HYDRAULIC CALCULATIONS -- PIPE CHARACTERISTICS DT.

12/10/01
COMPANY :
DESIGNER :
CLIENT :
PROJECT : FIRE PROTECTION SYSTEM FOR
JOB NO. :
SYSTEM : MEDIUM VELOCITY WATER SPRAY SYSTEM FOR 32Mø x 15M HT HSD TANK
NOZZLE DISCHARGE FLOW NODE NODE PIPE LENGTH FITTINGS EQUIV. TOTAL HEAD LOSS TOTAL LOSS MINIMUM
NO. THRU NOZZLE IN LPM FROM TO SIZE NOS. LENGTH LENGTH PRESSURE
IN LPM REQD.
34 MM MTRS Elbow Tee MTRS Mbars Mbars Mbars
TOP RING HAVING NOZZLE WITH K FACTOR 34 MIN PRESSURE AT REMOTE NOZZLE 1790.00
1 45.49 101 102 100 2.2 1 3 5.2 0.016 0.0832 1790.08
2 45.49 90.98 102 103 100 2.2 1 3 5.2 0.056 0.2912 1790.37
3 45.49 136.47 103 104 100 2.2 1 3 5.2 0.119 0.6188 1790.99
4 45.5 181.97 104 105 100 2.2 1 3 5.2 0.203 1.0556 1792.05
5 45.51 227.48 105 106 100 2.2 1 3 5.2 0.307 1.5964 1793.65
6 45.54 273.02 106 107 100 2.2 1 3 5.2 0.431 2.2412 1795.89
7 45.56 318.58 107 108 100 2.2 1 3 5.2 0.573 2.9796 1798.87
8 45.6 364.18 108 109 100 2.2 1 3 5.2 0.734 3.8168 1802.68
9 45.65 409.83 109 110 100 2.2 1 3 5.2 0.913 4.7476 1807.43
10 45.71 455.54 110 111 100 2.2 1 3 5.2 1.11 5.772 1813.20
11 45.78 501.32 111 112 100 2.2 1 3 5.2 1.325 6.89 1820.09
12 45.87 547.19 112 113 100 2.2 1 3 5.2 1.558 8.1016 1828.19
13 45.97 593.16 113 114 100 2.2 1 3 5.2 1.809 9.4068 1837.60
14 46.09 639.25 114 115 100 2.2 1 3 5.2 2.078 10.8056 1848.41
15 46.23 685.48 115 116 100 2.2 1 3 5.2 2.364 12.2928 1860.70
16 46.38 731.86 116 117 100 2.2 1 3 5.2 2.669 13.8788 1874.58
17 46.55 778.41 117 118 100 2.2 1 3 5.2 2.991 15.5532 1890.13
18 46.74 825.15 118 119 100 2.2 1 3 5.2 3.332 17.3264 1907.46
19 46.96 872.11 119 120 100 2.2 1 3 5.2 3.691 19.1932 1926.65
20 47.19 919.3 120 121 100 2.2 1 3 5.2 4.069 21.1588 1947.81
21 47.45 966.75 121 122 100 2.2 1 3 5.2 4.466 23.2232 1971.03
22 47.73 1014.5 122 123 100 2.2 1 3 5.2 4.883 25.3916 1996.42
23 48.04 1062.5 123 124 100 2.2 1 3 5.2 5.319 27.6588 2024.08
24 48.37 1110.9 124 125 100 1.8 1 3 4.8 5.776 27.7248 2051.81
2051.81
1110.89 2221.8 125 226 150 3.0 1 1 6 9.0 2.952 26.568 2078.38
STATIC LOSS THRU. 3.0 M HT. 300 2378.38
2222 LPM TOTAL FLOW ON TOP RING AT 2378 Mbars PRESSURE
BOTTOM RING HAVING NOZZLE WITH K FACTOR 34 MIN PRESSURE AT REMOTE NOZZLE 1943.00
1 47.39 201 202 100 2.2 1 3 5.2 0.017 0.09 1943.09
2 47.39 94.78 202 203 100 2.2 1 3 5.2 0.061 0.32 1943.41
3 47.4 142.18 203 204 100 2.2 1 3 5.2 0.129 0.67 1944.08
4 47.41 189.59 204 205 100 2.2 1 3 5.2 0.219 1.14 1945.22
5 47.42 237.01 205 206 100 2.2 1 3 5.2 0.331 1.72 1946.94
6 47.44 284.45 206 207 100 2.2 1 3 5.2 0.465 2.42 1949.35
7 47.47 331.92 207 208 100 2.2 1 3 5.2 0.618 3.21 1952.57
8 47.51 379.43 208 209 100 2.2 1 3 5.2 0.792 4.12 1956.69
9 47.56 426.99 209 210 100 2.2 1 3 5.2 0.985 5.12 1961.81
10 47.62 474.61 210 211 100 2.2 1 3 5.2 1.198 6.23 1968.04
11 47.7 522.31 211 212 100 2.2 1 3 5.2 1.43 7.44 1975.47
12 47.79 570.1 212 213 100 2.2 1 3 5.2 1.681 8.74 1984.22
13 47.89 617.99 213 214 100 2.2 1 3 5.2 1.952 10.15 1994.37
14 48.02 666.01 214 215 100 2.2 1 3 5.2 2.242 11.66 2006.02
15 48.16 714.17 215 216 100 2.2 1 3 5.2 2.551 13.27 2019.29
16 48.31 762.48 216 217 100 2.2 1 3 5.2 2.879 14.97 2034.26
17 48.49 810.97 217 218 100 2.2 1 3 5.2 3.227 16.78 2051.04
18 48.69 859.66 218 219 100 2.2 1 3 5.2 3.594 18.69 2069.73
19 48.91 908.57 219 220 100 2.2 1 3 5.2 3.982 20.71 2090.44
20 49.16 957.73 220 221 100 2.2 1 3 5.2 4.389 22.82 2113.26
21 49.43 1007.2 221 222 100 2.2 1 3 5.2 4.818 25.05 2138.31
22 49.72 1056.9 222 223 100 2.2 1 3 5.2 5.267 27.39 2165.70
23 50.04 1106.9 223 224 100 2.2 1 3 5.2 5.737 29.83 2195.53
24 50.38 1157.3 224 225 100 1.8 1 3 4.8 6.23 29.90 2225.44

1157.3 2314.6 225 226 150 1 1 6 6 3.184 19.104 2244.54


2315 LPM TOTAL FLOW ON BOTTOM RING AT 2245 M bars PRESSURE

TOTAL FLOW TOP & BOTTOM RING 2222 + 2315 = 4537 LPM @Mbars 2244.54

4537 226 227 200 78 4 1 15 93 2.561 238.17 2483

STATIC LOSS THRU. 11.4 M HT. 1140.00 3623


TOTAL FLOW REQD. AT TAPPING POINT NEAR HYDRANT MAINS FOR TANK NO. T-04 A/B/C/D 4537 LPM @ BARS 3.62