Factory Acceptance Test (FAT)

CRAC STULZ
(17/01/2019 – 21/01/2019)

1. Testing Method
The performance test of the close control air conditioning units in the STULZ
test center are carried out in accordance with GB19413-2010. The test center is a
closed-off area at the end of the assembly line.
The test center is designed for performance and functionally testing under
specific climatic conditions. In the control room the attendant take place and
witness the test procedure. The entire test center is supervised from the control
room. During the test, all measured data is monitored, logged and corresponding
values are calculated in real time.

Climatic Chamber is using to take the test, the test specimens are put
through numerous test. These include test for compliance with safety
requirements, performance test, sound test and function test of the entire unit at
data center operation/ special running condition.
The time taken to reach stable operating can vary depending on the test
parameter and size of device. In general, setting takes 60-90 minutes per operating
condition, the testing recording from 0 minute, 10 minutes, 20 minutes, 30 minutes,
40 minutes, 50 minutes, and 60 minutes.
Function test was testing to check the function of all component that
installed in CRAC Unit (water leak, communication, etc.) and measure the time of
change over, damper opening, and total time when power source transfer unit until
fan speed 100%.

2. CRAC Testing
Once steady operating conditions are met at the design load, measurement and
performance data will be acquired continuously for a period not less than 60
minutes. Steady conditions must be sought and obtained prior to this, which may
take a prolonged period.
Graphical data during the extended full load test duration will prove and
demonstrate performance, along with screen shoot of “significant” quantities and
parameters, at equally spaced intervals should be taken throughout the test period
and included within the final report. The tolerance for data testing is:
Tolerance
Description Unit
Min Max
Return Air Temperature °C - 0,2 + 0,2
Supply Air Temperature °C - 0,2 + 0,2
Air Volume Flow m3/h - 5% +5%
External Pressure Pa - 5% +5%
Power Consumption Fan kW - 8% +8%
Medium Inlet Temperature °C - 0,1 + 0,1
Medium Outlet Temperature °C - 0,1 + 0,1
Medium Volume Flow m3/h - 1% +1%
Net Cooling Caoacity, Total kW - 8% +8%
Net Cooling Caoacity, Sensible kW - 8% +8%