You are on page 1of 16

TGP145 HV GAS INSULATED SWITCHGEAR

(GIS)

Energy, Fast!

tgood.com
TGOOD produces over 5000
switchgear units annually for
projects around the globe

PRODUCT OVERVIEW

High performance alternative to air insulated systems.


Best-in-class lead times measured in weeks, not months.
Immune to harsh environmental conditions.
Sealed GIS is safe to touch and inherently arc-resistant.
Compact factory-pressurized modules save space and reduce
cost compared to traditional GIS.
May be pre-assembled within a prefabricated E-House
or mobile trailer-mounted substation.

2 TGP145 HV Gas Insulated Switchgear www.tgood.com


KEY BENEFITS
PROVEN APPLICATIONS MODULAR DESIGN
Compact design ideal for space- Standard configurable modules allow
constrained projects in crowded cities reduced lead times for any customer
and congested industrial zones. arrangement.

Outstanding performance in harsh Fully assembled, pressurized and tested


environments, including high altitude, in the factory.
heavily polluted, coastal, desert and
Modules can be energized within 24 hours
arctic sites.
of delivery.
Low audible noise and electric field
Significant cost savings over traditional
emissions make this product attractive
GIS solutions.
for densely populated areas.

SAFE, RELIABLE,
AND LOW-MAINTENANCE
Grounded tank design is safe to touch.

Completely arc-resistant.

Modules connected with gas-tight


flanges, delivering decades of reliable
operation.

TGP145 HV Gas Insulated Switchgear 3


PRODUCT DESIGN

Modules individually configured and tested within


an ISO 9001 factory environment.
Corrosion-free aluminum housings ensure safe
encapsulation of factory-filled SF6 gas.
Simple gas filling requires top-up with SF6 bottles only;
no complex gas processing equipment required.
Compact modules require no special shipping
considerations.

2 CIRCUIT BREAKER

The circuit breaker module is comprised of two


interconnected structures: the stored-energy spring
mechanism and the current interrupting unit.

1. Circuit Breaker Module: Integral Components


2. Spring Operating Mechanism Assembly
CURRENT INTERRUPTING UNIT
Two separate current-carrying contact paths for
each current interrupting unit; main contacts
1
disconnect first and connect last to minimize
arcing damage.

2 During a short circuit, arc-generated thermal


pressure assists the spring operating mechanism
3 to quickly pull contacts apart.

Arc-quenching design provides exceptional


4
durability by minimizing mechanical stresses on
circuit breaker components.
5
6
7
8 1. Arcing Contact (Fixed)
9 2. Main Contact (Fixed)
3. Nozzle
10 4. Arcing Contact (Moving)
5. Main Contact (Moving)
6. Contact Cylinder
7. Thermal Expansion Chamber
8. One-Way Valve
9. Pressure Relief Valve
10. Pressure Relief Spring

STORED-ENERGY SPRING MECHANISM


Provides force to efficiently and reliably open and
close the circuit breaker.

Compact layout allows for straightforward viewing


of spring mechanism position.

Sealed bearings and maintenance-free charging


mechanism deliver decades of problem-free
operation.
Spring Operating Mechanism

www.tgood.com TGP145 HV Gas Insulated Switchgear 5


Current Transformer Structure Three Position Switch SF6 Outdoor Bushings

THREE POSITION SWITCH HIGH-SPEED EARTHING SWITCH


Single three-position switching module Maintenance-free electric motorspring
incorporates both isolation and earthing mechanism delivers fast and reliable
functions. operation.

Position indicators allow visual inspection Arc-resistant contacts enable use in


of switch position. transmission line grounding applications.

SEALED THREE PHASE BUS LIGHTNING SURGE ARRESTORS


Sealed connection modules available in Provides protection from excessive
a variety of configurations to enable GIS voltages that may occur in case of a
arrangements according to any customer lightning strike or switching transient.
requirement.
Online monitoring and surge-count with the
Bellows-type expansion joints use of integrated current sensors.
between modules mitigate the effect of
temperature-related changes and allow for SF6 OUTDOOR BUSHINGS
practical site assembly tolerances.
Suitable for outdoor termination to
CURRENT AND POTENTIAL overhead lines and transformer bushings.
TRANSFORMERS
CABLE TERMINAL UNITS
Current transformers and potential
transformers provide key measurement Allows for the connection of typical high-
and system protection functions. voltage cable types to the GIS system.

Three-phase CT and PT modules can


be positioned at any point within the GIS
LOCAL CONTROL CABINET
system.
Provides central control and monitoring of
Wide range of protection and metering the GIS system, including operation control,
classes available. signal collection, relay protection, and SF6
monitoring.

