Professional Documents
Culture Documents
Cad Drawing Standards PDF
Cad Drawing Standards PDF
APPENDIX D
Page 1
APPENDIX D
CAD DRAWING STANDARDS
1.1 Purpose
The purpose of this appendix is to provide the standards and specifications necessary to create
construction and as-built CAD drawings in a manner that produces a consistent and uniform set of
drawings. Additionally it facilitates the future modification of these same drawings and minimizes the
integration effort required to incorporate these drawings into the Lockheed Martin Space System
Facilities’ master as-built drawing databases. The goal of Lockheed Martin Space System (LMSS)
Facility Technology Resource Management (TRM) group (see section 1.8) is to ensure that submitted
drawings by LMSS contractors and by LMSS Facilities’ Engineering groups adhere to these standards.
LMSS Contractors and LMSS Facilities’ Engineering groups are required to create CAD drawings
according to the following guidelines and those provided in Section 11 of the Design Standards.
in the submittal, as well. AutoCAD’s Pack&Go option is a preferable method of collecting and
submitting these drawings to LMSS.
B. As-Built Drawings
Submit a complete set of as-built drawings with all field as-built red-lines incorporated. These
drawings shall be in compliance with Section 11 and Appendix D of the Design Standards. Refer
to section 11 of the Design Standards for the project categories, description and requirements.
TITL E B LOC K
D R A WI NG N U M B E R
CAD FILE #
FOR CAD FILE NUMBER SEE SECTION2.10
SH 2 DWG. NO. REV
OF 5 1 5 6 -8 -3 0 5 E P -0 2 3 -2 3
I.E., 156-8-305EPD-023
FIGURE 1.1
A. CAD files of all approved as-built drawings shall be submitted on one of the following
media:
3 ½” floppies, CDs or ZIP disks. Each media shall be readable by a Windows based PC.
Macintosh and Unix media will not be accepted. At the time of release of these
standards, email submittals are not permitted.
B. Label each media with the Building Number, Project ER Number and Project Title.
(Example: B152, ER C44622, Major Modifications)
C. For projects with multiple building sites, group files onto separate media for each
building and label each media accordingly.
D. The contents of drawings shall comply with the most recent edition of the Facility
Engineering Design Standards, Section 11, Drawing Procedures.
E. AutoCAD Blocks shall be created in Layer “0” (zero) and names shall be descriptive so
that they can be easily identified and re-used. Avoid the use of symbols such as
(*,<>?”’;:@%&$!{ } / \) in block names. Block names for the title blocks (borders) and
standard symbol blocks must remain as is when obtained from LMSS TRM group. Do
not explode or rename these blocks.
F. CAD file layering convention (Names and Contents) shall adhere to Section 5.0, CAD
Layering Standards. Since the AIA CAD layering system is used, to the extent of
compatibility with the LMSS facilities CAD database, any additional required layer shall
be selected from the “AIA CAD layering guidelines” and approved by TRM group prior
to use on as-built drawings.
G. External referencing and the use of paper space environment are prohibited in as-built
drawings but acceptable in construction drawings.
H. All AutoCAD files shall be saved with AutoCAD's original ACAD.MNU.
I. Third party fonts shall not be used on submitted as-built drawing files.
J. Avoid the use of symbol characters, such as the ones shown in section 2.2.E above, in
naming of text and dimension styles. Use the underscore character if a space is needed in
style names for the purpose of clarity.
2.4 Units
Architectural units shall be used for all drawings except for the civil plans.
102 101
195D101AR01-000-R10.dwg
This CAD file ID represents a revision 10 of the first sheet of Architectural Reflected Ceiling
plan drawing for Area 01 on the First Floor of building 195D. The “000” denotes that drawing
to be an as-built drawing.
