You are on page 1of 25

ERDA’s Transformer Test Facility:

Capability Profiles and Technical Notes

ELECTRICAL RESEARCH AND DEVELOPMENT ASSOCIATION


ERDA Road, Makarpura
Vadodara – 390 010
E-mail: erda@erda.org; Web: www.erda.org

1
Contents

Sr. Topic
No.
1 Transformer Test Facility : ERDA’s Capability Profile

2 Condition Monitoring of Transformers and fault Diagnosis

3 Diagnostic Studies on Power Transformers

4 Condition Monitoring of Transformer Oil

5 High Efficiency Domain Refined CRGO grades for Transformers :


New Surge Sheet Test capability at ERDA

6 Domain Refined CRGO Grades: ERDA Augments Magnetic


Materials Test Laboratory with New capability for large size – Surge
Sheet – Transformer Core Laminations

7 Solid Dielecric Laboratory

2
1. Transformer Testing Facility: ERDA’s Capability Profile
1.1 Introduction

Transformers are one of the most important elements in the electrical power system. Any failure in a
transformer results in the disruption of electrical power supply to a large number of consumers. Hence, the
reliability and the quality of transformers have to be of a very high order. One way of checking the reliability
and the quality of a transformer is to carry out type tests on the transformers.

ERDA has complete type test facilities for carrying out testing of transformers. The Indian Standard on
transformers IS: 2026-2011 has been revised and is made in line with the IEC: 60076. The IS: 2026 has
listed a number of tests which can be carried out on transformers.

The routine tests mentioned in IS: 2026 (Part 1): 2011 are:

1. Measurement of Winding resistance


2. Measurement of Voltage ratio and check of phase displacement
3. Measurement of Short-circuit impedance and load loss
4. Measurement of No-load loss and current
5. Dielectric routine tests (High Voltage test and Impulse test)
6. Tests on on-load tap changers

The type tests are:

1. Temperature-rise test
2. Dielectric type tests

The special tests are:

1. Dielectric special tests


2. Determination of capacitances between windings to earth and between windings
3. Determination of transient voltage transfer characteristics
4. Measurement of zero-sequence impedance on three-phase transformer
5. Short-circuit withstand test
6. Determination of sound levels
7. Measurement of harmonics of the no-load current
8. Measurement of the power taken by the fan and oil pumps and
9. Measurement of insulation resistance to earth of the windings, and/or measurement of dissipation
factor of the insulation system capacitances

Moreover, other certification agencies such as Bureau of Energy Efficiency (BEE) have their own
requirements to judge the quality of transformers. ERDA has been carrying out testing of transformers since
the last four decades. Some specialized transformer tests are described below:

1.2 Short circuit test

This is one of the most important tests on the transformer to determine the quality of the design and the
manufacturing process. The test consists of subjecting each phase winding of the transformer to three shots
of 0.5 second duration and measuring the change of reactance of the transformer after each shot. ERDA
has carried out short circuit tests on more than 3,000 transformers, so far. ERDA has observed failure rate

3
of approximately 11% in transformers of ratings up to 500 kVA and more than 30% in ratings above 500
kVA up to 3150 kVA. Hence it can be seen that as the rating of the transformers increases their vulnerability
to withstand short circuit also increases.

ERDA has three short circuit laboratories and hence is providing very fast service to the customers in India
and abroad for short circuit testing.

1.3 Impulse test

After installation of transformer in a power system network, it has to withstand surge voltages in addition to
the continuous operating voltages for relatively short duration. These surge voltages are caused due to
either lightning or switching operations in the power system. The duration of lightning over voltages ranges
from tens to few hundreds microseconds whereas over voltages due to switching operations are for few
milliseconds. In general, the lightning voltages are higher in magnitude and are seasonal. The lightning
impulse voltages are not dependent on the voltage of the system. As a result, the importance of stresses
produced by lightning impulse decreases as the operating voltage increases. The switching over voltage
is caused due to switching operations & their magnitude depends on the system voltage. Insulation system
has its own breakdown characteristic for these surge voltages, depending on magnitude and duration of
the applied voltage. Lower the duration of applied voltage, higher will be the voltage at which breakdown
will occur.

In addition to the above two types of over voltages, power systems also experience power frequency over
voltages which are slightly higher than the nominal system voltages and are called temporary over
voltages. These types of over voltages, even if they exist for longer duration, are usually not dangerous in
the long run because equipment is designed to withstand much higher power frequency voltages for one
minute duration. But it may significantly degrade the insulation. The insulation is also deteriorated due to
ageing effect under normal working voltages. Even under ideal condition due to electro-chemical ageing,
there would be degradation of the insulation with time, which might lead to failure of insulation.

From the above, it is clear that the insulation design of the electrical equipment should be such that it shall
be capable of withstanding surge voltages. Therefore, all transformer windings are being designed to
withstand surge voltages. To ascertain the reliability of the transformer windings for surge withstand
capability, impulse voltage withstand test is carried out in the laboratory under simulated worst-case
conditions.

