BS 5486 : Part 2 : 1988


IEC 439-2 1987
UDC621.316.3.027.4:621.316.35

0 British Standards institution. No part of this publication may be photocopied or otherwise reproduced without the prior permission in writing of BSi

British Standard
Low-voltage switchgear and
controlgear assemblies
Part 2. Particular requirements for busbar
trunking systems (busways)

Ensembles d'appareillage à basse tension


Partie 2. Prescriptions particulières pour les canalisations préfabriquées

Niederspannungs-Scha1tgerätekombinationen
Teil 2. Besondere Anforderungen an Schienenverteiler

British Standards Institution


COPYRIGHT British Standards Institute on ERC Specs and Standards
Licensed by Information Handling Services
- -_ i_

B S I BS*5Lt8h P A R T * 2 88 W Lh24bhî O 0 4 2 2 4 8 b
BS 5486 : Part 2 : 1988

Contents
Page
Page
National foreword Inside front cover Appendix
Committees responsible Back cover F Example of determination ofR and X by
calculation from measurements for a three-phase
Specification a.c. busbar trunking system 11
1 General 1
2 Definitions 1
4 Electrical characteristics of assemblies 3
5 Information to be given regarding the assembly 3
7 Design and construction 3
8 Test specifications 5

National foreword
This Part of BS 5486 has been prepared under the direction ofthe Power Electrical Engineering Standards Committee and
supersedes BS 5486 : Part 2 : 1978, which is withdrawn. It is identical with IEC Publication 439-2 : 1987 ‘Low-voltage
switchgear and controlgear assemblies, Part 2 : Particular requirements for busbar trunking systems (busways)’, published by
the International Electrotechnical Commission (IEC).
This Part of BS 5486 is a supplement to BS 5486 : Part I , which specifies the general requirements for busbar tmnking
systems.
The following is adapted from the IEC preface.
Busbar trunking systems (busways) shall comply with all the general requirements specified in BS 5486 : Part 1, unless
otherwise indicated in this Part of BS 5486, and shall also comply with the additional particular requirements contained in
this Part.
This Part shall be read in conjunction with BS 5486 : Part 1. Its clauses and subclauses modify or replace the
corresponding clauses of BS 5486 : Part I ; their numbering therefore corresponds to the latter.
Where there is no corresponding clause or subclause in this Part, the clause or subclause ofBS 5486 : Part 1 shall apply
without modification.
Terminology and conventions. The text of the international standard has been approved as suitable for publication as a
British Standard without deviation. Some terminology and certain conventions are not identical with those used in British
Standards.

Cross-references
International standard Corresponding British Standard
IEC 439- I : I985 BS 5486 LOW-voltageswitchgear and controlgear assemblies
. Part I : 1986 Specification for type-tested and partially type-tested assemblies (general
requirements)
(Identical)
The Technical Committee has reviewed the provisions of IEC 570, to which reference is made in the text, and has decided
that they are acceptable for use in conjunction with this standard.
A related British Standard for IEC 570 is BS 4533 ‘Luminaires’ Section 2.6 : 1979 ‘Electrical supply track systems for
luminaires’.
Compliance with a British Standard does not of itself confer immunity from legal obligations. G

COPYRIGHT British Standards Institute on ERC Specs and Standards


Licensed by Information Handling Services
BSI BS*SLIBb P A R T r 2 88 Lb2Llbb7 OOLi22Li7 8
BS 5486 : Part 2 : 1988

British Standard

Low-voltage switchgear and controlgear assemblies


Part 2. Particular requirements for busbar trunking systems (busways)

1. General

1.1 Scope

Add the following paragraph :

T h i s s t a n d a r d also applies t o b u s b a r t r u n k i n g systems intended t o


s u p p l y luminaires t h r o u g h t a p - o f f u n i t s b u t does n o t apply t o s u p p l y
t r a c k systems i n accordance w i t h IEC Publication 570.

2. Definitions

2.1 . 1 . 2 Partially type-tested LV switchgear and controlgear


assemblies ( P T T A ) .

Not applicable,

2 . 3 . 4 Busbar trunking system [busway)

A t y p e - t e s t e d assembly i n t h e f o r m o f a conductor system comprising


b u s b a r s which 'are spaced and s u p p o r t e d by i n s u l a t i n g material i n a
duct, t r o u g h o r similar enclosure.