Revised May, 2005
Lockheed Martin Space Systems
FACILITY DESIGN STANDARDS
APPENDIX D
Page 6
Yello w Pen 2 .1
Cya n Pen 4 .2
Ma g enta Pen 6 .3
A Architectural
B ACAS
C Controls (mechanical)
E Electrical
F Fire Protection
M Mechanical
Q Equipment Engineering
S Structural
U Underground Utilities
V Building Evacuation
F Structural: Foundation
ACAS: Fences Access Control
Industrial Engineering: Interior Finishes
G Electrical: Grounding
Controls: Digital Elementary
ACAS: ACAS Coverage Below Floor
L Electrical: Lighting
ACAS: Manual Fire Alarm Signaling System Riser Diagram
Architectural: Interior Elevations
Revised May, 2005
Lockheed Martin Space Systems
FACILITY DESIGN STANDARDS
APPENDIX D
Page 10
O Not used
P Electrical: Power
Piping: Instrumentation Process Piping-HVAC Chilled water piping
Controls: Point to Point Wiring Schematics and Panel Layout
Details
ACAS: Closed Circuit Television System
U not used
W not used
Y not used
Major Group headings define the layer’s discipline. Refer to section 3.0 for a
listing of the disciplines and designated letters.
Modifier headings further define the Minor Group headings such as DEMO,
CONS, etc.
Elevation, Section, Detail and Schedule Layers [* is replaced by the discipline code letter]
Layer Description Color Linetype
Elevations
*-ELEV-FRAM Penetrations and changes in plane of the Green Continuous
elevation, outline of objects beyond
*-ELEV-OTLN Building outline and ground line (use thick Blue Continuous
pline for ground line)
*-ELEV-SURF Surface features, joints Yellow Continuous
*-ELEV-HIDN Hidden lines Red Dashed
Sections
*-SECT-MBND Material beyond section cut Green Continuous
*-SECT-MCUT Material cut by section Blue Continuous
*-SECT-PATT Textures and hatch patterns Varies ——
Details
*-DETL-MBND Material beyond section cut Green Continuous
*-DETL-MCUT Material cut by section Blue Continuous
*-DETL-PATT Textures and hatch patterns Varies ——
Schedules
*-SCHD-BLOK Schedule blocks Red Continuous
*-SCHD-TEXT Text placed inside the schedule blocks Red ——
*-SCHD-PATT Textures and hatch patterns Red ——
Diagrams
*-DIAG-LINE Components and connecting lines Green Varies
*-DIAG-TEXT Text associated with components Red ——
*-DIAG-PATT Texture and hatch patterns Red ——
5.3.4 ARCHITECTURAL REFLECTED CEILING PLAN – AR: (Use Architectural floor plan,
Mechanical floor plan and Electrical Lighting plan as reference)
Layer Description Color Linetype
A-WALL-DHED Door headers Green Continuous
A-WALL-WHED Window headers Green Continuous
A-CLNG-BRAC Ceiling seismic bracing Cyan Continuous
A-CLNG-GRID Ceiling grid Green Continuous
A-CLNG-OPEN Ceiling penetration Green Continuous
A-CLNG-SUSP Ceiling suspended elements Yellow Continuous
5.3.4 ACAS COVERAGE ABOVE CEILING – BA: (Use Architectural floor plan as reference)
Layer Description Color Linetype
B-ALRM-COMP Alarm components. Duct traps, and area Green Continuous
termination cabinets.
B-ALRM-NOTE General notes Red Continuous
B-ALRM-ZONE Zones and area designations. Green Continuous
B-ALRM-WIRE Wire and conduit requirements. Yellow Continuous
B-ALRM-CIRC Circuit numbers above ceiling Yellow Continuous
5.3.5 ACAS COVERAGE BELOW CEILING- BB: (Use Architectural floor plan as reference)
Layer Description Color Linetype
B-ALRM-COMP Alarm components. Duct traps, and area Green Continuous
termination cabinets.
B-ALRM-NOTE General notes Red Continuous
B-ALRM-ZONE Zones and area designations. Green Continuous
B-ALRM-WIRE Wire and conduit requirements. Yellow Continuous
B-ALRM-CIRC Circuit numbers above ceiling Yellow Continuous
5.3.6 ACAS COVERAGE ON ROOF – BR: (Use Architectural floor plan as reference)
Layer Description Color Linetype
B-ALRM-COMP Alarm components. Duct traps, and area Green Continuous
termination cabinets.