ERDA’s High Voltage laboratory is having 1600 kVp, 1200 kVp & 800 kVp impulse Voltage generators with
digital measuring systems with inbuilt software which can be used for conducting impulse tests on
transformers up to 400 kV class as per IEC: 60060. The following tests can be conducted using this facility:

1. Lightning Impulse Voltage Withstand Test


2. Switching Impulse Voltage Withstand Test
3. Transfer Surge Voltage Measurement

4
In the last three years, ERDA has tested more than 3,000 Power & Distribution Transformers of different
ratings from 5 kVA, 3.3 kV class to 100 MVA, 220 kV class. A compilation of the observed failure rates in
these tests are presented in the table and graph, below:

Transformer Failure Rate in Impulse Test

25

20
% Failure

15
Failure rate
10

0
11 kV 33kV 66 kV 132 kV 220 kV

Voltage Class

It can be seen that as the voltage class of the transformer increases, the failure rate of transformer increases
in the impulse test. Impulse test is one of the important dielectric tests conducted as a type test on a
transformer. No other dielectric test can detect the failure of insulation against lightning impulse other than
impulse test since the voltage distribution is different. To enhance the reliability of a transformer during its
operation, type tests need to be conducted. Tests like impulse, short circuit and heat run validates the
design of transformer from a reliability point of view.

Field Services

ERDA offers its services for carrying out measurement of transformer losses at the customers
manufacturing unit and also in the field. ERDA has been carrying out these tests on transformers for utilities
on a large scale. The results of the measurements help in accepting or rejecting the transformers.

Sweep Frequency Response Analysis is a condition monitoring tool mainly to detect the mechanical
integrity of transformers. Transformers are subjected to large electromechanical forces resulting from fault
currents, which causes core deformation and winding movement. During transportation and relocation,
transformers are subjected to impact which also causes winding movements. These faults if not detected
will manifest into dielectric or thermal faults within the transformer. This technique gives information about
mechanical integrity of transformers such as winding movements, inter-turn short circuit, hoop buckling,
axial shift and core damage.

Other tests on transformers which can be carried out at site include C and Tan measurements, insulation
resistance and polarization index measurements, partial discharge measurements using acoustic
techniques, etc.

5
2. Condition Monitoring of Transformers & The Fault Diagnosis
2.1 Capacitance and Tanδ

The measurement of capacitance and tanδ is one of the most useful, reliable and effective diagnostic tool
for a condition monitoring program. The capacitance value (C = εA/d) is dependent on the characteristics
of the dielectric material and on the physical configurations of the electrodes. The voids and impurities
present in the insulation may discharge partially during a voltage application and the effective distance `d’
between electrodes decreases. Hence the measured `C’ will increase, which indicates the presence of
partial discharges and deterioration of insulation. The tanδ measurement is another very important
measure of the quality of any insulation. It directly indicates the power dissipated by the insulation. The
variation of tanδ with applied voltage (tanδ tip up) provides useful information about the source of any
imperfection in the insulation. It increases with insulation deterioration and serves as an early indicator of
failure hazards. The absolute values of C and tanδ will vary depending on type of insulation & the design
and construction of equipment.

A low tanδ value is generally desirable. However, a good initial value of tanδ does not necessarily ascertain
a good quality of insulation. The measured high values of tanδ at low voltage gives an indication of the
contamination and presence of moisture content, while the tanδ tip up gives an indication of the impurities
and void content. Generally, the tanδ values shall not increase as the applied voltage increases outside
reasonable limits. Abnormally high tanδ values indicate that the bulk insulation has developed general
weakness. A higher tanδ tip-up at a certain applied voltage indicates presence of voids and impurities in
the insulation and the inception of PDs at this voltage. The increase in tanδ with passage of time also
indicates the ongoing deterioration of the insulation.

The initial test values obtained on new equipment, just after commissioning, forms the reference value for
future condition monitoring. However, periodic measurements can be started at any time, even on objects
which have been in service for many years. By measuring and comparing the latest values with those of
previous values monitored earlier, any undesirable condition such as presence of internal partial
discharges, moisture content in the insulation, conductive contaminants etc. can be identified and corrective
action can be performed and can be taken as reference.

For evaluation purpose, the absolute values of C and tanδ at various steps of voltage and the tip-up values
are verified for various types of insulation. A high tanδ tip-up shows defects and inception of partial
discharges in the insulation. High tanδ tip-up values with passing time also indicate deterioration of
insulation. The comparison of test results of equipment with previous results and the manufacturing data,
if available should be done. Also, the comparison of test results of similar equipments working under similar
environment and applications can be performed.

If the slope of C and tanδ curve vs voltage and time increases between successive measurements, it is an
indication that the measurements are required more frequently. The frequency of these tests for condition
monitoring depends on rate of change of these values vs. voltage and time. It can also depend on history
of failure data and on the environmental conditions.

In case of condition monitoring, the focus is more on the change in trend or values of capacitance and tan
delta over a time period rather than absolute values. Hence during measurement, care should be taken on
aspects such as resolution and accuracy of bridge, reliability of bridge, and repeatability of measurement,
& skill of testing personnel.

6
2.2 Sweep Frequency Response Analysis (SFRA)
Sweep Frequency Response Analysis is a condition
monitoring tool mainly used to detect the mechanical and
constructional integrity of transformers. Transformers are
subjected to large electromechanical forces resulting from
fault currents, which causes core deformation and winding
movement.

During transportation and relocation, transformers are


subjected to impact which also causes winding movements.
These faults if not detected will manifest into dielectric or
thermal faults within the transformer.

Sweep frequency Response analysis works on the principle


of measuring the response of the winding when subjected to
A transformer under SFRA test the low voltage signal of order of 10 Vp-p with varying
frequency from 20 Hz to 2 MHz. The response is measured
in terms of voltage transfer function in open circuit conditions
and short circuit condition. This response is plotted against
each frequency for each phase. The response of individual
phases are compared for any deformation or short circuit in
windings. It is recommended to record SFRA responses for
new Transformers to serve as reference values.

