0 74 C
convenient,1 4easy to use form,
EN3 1 DI S4 of Energy. This new
Conservation
E N 3
installation. It 4 6 been
06also
has
avoiding
3 prepared calculations.
12
the need
13 for detailed 15 DIS2includes a chapter on
edition also
4 With full colour requirements for Scotland.
to provide a design sequence,5 J16U illustrations and easy-to-read text, it
calculations andBdata for a complete
1 0 U7F for all electricians, U14
U
design to be carried out. It is
2 is essential
electrical contractors and their
9 intended to include all necessary
J 1 6 L managers, 14
74Cinstallation designers, and
5K cable and equipment data to carry
0 6 6 7 9 EN2 and
4 10 1 students
8
in further education
out the calculations.
11 professional training. EN1 4503
1 2 14
J16U
It includes calculations and necessary
UD3 13 OUT6
1Dfound in the
reference dataUnot GS5 12
1 7 1 1 O U T 5 0
design packages, such as cable For further information, or to order 4
7 4C14 GS4 online, 1visit
conductor and sheath 69
406temperatures J1 6 L 9 OU T 6
8 for harmonics.
and allowances 10 11
www.theiet.org/wiringregs 7 OUT3
6 19 GS 3 4
5 O U T 2 2
U1C U7E GS2
GS1 3 O U T 1
New Books J16U IEE Electrical Courses
S 5
4 G To be notified when associated
19 new Wiring EN2 the1IET is Drunning
Throughout 2008 IS4 a full
Regulations books are published, please visit programme of courses1and DIS2
5 associated City &
L
3 Gwww.theiet.org/wrf
S1 Guilds exams to enable you to U 16 to the new
train
and submit your details. 17th Edition standard. To view a list of courses
R23 and book online visit
QI www.theiet.org/wmcourses
10M 2N4393 4503
14
1 3 O U T 6 I N 6 2
GS5 1
1 1 O U T 5 IN5 10
A 11 The IEE is a registered trademark of the Institution of Engineering GS4and TechnologyT4 IN4
B 10 R 1 9 9 OU
3
1
G S 3 7 O U T 3 I N3 64
C 9 The Institution of Engineering and Technology is registered as a Charity in England & Wales (no 211014) and Scotland (no SCO38698)
22
working knowledge of the 16th Edition conversant with the format, content point that persons sitting any of
of BS 7671 but are specifically aimed at and application of the current edition the 17th Edition examinations
persons who have already achieved of BS 7671. Given the relatively short described above may only make
one of the qualifications addressing time that will have elapsed since reference to the 17th Edition during
BS 7671 listed below: candidates obtained their 16th Edition the examination.
I City & Guilds Level 3 Certificate in qualification, these qualifications focus
the Requirements for Electrical on the main additions and alterations Inspection, testing and certification
Installations BS 7671: June 2001 from the 16th Edition that have been Although the 17th Edition contains a
(2381), or incorporated in the 2008 17th Edition. number of changes relating to
I City & Guilds Level 3 Certificate in These qualifications consist of inspection, testing and certification,
Electrotechnical Technology around 7½ hours of instruction, these should be covered in sufficient
Installation (Building and typically delivered over one day or depth during a course leading to the
Structures) (2330-07), or three evenings. City & Guilds 2382 or EAL 17th Edition
I City & Guilds Level 3 Certificate in Candidates have 1 hour to answer 30 qualifications and as such it has not
Electrotechnical Technology questions. In the case of the City & been considered necessary to require
Electrical Maintenance (2330- 08), or Guilds qualification, assessment is by persons who have successfully
I City & Guilds Level 3 Certificate in a multiple-choice test sat via a completed a 16th Edition era (2391-01)
Electrical Installation Part Two computer using the GOLA online City & Guilds inspection and testing
(2360) (from January 1st 2004 system and the case of the EAL qualification to have to undertake any
onwards only) qualification, candidates may sit inspection and testing specific
either a conventional paper format or upgrading training. However, the
On completion of these updating online examination. current version of the City & Guilds
qualifications, candidates should be It is worth mentioning at this qualification (the 2392-10) and the EAL
Level 3 Diploma in Inspecting and Relating to the 17th Edition qualifications are available to help
Testing Electrotechnical Systems and I 2382-10 17th Edition. persons to become conversant with the
Equipment have been updated such To accompany the 2 hour, current requirements contained
that they now relate to the 17th Edition 60 question examination within the 17th Edition. The IET also
requirements. I 2382-20 16th to 17th Edition update. offer a wide range of training options
To accompany the 1 hour, 30 relating to electrical installation,
Help with the examinations question examination maintenance, safety and legislation.