T h e assembly may consist of u n i t s such a s :


- b u s b a r t r u n k i n g u n i t s w i t h o r w i t h o u t t a p - o f f facilities,
- phase transposition, expansion, flexible, feeder and adapter u n i t s ,

- tap-off units.

Note.- T h e t e r m " b u s b a r " does n o t p r e j u d g e t h e geometrical shape,


size o r dimensions o f t h e conductor.

Add the following definitions :

2.3.5 Busbar trunking unit

A u n i t o f a b u s b a r t r u n k i n g system complete w i t h busbars, t h e i r


s u p p o r t s and insulation, e x t e r n a l enclosure and a n y f i x i n g and
connecting means t o o t h e r units, w i t h o r w i t h o u t t a p - o f f f a c i l i t i e s .

Note.- T r u n k i n g u n i t s may have d i f f e r e n t geometrical shapes such a s


s t r a i g h t length, elbow, tee o r cross.

I -7

I [IEC page 91
COPYRIGHT British Standards Institute on ERC Specs and Standards I
Licensed by Information Handling Services
B S I BS*548h PART*Z Bä ~~
l b 2 4 h b 7 00422.50 4
BS 5486 : Part 2 : 1988

2.3.6 Busbar trunking unit with tap-off facilities

A b u s b a r t r u n k i n g u n i t designed t o enable t a p - o f f u n i t s t o b e
installed a t one o r more points a s predetermined by t h e manufacturer.

T h e connection of t a p - o f f u n i t s t o t h e b u s b a r t r u n k i n g u n i t may o r
may not r e q u i r e t h e b u s b a r system t o b e disconnected from t h e
supply.

2.3.7 Busbar trunking unit with trolley-type tap-off facilities

A b u s b a r t r u n k i n g u n i t designed t o p e r m i t t h e use o f r o l l e r - o r
brush-type tap-off units.

2.3 .i3 Busbar trunking adapter unit


A b u s b a r t r u n k i n g u n i t intended t o connect t w o u n i t s of t h e same
system b u t o f d i f f e r e n t t y p e o r o f d i f f e r e n t rated c u r r e n t .

2.3.9 Busbar trunkìng expansion unit

A b u s b a r t r u n k i n g u n i t intended t o p e r m i t a certain movement in t h e


a x i a l d i r e c t i o n of t h e b u s b a r t r u n k i n g system, e . g . thermal expansion.

2.3.1 O Busbar phase transposition unit

A b u s b a r t r u n k i n g u n i t intended t o change t h e relative positions o f


t h e phase conductors in o r d e r t o balance t h e i n d u c t i v e reactances o r
t o transpose t h e phases (such as L I - L 2 - L 3 - N t o N-L3-L2-L1).

2.3.1 1 Flexible busbar trunking unit

A b u s b a r t r u n k i n g u n i t h a v i n g conductors and enclosures designed


t o b e b e n t d u r i n g installation.

2.3.12 Busbar trunking feeder unit

A b u s b a r t r u n k i n g u n i t s e r v i n g as a n y incoming u n i t . T h e
6
connection of t h e feeder u n i t t o t h e s u p p l y may o r may not r e q u i r e t h e
s u p p l y t o b e disconnected.

2.3.13 Tap-off unit

A n outgoing u n i t f o r t a p p i n g - o f f power f r o m t h e b u s b a r t r u n k i n g
u n i t with tap-off facilities (see Sub-clause 2.3.6), such as rollers,
brushes o r p l u g - i n devices.

[IEC page I i ]
COPYRIGHT British Standards Institute on ERC Specs and Standards
2
-
Licensed by Information Handling Services
BSI B S * 5 4 8 b P A R T * 2 8 8 E Lb2Libb7 OOLi225L b I
BS 5486 : Part 2 : 1988

4. Electrical characteristics of assemblies


O Add Sub-clause 4.10 as follows:

4 . 1O Resistance and reactance values

T h e manufacturer shall state in t h e manner described in Clause 5 t h e


following mean values of t h e d i f f e r e n t phases, if a n y :

R = t h e mean ohmic resistance o f t h e t r u n k i n g system p e r metre


l e n g t h p e r phase:

- f o r a l l b u s b a r t r u n k i n g systems i r r e s p e c t i v e of r a t e d c u r r e n t :
resistance R a t a conductor temperature of +20 OC;
20

- f u r t h e r , f o r busbar t r u n k i n g systems w i t h a r a t e d c u r r e n t
g r e a t e r than 630 A : resistance R t when thermal e q u i l i b r i u m is
reached a t a n ambient temperature of +20 OC f o r t h e r a t e d
current.