SFRA technique gives information about mechanical integrity


of transformers such as winding movements, interturn short
circuit, hoop buckling, axial shift, core damage.

Typical wave shape


2.3 Dielectric Response Analysis (DRA)

Dielectric response analysis is a very


powerful tool for diagnosis of problems
related to insulation systems. This
technique is a combination of the
Polarization and Depolarization Current
method (PDC) in time domain and
Frequency Domain Spectroscopy (FDS)
in a wide frequency range.

DRA & FDS are generally used for:

 Analysis of water content in oil-paper


insulations of Power and Instrument
transformers Measurement circuit
 Diagnosis of Oil Impregnated Paper,
Resin Bonded Paper and Resin
Impregnated Paper HV bushings
 Diagnosis of Generator and Motor
insulation, &
 Diagnosis of Cable insulation

7
Dielectric spectroscopy works on the principle of measuring the dissipation factor of insulation material at
wide range of frequencies ranging from 1mHz to several kHz. Dissipation factor is frequency and
temperature dependent. By injecting test signals at different frequency, dielectric response /dielectric loss
curve is plotted against each frequency. This profile represents the properties of insulation system in the
transformers and is used to assess the moisture content.

2.4 Acoustic Emission Detection Techniques

The partial discharge (PD) result is localized and is instantaneous release of energy. The energy released
in a PD produces a number of effects such as chemical and structural changes in the material and electro-
magnetic effects. The Acoustic Discharge Detection is based on detection of the mechanical/acoustic
signals emitted from the discharge.
A fraction of the released energy from the PD source heats the adjacent material and can evaporate some
of it, creating a small explosion. The discharge acts as a point source of acoustic waves that propagates
throughout the insulation. These acoustic waves can be detected by suitable sensors kept on the apparatus
tank, the output of which can be analyzed using a conventional data acquisition system.
The Acoustic Emission Sensor is a piezo-electric transducer, which converts the acoustic signals to
corresponding electrical signals proportional to the velocity of the media/surface to which they are attached.
These sensors can be of various frequency ranges (30 kHz/150 kHz). Such resonant sensors are usually
mounted with a thin layer of acoustic couplant (e.g. grease) to ensure good contact and sensitivity and are
fixed at the place by magnetic hold-downs, tape, elastic bands etc.

The output AE signals from the sensors are pre-amplified, filtered, further amplified and these signals can
be directly fed to a computer and can be analyzed using dedicated software.

Acoustic signal emitted from Partial Discharge Source

As shown above, the PD is modeled as a point source radiating as an acoustic wave in a homogeneous
medium with straight propagation path to the sensors. The main components for Acoustic Emission test
are as follows:

 Integrated sensors with pre-amplifiers


 Suitable length of cables
 Software
 HMI (Human Machine Interface)

8
2.4.1 Acoustic Emission Sensor

The AE signals reaching the tank wall of the


transformer is detected by the AE sensor. The sensor
is a piezo-electric transducer, which converts the
mechanical/acoustic waves into electrical signals.
They are sensitive to the transient acoustic signals
resulting from PD, but are insensitive to the vibration
& general noise. Constant force, magnetic hold-
downs are used to press the sensors against the tank
wall. On microscopic scale, the surfaces of the tank
and even that of the sensor are quite rough and only
a few points will be in touch with each other. The
required contact is achieved by applying some thin
layer of viscous gel between the sensor and the flat
surface of the tank. The viscous gel will fill the gaps
and allow the pressure signals to uniformly transfer
between the surfaces. Acoustic Emission testing on 400 kV transformer

2.4.2 Advantage of Acoustic Emission Technique

 It is independent of external electro-magnetic interference.


 Its sensitivity is independent of the capacitance of the test object
 Location of PD sources in large equipment is possible once it is detected.
 It is an ‘on line’ condition monitoring tool

9
3. Diagnostic Studies on Power Transformers
3.1 Case Study 1: 220/132/11 kV, 150 MVA transformer

Dissolved Gas Analysis (DGA) of oil showed that Acetylene (C2H2), Methane (CH4), Ethane (C2H6) &
Hydrogen (H2) were in increasing trend. Analysis of these gases showed that high energy of partial
discharges are present inside the transformer.

On the basis of DGA results, it was recommended to carry out online Acoustic Emission test on the
transformer. Acoustic Emission test was carried out and observations were made as shown as below:

Scattered Acoustic Emission Discharges around B-Ph Winding

Few electrical discharges were observed around B- ph winding side in scattered form but no concentrated
clusters were found. When results of DP test on paper insulation was checked, it was found that the DP
value of paper insulation was 171. DP value lower than 350 indicates deterioration of paper insulation.

High dB level (80 db) of Acoustic Emissions Inside B-Ph OLTC Selector Switch

As shown above, it was found that high db level of Acoustic Emission signals were observed inside OLTC
selector switch. Probable location of PD source was found approximately at 650mm, 750mm, 650mm of x,
y, z coordinates respectively. Based on these results it was recommended to open the OLTC selector switch
in the presence of OEM and thoroughly check the location.

10
Subsequently the OLTC selector switch was overhauled and rectified at site.

Arcing observed in OLTC selected switch

The study showed correlation between the diagnostic tests and faults.