B-ALRM-NOTE General notes Red Continuous
B-ALRM-ZONE Zones and area designations. Green Continuous
B-ALRM-WIRE Wire and conduit requirements. Yellow Continuous
B-ALRM-CIRC Circuit numbers above ceiling Yellow Continuous
5.3.7 ACAS COVERAGE BELOW FLOOR – BG: (Use Architectural floor plan as reference)
Layer Description Color Linetype
B-ALRM-COMP Alarm components. Duct traps, and area Green Continuous
termination cabinets.
B-ALRM-NOTE General notes Red Continuous
B-ALRM-ZONE Zones and area designations. Green Continuous
B-ALRM-WIRE Wire and conduit requirements. Yellow Continuous
B-ALRM-CIRC Circuit numbers above ceiling Yellow Continuous
5.3.9 MANUAL FIRE ALARM SIGNALING SYSTEM - BJ: (Use Architectural floor plan as
reference)
Layer Description Color Linetype
B-FIRE-COMP Components Green Continuous
B-FIRE-NOTE General notes Red Continuous
B-FIRE-ZONE Zones and area designations. Green Continuous
B-FIRE-WIRE Wire and conduit requirements. Yellow Continuous
B-FIRE-CIRC Circuit numbers above ceiling Yellow Continuous
5.3.12 SOUND MASKING SYSTEM - BN: (Use Architectural floor plan as reference)
Layer Description Color Linetype
B-MASK-COMP Components Green Continuous
B-MASK-NOTE General notes Red Continuous
B-MASK-ZONE Zones and area designations. Green Continuous
B-MASK-WIRE Wire and conduit requirements. Yellow Continuous
B-MASK-CIRC Circuit numbers above ceiling Yellow Continuous
5.3.13 CLOSED CIRCUIT TELEVISION SYSTEM - BP:(Use Architectural floor plan as reference)
Layer Description Color Linetype
B-CCTS-COMP Components Green Continuous
B-CCTS-NOTE General notes Red Continuous
B-CCTS-ZONE Zones and area designations. Green Continuous
B-CCTS-WIRE Wire and conduit requirements. Yellow Continuous
B-CCTS-CIRC Circuit numbers above ceiling Yellow Continuous
5.3.15 PUBLIC ADDRESS SYSTEM – BC: (Use Architectural floor plan as reference)
Layer Description Color Linetype
5.3.17 FENCES’ ACCESS CONTROL SYSTEM – BF: (Use Architectural floor plan as reference)
Layer Description Color Linetype
B-FENC-COMP Components Green Continuous
B-FENC-NOTE General notes Red Continuous
B-FENC-ZONE Zones and area designations. Green Continuous
B-FENC-WIRE Wire and conduit requirements. Yellow Continuous
B-FENC-CIRC Circuit numbers above ceiling Yellow Continuous
5.3.18 SITE CIVIL PLAN-G0 (these layers are also used in Architectural building site plans)
Layer Description Color Linetype
G-BLDG Footprint of Buildings / overhangs (dashed) White Continuous
G-PKNG-STRP Parking lot striping, handicapped symbol, Yellow Continuous
wheel stops
G-PKNG-NOTE Parking lot notes Red Continuous
G-ROAD-CNTR Roads center lines Red Center
G-ROAD-CURB Face of curb, Green Continuous
G-ROAD-PAVE Back of curb, line of gutter,
G-ROAD-NOTE Road and street notes and names Red Continuous
G-RAMP All Ramps including handicap and docking White Continuous
areas
G-STRM-CULV Culverts headwalls, drainage inlets Red Continuous
G-STRM-IDEN Storm sewer system annotation Red Continuous
G-STRM-DTCH Drainage ditches Green Dashed
G-STRM-FIXT Storm drainage surface Features (catch Green Continuous
basins, manholes)
G-TOPO Contour Lines, Elevations and associated #8 Phantom
notes
G-PROP Property Lines including bearing, distance 12 Phantom
and associated notes
G-COMM Site communication/telephone poles, boxes, Red Continuous
towers
G-WATR Domestic water-manholes, pumping stations, Green Continuous
storage tanks and associated notes
G-FIRE Fire protection-hydrants, connections and Green Continuous
associated notes
G-NGAS Natural gas-manholes, meters, storage tanks Green Continuous