X = t h e mean reactance o f t h e t r u n k i n g system p e r metre l e n g t h p e r


phase a t r a t e d f r e q u e n c y .

T h e values o f R and X may b e determined by d i r e c t measurement o r


by calculations f r o m measurements (see Appendix F ) .

5. Information t o b e g i v e n r e g a r d i n g t h e assembly

5.1 Nameplates
Add Item r ) as follows

r ) mean resistance and reactance values

7. Design a n d c o n s t r u c t i o n
7.1 .I General
Add the following t e x t :

B u s b a r trunking systems shall b e designed as type-tested low-


voltage switchgear and c o n t r o l g e a r assemblies ( T T A ) .

According t o t h e manufacturer's indications, busbar t r u n king


systems a r e i n t e n d e d t o w i t h s t a n d :
- e i t h e r normal mechanical loads (see Sub-clause 7.1.1.1),
- o r heavy mechanical loads (see Sub-clause 7.1.1.2),
- o r special mechanical loads (see Sub-clause 7.1.1.3).

[IEC page 131


COPYRIGHT British Standards Institute on ERC Specs and Standards
Licensed by Information Handling Services
BSI B S * C 4 8 6 P A R T * 2 8 8 W Lb24bb9 OOq2252 8 M
BS 5486: Part 2 : 1988

7.1 .I - 1 Normal mechanical loads

For b u s b a r t r u n k i n g systems, normal mechanical loads include, in


addition t o t h e i r own weight, mechanical loads imposed by t h e feeder
and t a p - o f f u n i t s .

Notes 1.- T h e necessary mechanical rigidity m a y b e obtained by t h e


choice of material, i t s thickness, i t s shape, and/or by t h e
number and position of f i x i n g points as indicated by t h e
manufacturer.

2.- Feeder u n i t s supported by t h e i r own separate f i x i n g s shall


not b e included in normal mechanical loads.

7.1 . 1 .2 Heavy mechanical loads

For b u s b a r t r u n k i n g systems, heavy mechanical loads include, i n


addition t o t h e normal mechanical loads, additional loads such as t h e
weight of a person.

Notes 1,- T h e necessary mechanical rigidity may b e obtained by t h e


choice of material, i t s thickness, i t s shape, and/or by t h e
number and position o f f i x i n g points as indicated by t h e
man u f a c t u r e r .

2.- T h e statement does n o t imply t h a t t h e b u s b a r t r u n k i n g


system may be used a s a walkway.

7.1 .I . 3 Special mechanical loads

T h e ability of b u s b a r t r u n k i n g systems t o w i t h s t a n d o t h e r additional


loads, such as l i g h t i n g apparatus, additional cables, ladder supports,
etc., s,hall b e subject t o agreement between manufacturer and u s e r .

7.1 .I .4 Insulating materials

Self-extinguishing properties of insulating materials are under


con s idera t io'n.
Add Sub-clause 7.1.4 as follows:

7.1.4 Requirements for the correct connection of tap-off units

When a b u s b a r t r u n k i n g system with predetermined t a p - o f f facilities


has a p r o t e c t i v e conductor o r a n e u t r a l conductor o r both, t h e design
shall b e such that, f o r reasons of safety, i n c o r r e c t assembly of a n y
p a r t of t h e system o r connection of t h e t a p - o f f u n i t s is p r e v e n t e d .

I n t h e case of d . c . o r single-phase a.c. t h e o r d e r o f polarities shall


b e maintained t h r o u g h o u t t h e e n t i r e length of t h e system.

[IEC page I51 4


COPYRIGHT British Standards Institute on ERC Specs and Standards
Licensed by Information Handling Services
BSI B S * 5 4 8 6 P A R T S 2 138 3624669 0042253 T
BS 5486 : Part 2 : 1988

In case of three-phase a.c., t h e phase sequence shall b e maintained


along t h e e n t i r e l e n g t h of t h e system.

Table 111: Temperature-rise limits

Replace footnote 4 ) b y the following:

Unless otherwise specified in t h e case of e x t e r n a l surfaces o f


enclosures of b u s b a r t r u n k i n g systems which a r e accessible b u t do not
need t o b e touched d u r i n g normal operation, an increase i n t h e tempe-
r a t u r e - r i s e limits by 25 K i s permissible f o r metal surfaces and by
15 K f o r i n s u l a t i n g surfaces.