3.2 Case Study - 2 : 220/33/22 kV, 50 MVA transformer

Incremental trend of key gases like Acetylene (C2H2), Methane (CH4), Ethane (C2H6) were found in DGA of
oil and hence it was recommended to conduct Acoustic Emission test to pinpoint the probable location of
PD.

From the analysis of the recorded data, low energy electrical discharges were observed near Y phase of
33 kV as shown below:

Probable Location of Low Energy Electrical Discharges near the Y phase Bushing on 33 kV Side at
approximately 2200mm, 3100mm, 600mm x, y, z co-ordinates, respectively.

The above said transformer was opened by the repairer at site and it was found to have loose connection
of Y phase of 33 kV winding.

Conclusions:

The above mentioned case studies show how acoustic emission detection technique can be very effective
and useful for ON – LINE detection & location of PD in power transformer. The above case studies also
show how relevant this technique is in conjunction with dissolved gas analysis of transformer oil to pinpoint
the partial discharge location inside the transformer without opening the transformer. It is a non-intrusive
& cost effective ON-LINE discharge detection method for power transformer.

11
4. Condition Monitoring of Transformer Oil
4.1 Introduction

Deterioration of transformer oil begins the moment oil is filled in a transformer. Due to ageing and oxidation,
the oil produces undesirable products such as acids, sludge, moisture etc., which affect the service life of
the transformer significantly. Oxidation of oil results from a process that begins when oxygen combines
with unstable hydrocarbons under catalytic effect of the other materials present in the transformer, as shown
in scheme below:

Unstable Hydrocarbons (oil) + Oxygen + Catalyst + Accelerator = Oxidation by-products

The source of oxygen is from the atmosphere or gas dissolved in oil. Catalyst is the substance that
increases the rate of oil degradation. Moisture, copper, oxygen and other construction materials act as
catalysts for oil degradation. Moisture enters from atmosphere during breathing action of transformer,
leakage through tank and also as by-product of insulation ageing. Electrical and thermal stresses act as
accelerators for ageing.

Formation of sludge is the final stage of the above deterioration process. Sludge is also formed when acid
attacks iron, copper, varnish, paints etc. Sludge adheres to the solid insulation, side walls of tank, & also
settles in ventilating ducts. As a consequence of sludge formation, the oil darkens in color and its acidity
begins to increase, thereby increasing sludge formation rate and consequently causing other electrical
properties such as Dielectric Dissipation Factor (Tan delta) to increase & the Specific Resistance
(Resistivity) to decrease leading to the reduction in the life and potential interruption of normal functioning
of the transformer.

4.2 Condition Monitoring & Evaluation of Transformer Oils

Condition monitoring of the transformer oil is vital as it enables estimation of the remaining life of a
transformer by estimating the quality of transformer oil periodically. The details of requirements for new
transformer oil are shown in Table: I. Tables: II-A and II-B detail out test requirements of unused oil and
recommended tests for oils in service, as a function of voltage class rating, as per IS:1866 – 2000. The
significance of the various tests is presented in Table: III. After energizing of transformer and during the
course of its service operation, eight tests are recommended to be evaluated periodically. The frequency
of these individual tests is tabulated in Table: IV. If rapid deterioration is observed then the following is
recommended:

i) To confirm the last value by means of a further test on a fresh sample.


ii) To inform the manufacturer of the equipment.
iii) To check the condition of the oil more frequently according to the size of equipment and the degree of
deterioration observed.

Table : I: Characteristic Tests for New Transformer Oil as per IS: 335 – 1993

Sr. Property Test Method Requirement


No.
A. Physical Properties

1. Appearance IS : 335 – 1993 The oil shall be clear


and transparent and
free from suspended
matter or sediments
2. Density at 29.5 C, g/cm3 IS : 1448 (Pt.16) 1990 Max. 0.89
3. Kinematic Viscosity IS : 1448 (Pt. 25) 1976 Max. 27
At 27°C, cSt
4. Interfacial tension IS : 6104 – 1971 Min. 0.04

12
At 27°C, N/m
5. Flash Point (PMCC), °C IS : 1448 (Pt.21) 1992 Min. 140
6. Pour Point, °C IS : 1448(Pt.10) 1970 Max. –6

B. Chemical Properties

7. a. Neutralization Value (Total acidity) mg IS : 1448 (Pt. 2) 1967 Max. 0.03


KOH/g of oil
b. Inorganic acidity / alkalinity NIL
8. Corrosive Sulphur IS: 335–1993 (Apdx. A) Non – Corrosive
9. Oxidation Stability IS: 335–1993 (Apdx. B)
a. Neutralization Value after oxidation (mg Max. 0.40
KOH/g)
b. Total sludge after oxidation (% by wt.)
Max. 0.10
10. Presence of oxidation inhibitor IS : 335 – 1993 The oil shall not contain
ASTM D : 2668 – 1987 anti oxidant additives
(value of 0.05 % (Max.)
shall be treated as
absence of inhibitor)
11. Water Content IS : 335 – 1993 Max. 50
(PPM) Appendix E

C. Electrical Properties

12. Electric Strength (BDV) kV (RMS) IS : 6792 – 1992


a. New unfiltered oil
b. After filtration (filter the oil if 30 kV is not Min. 30
obtained) Min. 60

