Professional Documents
Culture Documents
GENERATOR KVA.
were built with magnetic materials in the 0.8 power factor +.A0A
end structures, which contributed to heat- cylindrical rotor
ing in these portions of the machine. The generator z
operation in the underexcited region of Short circuit ratio Of J
+0.8 _ _ 8_\
_ _
machines built prior to about 1925 should generator = 0.9 ~_\
be approached advisedly and preferably Equivlent Xd = +0.6 -RATED FIELD CURRENT
should be checked by temperature meas- 1/TCR=1.111LMIT
Maximum turbine
urement under actual operating condi- output = generator +0.4
tions. As a result of design progress, kilovolti i RATED PF.
experience and tests indicate that modern
X +0,2 _ ,;4 - d -1-25-
Figure 2. System vector diagram i
0H
X / KILC0.2WATTS 0.4
PER UNIT \_ 08_
L / CONSTANT FIELD CURRENT LOCUS 0.6 0 RATED ARMATURE
90 AT PULLOUT GCURRENT LIMIT
w -
0.2 AREA OF OPERATION
d PULLOUT POWER d EAd s /Y OF VOLTAGE REGULATOR
0.~~~~~~~~~~~~~~~~~~.0
4-1.6
KW. L OA D I0.00
__<
0.8 0.9 ~~~.0 0.9
be maintained for machines on manual voltage will probably be less than rated In Figure 7 the difference between the
control in order that they may pick up when the machine is required to absorb straight line at 45degrees with the horizon-
their expected share of load without loss of large amounts of leading reactive kilovolt- tal axis and the curves may be interpreted
synchronism. amperes. Figure 6 shows the effect at any kilowatt loading as the permissible
For a typical machine, Figure 4 shows generator terminal voltage has on permis- power increment at that initial loading.
that a machine initially loaded to 80 per sible power increments for power factors. The increase in the power increment as
cent kilowatts at 0.9 power factor lead between 0.95 lag and 0.95 lead. The initial power factor goes from the leading
can pick up about 7 per cent in power be- desirability of voltage regulator control to the lagging region is evident. To
fore going out of step. It also shows that when operating in the leading region and accept the maximum turbine output, an
with 80 per cent initial kilowatt load at 0.6____________
1.0) power factor, the pullout power ex- SCR.,: 0.9,
ceeds the turbine capability. Margins in F xe: O Z ||0.2
permissible pwrincrement aesmall in > NTA s.LA:O[13
mintaned
thebehigher or mchies o
load regions manal
at 0.8 power0factor vlcrement forostabily
l bels0.9 la atd
w 0.4 1
I Fgr
0.9the. dife05c bewenh
ing from doubling the equivalent system time it does give an indication of the mar- LI SCR: 0.9_//
reactance is shown in Figure 8. Figure 9 gins which are available through the auto- e -f---
shows the effect of decreasing generator matic control of excitation, which are
short-circuit ratio from 0.9 to 0.6. Quali- available to meet emergency system condi- J S DA
tatively from Figures 8 and 9, the con- tions.
elusion may be drawn that generator pull- Some voltage regulators permit the 0.4
out power is not greatly affected by small INCREMENT
changes in its short circuit ratio or in sys- SCR. a 0.6
tem stiffness. 1.6 UNITY PF. INITIAL LOAD
SCR. 10.9
Voltage Regulator Operation Xd__Xd _ I_
_-_
0 0.2 0.4 0.6 0.8 1.0
When the excitation of a machine is t
under the control of a voltage regulator, 1.2 _INITIAL KW. LOAD PER. UNIT
adjusted to maintain rated voltage at the n
TRNE OTU lue99. Pullout
Figure power
oe versus initial kilowatt
Z.,r_/E.KYA. load Forulu essIiilklwt
-
machine terminals, the generator will ,, . -_ --
_ - - dKierent short-circuit ratios
stably accept the maximum turbine out- X x 0.2
put in any practical case. The curves in s voltage regulator, and machine stand-
Figure 10 assume that the excitation sys- Jpit
tem has a ceiling voltage 50 per cent in
excess of the required slip ring voltage at X_x 0.4. Transient Stability
the rating of the main generator. This is
equivalent to having an exciter of 300- 04 Since the voltage behind transient react-
volt ceiling and rated generator slip ring PERMISSI BLE POWER ance is not affected greatly by power fac-
volts of 200 which is representative of INITAL 0.8 KW LOAD 1.0 PF. tor at rated terminal voltage, transient
present day practice. Terminal voltage X 0.4 stability limits are almost unaffected by
of the generator is assumed to be 1.0; initial loading conditions. Voltage regu-
the exciter is at ceiling; 90 degrees exists 0o lators with usual rates of response and
between machine excitation voltage and 0 0.2 0.4 0.6 0.8 1.0 ceilings affect these limits by a rather
equivalent system voltage. For ceiling lNITIAL Kw. LOAD PER.UNIT minor amount. Of course, transient syn-
Figure 8. Pullout power versus initial kilo- chronizing torques are high as compared
watt load for different external reactance to the steady-state stability limits and
1.6 - 0.20 e of importance in determining whether
SCR.: 0.90 synchronism will be lost after a system
Xd R1.111 adjustment of the'lower limit of excitation shortcircuithasbeencleared.