7 . 6 . 2 . 1 Accessibility
F i r s t p a r a g r a p h n o t applicable.

8 . T e s t specifications
Replace the existing text b y the following:

8 . 1 . 1 T y p e tests (see Sub-clause 8 . 2 )


T y p e tests a r e intended t o v e r i f y compliance w i t h t h e requirements
l a i d down i n t h i s s t a n d a r d f o r a g i v e n ' t y p e o f b u s b a r trunking
system.

T y p e tests s h a l l b e c a r r i e d o u t on a sample of such a b u s b a r


t r u n k i n g system o r on such p a r t s of b u s b a r t r u n k i n g systems
manufactured t o t h e same o r a similar d e s i g n .

T h e y shall b e c a r r i e d o u t on t h e i n i t i a t i v e of t h e manufacturer.

T y p e tests include:

a) v e r i f i c a t i o n of t e m p e r a t u r e - r i s e limits
(Sub-clause 8 . 2 . 1 , Publication 439-I),

b) v e r i f i c a t i o n of t h e d i e l e c t r i c p r o p e r t i e s
(Sub-clause 8 . 2 . 2 , Publication 439-I),

c) verification of t h e short-circuit strength


(Sub-clause 8 . 2 . 3 , Publication 4 3 9 - l ) ,

d) v e r i f i c a t i o n of t h e c o n t i n u i t y of t h e p r o t e c t i v e c i r c u i t
(Sub-clause 8 . 2 . 4 , Publication 4 3 9 - l ) ,

e) v e r i f i c a t i o n of clearances and creepage distances


(Sub-clause 8 . 2 . 5 , Publication 4 3 9 - l ) ,

r-

5 [IEC page 171


COPYRIGHT British Standards Institute on ERC Specs and Standards
Licensed by Information Handling Services i
~~ -

BSI B S x 5 4 8 b PART*2 88 9 L b 2 Y b b î 0 0 4 2 2 5 Y L m
BS 5486 : Part 2 : 1988

f) v e r i f i c a t i o n o f mechanical operation
(Sub-clause 8 . 2 . 6 , Publication 4 3 9 - l ) ,

g) verification of t h e degree of protection


(Sub-clause 8 . 2 . 7 , Publication 439-I),

h ) v e r i f i c a t i o n of resistance and reactance


(Sub-clause 8 . 2 . 8 of this publication) ,

i) verification of s t r u c t u r a l s t r e n g t h
(Sub-clause 8 . 2 . 9 of this publication),

k) verification of t h e endurance of t r u n k i n g systems with t r o l l e y t y p e


t a p - o f f facilities
(Sub-clause 8 . 2 . 1 0 o f t h i s p u b l i c a t i o n ) .

These tests may b e c a r r i e d o u t in any o r d e r and/or on d i f f e r e n t


samples of t h e same t y p e .

If modifications are made t o t h e components of t h e assembly, new


t y p e tests have t o be c a r r i e d o u t o n l y i n so f a r as such modifications
a r e likely t o a d v e r s e l y affect t h e results o f these tests.

Note.- Reference should also b e made t o t h e additions t o Sub-


clauses 8 . 2 . 1 and 8 . 2 . 3 g i v e n in t h i s p a r t of t h e publication.

8 . 2 T y p e tests
8 . 2 . 1 Verification of temperature-rise limits
8 . 2 . 1 . 2 Arrangement of the busbar trunking system
T h e b u s b a r t r u n k i n g system t o b e t e s t e d shall b e a r r a n g e d as in
normal use, w i t h a l l covers, etc., i n place.

T h e c u r r e n t rating of a busbar t r u n k i n g system is affected by t h e


mounting arrangement. T h e r e f o r e t h e temperature r i s e t e s t has t o b e
performed with t h e r a t e d c u r r e n t a p p r o p r i a t e t o t h e mounting a r r a n g e -
ment(s) stated by t h e manufacturer. If o n l y one t e s t is performed, t h e
most unfavourable mounting arrangement shall be used.

8 . 2 . 1 . 3 Temperature-rise tests
A t e s t shall b e performed o v e r a total length of a t least 6 m
i n c l u d i n g a t l e a s t one j o i n t .

T h e t e s t c u r r e n t s shall b e substantially equal i n t h e l i v e conductors.