13. Dielectric dissipation factor (Tan ) at 90°C IS : 6262 – 1971 Max. 0.002
14. Specific resistance (Resistivity) ohm. cm
a) at 90°C
b) at 27°C Min. 35 x 1012
Min. 1500 x 1012
D. Ageing Characteristics

15. Accelerated ageing open beaker method IS : 335 – 1993 & -


with copper catalyst IS : 12177 – 1987

16 a. Specific resistance (Resistivity), Ohm. IS : 6103 - 1971


cm
1) at 27°C Min. 2.5 x 1012
2) at 90° C Min. 0.20 x 1012
17 b. Dielectric dissipation factor (Tan ) at IS : 6262 – 1971 Max. 0.2
90°C
18 c. Total acidity, IS:1448 – (Pt. 2) – 1967 Max. 0.05
mg KOH/gm of oil
19 d. Total sludge value, % by weight IS : 12177 – 1987 Max. 0.05

TABLE : II - A: Recommended Limits for Unused Mineral Oil Filled in a Transformer as per IS:1866 – 2000

Highest voltage of equipment, kV


Property
< 72.5 72.5 to 170 > 170
Appearance Clear, free from sediment and suspended matter
Density @ 29.5°C (g/cm), Max. 0.89 0.89 0.89
Viscosity @ 27°C (cSt), Max. 27 27 27
Flash Point, (°C), Min. 140 140 140
Pour Point (°C), Max. -6 -6 -6
Neutralization value (mg KOH/g) Max. 0.03 0.03 0.03

13
Water Content (ppm), Max. 20 15 10
Interfacial tension (mN/m), Min. 35 35 35
Dielectric dissipation factor @ 90°C, Max. 0.015 0.015 0.010
Resistivity @ 90°C x 1012 (ohm – cm), Min. 6 6 6
Breakdown voltage (kV), Min. 40 50 60

TABLE : II- B: Recommended Oil Tests & Requirements for Transformer in Service as per IS: 1866 – 2000

Highest voltage of equipment, kV


Property
< 72.5 72.5 to 170 > 170
Breakdown voltage (kV), Min. More than 30 More than 40 More than 50
Water Content (ppm), Max. Max. 50 Max. 40 Max. 30
Neutralization value (mg KOH/g), Max. Max. 0.3 Max. 0.3 Max. 0.3
Sediment & Sludge, % by Mass ND ND ND
Resistivity at 90°C, x 1012 (Ohm.cm), Min. 0.1 x 1012 0.1 x 1012 0.1 x 1012
Dielectric dissipation factor at 90°C, Max. 1.0 1.0 0.2
Interfacial tension (mN/m), Min. 15 15 15
Flash Point, (°C), Min. 125 125 125

TABLE : III: Significance of Various Oil Characteristics & Properties

Sr. Test Significance Action to be taken if outside the limit


No.

1. Electric Strength Conductive contaminants and Recondition oil or alternatively, if more


(Break Down moisture present in the oil economic or other tests dictate,
Voltage) replace oil

2. Water Content Reveals total water content leak or Recondition oil or alternatively, if
cellulosic deterioration more economic or other tests dictate,
replace oil

3. Dielectric Dissipation Reveals presence of moisture, Reclaim or replace oil, (limit to be


Factor (Tan delta) resins, varnishes, or their products adopted, depends on the type of
of oxidation in oil equipment and instructions from the
manufacturer)

4. Specific Resistance Conductive impurities at room Recondition if the value of the Tan
(Resistivity) temp., reveals the presence of delta permits, reclaim or replace if not
water or cold perceptible material

5. Neutralization Value Acid present in the oil Reclaim or replace oil


(Total Acidity)

6. Sediment and /or Indicates deterioration Recondition oil, if sediment is


Perceptible Sludge detected. Alternatively, if more
economic or other tests dictate
replace oil

7. Flash Point Sudden drop in flash point is Reclaim or replace oil after checking
indicative of unsatisfactory the causes
working condition of transformer

8. Interfacial Tension Sludge and polar contaminants Reclaim or replace oil


present in the oil

14
TABLE : IV: Test Frequency for Oil of Transformer in Service

Sr. Test Frequency


No.

1. Electric Strength and Water Content After filling or refilling prior to energizing then
after 3 months and after one year

2. Specific Resistance, Dielectric Dissipation After filling or refilling prior to energizing then
Factor, Neutralization Value, Sediment and/or after 3 months and after 2 years
Perceptible Sludge, Flash Point and Interfacial
tension

4.3 Field Tests on Transformer Oil

Preliminary information about quality of insulating oil can be gathered on site as follows:

By Conducting Electric Strength and Acidity Tests

Electric strength and acidity test kits are available in the market for conducting these field tests

By Visual Examination of Oil

Useful information about the trend of changes in the oil can be determined from its colour and odour. As
examples:

a) Cloudiness in oil may be due to suspended moisture or sediments such as iron oxide or sludge.
b) Dark brown coloured oil may indicate the presence of dissolved asphaltenes.
c) A green colour indicates the presence of dissolved copper compounds and a rapid deterioration
of the oil may be expected.
d) Acrid acid smell indicates the presence of volatile acids which can cause corrosion.

4.4 Oil Quality Index System (OQIS)

An important measure of oil quality is based on “Oil Quality Index System”. High Inter Facial Tension (IFT)
means the transformer oil is relatively sludge free and therefore purer than oil with lower IFT. Conversely,
high Neutralization Number (Acidity, NN) indicates high acid content and badly deteriorated oil. Hence
dividing the IFT (Dynes / cm) by the Neutralization Number or the Acidity (mg KOH/g of oil) provides an
excellent, numerical means of evaluating the condition of oil. This is known as “Oil Quality Index Number”.