MAX. TUJRBINE $ |,- as a function of turbine kilowatt load or of For a turbogenerator on an average
.- 1.2
OUTPUT = GEN. KVA.>N
.1 the generator kilovar output. Area system operation at unit; or in the leading
1 CGKL on Figure 3 suggests a range for power factor region will have a small
PR:0.B LAG -1 .041efc pntanin iis With ihmn
a: PZ L |\| the setting of these limits which will in effect upon transient limits. man-
i.0 0 *_,:
PF
5 most cases leave a considerable margin ual control of excitation, generators should
between system requirements and ma- be operated with sufficient excitation so
w
0.80.8 /T <OP.BLEAD
/ | chineincapability.
I ;//
tion this Manualthecontrol opera-
region
allows generatorsto that they can
increment after stably
the transient phaseload
accept their is
0 _ _ _ _ |_ |
accept a reasonable load increase before
pullingoutofstep; however, itshouldbe
over. Vo'tage regulators
excitation rap dly enough during the
can adjust
_J pullI | realized that Figure 3 represents condi- transient perioe, so that any load may be
|J ;/ .\ tions for rated generator terminal voltage, assumed up to the generator rating.
0.4 | ASPERMISSIBLE POWER | and that allowable power increments are Voltage regulator control permits opera-
|/ INCREMENT reduced as the generator voltage is de- tion closer to the steady-state stability
PE PNfLEADIONAG 04K8|
creased. Voltage regulator control ration- .limit.
/l 0 | | ~~~~ally permits operation closer to the steady-
___ ___ __l_l _ state stability limit and possibly beyond Nomenclature
0 0.2 0.4 0.6 0.8 1.0 those shown by operation in the "dy- UntKa=uiklol-mprssth
INITIAL KW. LOAD PER UNIT namic" stability region. However, opera- generKatori ralvoted kilvot-mpre
pee
Figure 7. Pullout power versus initial load at tion below the line GC on Figure 3 should which is equal to the maximum rated
different power factors be approached advisedly from the system, turbine output
I- Xd = EdEja-EtEJ1
Ed-Et and a radius of
Appendix I jX (8) E[d.
Figure 3 shows approximate reactive and I* EdiaEi (9) 2eXd]_
real power limits on the basis of rated volt- -iXd In Figure 3, the center of circlewDF is at
age at the machine terminals. These limits rE J ~ i 11102
may be readily estimated in the following P+jQ =Ete'rI d IXl (10) (1)2[(.1+.)_1 j=2.045
down the
center
bO
B
ZQ
Xo
W
--.
Arms-
.--
Hottest
d-c field current. The greater the field cur-
rent the lower will be the flux in the fingers
to 1.0 represents the full load temperature
limit of the armature. Full load field current
t, ;, X ~ture Field Finger and the less the heating effect produced by may be determined by adding the field cur-
rents for no-load and synchronous reactance
iron losses. The maximum heating occurs
-42.3.. 470. .0.97 Lag.. ..33.7... 50.5... 59.5 where the a-c flux density is greatest, which at the rated power factor angle. This is the
42__._8_5__._9_Lea_______.____.___.__ in the machine that failed is at the center of triangle GHB and since GB is the full load,
Note: Armature temperature by embedded detec- the phase belts. field current, the curve BJ with center at G
tor. Field temperature by change in resistance. This local heating effect will not be ob- represents the maximum loading in the
Machine rated 44,705-kva 0.85-power factor, 13,200 served in readings of the usual embedded region where field temperature is the limit.
volts ' temperature detectors and will be apparent The steady-state stability limit is an arc