A n y unintentional c i r c u l a t i o n of a i r in t h e section u n d e r t e s t shall b e


prevented, e.g. by closing t h e ends.

[I EC page I 91 6
COPYRIGHT British Standards Institute on ERC Specs and Standards
i
-
i
Licensed by Information Handling Services
B S I BS*548h PART*2 8 8 W 11h24bh9 0042255 3
BS 5486 : Part 2 : 1988

A n o t h e r temperature-rise t e s t shall b e made on each size of t a p - o f f


u n i t designed t o b e connected t o t h e b u s b a r t r u n k i n g system. For t h i s
test, t h e t a p - o f f u n i t s h a l l c a r r y i t s r a t e d c u r r e n t and t h e b u s b a r
t r u n k i n g system shall b e supplied with i t s r a t e d c u r r e n t .

T h e size and t h e disposition of e x t e r n a l conductors used f o r t h e t e s t


s h a l l b e p a r t of t h e t e s t r e p o r t .

T h e t e s t s h a l l b e made f o r a s u f f i c i e n t time f o r t h e temperature r i s e


t o reach a constant value ( b u t n o t exceeding 8 h ) . In practice, t h i s
condition i s reached when t h e v a r i a t i o n does n o t exceed 1 K p e r h o u r .

Note.- I n practice, t o shorten t h e t e s t t h e c u r r e n t may b e increased


during t h e f i r s t p a r t o f t h e test, it being reduced t o t h e
specified t e s t c u r r e n t a f t e r w a r d s .

In t h e absence of detailed information a s t o t h e service conditions,


t h e cross-section o f t h e e x t e r n a l conductors s h a l l b e as follows: (see
Publication 439-1).

8.2.3 Verification of the short-circuit strength 3

8.2.3.2.1 Test arrangement

T h e b u s b a r t r u n k i n g system shall b e set u p as in normal use. T h e


t y p e t e s t s h a l l b e c a r r i e d o u t on a n assembly comprising a t least one
b u s b a r trunking feeder u n i t connected t o t h e a p p r o p r i a t e number of
s t r a i g h t t r u n k i n g u n i t s t o obtain a l e n g t h of not more t h a n 6 m.

O t h e r t y p e s of t r u n k i n g u n i t s and t a p - o f f u n i t s n o t included i n t h e
above t e s t shall b e tested i n d i v i d u a l l y .

8.2.3.2.5 Results t o be obtained

A f t e r t h e test, t h e conductors shall n o t show a n y u n d u e deforma-


t i o n . Slight deformation of b u s b a r s i s acceptable p r o v i d e d t h a t the
clearances and creepage distances specified i n Sub-clause 7.1.2 a r e
s t i l l complied w i t h a n d t h a t t h e deformation does n o t i n t e r f e r e w i t h t h e
p r o p e r connection of t a p - o f f u n i t s . Also, t h e insulation o f t h e conduc-
.tors and t h e s u p p o r t i n g i n s u l a t i n g p a r t s s h a l l n o t show a n y s i g n i f i c a n t
signs o f deterioration, t h a t is, t h e essential characteristics o f t h e
insulation remain such t h a t t h e mechanical and d i e l e c t r i c p r o p e r t i e s of
t h e equipment s a t i s f y t h e requirements o f t h i s s t a n d a r d .

T h e detection device s h a l l n o t i n d i c a t e a f a u l t c u r r e n t .

T h e r e shall b e no loosening o f p a r t s used f o r t h e connection of


conductors and conductors shall n o t separate f r o m t h e outgoing I
terminals. I

T h e effectiveness of t h e p r o t e c t i v e conductors e n s u r i n g protection


against e l e c t r i c shock i n case of a f a u l t shall n o t b e impaired.

/ .
7 [IEC page 211
COPYRIGHT British Standards Institute on ERC Specs and Standards
Licensed by Information Handling Services
B S I BSm548b P A R T * Z 88 m l b 2 4 b b 7 0 0 ~ 2 Z 5 65

Deforination of t h e enclosure i s permissible t o t h e e x t e n t t o which


t h e degree of protection is not impaired and t h e clearances a r e n o t
reduced t o values which a r e less t h a n those specified.

A n y d i s t o r t i o n of t h e b u s b a r c i r c u i t o r t h e frame of t h e assembly
which impairs normal i n s e r t i o n o f withdrawable o r removable u n i t s shall
b e deemed a f a i l u r e .