IFT(Dynes/cm)
Oil Qualiy index No. (OQIN) =
NN(mg KOH/g)

If for example, IFT is 45 dynes / cm (or 0.045 N/m) and total acidity is 0.03 mg KOH / g then,

45
= = 1500
0.03

15
Classification of oil based on above index is described in Table V, below:

TABLE: V - A

Sr.No. Interfacial Tension Neutralization OQIN Colour Oil Quality Class


dynes / cm IFT number mg KOH/g
NN

1. 30.0 – 45.0 0.00 – 0.10 300 – 1500 Pale– Yellow Good oil

2. 27.1 – 29.9 0.05 – 0.10 271 – 600 Yellow Proposition A Oils

3. 24.0 – 27.0 0.11 – 0.15 160 – 318 Light Yellow Marginal Oils

4. 18.0 – 23.9 0.16 – 0.40 45 – 159 Amber Bad Oils

5. 14.0 – 17.9 0.41 – 0.65 22 – 44 Brown Very bad oils

6. 9.0 – 13.9 0.66 – 1.50 6 – 21 Dark Brown Extremely bad oils

7. -- 1.51 or more -- Black Oil in and


disastrous condition

TABLE : V - B

Quality Index (IFT/Tan delta) Condition of oil

100 – 65 Very Good oil

65 – 30 Oil to be kept under observation and filtered to


improve its quality

Less than 30 Oil should be removed from the equipment and


reclaimed.

16
5. High Efficiency Domain Refined CRGO Grades for Transformers:
New Single Sheet Test Capability at ERDA

High performance - low loss - transformer manufacturers are rapidly assimilating and adopting domain
refined CRGO steel grades for making magnetic circuits of their transformers. Typically such grades have
higher Goss grain orientation with lower statistical misalignments from the ideal cube on edge {110}<001>
texture of easy magnetization. This translates into lower core loss in comparison to conventional CRGO
grades by as high as 12-15% for comparable lamination thickness, as well as higher magnetic induction
and permeability at a given magnetizing force. Further, domain refined grades also exhibit significantly
lowered magnetostriction effect which results in reduction in the transformer “hum” during operation.
Domain refining technologies are typically required to counteract the higher eddy current generation
propensity in such grades due to their intrinsic larger grain size. Domain refining creates centres of second
& third order residual stresses in individual grains, which act as electron scattering centres leading to
generation of “apparent” domain walls with reduced spacing resulting in the reduction of intensity of eddy
currents (without effecting the thermodynamic driving force for domain wall rotation). Domain refining is
carried out by the technique of laser scribing or plasma processing.
Domain refined grades are sensitive to thermal processing (annealing), as such treatments can easily
result in relaxation of the localized second & third order stress centres leading to increased core loss due
to an enhanced eddy current component. Therefore, to ensure that characterization of magnetic properties
of domain refined grades is carried out with the highest degree of fidelity, it is important that the surface
area of the test specimen be as high as possible with reference to its perimeter. Since the surface area to
perimeter ratio scales linearly with the cumulative “perimetral” edge length, high fidelity of test results can
be attained by using large area test specimens. Therefore, national test standard IS 3024 (grain oriented
electrical sheet and strip) mandates in its amendment no. 2 to clause 15 (sub clause 15.4) that core loss,
exciting current (apparent power) and peak permeability tests on domain refined grades must be carried
out using the “single sheet” test technique.
Keeping in view the above special requirement for testing of domain refined CRGO grades as per IS 3024
and IS 649 (methods of testing steel sheets for magnetic circuits of power electrical apparatus) as well as
the requirements of international standard IEC 60404-3 (methods of measurement of the magnetic
properties of magnetic sheet and strip by means of a single sheet tester) for both CRGO and CRNO grades,
ERDA has recently augmented its existing state-of-the-art soft magnetic materials laboratory with a brand
new BROCKHAUS – Germany make single sheet magnetic property measurement test station (see Fig.
1), which has been backward integrated with a BROCKHAUS make power source and control centre (see
Fig. 2) to enable the conduct of fully automated magnetic property tests on single sheet specimens, in
addition to the already existing capability for testing of specimens in form of toroids, strips, & stampings.
This test station has been designed as per the requirements of IEC 60404-3 and IS 649. The new
measurement station can accommodate a single sheet of dimensions 500 mm x 500 mm with maximum
thickness of 1 mm (approximate sample mass of 1.5 kgs). Using this facility, full series of magnetic tests
such as core loss, magnetization (polarization), permeability, apparent power, and B-H hysteresis can be
conducted on single sheets in the frequency range of 3 Hz upto 150 Hz with applied field strength ranging
from 1 A/m to 30,000 A/m. Typically polarizations of upto 2 Tesla can be easily attained.
With the availability of this new single sheet test station, the capability of the magnetic materials laboratory
at ERDA to conduct tests as per various national & international standards stands upgraded as below:
Major National & International  IS : 648, IS : 649, IS : 3024 (including single sheet tests on
Test Codes for Which Laboratory domain refined grades) & IS : 15391
is Equipped  IEC 60404-3 (single sheet testing of CRGO & CRNO)
 IEC : 60404-8-2, IEC: 60404-8-3, IEC: 60404-8-4,
IEC: 60404-8-7
 ASTM – A 683, ASTM – A 677
 ASTM – A 876, ASTM – A 876 (A 343)