6 TGP145 HV Gas Insulated Switchgear


PRODUCT SPECIFICATIONS
Item Unit Specification

Rated Voltage kV 145

Rated Current
A 3150/4000
(breaker/busbar)
Withstand Voltage
kV (1 min) 275/315
(phase-to-ground/phase-to-phase)
Lightning Impulse Voltage kV Peak
650/750
(phase-to-ground/phase-to-phase) 1.2/50μs

Short-time Withstand Current kA (3s) 40

Peak Withstand Current (50Hz/60Hz) kA 100/104

SF6 Pressure at 20°C (filling pressure/minimum pressure) mPa 0.6/0.5

SF6 Leakage %/year ≤ 0.1

Rated Operating Sequence o-0.3s-co-180s-co

Corona Extinction % 110

Partial Discharge (interval) pC ≤5

Lifetime Ratings

Breaker (mechanical) open/close > 10,000

Breaker (electrical) short circuit trip 20

Three Position Switch open/close > 3,000

Quick Action Earthing Switch open/close > 5,000

ENVIRONMENTAL SPECIFICATIONS
Item Units Specification

Operating Environment Indoor/Outdoor

Ambient Temperature °C -25 to +40

Elevation metres above sea level ≤1,000

≤ 90% Monthly Average


Relative Humidity %
≤95% Daily Average
Horizontal Acceleration: ≤ 0.4G;
Seismic Intensity G
Vertical Acceleration: ≤ 0.2G

8 TGP145 HV Gas Insulated Switchgear


Modular HV
GIS Substation

www.tgood.com TGP145 HV Gas Insulated Switchgear 9


Feeder 2 Feeder 1
C B A C B A

Bus Coupler

Transformer 2 Transformer 1 TPS


A B C A B C

B LCC

Typical Transformer Branch Connection A

ES

CT TPS

TPS GCB
3250

BUS CT

5600

10 TGP145 HV Gas Insulated Switchgear


SINGLE BUS LAYOUT

Bus coupler design facilitates system upgrades and allows the Substation to continue
operation while expansions takes place. Flanged connections on the GIS modules allows for
the safe and straight-forward addition of additional modular components as required.

15000
B B

A C A

6750
TPS TPS TPS
TPS
TPS TPS

LCC LCC LCC LCC LCC LCC

A C A C
15000
B B

LEGEND
BUS: Main Busbar GCB: Gas Insulated Circuit Breaker
CT: Current Transformer LCC: Local Control Cabinet
ES: Earthing Switch TPS: Three Position Switch
FES: Fast Earthing Switch All Units in Millimetres

www.tgood.com TGP145 HV Gas Insulated Switchgear 11


DOUBLE BUS LAYOUT

Critical load centers and power generation facilities commonly use


a double bus GIS configuration. The two busbars can be operated
separately or tied together. Double bus configurations can reduce the
short circuit current, extend the standard maintenance period, and
enhance power supply reliability.

Bus 2
Bus 1

6750
Bus Coupler

Feeder 1 Feeder 2
Transformer 1 Transformer 2

Typical Feeder Branch Connection


FES

TPS

CT TPS
CTU
TPS GCB

LCC

2000
6630

12 TGP145 HV Gas Insulated Switchgear


LCC LCC LCC LCC LCC LCC LCC

ES ES

TPS TPS TPS TPS TPS TPS TPS

7200

LEGEND
BUS: Main Busbar GCB: Gas Insulated Circuit Breaker
CTU: Cable Terminal Unit LCC: Local Control Cabinet
CT: Current Transformer TPS: Three Position Switch
ES: Earthing Switch All Units in Millimetres
FES: Fast Earthing Switch

www.tgood.com TGP145 HV Gas Insulated Switchgear 13


BUS TIE LAYOUT

Bus ties are commonly utilized in congested industrial and residential


areas. Two high voltage incoming lines with two step-down transformers
ensure a highly flexible and reliable power supply.

Feeder 1 Feeder 2
A BC A BC

Transformer 1 Bus Coupler Transformer 2


A BC A BC

Typical Bus Coupler Branch Connection

ES FES

TPS CT TPS
TPS
TPS GCB
BUS CT
2220

7550

14 TGP145 HV Gas Insulated Switchgear


TPS
TPS
TPS

TPS

10550
LCC LCC LCC LCC LCC

ES ES

TPS TPS

TPS TPS TPS

TPS
TPS

10400

LEGEND
BUS: Main Busbar GCB: Gas Insulated Circuit Breaker
CT: Current Transformer LCC: Local Control Cabinet
ES: Earthing Switch TPS: Three Position Switch
FES: Fast Earthing Switch All Units in Millimetres

www.tgood.com TGP145 HV Gas Insulated Switchgear 15


TGQDMK400010

TGOOD Global Ltd. Tel: + 852 2393 8005


Unit B, 8/F, Shun Ho Tower, Fax: + 852 2393 8808
24-30 Ice House Street, sales@tgood.com
www.tgood.com Central, Hong Kong