In case of doubt, it shall b e checked t h a t t h e apparatus incorporated


in t h e assembly i s i n a condition a s p r e s c r i b e d i n t h e relevant spe-
cifications.

Add Sub-clauses as follows:

8 . 2 . 0 Verification of resistance and reactance

T h e mean values of resistance and reactance (see Sub-clause 4.10 of


t h i s publication) are determined on a t e s t specimen having a total
l e n g t h of a t l e a s t 6 m i n c l u d i n g a t least one j o i n t .

The method o f determination shall b e chosen by t h e manufacturer.


A n example of calculation f r o m measurements is g i v e n in Appendix F.

8 . 2 . 9 Verification of structural strength

According t o t h e mechanical loads indicated by t h e manufacturer, t h e


verification of t h e s t r u c t u r a l s t r e n g t h o f b u s b a r t r u n k i n g systems
intended f o r horizontal installation shall b e made in accordance w i t h
t h e following t e s t procedures:

- f o r normal mechanical loads: see Sub-clause 8 . 2 . 9 . 1 ,


- f o r heavy mechanical loads: see Sub-clause 8 . 2 . 9 . 2 ,
- f o r special mechanical loads: see Sub-clause 8 . 2 . 9 . 3 .

8 . 2 . 9 . 1 Verification of the structural strength with normal mechanical


loads

These tests v e r i f y t h e s t r u c t u r a l s t r e n g t h w i t h normal mechanical


loads according t o Sub-clause 7 . 1 , I . 1.

8.2.9.1.1 T h e f i r s t t e s t shall b e made on one straight t r u n k i n g u n i t ,


which is s u p p o r t e d as in normal use a t t w o positions spaced a t t h e
distance D . This distance D shall b e t h e maximum distance between
s u p p o r t s specified by t h e manufacturer.

Note.- T h e location and form of t h e s u p p o r t s a r e t o b e specified by


t h e manufacturer.

A mass M s h a l l b e placed w i t h o u t dynamic loading on a square rigid


piece with sides equal t o t h e width of t h e b u s b a r t r u n k i n g system, a t
t h e midpoint bstween t h e s u p p o r t s on t o p o f t h e enclosure. T h e mass
M shall b e equal t o t h e mass m of that p a r t of t h e t r u n k i n g u n i t which
i s between t h e s u p p o r t s p l u s an additional mass r n ~equal t o t h e
maximum load imposed by t h e feeder and t a p - o f f u n i t s specified by t h e
manufacturer t o b e connected t o t h e l e n g t h D .

[IEC page 731 8


COPYRIGHT British Standards Institute on ERC Specs and Standards
Licensed by Information Handling Services
i

B S I BS*548b PART*2 8 8 W Lb2Libb7 0 0 4 2 2 5 7 7 W


BS 5486 : Part 2 : 1988

T h e d u r a t i o n of t h e t e s t shall b e 5 min.

IM I
M = m + mL

m = mass o f t h e trunking u n i t
I
l between s u p p o r t s

mL= mass o f t h e feeder and


t a p - o f f un i t s

8.2.9.1.2 A second t e s t shall be made on t w o s t r a i g h t t r u n k i n g u n i t s


joined t o g e t h e r a n d s u p p o r t e d as in normal use a t t h e minimum number
of positions a t t h e maximum distances D a n d DI. T h e distance D is
that specified i n Sub-clause 8.2.9.1.1; t h e distance D1 i s t h e maximum
distance between s u p p o r t s adjacent t o a j o i n t as specified by t h e
manufacturer. T h e j o i n t shall b e placed midway between t h e s u p p o r t s .

A mass M l shall b e placed w i t h o u t dynamic loading on t o p o f t h e


enclosure a t t h e j o i n t on a square rigid piece with sides equal t o t h e
w i d t h of t h e b u s b a r t r u n k i n g system. T h e mass M l shall b e equal t o
t h e mass ml o f those p a r t s o f t h e t r u n k i n g units, i n c l u d i n g t h e joint,
between t h e s u p p o r t s located a t distance D I p l u s a n additional mass
mLI equal t o t h e maximum load imposed by t h e feeder and t a p - o f f u n i t s
specified by t h e m a n u f a c t u r e r t o b e connected t o t h e l e n g t h D l .

T h e d u r a t i o n o f t h e t e s t shall b e 5 min.