and associated notes
G-SSWR Sanitary sewer-manholes, pumping stations Green Continuous
and associated notes
Revised May, 2005
Lockheed Martin Space Systems
FACILITY DESIGN STANDARDS
APPENDIX D
Page 17
5.3.20 ELECTRICAL LIGHTING PLAN – EL: (Use Architectural floor plan as reference)
Layer Description Color Linetype
E-LITE-SPCL Special Lighting Green Continuous
E-LITE-EMER Emergency Lighting Blue Continuous
E-LITE-CLNG Ceiling-mounted Lighting Green Continuous
E-LITE-FLOR Floor-mounted Lighting Blue Continuous
E-LITE-WALL Wall-mounted Lighting Cyan Continuous
E-LITE-SWCH Lighting Switches Green Continuous
E-LITE-EXIT Exit Lighting Red Continuous
E-LITE-NUMB Lighting Circuit Numbers Red Continuous
E-LITE-WIRE Lighting wiring and conduit Red Center
5.3.21 ELECTRICAL POWER PLAN – EP: (Use Architectural floor plan as reference)
Layer Description Color Linetype
E-POWR-WALL Power wall Receptacles Green Continuous
E-POWR-CLNG Power Ceiling Receptacles and Devices Blue Continuous
E-POWR-PANL Power Panels Blue Continuous
E-POWR-EQPM Power Equipment-includes outlines of Green Continuous
equipment shown in other disciplines
E-POWR-WIRE Power wiring and conduit Red Center
5.3.22 ELECTRICAL GROUNDING PLAN – EG: (Use Architectural floor plan as reference)
Layer Description Color Linetype
E-GRND-CIRC Ground system circuits Blue Continuous
E-GRND-REFR Reference ground system Blue Continuous
E-GRND-EQUI Equipment ground system Blue Continuous
E-GRND-DIAG Ground system diagram Green Continuous
5.3.27 MECHANICAL PIPING PLAN – MP: (Use Architectural floor plan as reference)
Layer Description Color Linetype
M-CWTR-EQPM Chilled water equipment and associated notes Blue Continuous
M-CWTR-SUPL Cold water supply lines and associated notes Cyan Continuous
M-CWTR-RTRN Cold water return lines and associated notes Cyan Continuous
M-HWTR-EQPM Hot water equipment and associated notes Green Continuous
M-HWTR-SUPL Hot water supply lines and associated notes Red Continuous
HWTR-RTRN Hot water return lines and associated notes Red Continuous
5.3.29 PROCESS PIPING PLAN – PP: (Use Architectural floor plan as reference)
Layer Description Color Linetype
M-BRIN-EQPM Brine system equipment and associated notes Green Continuous
M-BRIN-PIPE Brine system piping and associated notes Green Continuous
M-CMPA-CEQP Compressed air equipment and associated Cyan Continuous
notes
M-CMPA-CPIP Compressed air piping and associated notes Cyan Continuous
M-CMPA-PEQP Process air equipment and associated notes Cyan Continuous
5.3.31 SITE UTILITIES PLAN - U0 (uses the Site topo plan as reference)
Layer Description Color Linetype
U-STRM Storm drain pipes and all related notes Red Dashed
U-WATR Domestic water pipes and all related notes Yellow Continuous
U-FIRE Fire protection pipes and all related notes Green Continuous
U-NGAS Natural gas pipes and all related notes Cyan Continuous
U-SSWR Sanitary sewer pipes and all related notes Blue Continuous
U-ELEC Electricity lines and all related notes White Fenceline 2
U-CWTR Chilled water lines and all related notes Continuous
U-COMM Telephone communication lines and all Blue Continuous
related notes
Revised May, 2005
Lockheed Martin Space Systems
FACILITY DESIGN STANDARDS
APPENDIX D
Page 21
U-STDR Storm drain pipes and all related notes Blue Continuous
U-IRRG Irrigation pipes, sprinkler and all related 41 Continuous
notes
5.3.34 AREA Space Allocation Reports(SAR) - IS: (Use Architectural floor plan as reference)
Layer Description Color Linetype
Varies All layers are assigned by the SAR Vaires Varies
Application.