17
Single Sheet Tests (Domain  Core loss
Refined CRGO as well as CRNO)  Polarization (Magnetization)
 Permeability
 Apparent Power
 B-H Curve/Hysteresis Loop

Tests for CRGO & CRNO  Core Loss at Magnetic Flux Up to 2.0 T at 50 Hz or 60 Hz
 B-H Curve / Hysteresis Loop

Tests for CRGO  Magnetic Polarization & Permeability at 800 A/m


 Specific Exciting Power

Tests for CRNO  Magnetic Polarization at 2500 A/m, 5000 A/m &
10000 A/m
 Anisotropy of Losses at 1.5 T & 50 Hz
 Specific Exciting Power

Electrical Property Tests  Electrical Resistance

Surface Insulation Property Tests  Insulation Resistance / Insulation Resistivity at Room


Temperature or 150 °C
 Inter-laminar Resistivity
 Thermal Effect on Coating
 Effect of Solvent / Resistant to Solvent
Physical & Mechanical Property  Ductility / No. of Bends
Tests  Hardness
 Stacking Factor / Lamination Factor
 Lamination Thickness
 Chemical Composition

Effect of Ageing on Core-loss  Core-loss after ageing at 225 ± 5 °C for 24 hrs or


Tests at 150± 5 °C for 168 hrs

Capability for Stress Relief  Heat treatment at 800 ± 20 °C in slightly reducing or neutral
Annealing Prior to Testing atmosphere

18
BROCKHAUS Make Single Sheet Test Station BROCKHAUS Make Power Source and Control Centre
with Epstein, Toroid, & Stamping Test Stations

19
6. Domain Refined CRGO Grades: ERDA Augments Magnetic
Materials Test Laboratory with New Capability for Evaluating Large
Size – Single Sheet – Transformer Core Laminations
Origin of Size Effects in Domain Refined CRGO Grades

In domain refined CRGO grades annealing treatment cannot be carried out after the shearing/working
action. The reason behind this being the fact that these high performance CRGO grades attain their higher
magnetic flux density induction and lower core loss properties due to specially engineered a-priori mis-
orientation angle of the easy direction of magnetization by less than 30 of the rolling direction. This is
typically implemented by reducing the specific grain boundary area by growing large sized grains.
Unfortunately the larger grain size increases the eddy current loss as well as the coupled domain wall –
eddy current loss. These additional losses are subsequently offset by a special treatment of “domain
refining” using laser scribing or plasma processing techniques. These refining treatments essentially create
second and third order stress zones in the lattice which aid in scattering electrons and thus increase lattice
resistivity (resulting in reduction of eddy current loss) but do not have any inhibitive affect on ease of
domain wall rotation (and hence the hysteretic losses are unaffected). This domain refining affect is easily
"reverted” or “destroyed” by any post refining annealing/thermal treatment resulting in much larger eddy
current losses which nullifies the positive effect of such treatments on mitigating the hydrostatically stressed
compressive zones near the point of strip/sheet shearing to reduce the fractional number of mis-oriented
domains.

Optimal Specimen Size for Domain Refined CRGO Grades

In light of these facts, national & international CRGO test codes have used optimization techniques to fix
the specimen dimensions for the domain refined grades as at least 500 mm (L) x 500 mm (W) [IS 3024
states specimen size requirement as 500 – 530 mm (L) x 500 mm +0mm/-5 mm (W), with recommended
length of 500 mm], which is much greater than the recommended specimen size of 305 mm (L) x 30 mm
(W) for traditional CRGO grades. When one computes the relative disturbed zone mis-oriented domains
in a specimen of this size with the recommended specimen size of 305 mm x 30 mm for the non-domain
refined CRGO, one finds a factor of nearly 10 times. In other words, the disturbed zone in specimen size
of 500 mm x 500 mm is about 10 times lower than the disturbed zone in the specimen size of 305 mm x 30
mm. This factor of 10 more than offsets the incremental core loss reduction benefit that would have been
obtained in reduction of compressive hydrostatic stresses in the disturbed “sheared” zones at the specimen
edges.

New Test Capability at ERDA for Single Sheet Domain Refined CRGO Grades

Keeping in view the above special requirement for testing of domain refined CRGO grades as per IS 3024
and IS 649 (methods of testing steel sheets for magnetic circuits of power electrical apparatus), ERDA has
recently augmented its existing state-of-the-art soft magnetic materials laboratory with a brand new
BROCKHAUS – Germany make single sheet magnetic property measurement test station, The new
measurement station can accommodate a single sheet of dimensions 500 mm x 500 mm with maximum
thickness of one mm (approximate sample mass of 1.5 kgs). Using this facility, full series of magnetic tests
such as core loss, magnetization (polarization), permeability, apparent power, and B-H hysteresis can be
conducted on single sheets in the frequency range of 3 Hz up to 150 Hz with applied field strength ranging
from 1 A/m to 30,000 A/m. Typically polarizations of up to 2 Tesla can be easily attained.

20
To ensure reliable magnetic property measurements including core loss values, testing of domain refined
CRGO grades should be only conducted using the 500 mm (L) x 500 mm (W) single sheet test facility,
which is now available in the country at ERDA.