I Mf

I
I
I I
\ I \

c I D L

-
- ml + mLl

ml
= mass o f t h e t r u n k i n g u n i t s i n c l u d i n g j o i n t between s u p p o r t s a t
distance DI

mLl = mass o f t h e feeder and t a p - o f f u n i t s

8.2.9.2 Verification of t h e structural strength with heavy mechanical loads

These tests v e r i f y t h e s t r u c t u r a l strength with heavy mechanical


loads according t o Sub-clause 7.1.1.2.

9 [IEC page 251


COPYRIGHT British Standards Institute on ERC Specs and Standards
Licensed by Information Handling Services
BSI B S * 5 4 8 b ~
PART*Z 88 9 1624bbï 0042258 9
~ ~~ ~
m
BS 5486 : Part 2 : 1988

8.2.9.2.1 The t e s t described in Sub-clause 8 . 2 . 9 . 1 . I shall b e . p e r f o r m e d


w i t h t h e mass

M = m + mL + 90 k g

8.2.9.2.2 The t e s t described i n Sub-clause 8.2.9.1.2 shall b e performed


w i t h t h e mass
- 90 kg
Ml - ml + "LI +

8.2.9.3 Verification of the structural strength w i t h special mechanical


loads

The t e s t s v e r i f y i n g t h e s t r u c t u r a l s t r e n g t h w i t h special mechanical


loads (Sub-clause 7. I . I .3) shall be t h e subject of a n agreement
between manufacturer and u s e r .

8.2.9.4 Results to be obtained

D u r i n g and a f t e r these t e s t s , n e i t h e r t h e t r u n k i n g u n i t s n o r t h e
j o i n t o r p a r t s of them shall break; i n addition, t h e r e shall be no
deformation of t h e enclosure which would compromise t h e degree of
protection o r reduce t h e clearances and creepage distances t o values
which a r e less t h a n those specified (see Sub-clause 7.1.2 of IEC
Publication 439-1). A f t e r t h e t e s t , t h e r e shall be no appreciable p e r -
manent deformation which, f o r example, would be liable t o i m p a i r the
c o r r e c t insertion of incoming and outgoing u n i t s . ,

D u r i n g and a f t e r these t e s t s the protective circuit shall remain


functional.

A f t e r each of t h e t e s t s according t o Sub-clause 8.2.9.1, 8.2.9.2 o r


8.2.9.3, t h e t e s t assemblies shall w i t h s t a n d t h e dielectric t e s t accord-
i n g t o Sub-clause 8.2.2 of IEC Publication 439-1.

8.2.1 O Verification of the endurance of t r u n k i n g systems w i t h trolley


type tap-off facilities

With t h e s l i d i n g contacts c a r r y i n g t h e i r rated c u r r e n t a t rated


voltage, it shall b e p o s s i b l e t o c a r r y o u t successfully 10 O00 cycles of
t o and from movements along t h e conductors o f t h e t r u n k i n g system.

In t h e case of a.c., t h e power factor of t h e load shall be f r o m 0.75


to 0.8.

T h e speed of t h e t r o l l e y c a r r y i n g the sliding contacts and the


distance t h r o u g h which it moves shall be determined by t h e operating
conditions for which it i s designed, If the t r o l l e y i s intended t o sup-
p o r t a tool o r other mechanical load, an equivalefit w e i g h t shall b e
suspended f r o m it d u r i n g t h e t e s t .

A f t e r completion of t h e t e s t , t h e r e shall be no mechanical o r elec-


t r i c a l defect, whether by undue p i t t i n g , b u r n i n g o r welding of t h e
contacts.

[IEC pagc 771 10


COPYRIGHT British Standards Institute on ERC Specs and Standards
Licensed by Information Handling Services
-
U
E S 1 BSU548b PARTU2 A B ILb2LibbS 0 0 4 2 2 5 9 O
BS 5486 : Part 2 : 1988

Add an Appendix F as follows:

APPENDIX F

EXAMPLE OF DETERMINATION OF R AND X B Y CALCULATION FROM


MEASUREMENTS FOR A THREE-PHASE A . C . BUSBAR
TRUNKING SYSTEM

T h e following measurements shall b e recorded f r o m t h e t e s t d a t a obtained


d u r i n g t h e temperature-rise test:

V = t h e average r . m . s . line-to-line voltage d r o p i n v o l t s

V = ‘12 + ‘23 + ‘31


3

I = t h e average r . m . s . c u r r e n t in amperes

Il + l2 l 3+

I =
3

P = t h e t o t a l three-phase power in watts

L = t h e l e n g t h i n metres f r o m t h e voltmeter leads connected a t t h e input


end t o t h e p o i n t where t h e b u s b a r s are connected together a t t h e
o u t p u t end.

