Dimensions
Unit: mm Dimension: 302(L)×175(W)×328(H)
Terminal F10
F.V/Time 15MIN 30MIN 1HR 2HR 3HR 4HR 5HR 6HR 8HR 10HR 20HR
1.60V 733.2 5 6 7 .7 3 6 5 .4 2 1 7 .2 161.8 129.0 1 0 8 .6 91.20 73.62 6 1 .5 4 3 1 .6 9
1.65V 697.2 5 4 5 .1 3 4 9 .5 2 0 9 .3 155.0 124.4 1 0 4 .1 89.01 70.33 5 9 .3 4 3 0 .5 6
1.70V 650.1 5 1 3 .9 3 4 2 .7 2 0 5 .9 151.6 123.3 1 0 2 .9 86.81 69.23 5 8 .2 4 2 9 .9 9
1.75V 577.1 4 5 6 .8 3 1 5 .6 1 9 4 .6 143.7 116.5 9 8 .4 1 82.41 67.03 5 7 .1 4 2 9 .4 3
1.80V 496.8 4 2 1 .2 2 9 7 .5 1 8 5 .5 138.0 115.4 9 5 .0 2 81.31 65.93 5 4 .9 4 2 8 .3 0
1.85V 420.1 3 7 9 .2 2 7 4 .9 1 7 5 .3 131.2 106.3 9 0 .4 9 76.92 62.63 5 2 .7 4 2 7 .1 6
100
120 Su ppleme ntary ch arge required
0℃ (Ca rry ou t suppleme ntary ch arge
before us e if 100% ca pacity is
100 80 requires)
Capacity (%)
10℃
Su ppleme ntary ch arge required
Capacity(%)
80 60 before us e.
This su ppleme ntary ch arge wi ll help
to recover the ca pacity an d sh ould
60 20℃ be ma de as ea rly as po ssible.
100% 80% 50% 30% 15% 40 40℃ 30℃
D.O.D D.O.D D.O.D D.O.D D.O.D
Su ppleme ntary ch arge ma y of ten
40 fail to recover the ca pacity.
The ba ttery sh ould ne ver be left
20 standing till this st ate is reached
20
0
Su ppleme ntary ch arge an d st orage
2 4 6 8 10 12 14 16 18 20 22 24 guidelines
0 400 800 1200 1600 2000 2400
Number of Cycle(Times) Storage Time (months)
C h a rg e V o lu m e (% )
C h a rg e C u rre n t (C A )
Fast -0.2Cx2h+0.3CAx4.0h Generally specking, the most important factors is depth of discharge.