The IET and City & Guilds have I 2391-10 Inspection and testing The IET courses unit offers a wide
worked together to produce a series of range of courses relating to the
books called Exam Success, the aim of Relating to the IEE Code of practice for electrical design, inspection and
which is to assist candidates in their In-service inspection and testing of testing full details of which can be
preparation for sitting City & Guilds electrical equipment obtained from the current course
electrical installation/maintenance I 2377 Covers both the Management brochure or from
related examinations and which are of electrical equipment maintenance http://www.theiet.org/careers/courses
intended to complement the tuition (2377-100) and the Inspection and /electrical/index.cfm
provided from attendance on a course testing of electrical equipment (2377- Courses are provided at venues
of study. Where necessary these have 200) examinations. throughout the UK and can also be
been revised to reflect the content of offered in–house to organisations.
the 17th Edition. A newly revised version of the On-site Assistance to aid the successful
These books contain useful tips to aid Guide based upon the content of the completion of these qualifications can
in revision for and sitting the 17th Edition has also been released be obtained from the Exam Success
examinations and contain a number of recently. series of books produced by The IET
sample question papers and model in collaboration with City and Guilds.
answers with explanations. In the case Summary The On-site Guide and Exam Success
of the 2377 and 2382 17th Edition Regulation 16 of The Electricity at series of books can be obtained
examinations, advice is also given on Work Regulations 1989 requires directly from the IET or from most
what to expect when sitting a GOLA persons involved in electrical work to large bookshops.
computer based examination for the be competent to do so. Technical Anyone seeking further information
first time. Although not specifically knowledge is one of the elements of on City & Guilds courses should refer
designed to accompany the EAL the measure of competency. As such to City & Guilds directly or consult
qualifications, the sample questions and anyone involved in low voltage their website at
model answers would also be of use to electrical installation or maintenance www.cityandguilds.com/
persons attempting the EAL equivalents work should develop a sound working Anyone seeking further information
of the City & Guilds qualifications. knowledge of the 17th Edition on EAL courses should refer to EAL
The Exam Success series of (BS 7671:2008). directly or consult their website at
publications is as follows: A number of training courses and www.eal.org.uk I
24
Content
The 17th Edition introduces a number of requirements for Example 2 - Three-way split board with two 30 mA RCDs
RCDs, such as, for socket-outlet circuits in domestic and The three-way division of an installation to provide ways
similar installations for use by non skilled people, for circuits unprotected by RCDs for, say, fire systems and for two
of locations containing a bath or shower and for cables separate 30 mA RCDs to ensure that part of the installation
without earthed metallic covering installed in walls or will remain energised in the event of a fault. Unprotected
partitions at a depth of less than 50 mm and not protected by circuits will usually need to be installed in earthed metal
earthed steel conduit or similar, amongst others. conduit or wired with earthed metal-sheathed cables or, in
The On-Site Guide offers guidance on meeting these some cases, installed on the surface; see figure 2.
requirements by showing different permutations of RCDs,
RCBOs and circuit-breakers at consumer units. Two Further information
examples are given here. The On-Site Guide forms part of the suite of guidance
publications issued by the IET, for which, there is a rolling
Example 1 - RCBOs programme to update and publish. The On-Site Guide is
The use of RCBOs, see figure 1, will minimize inconvenience available now. I
in the event of a fault and is applicable to all systems. Such a
consumer unit arrangement also easily allows individual Price: £20
circuits, such as to specifically labelled sockets or fire Available: From August 2008
alarms, to be protected by a circuit-breaker without RCD Format: Paperback, wire-bound
protection. Such circuits will usually need to be installed in Product Code: PWGO170B
earthed metal conduit, wired with earthed metal-sheathed ISBN: 978-086341-854-9
cables or, in some cases, installed on the surface. Pagination: 188 pp
ELECTRICAL
COURSES
Book Ahead for 2009 at 2008 prices
Routes to Competence:
17th Edition
• Workshop upgrade and City & Guilds
2382-20 exam
• Level 3 Certificate in the Requirements for
Electrical Installations 17th Edition and
City & Guilds 2382-10 exam
• 17th Edition Design
N
for EW
200
9!
Inspection and Testing
• Level 2 Certificate in Fundamental
Inspection, Testing and Initial Verification
(City & Guilds 2392-10)
• Level 3 Certificate in Inspection, Testing
& Certification of Electrical Installations
(City & Guilds 2391-10)
Save time and money with training on your company premises. A delegate from
Network Rail had this to say “Very good presenter, flexible approach and
tailored presentation to meet our requirements.”
www.napit.org.uk