Calculate t h e impedance Z, t h e a l t e r n a t i n g c u r r e n t resistance R , and t h e


reactance X , in ohms p e r metre on line-to-neutral basis, as follows:

V
Z =
45 I L

X = (Z2- R 2 ) 1/2

Note. - A more elaborate method o f calculation i s u n d e r consideration.

[IEC page 291


COPYRIGHT British Standards Institute on ERC Specs and Standards
Licensed by Information Handling Services
-
BSI B S * 5 4 â b PART*2 ô€! l b 2 4 b b î 0042260 7 M

Publications referred to
1
See national foreword.

Previous page
is blank
COPYRIGHT British Standards Institute on ERC Specs and Standards
Licensed by Information Handling Services
-
BSI BS*C4Bb PART*Z BB Lb24bb7 0 0 4 2 2 6 3 7 W

BS 5486 : Part 2 : 1988


IEC 439-2 : 1987

This British Standard, having been prepared under the direction BSI. This does not preclude the free use, in the course of
of the Power Electrical Engineering Standards Committee, was implementing the standard, of necessary details such as symbols and
published under the authority of the Board of BSI and comes into size, type or grade designations. Enquiries should be addressed to
effect on 30 November 1988. the Publications Manager, BSI, Linford Wood, Milton Keynes
MK14 6LE. The number for telephone enquiries i s 0908 220022
O British Standards Institution, 1 9 8 8 and for telex 825777.
First published February 1 9 7 8 Contract requirements. A British Standard does not purport to
First revision November 1988 include all the necessary provisions of a contract. Users of British
Standards are responsible for their correct application.
ISBN O 5 8 0 1 6 9 7 8 2

The following FISI references relate to the work on this standard: Revision of British Standards. British Standards are revised, when
Committee reference PEL/I 2 Draft for comment 85/33085 DC necessary, by the issue either of amendments or of revised editions.
~~
It is important that users of British Standards should ascertain that
they are in possession of the latest amendments or editions.
British Standards Institution. Incorporated by Royal Charter, BSI i s
the independent national body for the preparation of British Automatic updating service. BSI provides an economic, individual
Standards. It is the UK member of the International Organization and automatic standards updating service called PLUS. Details are
for Standardization and UK sponsor of the British National available from BSI Enquiry Section a t Milton Keynes, telephone
Committee of the International Electrotechnical Commission. 0908 221 166, telex 825777.
In addition to the preparation and promulgation of standards, BSI
offers specialist services including the provision of information Information on all BSI publications is in the BSI Catalogue,
through the BSI Library and Standardline Database; Technical Help supplemented each month by BSI News which i s available to
to Exporters; and other services. Advice can be obtained from the subscribing members of BSI and gives details of new publications,
Enquiry Section, BSI, Milton Keynes MK14 6LE. telephone revisions, amendments and withdrawn standards. Any person who,
0908 221166, telex 825777. when making use of a British Standard, encounters an inaccuracy or
ambiguity, i s requested to notify BSI without delay in order that
Copyright. Users of British Standards are reminded that copyright
the matter may be investigated and appropriate action taken.
subsists in a l l BSI publications. No part of this publication may be
reproduced in any form without the prior permission in writing of

Committees responsible for this British Standard


The preparation of this British Standard was entrusted by the Electrical Contractors' Association
Power Electrical Engineering Standards Committee (PEL/-) t o Electrical Installation Equipment Manufacturers' Association
Technical Committee PEL/I 2 upon which the following bodies (BEAMA Ltd)
were represented: Electricity Supply Industry in England and Wales
ASTA Certification Services Engineering Equipment and Materials Users' Association
Association of British Mining Equipment Companies ERATechnology Ltd
Association of Supervisory and Executive Engineers GAMBICA (BEAMA Ltd)
British Gas plc Health and Safety Executive
Building Employers' Confederation National Inspection Council for Electrical Installation Contracting
Department of Trade and Industry, Consumer Safety Unit, Transmission and Distribution Association [BEAMA Ltd)
CA Division