Automated Test Station for Magnetic Close-up of Epstein Test Frame Adapter for Toroidal Core Specimen
Properties Characterization

Attachment for Testing of Single Strips & Test Set-up For Stacking Factor of New Brockhaus Make Single Sheet
Shape Magnetic Core Strips Test Station

A Dedicated (Walker Scientific Make) DC B- Surface Insulation Resistivity (SIR) Comparative CRGO Lamination
H Loop Equipment Test Setup Dimensions of Single Sheet Domain
Refined and Epstein Specimens
A summary of the test capability of the augmented soft magnetic materials laboratory at ERDA is as below:

National & International Test Codes for Which Laboratory is Equipped:

 IS: 648, IS: 649, IS: 3024 (including single sheet tests on domain refined grades) & IS: 15391
 IEC: 60404-3 (single sheet testing of CRGO & CRNO)
 IEC: 60404-8-2, IEC: 60404-8-3, IEC: 60404-8-4, IEC: 60404-8-7
 ASTM – A 683, ASTM – A 677
 ASTM – A 876, ASTM – A 876 (A

21
Magnetic Property Tests Including Single Sheet Tests (Domain Refined

CRGO as well as CRNO):

 Core loss
 Polarization (Magnetization)
 Permeability
 Apparent Power
 B-H Curve/Hysteresis Loop

All Other Critical Electrical, Insulation, Mechanical & Chemical Tests

To ensure the highest possible efficiency, reliability & maintainability of transformers in the field, it is of the
up-most criticality that the highest quality CRGO laminations be selected for fabricating the transformer
cores, as the power coupling between primary & secondary terminals occurs only through the transformer
core. Use of inferior grade transformer cores derived from second grade CRGO coil rejects, CRGO scrap,
& CRGO cores obtained from dismantled – used - transformers taken out of service due to degraded
reliability can play havoc with the quality of the transformer manufactured.

Since it is almost impossible to visually identify second grade CRGO laminations derived from coil rejects,
scrap, or used transformers, it is important that the CRGO coils being procured for fabricating transformer
laminations be systematically sampled for conducting the full - elaborate - range of certification and quality
assessment checks at independent magnetic core evaluation laboratories such as that existing at ERDA
for CRGO grades in general and CRGO domain refined grades, in particular.

22
7. Solid Dielectrics and Polymers Group at ERDA
The reliability and useful service life of transformer is essentially determined by the optimality of the design
of its insulating system along with the quality and integrity of the insulating materials deployed for
engineering the system. Nowadays due to leapfrog advances in field of polymer science, engineering and
engineered molecular materials, a large category of solid dielectric materials are available for application
as insulating systems in electric machinery. To ensure the highest possible reliability of these materials, it
is important that prior to their use, the materials be systematically subjected to various certification tests as
per relevant national & international standards. The Solid Dielectrics & Polymers group at ERDA has an
array of sophisticated facilities & instrumentation for certification confirmatory testing & characterization of
a large class of dielectric & polymeric materials in various forms and shapes, as per national and
international standards. These state-of-the-art facilities include instrumentation for
characterization/identification of rubbers & plastics, determination of glass transition (Tg) and melting point
(Tm) of polymers as well as measurement of degree of polymerization.

A subset of the solid dielectric & polymeric materials routinely tested along with relevant national &
international test codes include:

1 Papers IS:9335-3(1), 14 Fiber-Glass BS:4994


BS:5626, Reinforced Laminates BHEL-
IEC:554 & BHEL AA0851701
AA 21111
2 Press Phan Paper IS:8570 15 Rubberized Cork IS:4253-1,2
Sheet
3 Press Boards and Pre IS:1576 16 PGAM Tape / Semica Industry
Compressed Boards IEC:60641 Therm Tape specifications
4 Laminates IS:2036, 17 Rubber / Fiberglass BS:2848
IS:10192, Sleeves
IS:1998 18 Poly Propylene Film IS:11298
5 Cable Jointing IS:10333 JS:C2330
Compounds IS:13465-2 19 Fireman Axe, Multi IS: 926
6 Adhesive Tapes IS:2448-1 Edge Rescue Axe
IS:2448-2 20 SMCs/DMCs IS:13410,IS:134
IS:7809-1 11
IS:7809-2 21 Cable Truncking BS:4678
IS:7809-3(1) 22 Piercing Connectors NFC 33-020
IEC: 454 23 Dead-end Clamps NFC 33-041

7 Non-Ignitable Boards IS:4248, IS:4249 24 Rubber IS:3400/ASTM D


8 Plastics ASTM 3677
specifications 25 Insulating Sleeves BS:2848
9 B-Stage Epoxy Glass IS:13066 26 Cable Filling ASTM D 3895/
Cloth Compound/Cable ASTM D 4565
10 Molding Materials IS:3669 Outer Sheath for
IS:2221 Oxidative Induction
Time (OIT)
11 Varnishes IS:10026-1 27 Security Seals As per GEB
IS:10026-2 specification
IS:10026-3(1-8) 28 Identification of ASTM D 3677
Rubber / Plastics
12 Resin DIN:46456
DIN:46448 29 Degree of IEC 60450
13 Combined Flexible IEC:60626-2 Polymerization (DP)
Insulation Sheets IEC:60626-3 of Paper

23
30 Glass Transition ASTM D 3418
Temperature (Tg) and
Melting Point
(Tm) of Polymeric
Materials

UV - Accelerated Ageing - Weathering Test


Chamber

24
25

You might also like